Professional Documents
Culture Documents
Actuators Structure of Discussion
Actuators Structure of Discussion
1 2
Actuator
Some examples shown.
System Positioner: pneumatic or digital
F1 F2
T1 T2
Sensor
System
Controller TC
T
TT
Reference: http://www.che.ttu.edu/pcoc/software/ppt.htm
3 4
Alternative: variable speed drive 2. Control valves
• A variable speed motor Selecting a control valve involves choosing the
may be used e.g. to • valve type
adjust the flow through • valve trim characteristics and size
a pump. • valve actuator operating method, style and size
• This is more efficient • valve positioner and other accessories.
than controlling flow
with a valve after a Wrong choices can degrade control system performance e.g.
constant speed pump. • valve too small – plant disturbances cannot be controlled
• valve too big – may operate too close to the closed position
• More costly to install;
• undersized actuator will not be able to overcome the hydraulic and
requires “blocking resistive forces (stiction) in the valve, leading to erratic operation
valve” to block flow • Inappropriate valve positioner can introduce instability into the
when the motor is off. control system.
Reference: Improving the effectiveness of basic closed loop control systems,
Reference: Process Control Special Short Course 2006 - Fisher-Rosemount Systems 5 6
www.carbontrust.co.uk.
butterfly valves.
9 10
Reference: Improving the effectiveness of basic closed loop control systems, www.carbontrust.co.uk. 11 Reference: http://www.bray.com 12
Valve actuators – advantages and 2.4 Valve positioners
disadvantages Positioners are local controllers that
ensures that the valve achieves the
position requested by the loop
controller with minimum overshoot,
and fastest possible recovery after a
disturbance. A valve positioner may be
used to overcome problems with the
dynamic control of a valve e.g. stiction.
Positioners are best used when the overall closed loop control system
is slow.
Example of a pneumatic positioner.
The device has a diaphragm (hidden);
The actuator needs to be sized for each application. It has to generate an increase in signal pressure on the
enough force to open and close the valve, while overcoming the diaphragm causes a shaft to rotate,
dynamic flow and resistive forces in the valve. until the force on a feedback spring is
equal to the force from the air pressure
Reference: Improving the effectiveness of basic closed loop control systems, www.carbontrust.co.uk. 13 signal on the diaphragm. Reference: http://www.bray.com 14
A VSD is a replacement for valves that constrict the output of fixed For loads with constant torque (e.g. conveyers), the power absorbed
speed pumps. VSD’s can control the motor directly rather than using the the drive (and hence, the energy consumed) is directly proportional
gearboxes, switches, belts or pulleys to adjust the fan speed. to the speed. Hence, the energy saving potential is less.
A VSD is best used (for energy saving purposes) with a motor that
Many types of equipment are now sold with built in VSD’s e.g. pumps,
has a load requiring a variable torque (such as centrifugal pumps and
fans and air conditioning units.
fans).
15 16
VSD example application 4. Specifying and sizing control valves
On an air fan in a furnace,
running at a fixed speed. The Typical (globe) valve – air to close (A-C) or fail-open valve
process demand typically
varies; the air fan speed is
constant and a damper
restricts the flow to match the
demand (or duty). This is
inefficient, as the input power
to the fan is not reduced as
the airflow falls.
When a VSD is fitted, fan
speed can be controlled
instead of throttling the output;
the damper can now be
opened fully. If required airflow
is 50% (on average) of full
output, energy consumption of
the fan system is reduced to
12.5% (cube of the speed).
17 18
Reference: http://www.che.ttu.edu/pcoc/software/ppt.htm
Air to open (A-O) or fail-closed valve Specifying and sizing control valves
A design equation used for sizing control valves relates the valve stem
position, x, to the actual flow rate, Q, by means of the valve flow
coefficient, C V :
∆Pv
Imperial units: Q = C v f ( x ) , Q measured in gallons per minute,
sp.gr.
∆Pv measured in p.s.i. (pounds per square inch), sp.gr. = specific gravity.
∆Pv
S.I. units: Q = C v f ( x )
, Q measured in cubic meters per second,
ρ
∆Pv measured in Pascals (Pa), ρ = density.
21 22
23 24
Specifying and sizing control valves Specifying and sizing control valves
25 26
Specifying and sizing control valves Specifying and sizing control valves
27 28
Specifying and sizing control valves Tutorial question
29 30
31 32
33 34
35 36
Tutorial example 2
37 38
39 40
41 42
43 44
Tutorial example 3 5. Further learning – virtual lab
http://www.cheric.org/education/control - Laboratory
3: Understanding the actuator: control valve.
This is a website with Java applets, covering
(a) Instrumentation for control valve.
(b) Selection of valve size and valve plug.
(c) Fail safe mode of control valve.
(d) Inherent and installed characteristics.
(e) Hysteresis and valve positioner.
45 46
47 48
Question Answer
Which of the
• The control valve always remains within its limits when used for
following control: it is never fully closed or fully open.
statements False. It would be preferable to have the control valves (and pumps, etc.) that are large enough
are true ? to compensate for disturbances; unfortunately, this is not always the case.
True. The selection of the manipulated valve has a significant influence on the behaviour of
the controlled variable.
• The control valve always remains within its limits when used for
control: it is never fully closed or fully open. • A control valve % opening is usually changed by adjusting an
electric motor that moves the stem position.
• The selection of which valve to manipulate influences the
behaviour of the controlled variable. False. Electric motors are not usually used to adjust the stem positions in control
• A control valve % opening is usually changed by adjusting an vales. Normally control valves are adjusted pneumatically. The electronic signal is transmitted
electric motor that moves the stem position. near the valve and is converted to proportional air pressure that is transmitted to the valve via a
short pipe. The pressure slightly deforms the diaphragm and changes the stem position.
49 50