Professional Documents
Culture Documents
Energy & Buildings: Hui Li, Long Ni, Yang Yao, Cheng Sun
Energy & Buildings: Hui Li, Long Ni, Yang Yao, Cheng Sun
a r t i c l e i n f o a b s t r a c t
Article history: Earth to Air Heat Exchangers (EAHEs) are reliable complements for conventional HVAC systems. During
Received 18 January 2019 summer, EAHE cooling can help reduce energy consumption. In the present study, to evaluate the cooling
Revised 25 April 2019
performance of a two-layer EAHE ventilating system, experimental work was conducted from May to Au-
Accepted 4 May 2019
gust 2017. Because EAHE performance largely depends on the thermal characteristics of soil, an irrigation
Available online 13 May 2019
system was adopted to experimentally verify the effect of soil moisture content. Air temperature showed
Keywords: an average drop of 14.6 °C and the average total cooling capacity was 8792 W. The system exhibited a
Earth to air heat exchanger maximum coefficient of performance (COP) of 27.2, implying that the system provides fresh-air cooling
Ventilation with little electricity input. Under cooling mode, the surrounding soil temperature increased continuously
Precipitation due to the operation of the system. An irrigation system was adopted to simulate natural precipitation;
Soil moisture content when the soil moisture changed from 0.37 cm3 /cm3 to 0.42 cm3 /cm3 , air temperature decreased by 1.6 °C
Cooling performance
at the pipe outlet. The results show that using EAHE under wet conditions resulted in a large cooling ca-
pacity and COP, which indicates that a short pipe length or shallow depth is required for achieving a
similar cooling capacity under wet soil conditions.
© 2019 Elsevier B.V. All rights reserved.
https://doi.org/10.1016/j.enbuild.2019.05.007
0378-7788/© 2019 Elsevier B.V. All rights reserved.
H. Li, L. Ni and Y. Yao et al. / Energy & Buildings 196 (2019) 280–292 281
Fig. 1. Schematic diagram of the EAHE fresh-air supply system used in this study.
contained 14 floors and the experimental area was located on the Table 3
Air volume determination for the system.
first floor. The EAHE system employed aims to provide fresh air
to two exhibition rooms; the areas of Room 1 and Room 2 were Useable Occupant Per-person Total air
255.8 and 70.5 m2 , respectively. Due to space constrictions, roof Room No. area density ventilation rate rate
air supply and floor air supply were adopted in Room 1 and Room / m2 m2 /per m3 /h•per m3 /h
2, respectively. The system consisted of two main parts – an out- Room 1 255.8 10 30 780
door EAHE on the buried-pipe side and user-side air supply sys- Room 2 70.5 10 30 210
Total 990
tem. Fig. 1 shows a schematic diagram of the EAHE fresh-air supply
system. Main functions of Heat Recovery Unit (HRU) can be con-
cluded as: (1) recover exhausted heat; (2) provide part of the driv-
ing power; (3) purify the outdoor fresh air. Considering the space Table 3. During the cooling operation, ambient fresh air first en-
limitations, an integrated HRU unit was adopted in the present tered the EAHE due to the suction action of the outdoor blower.
work. Heat recovery function is indispensable during heating oper- Fresh air was cooled by the EAHE due to the thermal inertia of
ation and can undertake average 39.5% fresh air heating load [11]. soil, after which it moved into the HRU through a connecting pipe.
However, during cooling, the HRU acts just as a driver and purifi- Well-cooled fresh air was separately sent to Room 1 using roof air
cation device as the heat recovery function is unnecessary and by- supply and to Room 2 using floor air supply.
passed in summer months. Detailed information on the system can It is worth noting that the configuration of the EAHE shown
be found in Table 2. in Fig. 2 is a new design that had not been previously installed
Air from the buried pipes was supplied to two rooms. The to- in China. In order to achieve a large heat exchange as well as
tal volume flow rate of ventilated air through the heat exchanger save land use, a horizontal U-shaped heat exchanger design was
was 985 m3 /h; this value was calculated using the fresh air stan- adopted. The EAHE comprised of two parallel horizontal U-shaped
dard GB50736-2012 [33]. During whole cooling operation, airflow steel pipes, each with an inner diameter of 0.26 m. In order to
rate was maintained at this value. Detailed results are shown in achieve a uniform air distribution, a large diameter was adopted
Table 2
Detailed parameters of the components of the experimental system.
Diameter mm 150 200 250 300 Various instruments were used to record and measure the ther-
mal parameters of air and soil at different locations and airflow
Air velocity m/s 15.8 8.8 5.65 3.92
Specific frictional head loss Pa/m 21.5 5.0 1.61 0.65 velocity through the EAHE system. Ten sections along the pipe
length were selected as measurement points for air temperature
and moisture content (Fig. 3). Airflow velocity through the EAHE
pipe was measured using a hot wire-type anemometer. As the
EAHE pipe shown in Fig. 3 was buried underground, two mea-
surement sections of air velocity located at the connection pipe
between outdoor EAHE and indoor HRU, see Fig. 1. The straight
for the main pipes [34]. When selected the pipe diameter, resis- pipe length of the connecting pipe was 17.0 m, which meets the
tance was an important parameter since it will influence both length requirement for straight pipe sections for airflow measure-
system energy consumption and initial cost. After calculation ment. The arrangement of measurement points is depicted in Fig. 4
of pipe specific frictional head loss, present design has been [35].
determined. Results of specific frictional head loss were listed in Soil temperature and moisture content were measured with
Table 4. Under present design, resistance of EAHE occupied 8.5% of two types of sensors. The arrangement of soil sensors is shown in
total system resistance. Fig. 5.
Fig. 3. Monitoring cross sections for air temperature and relative humidity inside the EAHE.
284 H. Li, L. Ni and Y. Yao et al. / Energy & Buildings 196 (2019) 280–292
the pipe end in soil; the reference hole was free from any heat
exchanger influence. After installing the sensors, the original soil
was used to fill up the measurement holes, while taking care to
maintain the original density. Integrated sensors (see blue marks in
Fig. 5) were adopted in Section B and Section D to acquire mois-
ture data of the soil. Moisture content sensors were installed at
depths lesser than 2.5 m because the influence of natural precipi-
tation hardly reaches 3.0 m according to [36].
Detailed information on the measurement range and measure-
ment precision can be found in Table 5.
Table 5
Detailed specifications of the measurement equipment.
Table 6 The mass flow rate inside the system can be calculated using:
Detailed arrangement of precipitation tests.
+ 8.1328 × 10−3.49149( ) −1
373.16
T −1
h = cd · t (q + cv · t )d (7)
where h is the enthalpy of air (kJ/kg), cd is the average constant
pressure specific heat of dry air (1.01 kJ/(kg·K)), t is air tempera-
ture (K), q is the vaporization heat of water at 0 °C (2500 kJ/kg),
cv is the average constant pressure specific heat of water vapor
(1.84 kJ/(kg·K)), and d is moisture content in air (kg/kg).
With respect to condensation during the cooling operation, the
Fig. 7. Air temperature variation during the cooling operation (Airflow rate: 985
total cooling capacity (Qt , W) of the EAHE is evaluated using the m3 /h).
following equation:
Qt = m˙ (ho − hi ) (8)
where m˙ is the mass flow rate (kg/s), and ho and hi are the en-
thalpy of fresh air at the outlet and inlet, respectively, of the EAHE
(J/kg).
The COP of the integrated system for cooling fresh air during
summer can be calculated as
Q
COP = (9)
E
where E is the power consumption of the system (W), which in-
cludes power consumption of the outdoor blower and HRU. Both
sensible and total COP were calculated in the following analysis;
sensible cooling COP is represented by COPs and total cooling COP
is represented by COPt .
Average COP (COP ) of the EAHE was calculated using the fol-
lowing equation:
Q
COP = (10)
E
Error analysis was conducted based on the description provided Fig. 8. Relative humidity of and moisture content variation in air during the cooling
in [39] and the steps taken are described in the appendix. operation (Airflow rate: 985 m3 /h).
3. Results and discussion July, which is the hottest month in a year. The highest inlet tem-
perature occurred at 1330 h on July 6th. Due to the thermal iner-
3.1. Thermal behavior of the EAHE tia of the soil, oscillations in the air temperature reduced drasti-
cally from 36.3 °C at the pipe inlet to 13.8 °C at the outlet. It can
Fig. 7 shows the temperature of air at the inlet and outlet. It also be noticed that the drop in outlet air temperature across the
is obvious that the ambient air was effectively cooled after passing EAHE increased with an increase in inlet air temperature. The rea-
through the EAHE; in addition, its temperature range reduced. Dur- son for this observation can be attributed to enhanced convective
ing the cooling period in the experimental study, air temperature heat transfer between air and the surrounding soil due to the large
at the EAHE inlet varied from 9.6 to 36.3 °C, while the outlet tem- temperature difference between them.
perature varied between 4.0 and 17.1 °C. It should be noted that Fig. 8 depicts the variation in the relative humidity and mois-
the highest outlet temperature was much lower than that of un- ture content of air at the inlet and outlet of the EAHE. Relative
conditioned ambient air, which means that the EAHE can serve as humidity at the inlet varied across a wide range from 22.9% to
a cooling source and take up a part of the cooling load. The aver- 89.5%. At the pipe outlet, although the range of variation was
age air temperatures at the inlet and outlet were 25.6 and 10.9 °C, narrower when compared to the inlet, the actual values were
respectively. The mean temperature decrease between EAHE inlet higher, i.e., from 68.5% to 100%. It is worth noticing that relative
and outlet was approximately 14.6 °C. Besides, at the fixed airflow humidity at the outlet was 100% most of the time, which indi-
985 m3 /h, a maximum temperature drop of 23.7 °C was observed cates that condensation occurred inside the buried pipes. This
during the cooling operation. With respect to local climate con- can also be confirmed by observing air moisture content at the
ditions, the maximum ambient air temperature occurred during inlet and outlet. Air moisture content at the pipe outlet varied
H. Li, L. Ni and Y. Yao et al. / Energy & Buildings 196 (2019) 280–292 287
Fig. 10. Correlation between cooling capacity and inlet temperature. (a) Scatter plot and (b) correlation analysis.
inlet air temperature, the sensible cooling capacity decreased with tion, after which it decreased gradually, which means that water
an increase in air moisture content and led to a high outlet air migration requires time to reach a constant level.
temperature. After examining the correlation coefficients between Experiments on the enhancement function of soil moisture con-
different cooling capacities, it can be inferred that the strongest tent were conducted on two days (Aug 7th and 14th) after irriga-
correlation existed between the latent and total cooling capacities. tion to ensure uniform moisture distribution. The operation data of
Aug 4th and 9th was chosen as it was similar to the test day data.
3.3. Temperature and moisture content variation in soil during Ambient air temperature and moisture content values of the com-
irrigation experiments pared specimens are shown in Fig. 13 and summarized in Table 7.
In the field test, outer climatic conditions were hard to control. Al-
Soil is composed of air, water, and solid particles; its moisture though differences existed between the selected days, the general
content strongly affects its thermal conductivity. In order to ex- trend of these days was fairly consistent.
plore the effect of soil moisture content on EAHE performance, an Fig. 14 shows the drop in air temperature when the EAHE sys-
artificial precipitation device was adopted to change the soil mois- tem was operated on the selected days. The average inlet tem-
ture content. Irrigation tests were conducted on Aug 6th and 13th perature was 25.5 °C on both Aug 4th and 7th, while the average
and Fig. 12 shows the relationship between soil temperature and outlet temperature on Aug 7th was 0.6 °C lower than that on Aug
moisture content. It is clear that soil temperature decreased after 4th, since the soil moisture content on Aug. 7th was 0.03 cm3 /cm3
irrigation, thus conforming to the objective law of natural precip- higher than that of Aug. 4th.
itation. During first precipitation, soil moisture at the upper pipe Fig. 14(b) shows the changes occurring in air temperature
depth (–2.5 m) increased from 0.33 cm3 /cm3 to 0.36 cm3 /cm3 . The on Aug 9th and 14th. Comparison between these two days was
second precipitation resulted in a 0.05 cm3 /cm3 rise in moisture stronger than the previous condition. Soil moisture content was
content on an average. The EAHE system was operated the day af- 0.37 cm3 /cm3 on Aug 9th and 0.42 cm3 /cm3 on Aug. 14th, av-
ter precipitation to obtain an even distribution in soil temperature erage air temperature at pipe outlet were 13.0 °C and 11.4 °C, re-
and moisture content. The results obtained were also confirmed spectively. This phenomenon indicated that lower air temperature
by the data in Fig. 12; moisture content at the upper pipe depth can be achieved under larger soil moisture content. Besides, it
(–2.5 m) reached the highest value on the second day after irriga- can be noticed that the outlet temperature under wet conditions
H. Li, L. Ni and Y. Yao et al. / Energy & Buildings 196 (2019) 280–292 289
Fig. 11. Correlation between cooling capacity and inlet moisture content. (a) Scatter plot and (b) correlation analysis.
Table 7
Climate parameters of comparison days.
Fig. 14. Air temperature variations in dry and wet conditions on (a) Aug 4th and
7th and (b) Aug 9th and 14th (Airflow rate: 985 m3 /h).
at a distance of 0.3 m from the pipe wall was 0.8 °C. Meanwhile, al- Fig. 15. Sensible cooling capacity and COPs in dry and wet conditions on (a) Aug
though system operation increased soil temperature during week- 4th and 7th and (b) Aug 9th and 14th (Airflow rate: 985 m3 /h).
days, the soil recovered during weekends when the system was not
operated. Soil temperature near the pipe wall changed from 5.9 to
8.9 °C after operation from July 3rd to 10th and then reduced to
7.5 °C during the weekend. outdoor fan and HRU. The average power consumption was 676 W
during cooling use.
As for COP, it varied with respect to the cooling capacity (refer
3.5. Power consumption and coefficient of performance to Fig. 9). Both sensible and total cooling capacities were consid-
ered when measuring the system COP. During cooling operation,
Fig. 17 illustrates the changes occurring in power consumption sensible COPs varied between 2.2 and 13.1 with average value of
and COP during the cooling operation. The power consumption of 7.1. Value of total cooling COPt was similar to COPs since there ex-
the system was measured using a power meter. Though the heat isted no latent heat transfer at the beginning of cooling operation.
recovery function was bypassed during the cooling operation, HRU As inlet temperature rose, latent heat transfer occurred and COPt
still acted as a driving equipment and hence the total power con- gradually increased. The average COPt was 12.5 and its maximum
sumption of the system was composed of the consumption of the value was 27.2, which occurred at 16:45 on July 5th. The results
H. Li, L. Ni and Y. Yao et al. / Energy & Buildings 196 (2019) 280–292 291