Professional Documents
Culture Documents
Representation of Power System Components
Representation of Power System Components
6.1. Introduction
Electric power systems may be of great complexity and spread over large geographical area. An electric power
system consists of generators, transformers, transmission lines and consumer equipment (loads). The system
must be protected against flow of heavy short – circuit currents (which can cause permanent damage to major
equipment) by disconnecting the faulty section of system by means of circuit breakers and protective relaying.
It is necessary to know the maximum short-circuit currents that can occur at points of a system in order that
circuit breakers may be selected that are adequate to withstand the currents and operate successfully to cut out
the faulty section, and also in order that the protective relays may be selected for correct operation. The design
of machine, bus bars, isolators, circuit breakers etc., is based on the considerations of normal and short-circuits
currents.
It is also necessary to be able to calculate, approximately at least, the size of the protective reactors which must
be inserted in the system to limit the short circuit currents to a value which is not beyond that capable of being
withstood by the circuit breakers.
The short circuit currents in an AC system are determined mainly by the reactance of the alternators,
transformers and line up to point of fault in the case phase to phase faults. When the fault is between phase and
earth, the resistance of the earth path plays an important role in limiting the currents.
In case of circuit breakers their rupturing capacities are based on the symmetrical short circuit current which is
the simplest calculation among all types of short circuits. However, for determination of settings of relays it is
absolutely necessary to know fault current due to unsymmetrical fault condition too for which knowledge of
symmetrical components etc., is required.
1
transmission lines etc., can be solved as a single phase network composed of one of the three phases and a
neutral return, if it is balanced under normal operation. Many times, the components of the system are shown in
a single line diagram omitting the neutral also.
6.3.1. Single Line Diagram
The single line diagram of a power system network shows the main connections and arrangements of the system
components along with their data (such as output rating, voltage, resistance and reactance etc). In case of
transmission lines sometimes the conductor size and spacing’s are given. It is not necessary to show all the
components of the system on a single line diagram, eg circuit breakers need not be shown in a load flow study
but are must for protection study. In a single line diagram, the system components are usually drawn in the
form of their symbols. Generators and transformer connection – star, delta and neutral earthing are indicated by
symbols drawn by the side of the representation of these elements. Circuit breakers are represented by
rectangular blocks.
2
6.3.2 Impedance Diagram Representation of a Power System
A further simplification from the single line diagram, with its symbols for the various components, is to draw
the diagrams with impedances only. In impedance diagram, each component is represented by its equivalent
circuit. Loads are assumed to be passive (not involving rotating machines) and are represented by resistance and
inductive reactance in series. Neutral earthing impedances do not appear in the diagram as balanced conditions
are assumed.
In order to calculate the performance of a power system under load condition or upon the occurrence of a fault,
the one line diagram is used to draw the single phase or per phase equivalent circuit of the system. Refering to
the one line diagram of a sample power system shown in Fig. 6.2, Fig 6.3 combines the equivalent circuits for
the various components shown in Fig 6.2 to form the per phase impedance diagram of the system.
3
Fig 6.6 Reactance Diagram
Assumptions made for drawing reactance diagrams give results quite accurate for many power system studies,
such as short circuit studies etc., as winding resistances including the line resistances are quite small in
comparison with leakage reactance and shunt path which includes line charging and transformer magnetizing
circuit provide a very high parallel impedance with fault. In general it is to be noted that if the resistance is less
than one – third of the reactance, and resistance is ignored, the error introduced will not be more than 5%.
6.4 Percentage Resistance and Reactance and Base kVA and kVA
Resistance and reactance (and consequently impedance) may be expressed in percentage or ohmic terms. In the
case of rotating machines and transformers, manufacturer values are always in percentage terms while tables for
cables and overhead lines are always in ohmic terms. Calculations can be made using either but not a mixture.
For short circuit calculations, generally the percentage values are employed and therefore their understanding
essential.
Percentage Resistance. It is the voltage drop across the given resistance expressed as percentage of normal
voltage when carrying full load current pertaining to normal rating, ie.,
IR
%R = x 100 (6.0)
V
Where R is the resistance in ohms, I is the full load current and V is the rated voltage.
Percentage Reactance. Percentage reactance can be defined in the same way a percentage resistance. It is the
voltage drop across the given reactance expressed as percentage of nominal voltage when carrying full load
current pertaining to normal rating i.e.,
IX
%X = x 100 (6.1)
V
Where X is the reactance in ohms, I is the full load current and V is the rated voltage.
From equation (6.1) we have
( %X ) X V
X= ohms
1 X 100
4
( %X ) X V X V
X=
V X 1 X 100
( %X ) V ²
= ohms (6.2)
(Output ∈VA )100
When the voltage and the output are expressed in kV and kVA respectively, then
V V
X=
( %X ) X ( 1000 ) X ( 1000 ) X 1000
V
100 X (
1000 )
X1
( %X ) ( kV )2 X 10
= ohms (6.3)
kVA
( X ) (kVA )
Or %X = (6.4)
10(kV )²
Thus if actual reactance in ohms is given, percentage reactance can be determined and vice versa.
Base kVA. If numbers of equipments such as generators, transformers, transmission lines etc are connected in
parallel and their percentage resistances and reactances also refer to their respective kVA ratings, it is difficult
to compare these percentage resistances and reactances and their combined effect until and unless they are all
referred to a common kVA. This common kVA, which is taken as an arbitrary one is known as the base kVA of
the system.
A base kVA may be chosen in the following manner:
(i) Equal to the kVA rating of the largest unit connected in the network.
(ii) Equal to the sum of the kVA ratings of all the units connected in the network.
(iii) Any arbitrary value.
It must, however, be clearly understood that the value of the base kVA, has no bearing whatsoever on the
results; since in the ultimate formula for the calculation of short circuit current base MVA is to be taken into
consideration.
The conversion of percentage reactance at rated kVA to the percentage reactance at base kVA can be made by
using the following expression:
Base kVA
= x percentage reactance at rated kVA (6.5)
Rated kVA
Thus if a transformer is rated for 10,000 kVA and has percentage reactance of 7.5%, then the percentage
reactance at the base kVA of 25,000 shall be
5
25,000
= x 7.5 = 18.75%
10,000
Base kV. In some cases it is convienient to work in ohmic values of the various reactances rather than in
percentage values. The method would become simple if all the reactances relate to the same voltage but if step
up or step down transformers or other equipments operating at different voltages are also included, all the ohmic
values will have to be reduced to a common base voltage.
Reactances can be converted from one operating voltage to the other by the following relation
E2 2
X2 =
( )
E1
x X1 (6.6)
Drawbacks. 1. Some equations that hold in the unscaled cases are modified when scaled into per unit. Factors
such as √ 3 and 3 are removed or added by this method.
2. Equivalent circuit of the components are modified, making them somewhat more abstract. Sometimes phase
shifts that are clearly present in the unscaled circuit vanish in the per unit circuit.
6
6.5.2. Selection of Bases
For a common representation, base kVA and base voltages are to be chosen. Then the base current and the base
impedance can be expressed as follows:
Base voltage∈volts , V B
Base impedance, Z B = ohms
Base current ∈amperes , I B
VB X VB
=
IB X V B
V 2B
=
V B IB
VB VB
=
1000 ( )( )
X
1000
X 1000
V B IB
1,000
( k V B ) ² X 1,000
=
kV A B
(k V B) ²
= ohms (6.8)
MV A B
For a single phase, phase to neutral voltage, kVA per phase are taken as bases while in a three phase system,
three phase line to line voltage and three phase kVA are used as bases. This simplifies the calculations.
The base values in a system are so selected that per unit voltages and currents in the system are approximately
unity. Sometimes the base kVA is chosen equal to the sum of the ratings of the various equipments in the
system or equal to the kVA rating of the largest unit connected in the system. If in the network there is no
transformer present, the same base voltage is used throughout, but if transformers are present, the rule is to
change the base voltage in proportion to the transformation ratio of the transformer when transformer is
reached. Thus, all impedances in the network before the transformer is reached, including the transformer
primary leakage impedance, are expressed in per unit to a new base voltage which is the primary side base
voltage multiplied by the transformer transformation ratio. This is very important.
7
Voltage, current, volt-amperes and impedances are so related that selection of base values for any two of them
determines the base values of the remaining two. For example for a single-phase circuit we have the following
relations
SB = V B I B (6.9)
VB
ZB = (6.10)
IB
Where S B, V B , I B and Z B represent the base power, base voltage, base current and base impedance expressed in
volt-amperes, volts, amperes and ohms respectively. Thus from the above two equations, if any two of the four
quantities are specified, the remaining two may be determined without any problem. As mentioned earlier, base
kVA and base kV are usually specified. Let kV A B and kV B be the base kVA and base kV, then
Actual kV k V actual
Per unit kV = = (6.11)
Base kV kVB
Base kVA k VA B
Base current, I B = = amperes
Base kV kVB
(6.12)
Actual current
Per unit current, I pu =
Base current
Actual current
= x kVB (6.13)
k VA B
Base kV X 1,000
Base impedance, Z B =
Base current
kVB
= kVB x x 1,000
k VA B
( k V B ) ² X 1,000
= ohms
kV A B
Actual impedance
Z pu =
Base impedance
kV A B
Actual impedance x (6.15)
( k V B ) ² X 1,000
8
In a 3 phase system rather than obtaining the per unit values using per phase quantities, the per unit values can
be obtained directly by using three phase base quantities (total kVA, line-to-line voltage and line currents). Let
kV A B be the base kVA (total output of three phases) and k V B be the base line-to-line voltage in kV.
Assuming star connection (equivalent star can always be found)
k VA B
Base current, I B = amperes.
√3 k V B
k V B X 1000
Base impedance, Z B =
√3 X I B
k V B √3 k V B
= x x 1,000
√3 k VA B
( k V B ) ² X 1,000
= ohms (6.16)
kV A B
Per unit impedance,
Actual impedance
Z pu =
Base impedance
Actual impedance X kV A B
=
( k V B ) ² X 1,000
(6.17)
It should be noted that the same expression is obtained for a single phase and three phase systems. In power
system problems the data are given in terms of 3 phase kVA, line-to-line kV, the machine kVA and machine
phase-to-phase (or line-to-line) kV rating.
9
Example 6.0
Base voltage = 1,100 volts. Base kVA = 106 . What is the base impedance?
Solution
Base kVA = 106
1,100
Base kV = = 1.1kV
1,000
k VA B 106
Base current, I B = =
kVB 1.1
Base impedance can also be determined directly by substituting the values of base kVA ad base kV in Eq. (6.8)
ZB =
( k V B ) ² X 1,000 ( 1.1 )2 X 1,000
= = 0.00121Ω
kV A B 106
Example 6.1
If the resistance in ohms is 5Ω, find the per unit value. Given base kVA = 10 and base kV = 11.
Solution
Resistance, R = 5Ω
R 5
Per unit resistance, R pu = = = 0.000413pu
R B 12,100
Example 6.2
A single phase transformer is rated as 2.5kVA, 11/0.4kV. If the leakage reactance is 0.96Ω when referred to low
voltage side, then determine its leakage reactance in per unit.
Solution
Base voltage, k V B = 0.4kV
Z BLV =
( k V B ) ² X 1,000 ( 0.4 )2 X 1,000
= = 64Ω
kV A B 2.5
10
Leakage reactance in per unit,
Example 6.3
Determine the per unit impedance of a transmission line having an impedance of 30 + j110Ω on 100MVA and
132kV base voltage.
Solution
Impedance of line, Z = 30 + j110Ω
Z X kV A B
Per unit impedance, Z pu =
( k V B ) ² X 1,000
1.065
Per unit reactance = = 1.1002.
0.968
Therefore, to change from per unit impedance on a given base to per unit impedance on a new base, the
following equation applies:
base MVA new base kV given 2
Per unit Z new = per unit Z given
base MVA given
x ( )
base kV new
(6.19)
Example 6.5
11
The reactance of a generator is given as 0.25 per unit based on the generators of 18kV, 500MVA. Find its per
unit reactance on a base of 20kV, 100MVA.
Solution
100 18
From Equ. (6.19), New per unit reactance = 0.25 x
500
x ( )
20
² = 0.0405.
Example 6.6
A single phase 9.6kVA, 500V/1.5kV transformer has an impedance of 1.302Ω with respect to primary side.
Find its per unit impedance with respect to primary and secondary sides.
Solution
0.0096
With respect to primary, per unit impedance = 1.302 x = 0.05
(0.5)²
0.0096
Per unit impedance = 11.718 x = 0.05
(1.5)²
Per unit impedance of the transformer is same referred to primary as well as secondary.
Example 6.7
A 300MVA, 20kV three-phase generator has a subtransient reactance of 20%. The generator supplies a number
of synchronous motors over 64km transmission line having transformers at both ends shown in Fig 6.7. The
motors, all rated 13.2kV, are represented by just two equivalent motors. Rated inputs to the motors are
200MVA and 100MVA for M 1 and M 2 respectively. For both motors X”= 20%. The three phase transformer T 1
is rated 350MVA, 230/20kV with leakage reactance of 10%. Transformer T 2 is composed of three single phase
transformers each rated 127/13.2 kV, 100MVA with leakage reactance of 10%. Series reactance of the
transmission line is 0.5Ω/km. Draw the impedance diagram, with all impedances marked in per unit. Select the
generator rating as base in the generator circuit.
13.2
Base voltage at motor side = 230 x = 13.8kV
220
300
Per unit reactance of transformer T 1 = 0.1 x = 0.0857
350
300
Per unit reactance of transmission line = 0.5 x 64 x = 0.1825
230²
300 13.2
Per unit reactance of motor M 1 = 0.2 x
200
x ( )
13.8
² = 0.2745
300 13.2
Per unit reactance of motor M 2 = 0.2 x
100
x ( )
13.8
² = 0.549
13
Fig. 6.8 Per unit Impedance Diagram
14