TYPe 53 N/H
Our diversity is
your profit.
W2 Armaturen GmbH
Technical Data
Safety Shut Off Valve Permissible pressure pmax up to 25 bar
Type 53N/H DN 80; DN100; DN150;
Nominal widths
DN200; DN250; DN300;
Scope of Application DN350; DN400; DN500
Scope of type 53N/H safety shut off valve is to Type of connection DIN flanges PN10 to
prevent impermissibly high pressure and/or low PN40; ANSI flanges;
pressure from the system at the outlet side, e.g. a special flanges
gas pressure regulation system. It can be used for
all gases according to DVGW worksheet G260 and Valve diameter 80mm to 500mm
all non-aggressive gases.
(Special versions are available for other gases). Operating temperature -15°C to +60°C
2
W2 Armaturen GmbH
Installation Dimensions
Line Connections
Flow direction left-right
Ventilation G1/4 ⎫ for unsoldered, threaded pipe Ventilation in flow direction right
Measuring G1/4 ⎬ fitting with cutting ring accord. Measuring pulse in flow direction right
pulse ⎭ to DIN 2353 for pipe-ø 12x1.5 Hand lever in flow direction front
Flow direction and/or line connections can be
changed on customer request.
Standard Version
3
W2 Armaturen GmbH
Installation
The safety shut-off valve type 53N/H can be installed horizontally with the measuring element (I) upright or
vertically with the measuring element pointing to the side.
When installed vertically the flow direction on units with valve diameter up to 150 mm can be from top to bottom
or vice versa; on units with valve diameter greater than 150 mm the flow direction for units installed vertically
must be from top to bottom.
4
W2 Armaturen GmbH
Adjustments
Design
To adjust the threshold pressures loosen and
Type 53N/H safety shut off valve is composed of remove crown cover 2 with the special safety shut-
three assemblies: measuring element (I), driving off valve wrench.
mechanism (II) and regulating unit (III).
Measuring element is available in versions 53N and Upper threshold pressure
53H; 53N is used on a standard basis for operating The upper threshold pressure can be adjusted with
pressures up to 50 mbar, DH for operating the aid of the special safety shut-off valve wrench
pressures above 50 mbar. on spring plate 3. Turning to right increases the
value.
If the upper threshold pressure is set to above 3
Function bar adjust only in non-pressurized state after
Upper threshold pressure low pressure actuation, otherwise the
The pressure to be monitored reaches through the diaphragm can be damaged.
measuring pulse line 10 into diaphragm chamber
16. If the pressure increases to an impermissibly Lower threshold pressure
high value and exceeds the setting of the pressure Adjust lower threshold pressure with the special
safety shut-off valve wrench (17 mm) on the dome
spring 4, diaphragm 9 lifts together with release
spring plate 6. Turning to right increases the value.
bushing 11. This releases the balls 12 so that
If the lower threshold pressure is set to above
release piston 13 together with the lower rod 14
150 mbar adjust only in non-pressurized state
snap up releasing pawl 15. Valve 19 closes.
after low pressure actuation, otherwise the
Lower threshold pressure diaphragm can be damaged.
The pressure to be monitored reaches through the The setting for the lower threshold pressure has a
measuring pulse line 10 into diaphragm chamber slight effect on the upper threshold pressure. For
16. If the pressure decreases to an impermissibly this reason check and - if necessary - correct the
low value and overcomes the setting of the low setting for the upper threshold pressure each time
pressure spring 8, diaphragm 9 moves down the lower threshold pressure is adjusted.
together with release socket 11. The remaining
operation corresponds to that described previously Minimum pressure difference between
for the upper threshold pressure. operating pressure pb and special pressure ps:
Diaphragm rupture safety device
In the event of a diaphragm rupture the gas flows Guide range Drawing ∆pmin
into spring chamber 5 and reaches through the [bar] number ps - pb [bar]
ventilation line 7 into the atmosphere. The pressure Measuring Element N (pressure too high)
in diaphragm chamber 16 thereby decreases. The 0,030 - 0,150 4-53-16/4x100 0,020
remaining procedure corresponds to the sequence 0,150 - 0,250 4-53-16/5x100 0,020
above for lower threshold pressure. 0,250 - 0,500 4-53-16/6x100 0,030
Measuring Element N (pressure too low)
0,007 - 0,025 4-53-15/2,0x58 0,020
Starting Apparatus 0,025 - 0,070 4-53-15/2,5x49 0,030
Before initial operation (opening) ensure that valves Measuring Element H (pressure too high)
in back are closed. The integrated pressure 0,100 - 0,350 4-53-16/4x100 0,040
compensation valve 18 can be opened by slowly 0,350 - 0,850 4-53-16/5x100 0,040
lifting the hand lever 17 until resistance is felt. 0,850 - 1,600 4-53-16/6x100 0,080
When the pressure in front and in back of the valve 1,600 - 2,700 4-53-16/7x100 0,150
plate 19 has equalized slowly lift hand lever 17 2,700 - 4,200 4-53-16/8x100 0,200
further to the stop. The pressure to be monitored 4,200 - 7,000 4-53-16/9x100 0,300
reaches through measuring pulse line 10 into Measuring Element H (pressure too low)
diaphragm chamber 16 where it applies pressure to 0,040 - 0,120 4-53-15/2,0x58 0,030
diaphragm 9. Press release piston 13 down with 0,120 - 0,280 4-53-15/2,5x49 0,030
pushbutton 1 only after the operating pressure has 0,280 - 0,650 4-53-15/3,0x55.1 0,030
been reached so that the balls 12 can catch. The 0,657 - 1,050 4-53-15/3,6x48.2 0,050
release bushing 11 together with diaphragm 9 snap 1,050 - 1,500 4-53-15/4,0x49 0,100
into the zero position. Pushbutton 1 can be
released. Hand lever 17 can then be released
slowly until the pawl 15 makes contact with the
bottom rod 14. The safety shut-off valve is now
ready for operation.
5
W2 Armaturen GmbH
OPTION:
There are two versions of the isolating amplifier
required for control of the sensor:
- 230 VAC, 50 - 60 Hz
- 24 VDC
Each: (Eex ia) II C and with PTB certificate.
OPTIONS:
- with DVGW approval
- explosion-proof version
- for aggressive mediums
- for 24 VDC or 230 VAC, 50 - 60 Hz
6
W2 Armaturen GmbH
For industrial burner systems frequently a purely opens and the air from measuring element 3
mechanical safety device is required in addition to decreases through line VI-VII. Movement 3
(or instead of) an electronic monitoring device for actuates due to insufficient air, because the
the gas and air pressure. medium cannot flow through nozzle 4 quickly
Safety shutoff valve type 53N/H with two additional enough. Turning hand wheel 5 to the right
control regulators fulfills this requirement in all three increases the value.
cases: protection against gas pressure being to
high or to low and against to low air pressure (the Gas pressure to high
measuring element automatically also provides a Gas pressure I to be monitored reaches by gas
safety shutoff for air pressure to high). pulse line III to control regulator 2, type UH. When
gas pressure increases to an impermissibly high
Air pressure to low value and overcomes the setting of the spring in
Air pressure IV to be monitored reaches to nozzle 4 control regulator 2, the valve in control regulator 2
and air pulse line V into measuring element 3. opens and the air from measuring element 3
Further operation and adjustment for low (and high) decreases through line VIII-IX. Measuring element
air pressure corresponds to the sequence 3 actuates due to low air pressure, because the
described on page 5 for function and adjustments. medium cannot flow through nozzle 4 quickly
enough. Turning hand wheel 1 to the right
Gas pressure to low increases the value.
Gas pressure I to be monitored reaches by gas
pulse line II to control regulator 6, type DH. When Maintenance
gas pressure decreases to an impermissibly low We recommend checking this combination of safety
value and overcomes the setting of the spring in shut-off valve measuring element and additional
control regulator 6, the valve in control regulator 6
7
W2 Armaturen GmbH
7
W2 Armaturen GmbH
8
W2 Armaturen GmbH
Special Maintenance Instructions for any damage. The entire upper section can be
removed by loosening the allen screws on the
Measuring element N/H spring crown, H 18 (or on upper diaphragm
housing, N 11).
The measuring element can be removed for Then press the middle rod 12 and simultaneously
maintenance. For this loosen the screws on blind pull the entire unit up together with diaphragm 8
flange 3 and remove the complete element. and socket element 6. Now it is possible to check
Function also can be checked in the deinstalled and, if necessary, replace the parts mentioned
state. Before disassembling the element always previously.
release the pressure of high and low pressure All moving parts should be oiled lightly with a
springs. Observe the instructions in the section suitable agent before reassembling. ⇒
Adjustments (page 5).
During maintenance check especially the
diaphragm as well as the release socket and piston
9
W2 Armaturen GmbH
10
W2 Armaturen GmbH
11
W2 Armaturen GmbH
12
W2 Armaturen GmbH
13
W2 Armaturen GmbH
14
W2 Armaturen GmbH
15
COMPETENCE
IN GAS!
DIN-DVGW
• Gas-Take Over Stations • Safety Relief Valves
• Gas-Regulaton Cabinets • Overflow Regulatores
• Station Accessories • Vaccum Regulatores
• Gas-Pressure Regulators • Differential Pressure Regulators
• Safety Shut Off Valves • Special Design Regulators