Professional Documents
Culture Documents
Brosur ITU - FCU Aug-2016
Brosur ITU - FCU Aug-2016
ISO 9001:2008
G
GREEN
Ceiling Concealed
Cooling Capacity
AIR FLOW WATER FLOW WPD COOLING CAPACITY
MODEL CFM GPM Ft H2O BTU/h
(cmh) (l/s) (kpa) (kcal/h)
200 1.332 18.3 7,380
CC200
(340) (0.09) (54.9) (1,860)
300 1.998 8.2 10,721
CC300
(510) (0.13) (24.6) (2,703)
400 2.664 13.7 13,807
CC400
(680) (0.16) (41.1) (3,481)
600 3.996 5.5 20,394
CC600
(1,020) (0.26) (16.5) (5,142)
800 5,238 10.7 26,978
CC800
(1,360) (0.35) (32.1) (6,802)
1,000 6.667 6.1 33,844
CC1000
(1,700) (0.43) (18.3) (8,533)
1,200 7.992 9.1 41,085
CC1200
(2,040) (0.52) (28.1) (10,359)
1,400 9.324 20.4 49,493
CC1400
(2,380) (0.61) (61.2) (12,497)
Note :
1. Air Flow is measured at high speed fan
2. Water Pressure Drop are only for Chilled Water System
3. Cooling Capacity ratings are based on 80°F (26.7°C) EDB / 67°F (19.4°C) EWB and 45°F (EWT / 55°F (12.8°C)
1
Sound Power Level TYPE
FAN
SPEED
OCTAVE BAND PREQUENCIES (Hz)
125 250 500 1000 2000 4000 8000
dBA
Dimension
MODEL
CC200 CC300 CC400 CC600 CC800 CC1000 CC1200 CC1400
DIMENSION
A mm 483
B mm 772 873 1070 1197 1387 1590 1794 2184
C mm 286
2
SHOPPING CENTERS OFFICES HOTELS INDUSTRIES