Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

CERTIFICATE NO : 2014-1-0132

ISO 9001:2008
G
GREEN

Air Handling Units


(Double Skinned) CS Type
Features and Benefits
ITU's new Air Handling Unit is an improved product that offer a competitive value with superior quality. Our
wide range of units can provide adaptability to any commercial or industrial application. There are 15 types of
horizontal arrangements and 12 types for vertical arrangement which can accommodate airflow volumes
from 1,800 CFM to 59,200 CFM (3,100 CMH to 107 CMH).

These double skinned panel units with 1/2” OD copper tube and aluminum fin coils provide the optimum in Air
Handling Equipment. New AHU is designed to have an attractive appearance with its extruded aluminum
extruded frame and polyurethane injected panels which have excellent thermal properties (0.68 W/m2 K)
and maximum sound reduction through the casing. With a unique locking system where panels meet the
frame, there are no bolts and nuts visible on the outer surface of unit, making the AHU more simple, neat and
sturdy.

High Grade Aluminum Frame


Framework is designed with aluminum material and nylon corner connection for ease in building. It has more
advantages in flexibility and is possible to Completely Knock Down (CKD) and build in an area where access
or space is limited.

Injected Polyurethane Foam Panels


All panels are double-skinned (walled) panels and injected between with high efficiency Polyurethane foam
insulation material which give maximum thermal insulation and attenuation to break out noise. Double-
skinned (walled) panels have a smooth surface which makes cleaning easy to reduces risk of dirt collecting
on unit. This air tight characteristic makes it a superb application for hospitals, food industries and the
electronic industries as it ensures a clean air supply.

High Efficiency Coils


ITU ½” OD Copper tubes Cooling Coils for AHU units give maximum cooling and dehumidification and are
used in the standard Drainable Chilled Water Coils or optional Direct Expansion Coils with pre-engineered
direct expansion circuiting selection.

Fans
For duties up to 3 in-wg of Total Static Pressure, standard fans are Forward Curved heel while for a higher
Total Static Pressure, ITU offers either Forward Curved Medium Pressure or Backward Curved Wheel
depending on technical specifications.

Air Handling Unit Specifications


MODEL 032 050 074 113 156 217 270 336 402 490 578 666 754 879 1080
CMH 3,100 3,840 5,783 8,782 11,919 16,478 21,634 25,888 29,483 37,898 44,324 49,863 57,375 66,938 82,238
450
CFM 1,800 2,259 3,402 5,166 7,011 9,693 12,726 15,228 17,343 22,293 26,073 29,331 33,750 39,375 48,375
CMH 3,450 4,267 6,426 9,758 13,243 18,309 24,038 28,764 32,759 42,109 49,249 55,403 63,750 74,375 91,375
Air Flow 500
CFM 2,030 2,510 3,780 5,740 7,790 10,770 14,140 16,920 19,270 24,770 28,970 32,590 37,500 43,750 53,750
CMH 3,797 4,694 7,031 10,734 14,567 20,140 26,442 31,640 36,035 46,320 54,174 60,943 70,125 81,813 107,000
550
CFM 2,233 2,761 4,136 6,314 8,569 11,847 15,554 18,612 21,197 27,247 31,867 35,849 41,250 48,125 59,200
Face Area Sqr Ft 4.06 5.02 7.52 11.48 15.58 21.54 28.28 33.84 38.54 49.54 57.94 66.44 75 87.5 107.5
KW 23 28 42 68 90 128 171 194 222 304 358 403 414 483 618
4 Rows
MBtu/h 78 95 144 232 309 436 583 664 757 1,037 1,224 1,378 1,414 1,650 2,112
Cooling Coil
KW 26 34 50 77 102 144 192 237 269 341 403 453 477 542 703
5 Rows
MBtu/h 88 114 172 262 348 491 656 808 920 1,165 1,375 1,547 1,629 1,850 2,400
KW 28 37 55 83 119 157 208 257 292 371 437 492 575 668 767
6 Rows
MBtu/h 96 124 188 285 407 535 712 876 998 1,268 1,494 1,680 1,963 2,283 2,620
Capacity*
KW 31 40 61 93 126 176 234 273 310 394 465 523 612 714 858
8 Rows
MBtu/h 107 137 210 316 430 602 798 931 1,060 1,346 1,587 1,785 2,090 2,439 2,929

NOTE :
1. Air Flow ( CFM ) is measures at high speed
2. Water Pressure Drop are only for Chiller Water System
3. Cooling Capacity rating are based on 80F (26.7C) EDB / 67F (19.4C) EWB and 44F (6.7C) EWT

1
Horizontal Dimensions
MODEL 032 050 074 113 156 217 270 336 402 490 578 666 754 879 1080
Length mm 1,100 1,300 1,350 1,650 2,150 2,350 2,550 3,000 3,000 2,750 2,900 2,900 3,300 3,475 4,010
Basic Unit
Width 1 mm 1,175 1,175 1,300 1,400 1,400 1,600 1,750 1,750 1,950 1,604 1,604 1,804 1,804 2,100 2,100
Dimension Width 2 mm - - - - - - - - - 1,000 1,000 1,000 1,000 1,100 1,100
Horizontal Height mm 645 645 805 955 955 1,155 1,355 1,355 1,510 2,130 2,305 2,505 2,505 2,985 3,125
Weight Kg 194 213 258 331 410 527 665 826 876 1,346 1,570 1,830 1,954 2,875 3,122

Vertical Dimensions
MODEL 032 050 074 113 156 217 270 336 402 490 578 666
Basic Unit Length mm 1,100 1,300 1,350 1,650 2,150 2,350 2,550 3,000 3,000 2,750 2,900 2,900
Dimension Width mm 652 652 800 900 900 1,150 1,300 1,300 1,500 1,630 1,630 1,630
Vertical Height mm 1,170 1,170 1,495 1,865 1,865 2,270 2,545 2,545 2,965 3,760 3,975 4,175
Weight Kg 187 247 296 366 448 612 719 814 850 914 970 1,050

Fan Arrangements (for Horizontal & Vertical)

2
SHOPPING CENTERS OFFICES HOTELS INDUSTRIES

HOSPITALS BROADCASTINGS TERMINALS TRANSPORTATIONS

www.aircon.co.id Edition : August 2016