Professional Documents
Culture Documents
The Work Specified in This Section Includes:: PSCA II/div1/02 35 00
The Work Specified in This Section Includes:: PSCA II/div1/02 35 00
The Work Specified in This Section Includes:: PSCA II/div1/02 35 00
Additional borings and other exploratory operations may be performed by Contractor, at the
Contractor’s option and following the Owner’s approval. No change in the Contract Sum will be
authorized for such additional exploration undertaken by the Contractor.
3. The Contractor, by careful examination, shall inform himself as to the nature and location of the
work; the conformation of the ground; the nature of the subsurface and environmental
conditions; the location of the groundwater table; the character, quality and quantity of the
materials to be encountered; conditions of the neighboring / bordering structures and utilities;
the character of the equipment and facilities needed preliminary to and during the execution of
the work; and all other matters which can in any way effect the work.
4. The Contractor shall be held to have visited the site and to have familiarized himself with the
on-site existing conditions and neighboring / bordering buildings, properties, and utilities.
5. The Contractor shall investigate the conditions of public thoroughfares and roads as to
availability, clearances, loads, limits, restrictions, and other limitations affecting transportation
to, and ingress and egress of the site. The Contractor shall conform to all New York City and
State, and Federal regulations in regard to the transportation of materials to and from and at the
job site and shall secure in advance such permits as may be required.
1.06 PROTECTION
A. Neighboring / Bordering Structures:
1. In performing the work of this Section, or any other related Section, the Contractor shall take
care so as not to affect the stability and integrity of existing neighboring / bordering buildings
and structures or induce settlements in them.
2. Prior to commencement of any work, the Contractor shall consult the records and visit existing
neighboring/bordering structures, and note all conditions and limitations which might affect the
work required under this Section.
B. Existing Utilities:
1. The contractor shall locate existing underground utilities in and beyond the areas of work. If
utilities are indicated to remain in place, provide adequate means of support and protection
during the work.
a. Should uncharted, or incorrectly charted, piping or other utilities be encountered during
the work of this Section, consult utility owner immediately for directions. Cooperate with
Owner and utility companies in keeping respective services and facilities in operation.
Repair damaged utilities to satisfaction of utility owner.
b. Do not interrupt existing utilities serving facilities occupied by Owner or others, during
occupied hours, except when permitted in writing by the Construction Manager and then
only after acceptable temporary utility services have been provided. Provide minimum of
48-hour notice to the Construction Manager, and receive written notice to proceed before
interrupting any utility.
C. The responsibility for any damage to neighboring/bordering buildings, structures, utilities, sidewalks,
pavement, and other facilities in the vicinity resulting from the Contractor’s work of this Section will be
entirely his, and he shall take whatever measures are necessary to prevent the same.
D. Monitoring:
1. The Contractor shall establish monitoring points on neighboring / bordering structures and
sidewalks, subject to the Owner’s approval, to adequately monitor and otherwise keep him
informed of the conditions of these structures and sidewalks during the work..
2. As a minimum, monitoring points shall be established at the ground level at each corner of each
neighboring / bordering structure, and at 20 ft (minimum) spacing along the ground surface
along sidewalks.
3. Additional monitoring points shall be established and monitored away from the site so as to
establish initial elevations with distance from the site.
4. Establish and monitor all elevation points to an accuracy of 0.005 ft. Measure monitoring point
elevations at least twice a week during pile installation and sheeting, bracing, and underpinning
installation, and more frequently as needed when installation is immediately adjacent to
buildings. Record and report elevation of each benchmark at least twice a week while
installation is in progress.
PSAC II 01 42 00-2 References
350 Marconi Street November 16, 2009
Bronx, New York 100% Submission
PACKAGE 2
PSCA II\div1\02 35 00
5. Should monitoring point readings indicate a displacement exceeding 0.125 inch between two
consecutive readings or a cumulative displacement exceeding 0.25 inch, halt pile installation;
excavation; and sheeting, bracing, and underpinning operations until corrective action has been
provided by the Contractor and is acceptable to the Owner and Engineer. The above threshold
criteria are tentative; it shall be the Contractor’s responsibility to monitor conditions during his
work to assure the protection requirements specified herein are maintained.
6. The above described monitoring is the minimum required. The Contractor shall establish all
necessary monitoring measures as necessary to inform him of the conditions around the site and
that his work is not adversely impacting surrounding structures.
7. Contractor shall submit his monitoring plan consisting of monitoring point locations and method
of monitoring to the Construction Manager for review by the Owner’s Geotechnical Engineer.
E. Examine drawings to determine sequence of operations, and relation to work to other trades. Start of
work will signify acceptance of field conditions and will acknowledge coordination with other trades.
1.07 SUBMITTALS
A. Contractor shall submit for approval directly to Owner's Architect/Engineer, with copy to Owner, the
following:
1. Within 15 days of the acceptance of the Proposal and prior to pile installation, submit, for the
Engineer's approval, a detailed construction procedure and schedule for all the Work related to
the installation of piles and pile caps.
2. Manufacturer’s and/or Supplier’s certificate certifying that pile material complies with the
requirements specified herein.
3. Manufacturer’s and/or Supplier’s certificate certifying that method of treatment, chemical
composition and amount of retention of the preservative complies with requirements specified
herein.
4. A scaled plan showing clearly the designation and location of all piles by an identification
system, including cut-off elevations and column lines.
5. Pile driving hammer and cushion specifications prior to the start of any pile driving operation.
6. A scaled survey showing as-built location of piles as driven. The survey shall be prepared by a
licensed Professional Surveyor and shall include off-set distances with respect to the proposed
locations, as-built cut-off elevations, and deviations from vertical. The measurements shall be
done with a precise optical surveying equipment and shall be accurate to 0.005 ft.
1.08 QUALITY ASSURANCE
A. Codes and Standards:
1. Perform work specified herein and shown on the Contract Drawings in compliance with
applicable requirements of the NYC Building Code and requirements of all state and local
authorities having jurisdiction.
B. Quality Controlled Inspections:
1. All pile installation shall be performed under full time supervision and quality control inspection
by a New York State licensed Professional Engineer.
2. Contractor shall notify Owner's Geotechnical Engineer a minimum of 24 hours prior to start of
Work subject to controlled inspection.
C. Contractor’s Responsibilities:
1. The Contractor performing the work specified herein shall have at least five years experience in installing
Timber Piles including at least three projects of equivalent size and complexity as this Contract. The
Contractor’s Professional Engineer and Professional Land Surveyor shall be licensed in good standing in
the State of New York.
2. The Contractor shall cooperate with the Geotechnical Engineer to facilitate the progress of the
work.
1.09 DELIVERY, STORAGE AND HANDLING
A. Deliver materials to the project site in such quantities and at such times to assure the continuity of pile
installation operations, and to maintain the project schedule. Carefully handle pile materials by means
PSAC II 01 42 00-3 References
350 Marconi Street November 16, 2009
Bronx, New York 100% Submission
PACKAGE 2
PSCA II\div1\02 35 00
PART 2 - MATERIALS
2. Piles shall be driven with a single action steam or air hammer with a minimum rated energy of
15,000 ft-lbs. The hammer shall be kept in first-class condition so that the length of stroke will
be accurately maintained at all times during driving. The capblock material shall have uniform
elastic properties during driving, providing superior energy transmission, and shall be replaced if
crushed, burned or damaged. Any hammer not operating in accordance with the manufacturer’s
specifications shall be deemed unsatisfactory by the Geotechnical Engineer and shall be
replaced immediately by the Contractor.
3. Air compressors shall be of sufficient capacity to provide 25 percent additional air above that
shown in the manufacturer’s specification for air-driven hammers.
C. Leads
1. The leads of the pile driving rig shall be fixed at least at two points. The points shall be at least
half the length of the leads apart in order to maintain adequate alignment.
2. Use fixed rigid type pile driver leads that will hold the pile firmly in position and in axial
alignment with the hammer to ensure support of the pile during driving. Free-swinging leads
will not be permitted. Extend leads to within 2 ft. of the elevation at which the pile enters the
ground.
3. Leads shall be of sufficient length so that the use of a follower will not be necessary. Suitable
anvils or cushions shall be used to prevent undue damage of the pile butts. Pile driving shall be
continuous for each pile.
PART 3 - EXECUTION
A. General
1. No piles shall be driven in the absence of the Geotechnical Engineer.
2. All piles shall be driven by such methods and equipment as not to impair their strength and as to
ensure pile shafts retaining the initial driving resistance and lateral support of the soil.
3. Drive all piles using approved pile driving equipment and materials (i.e. hammer, cushion,
leads, driving shoe etc) specified above.
4. The Contractor shall coordinate the work such that the pile driving shall be continuous once the
pile is 10 ft or more into the bearing stratum.
5. The piles shall be driven sufficiently into the NYC Building Code class 7-65 material below the
organic materials to provide a minimum 30 ton allowable bearing capacity.
6. Minimum final pile driving resistance over the last foot of penetration into the bearing stratum is
30 blows per foot for a 15,000 ft-lbs rated energy hammer in accordance with the ENR formula
given the NYC Building Code. Driving resistance developed in the last foot of non-bearing
materials (i.e. organic materials) shall be deducted from the final driving resistance obtained in
the bearing stratum, as required by the NYC Building Code.
7. Piles that did not reach the bearing stratum and/or that did not provide the required final driving
resistance shall be rejected. Replacement pile or piles shall be driven at locations determined by
the design engineer at no additional cost to the Owner.
8. Carefully maintain the center of gravity for each group or cluster of piles to conform to the
locations shown on the drawings. Where piles are driven out of location, the Engineer may
require that an additional pile or piles be driven at a location and in a manner, which he may
specify. The unacceptable pile may be left in place or pulled, as the Engineer directs, without
additional payment to the Contractor for driving or pulling.
9. Carefully plumb the leads and the pile before driving. Take care during driving to prevent and
to correct any tendency of piles to twist or rotate.
10. If, during the driving of any piles, and of the piles previously driven show signs of heaving or
lifting, the Contractor shall redrive such piles to the required load-bearing capacity without
additional cost to the Owner.
11. Cut-off: After each pile has been driven and accepted, cut it off at the required top elevation.
Make cut perpendicular to the axis of the pile. The cutoff ends become the property of the
Contractor who is responsible for their removal and disposal.
B. Driving Tolerances
1. Piles shall be driven at locations shown in design drawings. Location of installed piles shall not
deviate more than 3 inches in any direction from the locations shown in design drawings.
Replacement pile or piles shall be driven at locations determined by the design engineer at no
additional cost to the Owner.
2. Piles shall be driven plumb unless otherwise noted in design drawings. Deviation from vertical
for installed piles shall not exceed 2% (or 1 inch horizontal per 4 feet of length). Replacement
pile or piles shall be driven at locations determined by the design engineer at no additional cost
to the Owner.
3. Piles that were damaged, cracked or broken during and after driving shall be rejected.
Replacement pile or piles shall be driven at locations determined by the design engineer at no
additional cost to the Owner.
3.05 INSPECTION
A. Installation of piles shall be subject to quality control inspection by the Owner's Geotechnical Engineer,
on behalf of the Owner.
B. The Owner's Geotechnical Engineer shall log the driving of each pile and determine when the pile has
reached the specified depth and driving resistance.
C. No pile shall be installed without the presence of the Owner's Geotechnical Engineer.
D. The Owner's Geotechnical Engineer shall notify the Contractor immediately of any defective piles and
advise the Contractor of appropriate remedial action. The Owner's Engineer shall communicate with the
Structural Engineer for revisions, additions, or replacement piles.
3.06 DAMAGED OR DISPLACED PILES
A. Damaged piles, and piles driven outside the required driving tolerances, will not be accepted.
B. Piles rejected after driving may be withdrawn or abandoned and cut-off, and additional piles driven to
replace the rejected units at the newly designated locations
C. Piles rejected after driving may be withdrawn or abandoned and cut-off, and additional piles driven to
replace the rejected units at the newly designated locations.
D. Solidly fill spaces that are left by withdrawn piles that will not be filled by new piles, using cohesionless
soil material such as gravel, broken stone, and gravel sand mixtures. Place and compact throughout the
length of the space.
E. Drive additional pile or piles where the pile centerline deviation exceeds 3 inches and an analytical
determination indicates the load on any pile exceeds 110% of the design load.
3.07 CUTTING-OFF
A. Tops of piles shall be cut off square at the elevation indicated on the Drawings. All work necessary to
extend pilecaps to piles driven or damaged below the cutoff level shall be done at no extra cost to the
Owner. This includes, but is not limited to, excavation, sheeting, bracing, pumping, and backfilling. All
excess pieces of timber shall be removed from the site and disposed of in a legal manner by the
Contractor without any cost to the Owner.
3.08 OBSTRUCTIONS
A. No extra payment will be made to the Contractor for the overcoming of obstructions under any conditions
whatsoever.
B. Spudding, pre-augering may be performed by the Contractor at their own expense and with the approval
of the Engineer for Controlled Inspection.
C. Excavations to remove obstructions may be performed by the Contractor at their own expense.
D. Additional piles driven in another location because of obstructions at any elevation are subject to the
approval of the Engineer of Record as specified under “Damaged or Displaced Piles”. The Contractor
must provide additional piles at his own expense and pay for the redesign and additional costs involved in
construction of pile caps and tie-beam.
3.09 AS-BUILT SURVEY
A. Upon completion of the installation of piles in each area of the foundation, as determined by the Owner's
Engineer and/or Construction Manager, the Contractor shall prepare a scaled as-built survey. This as-built
survey shall include as-driven location of piles in reference to the building column lines and deviation
from vertical.
B. The as–built survey shall be submitted to the Owner's Engineer for approval before construction of the
piles caps in any area.
C. The submission of the as-built survey shall be completed in a timely manner such that if any additional or
replacement piles are required, they can be executed prior to the Contractor demobilizing off the project
site.
3.10 CLEAN-UP
A. All debris resulting from excavation of objectionable material, removal of obstruction, cut-off butts, and
any material not to remain as part of the construction is to be removed and disposed of by the Contractor
in a legal manner at no additional cost to the Owner.
B. The site shall be cleaned at frequent intervals and no material shall be stored on the site in a manner,
which would obstruct the easy access of equipment and personnel.
END OF SECTION 02350
/conversion/tmp/scratch/57000027.docx