INVENTIO AG Technical Catalog

CH – 6052 Hergiswil
 group: 1–11.350 Energy Dissipation Type Buffer OP ... K 601 125 E
execut. office: BLN 18 Installation 8106 Page 1/3

Modification 1 General Provisions


1 8323 Oil–filler opening (cap)
Fig. 1
2 9410
HPH

Contact mounted
HP

DS–ST
zr

Oil–level indicator

 Type Height HP Stroke HPH Weight GP Oil contents


any way nor used for manufacturing nor communicated
This design and information is our intellectual property.
It must without our written consent neither be copied in

[mm] [mm] without oil [kg] [l] approx.


OP11/PH175 600 175 33 2
OP10/PH270 800 270 38 3
OP12/PH420 1150 420 50 4,5
OP3/PH640 1700 640 67 6,5
OP13/PH640
to third parties.

OP4/PH1000 2600 1000 93 10


OP14/PH1000
OP5/PH1630 4300 1630 215 35
OP6/PH2550 6700 2550 570 115
Form. DS–ST 107E93
k601125e
INVENTIO AG
CH – 6052 Hergiswil Energy Dissipation Type Buffer OP ... K 601 125 E Page 2

Mod.: 2

2 Mounting Procedure
Modification
– Take care to prevent corrosion of the plunger. Oil it periodically.
1 8323
– Plinth–plates: level them precisely horizontally by means of the spirit level and fix them in concrete.
2 9310

Fig. 2 Opening for filling–in concrete

Plinth–plate
55

Plinth

– Remove the upper nuts of the plinth–plates and mount the buffer
– Adjust the buffer by means of spirit level and plumb line (use shims if necessary).

3 Oil Filling
– Remove cap of plunger cover by means of screw driver.
any way nor used for manufacturing nor communicated
This design and information is our intellectual property.
It must without our written consent neither be copied in

– Open oil level indicator, so that air can escape.


– Fill–in oil ( up to the upper marking on the oil measuring stick).
– Close the opening immediately with the cap.
Oil quality: Observe the local regulations with regard to the viscosity index and pour–point !
 Viscosity at 40 [°C]: 68 [mm2/s] (cst)
to third parties. Form. DS–ST 107E93
k601125e
INVENTIO AG
CH – 6052 Hergiswil Energy Dissipation Type Buffer OP ... K 601 125 E Page 3

Mod.: 3

4 Contact Mounting
Modification

1 8323 Fig. 3 Contact holder


2 8932
3 9410 Operating bracket
Contact groove

Approx. 1[mm] play for switching


Strap

Plunger

min. 3,5 ... 4,5 [mm]


switching path
Pressure cylinder
Strap
Operating bracket

Contact holder
any way nor used for manufacturing nor communicated
This design and information is our intellectual property.
It must without our written consent neither be copied in

– Contact holder shall be screwed down on the cylinder by hand (not tightening) by means of strap (put strap on
contact holder, but pull it not through the cutouts).
– Operating bracket shall be adjusted exactly to the middle of the contact groove and strap tightened.
– Adjust the contact to Fig. 3 (by shifting in the slotted hole).
– Operate the contact and check whether still approx. 1 [mm] play is still available.
to third parties.

5 Performance Check
When the lift is ready for service, the buffer plunger shall be slowly pushed down completely.
Check the buffer stroke and resetting of the plunger, and the function of the contact (KP/KPG).
Form. DS–ST 107E93
k601125e