PAMPHLET
on
SMPS POWER PLANT FOR TELECOM
INSTALLATIONS
End User : Supervisory & Artisan Staff
CAMTECH/S/PROJ/2015-16//PAMPH/SMPS/TELE1.0
OCTOBER - 2015
SMR
SMR MCB
MCB
SMR Module
23.10.2015 3
SYSTEM ALARM
When mains AC is within the specified limit and still battery is
discharging then there is an alarm of “MOBD”.
When the system current more than 105% of the number of
modules present excluding redundancy then there is an alarm of
“System Over Load”.
Due to any reason if module is failed and on module there is an
alarm “FR/FC FAIL” then there is an alarm of “FR/FC FAIL” on system.
When Mains AC voltage is more than 300V or less than 90 V then
there is an alarm of “AC O/R.
If the system voltage increases beyond setting value (57.1V) then
there is an alarm of “LOAD VOLT HIGH”.
When battery is discharged below 44.4 V then there is an alarm of
DC U/V.
When battery is isolated manually with the help of isolation
switches then an alarm of “BATT ISOLATED” generated.
OPERATING PROCEDURE OF MICRO CONTROLLER BASED DSCA
Disclaimer:
It is clarified that this pamphlet does not supersede any existing provisions
laid down by RDSO, Railway Board or Zonal Railways. The pamphlet is for
guidance only and it is not a statutory document.