DC SUPPLY
CRANKING DROPOUTS
Able to survive 0 V for 100 mS, providing
supply was at least 10 V before dropout and
supply recovers to 5 V. This is achieved
without the need for internal batteries.
LEDs and backlight will not be maintained
during cranking.
GENERATOR & MAINS (UTILITY)
VOLTAGE RANGE
15 V to 415 V AC (Ph to N)
26 V to 719 V AC (Ph to Ph)
KEY FEATURES • Unbalanced load protection • Start & stop capability via SMS
• Configurable power-up mode • Independent earth fault protection messaging FREQUENCY RANGE
• MPU fail delay • Breaker control via fascia buttons • 3 configurable maintenance alarms 3.5 Hz to 75 Hz
• Enhanced graphical user interface • Fuel and start outputs configurable • Compatible with a wide range of MAGNETIC PICKUP
• Drag & drop advanced PLC editor when using CAN CAN engines, including tier 4 VOLTAGE RANGE
• MSC ID within PLC GenComm • 6 configurable DC outputs engine support +/- 0.5 V to 70 V
override • 2 configurable volt-free relay • Uses DSE Configuration Suite PC FREQUENCY RANGE
• 4-Line back-lit LCD text display outputs Software for simplified 10,000 Hz (max)
• Multiple Display Languages • 6 configurable analogue/digital configuration
INPUTS
• Five key menu navigation inputs • Licence-free PC software DIGITAL INPUTS A TO H
• LCD alarm indication • Support for 0 V to 10 V & 4 mA to • IP65 rating (with supplied gasket) Negative switching
• Heated display option available 20 mA sensors offers increased resistance to water ANALOGUE INPUTS A & F
• Customisable power-up text and • 8 configurable digital inputs ingress Configurable as:
images • Configurable 5 stage dummy load • Modules can be integrated into Negative switching digital input
0 V to 10 V sensor
• DSENet expansion compatibility and load shedding outputs building management systems 4 mA to 20 mA sensor
• Data logging facility • CAN, MPU and alternator (BMS) using MODBUS RTU Resistive sensor
• Internal PLC editor frequency speed sensing in one
ANALOGUE INPUTS B, C, D & E
• Protections disable feature variant KEY BENEFITS Configurable as:
• Fully configurable via PC using • Real time clock • Automatically transfers between Negative switching digital input
USB, RS232 & RS485 • Manual and automatic fuel pump mains (utility) and generator Resistive sensor
monitoring (kW, kvar, kVA, pf) RS232 or RS485 for accurate suit a wide range of applications for PANEL CUT-OUT
• Mains current and power engine hours balancing. user flexibility 220 mm x 160 mm
8.7” x 6.3”
monitoring (kW, kvar, kVA, pf) • MODBUS RTU support with • PLC editor allows user configurable
(DSE7320 MKII only) configurable MODBUS pages. functions to meet user specific MAXIMUM PANEL THICKNESS
• kW and kvar overload and reverse • Advanced SMS messaging application requirements. 8 mm
0.3”
power alarms (additional external modem
• Over current protection required) STORAGE TEMPERATURE RANGE
-40°C to +85°C
-40 °F to +185 °F
Deep Sea Electronics Plc maintains a policy of continuous development and reserves the right to change Registered in England & Wales No.01319649
the details shown on this data sheet without prior notice. The contents are intended for guidance only. VAT No.316923457 055-203/12/20 (2) US
DSEGenset®
ELECTRO-MAGNETIC COMPATIBILITY
SHOCK
BS EN 60068-2-27
Three shocks in each of three major axes
15 gn in 11 mS
DEGREES OF PROTECTION
PROVIDED BY ENCLOSURES
BS EN 60529
IP65 - Front of module when installed into the
control panel with the supplied sealing gasket.
DEUTZ
DSE7310/20 MKII ISUZU
PERKINS
CATERPILLAR
MTU
7 VOLVO
CUMMINS
OTHER SCANIA
MAINS (UTILITY) N/C VOLT FREE GENERATOR/ N/O VOLT FREE GENERATOR CHARGE FUEL & CRANK ELECTRONIC
SENSING OUTPUT LOAD CURRENT OUTPUT SENSING ALTERNATOR OUTPUTS ENGINES &
DSE7320 MKII ONLY (Flexible with CAN) MAGNETIC PICK-UP
VOLTS VOLTS D+
W/ L +
ISO 9001
Registered
Quality
Managem
ent 015