Download as pdf or txt
Download as pdf or txt
You are on page 1of 7

Rectangular Duct

RECTANGULAR DUCT
2000
ATAI is the leading HVAC Ductwork manufacturer in the Kingdom of Saudi Arabia. With leading edge
computer technology used in the design and manufacture of ducting, ATAI designs, configures and manu-
factures through Quality Accredited procedures (ISO 9001:2000) and hence meet every standard the
HVAC industry has to offer.

Design is carried out using Autocad as well as the capabilities of a full compliment of a design engineering
team qualified and experienced in HVAC Systems design and specification.

We have successfully completed large projects all over the Middle East where the two acknowledged
industry standards, DW144 and SMACNA were specified by world class consultants. We also manu-
facture ducting to customized specifications that may be required.

Besides working with clients in the Middle East we have served clients from as far as Egypt and Cyprus in
the north to Yemen and Sudan in the south. Through this wide market we have developed a transport
PAGE 1.1.1

network and an expertise to meet customer requirements in any GCC country, in fact anywhere in the
Region.
Rectangular Duct & Fittings
RECTANGULAR DUCT

DESCRIPTION

2000
Ductwork Manufactured to the following specifications:
* SMACNA
* DW144
* EUROVENT
Galvanized steel to ASTM A653 G90 zinc coating lock forming quality
* Painted or Epoxy Coating
* Plain end or flanged
* Black mild steel
* Aluminum
* Stainless Steel

Thickness:
* 0.4 mm thk. up to 3mm thk

Standard Straight Length 1200mm


PAGE 1.1.2
Rectangular Straight Duct

LONGITUDINAL
A SEAM
gth
d len
n dar
sta m
m 5m TRANSVERSE
0 0m 30
12 C CONNECTOR
RECTANGULAR DUCT

H B BEADING

W RECTANGULAR STANDARD
STRAIGHT DUCT
1200 mm Length
SPECIFICATION

A SEAM B BEADING C CONNECTOR

PITTSBURG SEAMS Beading standard distance is For connector details, refer to


Small Pittsburg for 26 to 22 ga. at every 305mm interval , up ATAI standard Duct construction
to 18 ga. steel thickness only. Schedule

2000
5/16"
Beading is only for standard
straight length of 1200mm

Duct shorter than 1200mm


Largest Pittsburg for 20 to 16 ga. and fittings will use cross-
breaking.

1/2"

Button Punch Snap Lock


PAGE 1.1.4

Butt Weld
Rectangular Fittings

W1-Width on end 1 W1-Width on end 1 W1-Width on end 1


W2-Width on end 2 W2-Width on end 2 W2-Width on end 2
H -Duct height H -Duct height H -Duct height
H W1
ST -Square throat ST -Square throat ST - Square throat
length (ATAI length (ATAI length (ATAI
standard is standard is standard is
ST
W1 127mm length 127mm length 127mm length
Q

W2 H
W2 H
H
W2
ST ST

Q - Degree

1 SQUARE THROAT ELBOW 45 DEGREES TAP 3 ANGLED ELBOW


2
1 Fitting no.1 if no vanes 45 degrees branch tap on main 3 Fitting no. 3 if no vanes
1V Fitting no.iv if with vanes 2 duct. 3V Fitting no. 3v if with vanes

RECTANGULAR DUCT
W1-Width on end 1 W1-Width on end 1
W1-Width on end 1 W2-Width on end 2 W2-Width on end 2
W2-Width on end 2 H W2 H -Duct height W2 H -Duct height
H
H -Duct height ST -Square throat L - Length
R - Radius length (ATAI O - Offset
Centerline rod ST standard is
= 3W = Std. Rod 127mm length
2 H - Duct height
Q - Degree
W1

H L
-If H on both ends
O are not the same,
W2
-If H on both ends H H indicate elevation
W1
are not the same, W3
indicate elevation ST

4 RADIUS TAP 5 TEE DOG LEG OFFSET EQUAL


6
Vanes depending on elbow 5 Fitting no.5 if no vanes ENDS
4 width 5V Fitting no.5V if with vanes 9
W1-Width on end 1 W1-Width on end 1 W1-Width on end 1
W2

2000
H W2 W2-Width on end 2 W2-Width on end 2 W2-Width on end 2
H H W2
H -Duct height H -Duct height H -Duct height
L - Length L - Length L - Length
-If H on both ends O - Offset
are not the same,
L indicate elevation L
L

-If H on both ends -If H on both ends


are not the same, O are not the same,
W1 H
W1 H W1
indicate elevation H indicate elevation
7 STRAIGHT SIDE TRANSITION 8 EQUAL SIDE TRANSITION 9 DOG LEG OFFSET UNEQUAL
10 Fitting no. 10 if transition is on right 13 Fitting no. 13 if offset is on left side,
11 side, and ftg. no.11 if inverted 12 14 and ftg. no.14 if inverted
W-Width W - Width W - Width
H -Duct height H -Duct height H -Duct height
H W H STRAIGHT TAP CONN.
R - Radius W L -Length L -Length
L - Length H
W
L R=L L
R 45¼
L
PAGE 1.1.5

CLINCH LOCKER
CLINCH LOCKER
CLINCH LOCKER

10 RADIUS TAP 45 DEGREES TAP 12


Radiused branch tap on main
11
45 degrees branch tap on main
STRAIGHT TAP CONN.
15 Straight branch tap on main duct.
duct. 16 duct. 17
Rectangular Fittings with Vanes

W = Duct width
ST= Throat, ATAI standard is 127mm but can vary
Q = Elbow degrees
RECTANGULAR DUCT

ST

ST

W = Duct width O

ST= Throat, ATAI standard


is 127mm but can vary
1 2
SQUARE THROAT ELBOW ANGLED ELBOW
1v with TURNING VANES 3v with TURNING VANES

W = Duct width
ST= Throat, ATAI standard is 127mm but can vary

2000
* SHORT BENDS

W = Up to 300mm no splitter
W = Over 300mm up to 500mm, 1 no. splitter. (W)
3
W
W = Over 500mm up to 1000mm, 2 no. splitter. (W,W )
6 2
ST W = Over 1000mm, 3 no. splitter. ( W , W, W )
12 4 2
PAGE 1.1.6

* LONG BENDS - (R=W), no splitter required.

3 TEE 4
RADIUS ELBOW
with TURNING VANES with SPLITTER VANES
5v 4
Rectangular Duct Accessories

26

RECTANGULAR DUCT
TURNING VANES
AEROFOIL SECTION AEROFOIL SECTION
TURNING VANES PROFILE

2000 PAGE 1.1.7

TURNING VANES
PERFORATED
AEROFOIL
TURNING VANES
SECTION
AEROFOIL SECTION
Rectangular Duct Accessories

A
B
C

D
RECTANGULAR DUCT

3" 3" or 4" 3"


(10" MAX. )

1/2 "

METAL FIRE RETARDANT METAL


FABRIC
FOLDED AS SHOWN ABOVE
E WITH SEALANT AND STAPLED
AT EVERY 1" INTERVALS
Flexible connector is commonly used

1 as adaptor between duct work and


units to avoid transfer of vibration and
noise due to it. 2 3

2000
FLEXIBLE CONNECTOR TO UNIT TYPICAL END JOINT OF FIRE TYPICAL SECTION DETAIL OF

A- Flame retardant fabric RETARDANT FABRIC CONNECTION BETWEEN THE


B- Metal edge adaptor METAL EDGE AND FIRE
C- Fabric joint. See detail No.2
D- Metal joint folded and pinned on edge.
E- Flexible Connector ends vary depending
RETARDANT FABRIC.
on requirement.
PAGE 1.1.8

You might also like