Professional Documents
Culture Documents
Engineering Systems LTD.: PROJECT: 90 KLPD Distillery Plant Section: Air Cooled Condenser Client
Engineering Systems LTD.: PROJECT: 90 KLPD Distillery Plant Section: Air Cooled Condenser Client
5 Cable Entry : From Top through detachable gland plates, 3mm Thk
15 Incomer Section : MCCB - TP, 630 Amp(Vendor to Specify), 55KA, O/L & S/C Protection
Voltmeter, Ammeter, KWH Meter (Multispan make) & Indication Lamps with
16 Metering Section : proper isolation, Swelctor Switches & necessary accessories as reqd.Ammeter
For Each VFD
As per the attaced Motor List ( Doc.No. MES/E&I/MES 407/ 002) All Outgoing
17 Outgoing Feeders
Feeders should be with MPCB/MCCB design.
3. All Push Buttons, Indication Lamps, Selctor Switches should be of Teknic make Only.
5. Energy Meter Should be of Schneider make model no. EM6436 with pulse output.
6. For Incomer Section consider 3 Nos Auxillary Contactor with 10 No. terminals for Phase Failure Feedback to
Notes: PLC
7. Axillary Relays should be of OMRON make only. Model No. MY2N with Socket & Pin
Air Cooled Condenser-301 For 5.5 7.5 10 75HP 13 25 *** 9-15 Working
3 ACC-301 A 160A TP
Integrated Evaporator VFD
5.5 7.5 10 13 25 *** 9-15 Working
Page 3 of 5
Contactor Rating
Motor Rating OLR
Full VFD (A)
Sr. Starter MPCB/ Feeder
Tag No. Description Load Incomer
No. Type MCCB Main Status
KW HP Current MCCB Star Amps
/Delta
Air Cooled Condenser-301 For 5.5 7.5 10 75HP 13 25 *** 9-15 Working
4 ACC-301 B 160A TP
Integrated Evaporator VFD
5.5 7.5 10 13 25 *** 9-15 Working
Air Cooled Condenser-302 For 5.5 7.5 10 60HP 13 25 *** 9-15 Working
5 ACC-302A 160A TP
Independent Evaporator VFD
5.5 7.5 10 13 25 *** 9-15 Working
Page 4 of 5
Contactor Rating
Motor Rating OLR
Full VFD (A)
Sr. Starter MPCB/ Feeder
Tag No. Description Load Incomer
No. Type MCCB Main Status
KW HP Current MCCB Star Amps
/Delta
Air Cooled Condenser-302 For 5.5 7.5 10 60HP 13 25 *** 9-15 Working
6 ACC-302A 160A TP
Independent Evaporator VFD
5.5 7.5 10 13 25 *** 9-15 Working
Page 5 of 5