FlexTop 2211 Universal Transmitter

Safety instructions
This instrument is built and tested according to the current EU-direc-
tives and packed in technically safe condition. In order to maintain this
condition and to ensure safe operation, the user must follow the hints
and warnings given in this instruction.
During the installation the valid national rules have to be observed.
Ignoring the warnings may lead to severe personal injury or substantial
damage to property.
The product must be operated by trained staff. Correct and safe
operation of this equipment is dependent on proper transport, storage,
installation and operation.
All electrical wiring must conform to local standards. In order to prevent
stray electrical radiation, we recommend twisted and shielded input
cables, as also to keep power supply cables separated from the input
cables. The connection must be made according to the connecting
diagrams.
Before switching on the power supply take care that other equipment
is not affected. Ensure that the supply voltage and the conditions in the
environment comply with the specification of the device.
Before switching off the supply voltage check the possible effects on
other equipment and the processing system.
WARNING
For electrical installation and commissioning of explosion protected
devices, the data given in the conformity cer tificate as also the local
regulations for installation of electrical apparatus within explosion pro-
tected areas must be considered. The intrinsically safe versions can be
mounted in the explosion hazarded area according to its specification
only connected to a certified intrinsically safe supply loop with the cor-
responding electrical values.

Non-Ex Application
RTD 230 Vac

3 4
5 4

6 3

- + 2 1

1 2
- +
+ -
4...20 mA 24 Vdc
FlexView FlexTop 2211 Power supply

This Ex-approved product is manufactured by:


Baumer A/S
Jacob Knudsens Vej 14
DK-8230 Aabyhoej
Denmark

www.baumer.com Installation Manual 5850-032


Design and specifications subject to change without notice Page 1
Configuring with FlexProgrammer
FlexProgrammer
Note:
Disconnect loop supply before
connecting the FlexProgrammer
1
2 1 to FlexTop 2211. FlexProgrammer
2

FlexProgrammer 9701
2 1 Red clip
1

2
Black clip

Note: Ambient temperature range 0...50°C

The FlexTop 2211 can be configured, using the 4...20 mA cable. The indication for a correct configuration sequence is:
The maximum distance depends on the cable type, resistance and 1) The LED on the FlexTop 2211 lights up constantly.
capacity. We recommend to use screened cables.
To be able to configure the FlexTop 2211 with the FlexProgrammer the Error indications during configuration:
dedicated software, Flex-program, must be loaded on the PC. 1) The LED on the FlexTop 2211 is not lighting.
The Flex-program has help menus for all functions. 3) An error message comes up on the PC.
During the configuration the new data are, by means of the FlexPro-
grammer, transferred from the PC to the FlexTop 2211, where they are Note: During the first power-up after a configuration the power-on time
stored in the internal memory. increases to approx. 10 sec.

Ex-Configuring
None of the two types of FlexProgrammer configuring unit must be
connected to the FlexView within the hazardous area.
Configuring procedure:
a) Disconnect mains from the 4...20 mA loop circuit.
b) Disconnect the FlexTop 2211 from the circuitry within
the hazardous area.
c) Bring the FlexTop 2211 to the safe area.
d) Connect the FlexProgrammer and perform the
configuring session.
e) Re-install the FlexTop 2211 in the hazardous area.
f) Connect the power supply to the circuit.

LED Function
The LED of the FlexTop indicate the actual status of the measured
value. The LED will be turned on continually as long as the measured
value result in an output current between 4 and 20mA. If the output
current is higher than 20mA or lower than 4mA the LED will twinkle
with 1Hz. The same twinkling behavior will occur if a sensor break
error is detected.

www.baumer.com Installation Manual 5850-032


Design and specifications subject to change without notice Page 2
Ex-Application
A FlexTop 2211 with type number 2221 0002 is approved for Ex ia IIC Sensor circuit parameters (terminals 3 to 6):
T5/T6 and ATEX II 1G. VDC < 6.6 V; IDC < 17 mA; Pout < 30m W; La < 99 mH; Ca < 3µF.
The FlexTop 2211 must be connected in the 4...20 mA loop circuit only.
The installation of FlexTop 2211 must be done in accordance with
prevailing guidelines for zones 0 or 1. FlexTop 2211 must be mounted in a housing, e.g. ø80mm stainless
steel housing (type number 81 43-110), DIN-B housing (type number
An Ex ia certified zener or isolation barrier with the entity parameters 81 43-120) or the like.
Vmax < 30 VDC; Imax < 0.1 A; Pmax < 0.75 W must be used. Refer to page 3 for futher technical data.

The FlexTop 2211 entity parameters (terminals + to -) are: WARNING


Li < 15 µH; Ci < 5 nF. This product contains no replaceable parts.
In case of malfunction the product must be shipped to Baumer for
repair.

Ex-Connection Diagram/Control Drawing

RTD Zone 0/1 Safe area 230 Vac

3 4

5 4

6 3

2 1 - +
- + 1 2
+ -
4...20 mA 24 Vdc

FlexTop 2211 Barrier FlexView Power Supply

Ex nA II T5, ATEX II 3G - Installation


A FlexTop 2211-0003 is Ex nA II T5, ATEX II 3G approved for ap- Ex-data
plication in hasardous areas in accordance with the current EU-direc-
Supply range 12...30 VDC, Max. 0,1A
tives. The product must be mounted in a suitable enclosures fulfilling
relevant requirement in EN 60 079-0 among these minimum IP54 Temperature class T1...T5.
ingress protection.

www.baumer.com Installation Manual 5850-032


Design and specifications subject to change without notice Page 3
Electrical Installation
RTD T/C Potentiometer Resistance

+
R R
T /C

No cable Internal CJC- No compensation {3} No compensation {3}


compensation {3} compensation

RTD T/C Potentiometer Resistance

+
R R

5850-032/ B1 This data sheet may only be reproduced in full.


RTD T /C

3-wire cable External CJC-compensation 3-wire compensation for 3-wire cable


compensation No cable compensation {3} transfer resistance {4} compensation

RTD T/C Potentiometer Resistance

R R
+

RTD T /C

4-wire cable External CJC-compensation 4-wire compensation for 4-wire cable


compensation 3-wire cable compensation transfer resistance {4} compensation

Current measurement Voltage measurement Notes


{3} Configurable compensation for cable resistance
{4} Transfer resistance between element and wiper

Accessories
R

I
+

Dimensional drawing
The FlexProgrammer 9701 is a dedicated tool to configure all
ø44 26.3 Baumer configurable products.

Type No. 9701-0001 complies:


FlexProgrammer
ø6 33 Cable with 2 aligator clips
Cable from FlexProgrammer to M12 plug for TE2
ø4 mounting hole. Cable from FlexProgrammer to M12 Plug for LFFS, LBFS and CPX
Spring loaded USB cable
mounting screws. CD with the FlexProgram software

www.baumer.com Installation Manual 5850-032


Design and specifications subject to change without notice Page 4