OWNER
PT PLN ( PERSERO )
UNIT INDUK PEMBANGUNAN SUMATERA BAGIAN SELATAN
Jl. Residen A. Rozak No. 2180, Sekojo Palembang 30118
CONTRACTOR
KONSORSIUM WIJATI-HASTA
Jl. Let Jend S Parman No. 52 Semarang 50232
Telp. 024 8441546 ( Hunting 7 Lines ) Fax. 024 8315360
PROJECT
DRAWING TITTLE
TECHNICAL SPECIFICATION
70 kV POWER CABLE ACCESSORIES (TERMINATION)
GITET 500 kV MUARA ENIM
SCALE :
A4 0015PJ-03ME-E/L-00-S7-118-02 1
TECHNICAL PARTICULARS AND GUARANTEES
PEMBANGUNAN EXT IBT-3 GITET 500/275 kV MUARA ENIM
NO. UNIT REQUIRED PROPOSED AND GUARANTEE PROPOSED AND GUARANTEE (DRM)
NO. UNIT REQUIRED PROPOSED AND GUARANTEE PROPOSED AND GUARANTEE (DRM)
1 Product Name to be mentioned Link Box for Earthing Link Box for Earthing
2 Type Designation to be mentioned For Termination/Straight Joint UEEBE1Q002
3 Application Outdoor/Manhole Outdoor / Manhole Outdoor / Manhole
4 Cabinet Stainless Steel Stainless Steel Stainless Steel
5 Support Insulator to be mentioned Epoxy Insulator Epoxy Insulator
6 Disconnect Link Bar to be mentioned MC Nylon MC Nylon
7 Gland For Bonding Cable to be mentioned Coppre Lug Coppre Lug
8 Gland For Earthing Cable to be mentioned Coppre Lug Coppre Lug
9 Busbar to be mentioned Tinned Copper Tinned Copper
10 Door Fixing Bolt to be mentioned Stainless Steel Stainless Steel
11 Box Earthing Bar Stainless Steel Stainless Steel Stainless Steel
12 Index Protection Rating IP54 (outdoor) Over than IP67/ Over than IP67 Over than IP67/ Over than IP67
NO. UNIT REQUIRED PROPOSED AND GUARANTEE PROPOSED AND GUARANTEE (DRM)
1 Product Name to be mentioned Link Box with SVL Link Box with SVL
2 Type Designation to be mentioned For Termination/Straight Joint UEEBS2Q002
3 Application Outdoor/Manhole Outdoor / Manhole Outdoor / Manhole
4 Cabinet Stainless Steel Stainless Steel Stainless Steel
5 Support Insulator to be mentioned Epoxy Insulator Epoxy Insulator
6 Cable Flexon to be mentioned Tape & Tube Tape & Tube
7 Surge Arrester ( SVL )
- Material to be mentioned Zinc Non Linear Resistor Zinc Non Linear Resistor
- Rated Voltage kV to be mentioned to be submitted 6kV
- Max. Voltage kV to be mentioned to be submitted 5kV (MCOV)
6.7kV (TOV)
8 Gland For Bonding Cable to be mentioned Coppre Lug Coppre Lug
9 Gland For Earthing Cable to be mentioned Coppre Lug Coppre Lug
10 Busbar to be mentioned Tinned Copper Tinned Copper
11 Protection Cover to be mentioned Stainless Steel Stainless Steel
12 Support Bar to be mentioned Epoxy Insulator Epoxy Insulator
13 Box Earthing Bar to be mentioned Stainless Steel Stainless Steel
14 Door Fixing Bolt to be mentioned Stainless Steel Stainless Steel
15 Index Protection Rating IP54 (outdoor) Over than IP67 Over than IP67
Specification
For
70kV XLPE Power Cable Accessory
1. Scope
2. Reference Standards
■ IEC 60840 : Power cables with extruded insulation and their accessories for rated voltages above 30kV(Um=36kV)
up to 150kV(Um=170kV)
4. Tests
5. Packing
All accessories shall be covered with strong wooden box, and each wooden box shall be marked with particulars of
accessories, i.e. description, size, quantity, gross and net weights, etc.
6. Reference Drawings
Item
Descriptions Drawing No.
No.
1 OUTDOOR SEALING END FOR 70kV XLPE CABLE UEMA06Q002
2 LINK BOX FOR EARTHING(1-1 WAY) UEEBE1Q002
3 LINK BOX WITH SVL(3-1 WAY, 2SVL) UEEBS3Q002
Doc. No. : LSPA20-S045
Rev. No. : 3
Page No. : 3 of 3
7.1 General
All materials shall be stored in a dry warehouse protected from the sunrays. Cases must be laid on a flat without loads
over them. Room temperature shall be controlled less than 35℃ and humidity also shall be less controlled than 50%.
Some components, in particular tapes and putties, could have a decay of physical characteristics due to storage time and
ambient temperature. Assuming the ambient temperature of the warehouse between 0 ℃ and 35 ℃, the following
storage time could be guaranteed:
UEMA06Q002
NTS MM 0
NOTE
UEEBE1Q002
NTS MM 0
NOTE
UEEBS3Q002
NTS MM 0
TECHNICAL SPECIFICATION
Low Voltage Cable (for cross bonding)
1.8/3 (3.6) kV, N2XCY (Cu/XLPE/CWS/PVC)
1. Applicable standard
The construction of cables shall be based on SNI IEC 60502-1.
Conductor Circular stranded of annealed copper wires, complied with IEC 60228.
Metallic screen Annealed copper wires applied concentrically than wrapped with binder tape
3. Cable identification
One lines of a distinctive marking shall be performed continuously on a suitable place of the surface of the
outer sheath by embossing or printing.
SNI IEC 60502-1 VOKSEL Cu/XLPE/CWS/PVC (N2XCY) 1 x 240/120 mm² 1.8/3 (3.6) kV
4. Test
The following test shall be carried out on complete cable and sample in accordance with SNI IEC 60502-1 and
the manufacturer standard.
1. Construction test
2. Conductor resistance test
3. AC voltage test
XLPE Insulation
Project No. :
Use/Customer :
Bid Title :
This paper shows the short-circuit current rating of the cable conductor.
Where:
IAD: short-circuit current calculated on an adiabatic basis 40.2 [kA]
ε: factor to allow for heat loss into the adjacent component 1.02
f
2AD .t 2 S 2 ln → IAD = 40.23 [kA]
i
where:
t: duration of short circuit 1 [sec]
K Constant depending on the material of the current carrying component 226 [As1/2/mm²]
S geometrical cross-sectional area of the current carrying component 240 [mm²]
θ f: final temperature 250 [ºC]
θi : initial temperature 45 [ºC]
β: reciprocal of temperature coefficient of resistance of the 234.5 [K]
current carrying component at 0ºC
2.3 Calculation of non-adiabatic factor for conductor
t t
1 FA F 2 B 1.02205
S S
where:
F Factor to account for imperfect thermal contact between conductor or wires and surround-ing or 0.7
adjacent non metallic materials
A, B Empirical constants based on the thermal properties of the surrounding or adjacent non- [(mm²/s)1/2]
metallic materials
C1 i
A where, C1 = 2464 [mm/m] 0.9657 [(mm²/s)1/2]
C i
C2 i
B where, C2 = 1.22 [K.m.mm²/J] 0.4685 [(mm²/s)1/2]
C i
σc Volumetric specific heat of the current carrying component 2.50E+6
σi Volumetric specific heat of the surrounding or adjacent non-metallic materials 2.40E+6
ρi Thermal resistivity of the surrounding or adjacent non-metallic materials 2.5 [K.m/W]
3. Conclusion
From the calculation above, we can observe that the calculated short circuit current for conductor (cable) withstand
short circuit rating 41.1 kA for 1 second.
LS-VINA Cable & System
South of Binh Bridge street, So Dau, Hong Bang, Hai Phong, Vietnam. Tel. 84.225 3529 786 Fax. 84.225 3824 969
Dear Sir,
This is to inform you that Bonding Cable 1.8/3 kV N2XCY 240mm2 will be sufficient to meet short circuit 40kA/1
sec according to IEC 60949 as per enclosed calculation.
Thank you for your attention.
Yours Truly,
Signed :
Name : Shi Wan Chun
Title : Sales Director