Produced on 19/02/2021 with Xpress Selection V9.1.0 - database DIL 16.1.

Project name CLINICA INTERNACIONAL


Project address Peru
Reference LIMA
Client name AKFGROUP
Revision GCM_01

Selection parameters of the indoor units can be found under the chapter Indoor unit details
Selection parameters of the outdoor units can be found under the chapter Outdoor unit details
Only the data published in the data book are correct. This program uses close approximations of these data.

1. Material List
Model Type Model Name Qty Description
Outdoor unit RXQ16TAYM 2 Cooling only VRV IV(TAYM)
RXQ8TAYM 6 Cooling only VRV IV(TAYM)
Indoor unit FXMQ125PAVE 3 VRV M-PA - Unidad de conducto montada en el techo
FXMQ140PAVE 2 VRV M-PA - Unidad de conducto montada en el techo
FXMQ32PAVE 28 VRV M-PA - Unidad de conducto montada en el techo
FXMQ80PAVE 1 VRV M-PA - Unidad de conducto montada en el techo
Branch unit KHRP26A22T 16 Refnet branch piping kit
KHRP26A33T 8 Refnet branch piping kit
KHRP26A72T 2 Refnet branch piping kit
Option or add-on BRC1E63 34 Wired Remote Controller (Navigation Remote Controller)

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 1
2. Indoor Unit Details
2.1. Table of Abbreviations
Name Logical name of the device
FCU Device model name
Tmp C Indoor conditions in cooling (dry bulb temp. / wet bulb temp.)
Rq TC Required total cooling capacity
Max TC Available total cooling capacity
Max SC Available sensible cooling capacity
Tevap Evaporating temperature of indoor unit coil
Tdis C Indoor unit discharge air temperature in cooling
Airflow Supplied airflow
Sound Sound pressure low and high
PS Power supply (voltage and phases)
MCA Minimum Circuit Amps
WxHxD WidthxHeightxDepth
Wght Weight of the device

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 2
2.2. ACCU-R-1 - RXQ8TAYM
Capacity data at conditions and connection ratio (94%) as entered
Name FCU Tmp C Rq TC Max TC Max SC Tevap Tdis C Airflow
°F Ton Ton Ton °F °F cfm
Tel/Data Closet FXMQ32PAVE 80.0 / 67.0 1.0 1.0 0.7 Auto 55.9 335
Tel/Data Closet FXMQ32PAVE 80.0 / 67.0 1.0 1.0 0.7 Auto 55.9 335
Tel/Data Closet FXMQ32PAVE 80.0 / 67.0 1.0 1.0 0.7 Auto 55.9 335
Tel/Data Closet FXMQ32PAVE 80.0 / 67.0 1.0 1.0 0.7 Auto 55.9 335
Tel/Data Closet FXMQ32PAVE 80.0 / 67.0 1.0 1.0 0.7 Auto 55.9 335
Tel/Data Closet FXMQ32PAVE 80.0 / 67.0 1.0 1.0 0.7 Auto 55.9 335

Required cooling capacity towards the outdoor unit: 6.0Ton.

The calculation shows the peak discharge temperatures (lowest temperature in case of cooling mode / highest
temperature in case of heating mode), assuming the indoor unit is running at full load at the given indoor
temperature design conditions. In practice the discharge temperature will modulate based on actual capacity
requirements and during defrost mode (heating mode).
The analysis of the suction and discharge temperature values may help in preventing a cold draft and to ensure a
thermal comfort level.

Name Sound PS MCA WxHxD Wght


dBA A mm kg
Tel/Data Closet 30-34 220V 1ph 0.6 550×300×700 25
Tel/Data Closet 30-34 220V 1ph 0.6 550×300×700 25
Tel/Data Closet 30-34 220V 1ph 0.6 550×300×700 25
Tel/Data Closet 30-34 220V 1ph 0.6 550×300×700 25
Tel/Data Closet 30-34 220V 1ph 0.6 550×300×700 25
Tel/Data Closet 30-34 220V 1ph 0.6 550×300×700 25

Outdoor unit placed at the same level as the indoor units.

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 3
2.3. ACCU-R-2 - RXQ8TAYM
Capacity data at conditions and connection ratio (94%) as entered
Name FCU Tmp C Rq TC Max TC Max SC Tevap Tdis C Airflow
°F Ton Ton Ton °F °F cfm
Tel/Data Closet FXMQ32PAVE 80.0 / 67.0 1.0 1.0 0.7 Auto 55.9 335
Tel/Data Closet FXMQ32PAVE 80.0 / 67.0 1.0 1.0 0.7 Auto 55.9 335
Tel/Data Closet FXMQ32PAVE 80.0 / 67.0 1.0 1.0 0.7 Auto 55.9 335
Tel/Data Closet FXMQ32PAVE 80.0 / 67.0 1.0 1.0 0.7 Auto 55.9 335
Tel/Data Closet FXMQ32PAVE 80.0 / 67.0 1.0 1.0 0.7 Auto 55.9 335
Tel/Data Closet FXMQ32PAVE 80.0 / 67.0 1.0 1.0 0.7 Auto 55.9 335

Required cooling capacity towards the outdoor unit: 6.0Ton.

The calculation shows the peak discharge temperatures (lowest temperature in case of cooling mode / highest
temperature in case of heating mode), assuming the indoor unit is running at full load at the given indoor
temperature design conditions. In practice the discharge temperature will modulate based on actual capacity
requirements and during defrost mode (heating mode).
The analysis of the suction and discharge temperature values may help in preventing a cold draft and to ensure a
thermal comfort level.

Name Sound PS MCA WxHxD Wght


dBA A mm kg
Tel/Data Closet 30-34 220V 1ph 0.6 550×300×700 25
Tel/Data Closet 30-34 220V 1ph 0.6 550×300×700 25
Tel/Data Closet 30-34 220V 1ph 0.6 550×300×700 25
Tel/Data Closet 30-34 220V 1ph 0.6 550×300×700 25
Tel/Data Closet 30-34 220V 1ph 0.6 550×300×700 25
Tel/Data Closet 30-34 220V 1ph 0.6 550×300×700 25

Outdoor unit placed at the same level as the indoor units.

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 4
2.4. ACCU-4-1_First part - RXQ8TAYM
Capacity data at conditions and connection ratio (62%) as entered
Name FCU Tmp C Rq TC Max TC Max SC Tevap Tdis C Airflow
°F Ton Ton Ton °F °F cfm
Tel/Data Closet FXMQ32PAVE 80.0 / 67.0 1.0 1.0 0.7 Auto 55.9 335
Tel/Data Closet FXMQ32PAVE 80.0 / 67.0 1.0 1.0 0.7 Auto 55.9 335
Tel/Data Closet FXMQ32PAVE 80.0 / 67.0 1.0 1.0 0.7 Auto 55.9 335
Tel/Data Closet FXMQ32PAVE 80.0 / 67.0 1.0 1.0 0.7 Auto 55.9 335

Required cooling capacity towards the outdoor unit: 4.0Ton.

The calculation shows the peak discharge temperatures (lowest temperature in case of cooling mode / highest
temperature in case of heating mode), assuming the indoor unit is running at full load at the given indoor
temperature design conditions. In practice the discharge temperature will modulate based on actual capacity
requirements and during defrost mode (heating mode).
The analysis of the suction and discharge temperature values may help in preventing a cold draft and to ensure a
thermal comfort level.

Name Sound PS MCA WxHxD Wght


dBA A mm kg
Tel/Data Closet 30-34 220V 1ph 0.6 550×300×700 25
Tel/Data Closet 30-34 220V 1ph 0.6 550×300×700 25
Tel/Data Closet 30-34 220V 1ph 0.6 550×300×700 25
Tel/Data Closet 30-34 220V 1ph 0.6 550×300×700 25

Outdoor unit placed at the same level as the indoor units.

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 5
2.5. ACCU-4-1_Second part - RXQ8TAYM
Capacity data at conditions and connection ratio (62%) as entered
Name FCU Tmp C Rq TC Max TC Max SC Tevap Tdis C Airflow
°F Ton Ton Ton °F °F cfm
Tel/Data Closet FXMQ32PAVE 80.0 / 67.0 1.0 1.0 0.7 Auto 55.9 335
Tel/Data Closet FXMQ32PAVE 80.0 / 67.0 1.0 1.0 0.7 Auto 55.9 335
Tel/Data Closet FXMQ32PAVE 80.0 / 67.0 1.0 1.0 0.7 Auto 55.9 335
Tel/Data Closet FXMQ32PAVE 80.0 / 67.0 1.0 1.0 0.7 Auto 55.9 335

Required cooling capacity towards the outdoor unit: 4.0Ton.

The calculation shows the peak discharge temperatures (lowest temperature in case of cooling mode / highest
temperature in case of heating mode), assuming the indoor unit is running at full load at the given indoor
temperature design conditions. In practice the discharge temperature will modulate based on actual capacity
requirements and during defrost mode (heating mode).
The analysis of the suction and discharge temperature values may help in preventing a cold draft and to ensure a
thermal comfort level.

Name Sound PS MCA WxHxD Wght


dBA A mm kg
Tel/Data Closet 30-34 220V 1ph 0.6 550×300×700 25
Tel/Data Closet 30-34 220V 1ph 0.6 550×300×700 25
Tel/Data Closet 30-34 220V 1ph 0.6 550×300×700 25
Tel/Data Closet 30-34 220V 1ph 0.6 550×300×700 25

Outdoor unit placed at the same level as the indoor units.

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 6
2.6. ACCU-4-2_First part - RXQ8TAYM
Capacity data at conditions and connection ratio (62%) as entered
Name FCU Tmp C Rq TC Max TC Max SC Tevap Tdis C Airflow
°F Ton Ton Ton °F °F cfm
Tel/Data Closet FXMQ32PAVE 80.0 / 67.0 1.0 1.0 0.7 Auto 55.9 335
Tel/Data Closet FXMQ32PAVE 80.0 / 67.0 1.0 1.0 0.7 Auto 55.9 335
Tel/Data Closet FXMQ32PAVE 80.0 / 67.0 1.0 1.0 0.7 Auto 55.9 335
Tel/Data Closet FXMQ32PAVE 80.0 / 67.0 1.0 1.0 0.7 Auto 55.9 335

Required cooling capacity towards the outdoor unit: 4.0Ton.

The calculation shows the peak discharge temperatures (lowest temperature in case of cooling mode / highest
temperature in case of heating mode), assuming the indoor unit is running at full load at the given indoor
temperature design conditions. In practice the discharge temperature will modulate based on actual capacity
requirements and during defrost mode (heating mode).
The analysis of the suction and discharge temperature values may help in preventing a cold draft and to ensure a
thermal comfort level.

Name Sound PS MCA WxHxD Wght


dBA A mm kg
Tel/Data Closet 30-34 220V 1ph 0.6 550×300×700 25
Tel/Data Closet 30-34 220V 1ph 0.6 550×300×700 25
Tel/Data Closet 30-34 220V 1ph 0.6 550×300×700 25
Tel/Data Closet 30-34 220V 1ph 0.6 550×300×700 25

Outdoor unit placed at the same level as the indoor units.

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 7
2.7. ACCU-4-2_Second part - RXQ8TAYM
Capacity data at conditions and connection ratio (62%) as entered
Name FCU Tmp C Rq TC Max TC Max SC Tevap Tdis C Airflow
°F Ton Ton Ton °F °F cfm
Tel/Data Closet FXMQ32PAVE 80.0 / 67.0 1.0 1.0 0.7 Auto 55.9 335
Tel/Data Closet FXMQ32PAVE 80.0 / 67.0 1.0 1.0 0.7 Auto 55.9 335
Tel/Data Closet FXMQ32PAVE 80.0 / 67.0 1.0 1.0 0.7 Auto 55.9 335
Tel/Data Closet FXMQ32PAVE 80.0 / 67.0 1.0 1.0 0.7 Auto 55.9 335

Required cooling capacity towards the outdoor unit: 4.0Ton.

The calculation shows the peak discharge temperatures (lowest temperature in case of cooling mode / highest
temperature in case of heating mode), assuming the indoor unit is running at full load at the given indoor
temperature design conditions. In practice the discharge temperature will modulate based on actual capacity
requirements and during defrost mode (heating mode).
The analysis of the suction and discharge temperature values may help in preventing a cold draft and to ensure a
thermal comfort level.

Name Sound PS MCA WxHxD Wght


dBA A mm kg
Tel/Data Closet 30-34 220V 1ph 0.6 550×300×700 25
Tel/Data Closet 30-34 220V 1ph 0.6 550×300×700 25
Tel/Data Closet 30-34 220V 1ph 0.6 550×300×700 25
Tel/Data Closet 30-34 220V 1ph 0.6 550×300×700 25

Outdoor unit placed at the same level as the indoor units.

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 8
2.8. ACCU-4-3 - RXQ16TAYM
Capacity data at conditions and connection ratio (94%) as entered
Name FCU Tmp C Rq TC Max TC Max SC Tevap Tdis C Airflow
°F Ton Ton Ton °F °F cfm
Data Center FXMQ125PAVE 80.0 / 67.0 4.0 4.0 2.8 Auto 57.7 1377
Data Center FXMQ125PAVE 80.0 / 67.0 4.0 4.0 2.8 Auto 57.7 1377
Data Center FXMQ125PAVE 80.0 / 67.0 4.0 4.0 2.8 Auto 57.7 1377

Required cooling capacity towards the outdoor unit: 12.0Ton.

The calculation shows the peak discharge temperatures (lowest temperature in case of cooling mode / highest
temperature in case of heating mode), assuming the indoor unit is running at full load at the given indoor
temperature design conditions. In practice the discharge temperature will modulate based on actual capacity
requirements and during defrost mode (heating mode).
The analysis of the suction and discharge temperature values may help in preventing a cold draft and to ensure a
thermal comfort level.

Name Sound PS MCA WxHxD Wght


dBA A mm kg
Data Center 40-44 220V 1ph 3.4 1400×300×700 45
Data Center 40-44 220V 1ph 3.4 1400×300×700 45
Data Center 40-44 220V 1ph 3.4 1400×300×700 45

Outdoor unit placed at the same level as the indoor units.

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 9
2.9. ACCU-4-4 - RXQ16TAYM
Capacity data at conditions and connection ratio (90%) as entered
Name FCU Tmp C Rq TC Max TC Max SC Tevap Tdis C Airflow
°F Ton Ton Ton °F °F cfm
Compressor Room FXMQ140PAVE 80.0 / 67.0 4.5 4.6 3.2 Auto 58.3 1624
Compressor Room FXMQ140PAVE 80.0 / 67.0 4.5 4.6 3.2 Auto 58.3 1624
Vacuum Room FXMQ80PAVE 80.0 / 67.0 2.5 2.6 1.9 Auto 56.9 883

Required cooling capacity towards the outdoor unit: 11.5Ton.

The calculation shows the peak discharge temperatures (lowest temperature in case of cooling mode / highest
temperature in case of heating mode), assuming the indoor unit is running at full load at the given indoor
temperature design conditions. In practice the discharge temperature will modulate based on actual capacity
requirements and during defrost mode (heating mode).
The analysis of the suction and discharge temperature values may help in preventing a cold draft and to ensure a
thermal comfort level.

Name Sound PS MCA WxHxD Wght


dBA A mm kg
Compressor Room 43-46 220V 1ph 3.4 1400×300×700 46
Compressor Room 43-46 220V 1ph 3.4 1400×300×700 46
Vacuum Room 39-43 220V 1ph 2.3 1000×300×700 35

Outdoor unit placed at the same level as the indoor units.

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 10
3. Outdoor Unit Details
3.1. Table of Abbreviations
Name Logical name of the device
Model Device model name
Tmp C Outdoor temperature in cooling
CC Available cooling capacity
Rq CC Required cooling capacity
EER EER at nominal conditions for standard efficiency series (nominal temperatures, 100% connection ratio and
without considering pipe length corrections)
Tmp H Outdoor conditions in heating (dry bulb temp. / wet bulb temp.)
HC Available heating capacity (integrated heating capacity)
Rq HC Required heating capacity
COP COP at nominal conditions for standard efficiency series (nominal temperatures, 100% connection ratio and
without considering pipe length corrections)
Piping Largest distance from indoor unit to outdoor unit
Bse Refr Standard factory refrigerant charge (5m actual piping length)
excluding extra refrigerant charge
For calculation of extra refrigerant charge refer to the databook
PS Power supply (voltage and phases)
MCA Minimum Circuit Amps
WxHxD WidthxHeightxDepth
Wght Weight of the device

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 11
3.2. Outdoor Details
Name Model Comb Tmp C CC Rq CC EER (*) Tmp H HC Rq HC COP (*)
% °F Ton Ton W/W °F Ton Ton W/W
ACCU-R-1 RXQ8TAYM 94 83.9 6.7 6.0 4.3
ACCU-R-2 RXQ8TAYM 94 83.9 6.7 6.0 4.3
ACCU-4-1_First part RXQ8TAYM 62 83.9 6.7 4.0 4.3
ACCU-4-1_Second part RXQ8TAYM 62 83.9 6.7 4.0 4.3
ACCU-4-2_First part RXQ8TAYM 62 83.9 6.7 4.0 4.3
ACCU-4-2_Second part RXQ8TAYM 62 83.9 6.7 4.0 4.3
ACCU-4-3 RXQ16TAYM 94 83.9 13.5 12.0 3.5
ACCU-4-4 RXQ16TAYM 90 83.9 13.5 11.5 3.5

(*) The EER and COP values are calculated at nominal conditions: nominal temperatures, 100% connection ratio
and without considering pipe length corrections.

Name Model Piping Refrigerant


m Type Bse Refr Ex Refr
kg kg
ACCU-R-1 RXQ8TAYM 7.5 R410A 5.9 n/a
ACCU-R-2 RXQ8TAYM 7.5 R410A 5.9 n/a
ACCU-4-1_First part RXQ8TAYM 7.5 R410A 5.9 n/a
ACCU-4-1_Second part RXQ8TAYM 7.5 R410A 5.9 n/a
ACCU-4-2_First part RXQ8TAYM 7.5 R410A 5.9 n/a
ACCU-4-2_Second part RXQ8TAYM 7.5 R410A 5.9 n/a
ACCU-4-3 RXQ16TAYM 7.5 R410A 10.4 n/a
ACCU-4-4 RXQ16TAYM 7.5 R410A 10.4 n/a

Name Model PS MCA WxHxD Wght


A mm kg
ACCU-R-1 RXQ8TAYM 380V 3ph 16.1 930×1657×765 185
ACCU-R-2 RXQ8TAYM 380V 3ph 16.1 930×1657×765 185
ACCU-4-1_First part RXQ8TAYM 380V 3ph 16.1 930×1657×765 185
ACCU-4-1_Second part RXQ8TAYM 380V 3ph 16.1 930×1657×765 185
ACCU-4-2_First part RXQ8TAYM 380V 3ph 16.1 930×1657×765 185
ACCU-4-2_Second part RXQ8TAYM 380V 3ph 16.1 930×1657×765 185
ACCU-4-3 RXQ16TAYM 380V 3ph 31 1240×1657×765 285
ACCU-4-4 RXQ16TAYM 380V 3ph 31 1240×1657×765 285

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 12
3.2.1. ACCU-R-1 - RXQ8TAYM

Model Type Model Name Qty Description


Outdoor unit RXQ8TAYM 1 Cooling only VRV IV(TAYM)
Indoor unit FXMQ32PAVE 6 VRV M-PA - Unidad de conducto montada en el techo
Branch unit KHRP26A22T 4 Refnet branch piping kit
KHRP26A33T 1 Refnet branch piping kit
Option or add-on BRC1E63 6 Wired Remote Controller (Navigation Remote Controller)

The capacity for 14.0-15.9CWB are at VRT powerful mode.

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 13
3.2.2. ACCU-R-2 - RXQ8TAYM

Model Type Model Name Qty Description


Outdoor unit RXQ8TAYM 1 Cooling only VRV IV(TAYM)
Indoor unit FXMQ32PAVE 6 VRV M-PA - Unidad de conducto montada en el techo
Branch unit KHRP26A22T 4 Refnet branch piping kit
KHRP26A33T 1 Refnet branch piping kit
Option or add-on BRC1E63 6 Wired Remote Controller (Navigation Remote Controller)

The capacity for 14.0-15.9CWB are at VRT powerful mode.

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 14
3.2.3. ACCU-4-1_First part - RXQ8TAYM

Model Type Model Name Qty Description


Outdoor unit RXQ8TAYM 1 Cooling only VRV IV(TAYM)
Indoor unit FXMQ32PAVE 4 VRV M-PA - Unidad de conducto montada en el techo
Branch unit KHRP26A22T 2 Refnet branch piping kit
KHRP26A33T 1 Refnet branch piping kit
Option or add-on BRC1E63 4 Wired Remote Controller (Navigation Remote Controller)

The capacity for 14.0-15.9CWB are at VRT powerful mode.

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 15
3.2.4. ACCU-4-1_Second part - RXQ8TAYM

Model Type Model Name Qty Description


Outdoor unit RXQ8TAYM 1 Cooling only VRV IV(TAYM)
Indoor unit FXMQ32PAVE 4 VRV M-PA - Unidad de conducto montada en el techo
Branch unit KHRP26A22T 2 Refnet branch piping kit
KHRP26A33T 1 Refnet branch piping kit
Option or add-on BRC1E63 4 Wired Remote Controller (Navigation Remote Controller)

The capacity for 14.0-15.9CWB are at VRT powerful mode.

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 16
3.2.5. ACCU-4-2_First part - RXQ8TAYM

Model Type Model Name Qty Description


Outdoor unit RXQ8TAYM 1 Cooling only VRV IV(TAYM)
Indoor unit FXMQ32PAVE 4 VRV M-PA - Unidad de conducto montada en el techo
Branch unit KHRP26A22T 2 Refnet branch piping kit
KHRP26A33T 1 Refnet branch piping kit
Option or add-on BRC1E63 4 Wired Remote Controller (Navigation Remote Controller)

The capacity for 14.0-15.9CWB are at VRT powerful mode.

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 17
3.2.6. ACCU-4-2_Second part - RXQ8TAYM

Model Type Model Name Qty Description


Outdoor unit RXQ8TAYM 1 Cooling only VRV IV(TAYM)
Indoor unit FXMQ32PAVE 4 VRV M-PA - Unidad de conducto montada en el techo
Branch unit KHRP26A22T 2 Refnet branch piping kit
KHRP26A33T 1 Refnet branch piping kit
Option or add-on BRC1E63 4 Wired Remote Controller (Navigation Remote Controller)

The capacity for 14.0-15.9CWB are at VRT powerful mode.

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 18
3.2.7. ACCU-4-3 - RXQ16TAYM

Model Type Model Name Qty Description


Outdoor unit RXQ16TAYM 1 Cooling only VRV IV(TAYM)
Indoor unit FXMQ125PAVE 3 VRV M-PA - Unidad de conducto montada en el techo
Branch unit KHRP26A33T 1 Refnet branch piping kit
KHRP26A72T 1 Refnet branch piping kit
Option or add-on BRC1E63 3 Wired Remote Controller (Navigation Remote Controller)

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 19
3.2.8. ACCU-4-4 - RXQ16TAYM

Model Type Model Name Qty Description


Outdoor unit RXQ16TAYM 1 Cooling only VRV IV(TAYM)
Indoor unit FXMQ140PAVE 2 VRV M-PA - Unidad de conducto montada en el techo
FXMQ80PAVE 1 VRV M-PA - Unidad de conducto montada en el techo
Branch unit KHRP26A33T 1 Refnet branch piping kit
KHRP26A72T 1 Refnet branch piping kit
Option or add-on BRC1E63 3 Wired Remote Controller (Navigation Remote Controller)

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 20
4. Piping Diagrams
Pipes marked with a short red stripe in the diagrams must be connected to the device with a reducing joint.

4.1. Piping ACCU-R-1


ACCU-R-1
RXQ8TAYM

⅜"×¾" ¼"×½"
KHRP26A33T

Tel/Data Closet
FXMQ32PAVE

⅜"×¾" ¼"×½"
KHRP26A22T

Tel/Data Closet
FXMQ32PAVE

⅜"×⅝" ¼"×½"
KHRP26A22T

Tel/Data Closet
FXMQ32PAVE

⅜"×⅝" ¼"×½"
KHRP26A22T

Tel/Data Closet
FXMQ32PAVE

⅜"×⅝" ¼"×½"
KHRP26A22T

Tel/Data Closet
FXMQ32PAVE

¼"×½"

Tel/Data Closet
FXMQ32PAVE

Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a
different pipe diameter might be required.

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 21
4.2. Piping ACCU-R-2
ACCU-R-2
RXQ8TAYM

⅜"×¾" ¼"×½"
KHRP26A33T

Tel/Data Closet
FXMQ32PAVE

⅜"×¾" ¼"×½"
KHRP26A22T

Tel/Data Closet
FXMQ32PAVE

⅜"×⅝" ¼"×½"
KHRP26A22T

Tel/Data Closet
FXMQ32PAVE

⅜"×⅝" ¼"×½"
KHRP26A22T

Tel/Data Closet
FXMQ32PAVE

⅜"×⅝" ¼"×½"
KHRP26A22T

Tel/Data Closet
FXMQ32PAVE

¼"×½"

Tel/Data Closet
FXMQ32PAVE

Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a
different pipe diameter might be required.

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 22
4.3. Piping ACCU-4-1_First part
ACCU-4-1_First part
RXQ8TAYM

⅜"×¾" ¼"×½"
KHRP26A33T

Tel/Data Closet
FXMQ32PAVE

⅜"×⅝" ¼"×½"
KHRP26A22T

Tel/Data Closet
FXMQ32PAVE

⅜"×⅝" ¼"×½"
KHRP26A22T

Tel/Data Closet
FXMQ32PAVE

¼"×½"

Tel/Data Closet
FXMQ32PAVE

Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a
different pipe diameter might be required.

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 23
4.4. Piping ACCU-4-1_Second part
ACCU-4-1_Second part
RXQ8TAYM

⅜"×¾" ¼"×½"
KHRP26A33T

Tel/Data Closet
FXMQ32PAVE

⅜"×⅝" ¼"×½"
KHRP26A22T

Tel/Data Closet
FXMQ32PAVE

⅜"×⅝" ¼"×½"
KHRP26A22T

Tel/Data Closet
FXMQ32PAVE

¼"×½"

Tel/Data Closet
FXMQ32PAVE

Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a
different pipe diameter might be required.

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 24
4.5. Piping ACCU-4-2_First part
ACCU-4-2_First part
RXQ8TAYM

⅜"×¾" ¼"×½"
KHRP26A33T

Tel/Data Closet
FXMQ32PAVE

⅜"×⅝" ¼"×½"
KHRP26A22T

Tel/Data Closet
FXMQ32PAVE

⅜"×⅝" ¼"×½"
KHRP26A22T

Tel/Data Closet
FXMQ32PAVE

¼"×½"

Tel/Data Closet
FXMQ32PAVE

Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a
different pipe diameter might be required.

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 25
4.6. Piping ACCU-4-2_Second part
ACCU-4-2_Second part
RXQ8TAYM

⅜"×¾" ¼"×½"
KHRP26A33T

Tel/Data Closet
FXMQ32PAVE

⅜"×⅝" ¼"×½"
KHRP26A22T

Tel/Data Closet
FXMQ32PAVE

⅜"×⅝" ¼"×½"
KHRP26A22T

Tel/Data Closet
FXMQ32PAVE

¼"×½"

Tel/Data Closet
FXMQ32PAVE

Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a
different pipe diameter might be required.

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 26
4.7. Piping ACCU-4-3
ACCU-4-3
RXQ16TAYM

½"×1⅛" ⅜"×⅝"
KHRP26A72T

Data Center
FXMQ125PAVE

⅜"×⅞" ⅜"×⅝"
KHRP26A33T

Data Center
FXMQ125PAVE

⅜"×⅝"

Data Center
FXMQ125PAVE

Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a
different pipe diameter might be required.

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 27
4.8. Piping ACCU-4-4
ACCU-4-4
RXQ16TAYM

½"×1⅛" ⅜"×⅝"
KHRP26A72T

Compressor Room
FXMQ140PAVE

⅜"×⅞" ⅜"×⅝"
KHRP26A33T

Compressor Room
FXMQ140PAVE

⅜"×⅝"

Vacuum Room
FXMQ80PAVE

Warning: The pipe diameter values are purely indicative. Depending on the required pipe lengths, a
different pipe diameter might be required.

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 28
5. Wiring Diagrams
P1P2 = Please select the cable type and size in accordance with the databook.
F1F2 = Please select the cable type and size in accordance with the databook.

5.1. Wiring ACCU-R-1


P1,P2
ACCU-R-1 Tel/Data Closet BRC1E63
RXQ8TAYM FXMQ32PAVE
IN F1,F2 F1,F2
L1,L2,L3,N 16.1A 3ph L, N 0.6A 1ph
P1,P2
Tel/Data Closet BRC1E63
FXMQ32PAVE
F1,F2
L, N 0.6A 1ph
P1,P2
Tel/Data Closet BRC1E63
FXMQ32PAVE
F1,F2
L, N 0.6A 1ph
P1,P2
Tel/Data Closet BRC1E63
FXMQ32PAVE
F1,F2
L, N 0.6A 1ph
P1,P2
Tel/Data Closet BRC1E63
FXMQ32PAVE
F1,F2
L, N 0.6A 1ph
P1,P2
Tel/Data Closet BRC1E63
FXMQ32PAVE
F1,F2
L, N 0.6A 1ph

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 29
5.2. Wiring ACCU-R-2
P1,P2
ACCU-R-2 Tel/Data Closet BRC1E63
RXQ8TAYM FXMQ32PAVE
IN F1,F2 F1,F2
L1,L2,L3,N 16.1A 3ph L, N 0.6A 1ph
P1,P2
Tel/Data Closet BRC1E63
FXMQ32PAVE
F1,F2
L, N 0.6A 1ph
P1,P2
Tel/Data Closet BRC1E63
FXMQ32PAVE
F1,F2
L, N 0.6A 1ph
P1,P2
Tel/Data Closet BRC1E63
FXMQ32PAVE
F1,F2
L, N 0.6A 1ph
P1,P2
Tel/Data Closet BRC1E63
FXMQ32PAVE
F1,F2
L, N 0.6A 1ph
P1,P2
Tel/Data Closet BRC1E63
FXMQ32PAVE
F1,F2
L, N 0.6A 1ph

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 30
5.3. Wiring ACCU-4-1_First part
P1,P2
ACCU-4-1_First part Tel/Data Closet BRC1E63
RXQ8TAYM FXMQ32PAVE
IN F1,F2 F1,F2
L1,L2,L3,N 16.1A 3ph L, N 0.6A 1ph
P1,P2
Tel/Data Closet BRC1E63
FXMQ32PAVE
F1,F2
L, N 0.6A 1ph
P1,P2
Tel/Data Closet BRC1E63
FXMQ32PAVE
F1,F2
L, N 0.6A 1ph
P1,P2
Tel/Data Closet BRC1E63
FXMQ32PAVE
F1,F2
L, N 0.6A 1ph

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 31
5.4. Wiring ACCU-4-1_Second part
P1,P2
ACCU-4-1_Second part Tel/Data Closet BRC1E63
RXQ8TAYM FXMQ32PAVE
IN F1,F2 F1,F2
L1,L2,L3,N 16.1A 3ph L, N 0.6A 1ph
P1,P2
Tel/Data Closet BRC1E63
FXMQ32PAVE
F1,F2
L, N 0.6A 1ph
P1,P2
Tel/Data Closet BRC1E63
FXMQ32PAVE
F1,F2
L, N 0.6A 1ph
P1,P2
Tel/Data Closet BRC1E63
FXMQ32PAVE
F1,F2
L, N 0.6A 1ph

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 32
5.5. Wiring ACCU-4-2_First part
P1,P2
ACCU-4-2_First part Tel/Data Closet BRC1E63
RXQ8TAYM FXMQ32PAVE
IN F1,F2 F1,F2
L1,L2,L3,N 16.1A 3ph L, N 0.6A 1ph
P1,P2
Tel/Data Closet BRC1E63
FXMQ32PAVE
F1,F2
L, N 0.6A 1ph
P1,P2
Tel/Data Closet BRC1E63
FXMQ32PAVE
F1,F2
L, N 0.6A 1ph
P1,P2
Tel/Data Closet BRC1E63
FXMQ32PAVE
F1,F2
L, N 0.6A 1ph

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 33
5.6. Wiring ACCU-4-2_Second part
P1,P2
ACCU-4-2_Second part Tel/Data Closet BRC1E63
RXQ8TAYM FXMQ32PAVE
IN F1,F2 F1,F2
L1,L2,L3,N 16.1A 3ph L, N 0.6A 1ph
P1,P2
Tel/Data Closet BRC1E63
FXMQ32PAVE
F1,F2
L, N 0.6A 1ph
P1,P2
Tel/Data Closet BRC1E63
FXMQ32PAVE
F1,F2
L, N 0.6A 1ph
P1,P2
Tel/Data Closet BRC1E63
FXMQ32PAVE
F1,F2
L, N 0.6A 1ph

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 34
5.7. Wiring ACCU-4-3
P1,P2
ACCU-4-3 Data Center BRC1E63
RXQ16TAYM FXMQ125PAVE
IN F1,F2 F1,F2
L1,L2,L3,N 31A 3ph L, N 3.4A 1ph
P1,P2
Data Center BRC1E63
FXMQ125PAVE
F1,F2
L, N 3.4A 1ph
P1,P2
Data Center BRC1E63
FXMQ125PAVE
F1,F2
L, N 3.4A 1ph

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 35
5.8. Wiring ACCU-4-4
P1,P2
ACCU-4-4 Compressor Room BRC1E63
RXQ16TAYM FXMQ140PAVE
IN F1,F2 F1,F2
L1,L2,L3,N 31A 3ph L, N 3.4A 1ph
P1,P2
Compressor Room BRC1E63
FXMQ140PAVE
F1,F2
L, N 3.4A 1ph
P1,P2
Vacuum Room BRC1E63
FXMQ80PAVE
F1,F2
L, N 2.3A 1ph

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 36
6. Device Options

The Xpress Selection Program is property of Daikin Europe NV. Daikin Europe NV cannot be held liable for any inaccuracy, reliability of the outcome of the Xpress Selection
Program.

SPEC IN
GCM
Page 37