Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 4

Main Contractor: Owner: Consultant: Project Name:

Toshka 3 (220/66/22 KV) GIS S/S


Date: Page:
SEP, 2021 1 of 4
Vendor: Document Number:

Sieyuan
Title.

CT PRIMARY INJECTION TEST

Test Report

for

220 KV GIS CT Primary Injection

Company MADKOUR WITNESSED BY (EETC)


Name
Signature
Date
Main Contractor: Owner: Consultant: Project Name:
Toshka 3 (220/66/22 KV) GIS S/S
Date: Page:
SEP, 2021 2 of 4
Vendor: Document Number:

Sieyuan
Title.

CT PRIMARY INJECTION TEST

Bay: W502 (AL ALMAIN-1)


Test Procedure:
 Check that all circuits are closed and tightened.
 Inject primary current on the CT terminals.
 Take the secondary readings on each circuit.
 Check core identification by shorting each core and check absence of secondary
current on the circuit.
 All the mentioned measuring points are according to the approved schematics.

Core No. CT Ratio Class


1 1250-2500/1 0.5M5
2 1250-2500/1 5P30
3 1250-2500/1 5P30
4 1250-2500/1 5P30

Company MADKOUR WITNESSED BY (EETC)


Name
Signature
Date
Main Contractor: Owner: Consultant: Project Name:
Toshka 3 (220/66/22 KV) GIS S/S
Date: Page:
SEP, 2021 3 of 4
Vendor: Document Number:

Sieyuan
Title.

CT PRIMARY INJECTION TEST

CORE-1: Used for Distance Protection Relay


 Injected Current = 300 A

Measured
Phase Reading in Relay (F301)
Current (A)
R I1
S I2
T I3
N N

CORE-2: Used for Bus Bar and Backup Protection


 Injected Current = 300 A

Measured Reading in Relay Measured


Phase Reading in Relay (A301)
Current (A) (A201) Current (A)

R I1 I1
S I2 I2
T I3 I3
N N N

Company MADKOUR WITNESSED BY (EETC)


Name
Signature
Date
Main Contractor: Owner: Consultant: Project Name:
Toshka 3 (220/66/22 KV) GIS S/S
Date: Page:
SEP, 2021 4 of 4
Vendor: Document Number:

Sieyuan
Title.

CT PRIMARY INJECTION TEST

CORE-3: Used for Metering


 Injected Current = 300 A

Reading in Measured Reading in Measured


Phase
Multi-Meter (P101) Current (A) Multi-Meter (P50) Current (A)
R I1 I1
S I2 I2
T I3 I3
N - - - -

Reading in Measured
Phase
Energy Meter (P302) Current (A)
R I1
S I2
T I3
N - -

Company MADKOUR WITNESSED BY (EETC)


Name
Signature
Date

You might also like