General Specifications
Gas Turbine
• Mercury™50 Recuperated Gas Turbine • NEMA Class F Insulation with F Rise • Turbine Compressor Cleaning
• Industrial, Single-Shaft • Continuous Duty Rating Voltages: Systems
• 10-Stage Axial Compressor – 3300, 6600, 11,000 (50Hz) – On-Crank
– Variable Inlet Guide Vanes and – 4160, 6900, 12,470, 13,800V(60 – Portable Cleaning Tank*
Stators Hz) • Package Power
– Compression Ratio: 9.9:1 Package – 120VDC Battery/Charger System*
– Inlet Airflow: 39.2 lb/sec • Mechanical Construction • Turbotronic ® 4 On-skid Gas Turbine
(17.9 kg/sec) – Steel Base Frame with Drip Pans Control System
– Vertically Split Case and Generator Alignment – Combination Gas Turbine and
• Combustion Chamber, Annular Type – 316L Stainless Steel Piping Control System
– Ultra-Lean-Premix Combustion • Start System – Standard Display with Discrete Event
System – Direct Drive AC Motor with Log, Strip Chart, Historical Trend,
– 8 Fuel Injectors VFD Control Mainteneace Screen
– Single Torch Ignitor System • Package Electrical Certification – Vibration and Temperature Monitoring
• Proximity Probe Vibration Transducers – NEC, CSA Class 1, Group D, Div 2 – English Display Text and Labels
• Turbine • Fuel System – Spanish, Portuguese, German,
– 2-Stage, Reaction – Natural Gas French or Simplified Chinese
– Clockwise Rotation – Landfill Gas* Display Text and Labels*
• Bearings – Digester Gas* – Auxiliary and Remote Display/
– 2 Radial: Viscous Damped • Integrated Lube Oil System Control Terminals*
Roller Bearings – Main/Pre/Post Lube – Auto Synchronizing
– 1 Thrust/Radial: Viscous Damped PumpBackupLube Pump – KW Import Control
Split Inner Race Ball Bearing – Air and Oil Cooler – KVAR/Power Factor Control*
– Water/Oil Lube Oil Cooler* – ControlNet Redundant Media,
Recuperator
– Integral Lube Oil Tank Ethernet, Data Highway Plus or
• Primary Surface Type Modbus RS232C/422/485 Supervisory
– Lube Oil Tank Heater
– Simplex Lube Oil Filter Interface*
Main Reduction Drive – Heat Recovery Application Interface*
– Duplex Lube Oil Filters*
• Epicyclic – Oil Mist Eliminator – Multi-Unit Applications: Load Shed
– 1500 or 1800 rpm (50 or 60 Hz) – Vent Flame Trap Control, Import/Export or kW/KVAR
– Vibration Monitoring: Acceleration • Air Inlet and Exhaust Systems Control Panels*
Transducer – Carbon Steel – InSight System™ Equipment Health
Generator – Stainless Steel* Management
• 4 Pole, 3 Phase, 6 Wire, – Barrier Type Filters – Printer/Logger
Wye Connected, Synchronous with – Self-Cleaning Filters • Documentation
Permanent Magnet Exciter – Inlet and Exhaust Silencers – Drawings
• Available Construction Type: – Inlet Evaporative Cooler* – Quality Control Data Book
– Open Drip-Proof – Inlet Chiller Coils* – Test Reports
• Sleeve Bearings • Enclosure – Operation and Maintenance Manuals
• Vibration Monitoring: Velocity – Complete Package • Factory Testing of Turbine and Package
Transducers – Fire Detection and CO2 – Non-Dynamic
• Class F Temperature Rise Suppresion System – Dynamic
• Class B Temperature Rise*
* Option
MERCURY 50
Recuperated Gas Turbine Generator Set
Power Generation
Power (kW)
Chilling (Absorp.) 5140 kW
(140,400 lb/hr) (1460 refrigeration tons)
4000
(690°F)
3000
*ASSUMPTIONS 2500
0 10 20 30 40 50 60 70 80 90 100 110 120
Nominal rating – per ISO Ambient Temperature (Deg F)
At 15°C (59°F), sea level DSM50PG_002M
No inlet/exhaust losses
Relative humidity 60%
Natural gas fuel with
LHV = 35 MJ/Nm3 (940 Btu/scf)
Heat Rate Thermal Efficiency
11000 42.
No accessory losses
Engine efficiency: 38.5% 10500 40
(measured at generator terminals)
Heat Rate (Btu/kW-hr)
10000 38
9000
34
8500
32
8000
0 10 20 30 40 50 60 70 80 90 100 110 120 30.
Ambient Temperature (Deg F) 0 10 20 30 40 50 60 70 80 90 100 110 120
DSM50PG_004M
Ambient Temperature (Deg F)
DSM50PG_003M
MINIMUM
CLEARANCE
3.2 m 4.0 m
REQUIRED
(10’ 5”) FOR (13’ 0”)
ENGINE REMOVAL
11.1 m 4.9 m
(36’ 6”) (16’ 0”)
Package Height: 3.7m (12’ 3”)