EXPANSION TANK VOLUME CALCULATION

PROJECT : AL-Nabaa Azeem Hospital

E VS
VT =
Pa Pa

Pf Po

Where :

SYMBOL DESCRIPTION EQUATION RESULTS

Percent Increase in the


volume of water in the system From Table 15 in Carrier Design Manual
E at chilled water higher
0.9
(Chapter 2. Water Piping)
temperature (%)
Chilled water piping system water volume
Total volume of water in the (Gallons) + Chiller water volume (Gallons) +
Vs 9627.835
system (gallons) AHU'S water volume (Gallons) + FCU'S water
volume (Gallons)

Pressure in the expansion


tank when water first enters,
Pa Atmospheric pressure 33.456
usualy atmospheric pressure
(feet of water absolute)

Initial fill or minimum


Pf pressure at the expansion City water pressure 66.000
tank (feet of water absolute)

Pump Head (feet of water Summation of Dynamic Losses existing in the


HP 150.000
absolute) chilled water piping system

Expansion Tank Level Height Height from the expansion tank level to the
LH 0.000
(meters) highest point in the chilled water piping system

{ Height from the expansion tank level to the


Static Head Affecting on the highest point in the chilled water piping system
SH Expansion Tank (feet of water 3 0.000
(m) x Water density (1000 kg/m ) x Specific
absolute) 2
Gravity (9.8 m/s ) } ÷ 2989

Pump Head (feet of water absolute) + City water


Maximum operating pressure
pressure (feet of water absolute) + Static head
Po at the expansion tank (feet of 216.000
depending on expansion tank location in the
water absolute)
chilled water circuit (feet of water absolute)

Minimum capacity of the tank


VT See Above Equation 251.622
(gallons)

● Finally We Can Select The Expansion Tank At A Tank Volume Of :


251.622 Gallons
952.491 Liters
0.952 Meter³
● Also We Can Select The Expansion Tank At A Maximum Operating Pressure Of :
216.000 Feet Of Water
6.456 Bar
93.639 Psi
● Notes :
* The Pump Water Volume is Neglected as It Is Considered As A Very Small Value.
* The Above Equation is Based On Carrier Design Manual (Chapter 2. Water Piping)
EXPANSION TANK VOLUME CALCULATION

PROJECT : AL-Nabaa Azeem Hospital

CHILLED WATER PIPING SYSTEM WATER VOLUME

Water Mass per Unit


Pipe Size {inch} Length {m} Water Volume {m³}
Length {kg/m}
1/2 0 0.196 0.000

3/4 670 0.344 0.230

1 1300 0.558 0.725

1 1/4 950 0.965 0.917


1 1/2 500 1.313 0.657

2 600 2.165 1.299

2 1/2 350 3.089 1.081


3 300 4.769 1.431

4 230 8.213 1.889


5 150 13.43 2.015

6 200 18.64 3.728


8 75 32.28 2.421

10 30 50.87 1.526
12 150 72.97 10.946

14 0 88.96 0.000

16 0 117.8 0.000
18 0 150.8 0.000

20 0 187.4 0.000

TOTAL CHILLED WATER PIPING SYSTEM VOLUME (M³) 28.864

TOTAL CHILLED WATER PIPING SYSTEM VOLUME


8768.870
(GALLONS)
● Notes :
The Above Water Mass Per Unit Length Is Taken From ASHRAE (HVAC
Systems And Equipment Chapter 40)
EXPANSION TANK VOLUME CALCULATION

PROJECT : AL-Nabaa Azeem Hospital

CHILLER WATER VOLUME

Operating Weight Shipping Weight


Unit Unit Qty. Water Volume {m³}
(kg) (kg)

CHILLER 4 9300 8800 2.000

TOTAL CHILLER WATER VOLUME (M³) 2.000

TOTAL CHILLER WATER VOLUME (GALLONS) 528.346

● Notes :

1- The Above Operating And Shipping Weight Are Taken From Chiller Submittal.

2- The Above Chiller Quantity Are For Both Active & Stand-By Chillers.
EXPANSION TANK VOLUME CALCULATION
PROJECT : AL-Nabaa Azeem Hospital

AIR HANDLING UNITS WATER VOLUME

Coil Tube Water Mass


Coil Tube No. of Length of Total Length
Outside per Unit Water
Unit Nominal No. of Rows Tubes per Each Tube of Coil
Diameter Length Volume {m³}
Size (inch) Row {m} Tubes {m}
(inch) {kg/m}

AHU-1 3/8 1/2 7 34 1.37 326.06 0.094 0.031

AHU-2 3/8 1/2 7 22 1.083 166.782 0.094 0.016

AHU-3 3/8 1/2 7 22 0.923 142.142 0.094 0.013

AHU-4 3/8 1/2 7 22 1.1 169.4 0.094 0.016

AHU-5 3/8 1/2 7 22 1 154 0.094 0.014

AHU-6 3/8 1/2 7 22 1 154 0.094 0.014

AHU-7 3/8 1/2 7 22 1 154 0.094 0.014

AHU-8 3/8 1/2 7 22 1 154 0.094 0.014

AHU-9 3/8 1/2 7 22 1 154 0.094 0.014

AHU-10 3/8 1/2 6 34 1.23 250.92 0.094 0.024

AHU-11 3/8 1/2 6 34 1.39 283.56 0.094 0.027

AHU-12 3/8 1/2 6 22 1.23 162.36 0.094 0.015

AHU-13 3/8 1/2 7 22 1 154 0.094 0.014

AHU-14 3/8 1/2 7 22 1 154 0.094 0.014

AHU-15 3/8 1/2 7 22 1 154 0.094 0.014

AHU-16 3/8 1/2 7 34 1.373 326.774 0.094 0.031

AHU-17 3/8 1/2 4 46 1.07 196.88 0.094 0.019

AHU-18 3/8 1/2 4 70 1.203 336.84 0.094 0.032

AHU-19 3/8 1/2 5 70 1.4 490 0.094 0.046

AHU-20 3/8 1/2 6 34 0.75 153 0.094 0.014

AHU-21 3/8 1/2 3 22 0.938 61.908 0.094 0.006

AHU-22 3/8 1/2 5 22 1.8 198 0.094 0.019

AHU-23 3/8 1/2 5 22 1.6 176 0.094 0.017

AHU-24 3/8 1/2 4 22 1.568 137.984 0.094 0.013

AHU-26 3/8 1/2 4 22 1.8 158.4 0.094 0.015

AHU-27 3/8 1/2 4 34 1.563 212.568 0.094 0.020

AHU-25 3/8 1/2 4 34 1.088 147.968 0.094 0.014


TOTAL AHU'S WATER VOLUME (M³) 0.501
TOTAL AHU'S WATER VOLUME (GALLONS) 198.517
● Notes :
The Above Water Mass Per Unit Length Is Taken From ASHRAE (HVAC Systems And Equipment
Chapter 40)
EXPANSION TANK VOLUME CALCULATION

PROJECT : AL-Nabaa Azeem Hospital

FAN COIL UNITS WATER VOLUME

Water
Coil Tube Total
Coil Tube No. of Length of Mass per Water
Outside No. of Length of
Unit Unit Qty. Nominal Tubes per Each Tube Unit Volume
Diameter Rows Coil Tubes
Size (inch) Row {m} Length {m³}
(inch) {m}
{kg/m}

FCU-1 85 3/8 1/2 3 12 1.098 41.724 0.094 0.333

TOTAL FCU'S WATER VOLUME (M³) 0.333


TOTAL FCU'S WATER VOLUME (GALLONS) 132.103
● Notes :
The Above Water Mass Per Unit Length Is Taken From ASHRAE (HVAC Systems And Equipment Chapter
40)