The en 50600 Series European Data Centre
The en 50600 Series European Data Centre
-
European
Data Centre
Standardisation
Layer One
Greece
www.it-cabling.com www.e-readybuilding.com
© 2015 e-Ready Building Limited P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721
Mike Gilmore
Standards Activities
The EN 50600 series
-
Member
European
JTC1 SC25 WG3: “Generic Cabling”
Data Centre
Leader
Standardisation
WG3 Cabling Implementation Task Group: ISO/IEC 14763-2
Meeting Secretary
WG3 Automated Infrastructure Management Ad-hoc: ISO/IEC 18598
Chairman
TC215
Electrotechnical Aspects of Telecommunication Equipment
Convenor
TC215 WG1: Cabling design
Meeting Secretary
Mike Gilmore, FIET
TC215 WG2: Cabling installation - QA and installation practices
Member
Managing Director
TC215 WG3: Facilities and infrastructures (data centres)
e-Ready Building Limited
Member
CEN/CLC/ETSI CG Green Data Centres
Mobile:
+44 (0)786 011 0563 Past-Chairman
e-mail: TCT/7: Telecommunications - Installation Requirements
mike.gilmore Chairman
@ TCT/7/1: Cabling: Infrastructure design, planning and commissioning
e-readybuilding.com Meeting Secretary
TCT/7/2: Cabling; Installation and UK implementation
FIA e-mail: TCT/7/3: Facilities and infrastructures
standards@fia-online.co.uk
Layer One
Greece Fibreoptic Industry Association Director
www.fia-online.co.uk standards@fia
9th October 2015
www.it-cabling.com www.e-readybuilding.com
© 2015 e-Ready Building Limited P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721
Data Centre Standardisation - Europe
Layer One
Greece
www.it-cabling.com www.e-readybuilding.com
© 2015 e-Ready Building Limited P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721
Data Centre Standardisation - Europe
Data
Data Data
Data
not restricted to
allows data centres inside other types of premises
dedicated premises
not restricted to buildings allows caves, containers etc.
Layer One
Greece
www.it-cabling.com www.e-readybuilding.com
© 2015 e-Ready Building Limited P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721
Data Centre Standardisation - CENELEC
The EN 50600 series Information technology - Data centre facilities and infrastructures -
EN 50600-1:2012
- General requirements
European
Data Centre Energy efficiency
Availability Physical security
Standardisation enablement
Protection against
• unauthorised access
• internal fire
• other internal environmental events
• external environmental events
www.it-cabling.com www.e-readybuilding.com
© 2015 e-Ready Building Limited P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721
Data Centre Design Standards - CENELEC
Layer One
Greece
www.it-cabling.com www.e-readybuilding.com
© 2015 e-Ready Building Limited P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721
ISO/IEC Activity
Layer One
Greece
www.it-cabling.com www.e-readybuilding.com
© 2015 e-Ready Building Limited P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721
Key Performance Indicators
For example, a design of power supply that is more task efficient under high load conditions may be
inappropriate for users who plan to predominantly operate under low load conditions (and vice versa)
OBJECTIVE KPI’S
... relate to specific elements of energy management for operational infrastructures including:
energy consumption, task efficiency, energy re-use and renewable energy
... define requirements for the measurement of operational infrastructures i.e. taking into account the
real operating conditions over a defined period of time
GLOBAL KPI’S
Objective KPIs... may be combined using a formula appropriate to the specific operational
infrastructure to produce one or more Global operational KPIs which reflects the overall performance
of the operational infrastructures against wider energy management targets
...which may be self-imposed by the operators or externally applied by legislators
Layer One
Greece
www.it-cabling.com www.e-readybuilding.com
© 2015 e-Ready Building Limited P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721
Data Centre Operation Standards - CENELEC
Layer One
Greece
www.it-cabling.com www.e-readybuilding.com
© 2015 e-Ready Building Limited P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721
Data Centre RM Standards - CENELEC
Layer One
Greece
www.it-cabling.com www.e-readybuilding.com
© 2015 e-Ready Building Limited P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721
CLC TR 50600-99-1
CEN CENELEC (CLC) ETSI
The EN 50600 series
European Committee European Committee European
- for Standardization for Electrotechnical Telecommunications
European Standardization Standardis Insitute
Data Centre
Standardisation
CEN-CENELEC-ETSI
CO-ORDINATION GROUP
GREEN DATA CENTRES
STATUS REPORT
An in-depth mapping of the
standardisation demands of
energy efficient and sustainable
data centres
BROCHURE
Primary objectives:
A “laymans” guide to
• provide basic definitions
the standardisation
• differentiate types of deliverable
• product, design, operation actions to support the
• define topic boundaries delivery of energy
• map existing deliverables efficient and sustainable
• identify opportunities data centres
• minimise duplication
• within ESOs and ISO/IEC
www.it-cabling.com www.e-readybuilding.com
© 2015 e-Ready Building Limited P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721
CLC/TR 50600-99-1
www.it-cabling.com www.e-readybuilding.com
© 2015 e-Ready Building Limited P. O. Box MT65, LEEDS, LS17 8YD. United Kingdom Tel: +44 (0) 113 232 3721
The Complete Package
DESIGN OPERATION
CLC/TR 50600-99-1
ASSESSMENT
EN 50600-4-2 EN 50600-4-X
Layer One
Greece
www.it-cabling.com www.e-readybuilding.com