Download as pdf or txt
Download as pdf or txt
You are on page 1of 13

Engineering Structures 26 (2004) 1993–2005

www.elsevier.com/locate/engstruct

Seismic behavior and retrofit of steel moment connections


considering slab effects
Young-Ju Kim a,, Sang-Hoon Oh b, Tae-Sup Moon a
a
Department of Architectural engineering, Hanyang University,17, Haengdang-dong, Seongdong-gu, Seoul,133-791, South Korea
b
Research Institute of Industrial Science & Technology, 79, Youngcheon Dongtan, Hwasung, Kyoungkido, 445-810, South Korea

Received 29 January 2004; received in revised form 19 July 2004; accepted 27 July 2004

Abstract

A series of five full-scale subassemblages were tested to investigate the contribution of the slabs and the effects of three types of
retrofit methods, no weld access hole, horizontal stiffener, and cover plate. The test included one bare steel specimen and four
composite specimens with floor slab. The results that emphasize the influence of the composite slab on connection behavior and
specific comments on the retrofit scheme are presented. The test result indicated that the strains near the bottom flange of the
composite beam connections were several times larger than those of the bare steel beam connections, resulting in a higher poten-
tial of fracture. Therefore, the slab effects are detrimental to the seismic behavior of the connection and should be considered in
the design. Horizontal stiffener detail of three retrofit schemes demonstrated very good potential in improving the ductility of
composite connections in existing buildings.
# 2004 Elsevier Ltd. All rights reserved.

Keywords: Slab effect; Retrofit; Deformation capacity; Strain concentration; Weld access hole; Horizontal stiffener

1. Introduction has floor slabs that have strength and are bonded to
supporting beams from full to partial composite actions,
During the Northridge earthquake in California in their actual behavior under an earthquake load will be
1994 and the Kobe earthquake in 1995, many steel different from that expected from bare steel connections.
buildings suffered from fracturing in the welded An illustration of composite beam to column con-
moment connections [1,2]. The performance of steel nections subjected to seismic load is shown in Fig. 1.
buildings during these earthquakes has raised questions Considering the effect of the concrete slabs, the neutral
regarding the reliability of the current connection axis moves toward the top flange when subjected to
method. The current connection design may be suscep- positive beam bending (concrete slab under com-
tible to failure in an earthquake. Investigation of these pression), and, consequently, this causes the strain on
fractured connections indicated that most of the frac- the bottom flange to be much larger than that of the
tures occurred at the bottom flange. After the earth- top flange. This strain concentration on the bottom
quake, many different types of connection methods flange may lead to premature failure of the connection,
have been suggested to solve the problem both in thus reducing the deformation capacity of composite
Japan and the US [3,4]. beam connections. Most beam to column connections
However, relatively little testing has studied the effects were designed on the assumption that composite beam
of a composite slab on steel moment connection beha- connections with slab have the same deformation
vior under cyclic loads. Since an actual steel building capacity as bare steel beam connections without slab.
The slab effects on the seismic behavior of the con-
 nection to date were not yet fully uncovered for the
Corresponding author. Tel.: +82-2-2290-0312; fax: +82-2-2296-
4145. case of a laterally loaded structure. In addition, less
E-mail address: kyj282@empal.com (Y.-J. Kim). testing has been directed towards retrofit methods for
0141-0296/$ - see front matter # 2004 Elsevier Ltd. All rights reserved.
doi:10.1016/j.engstruct.2004.07.017
1994 Y.-J. Kim et al. / Engineering Structures 26 (2004) 1993–2005

Nomenclature

f’c Compressive stress of concrete slab


Ki Initial stiffness
Mmax Maximum flexural moment
Mpc Plastic moment of composite beam
Mps Plastic moment of bare steel beam
V 1, V 2 Vertical displacement at connection by panel zone deformation
W Absorbed energy
ddt Total displacement at loading point
h Target rotation angle
hsmax Maximum skeleton rotation angle
hpanel Panel zone deformation angle
hsp Plastic rotation angle corresponding to plastic moment of steel beam
Rlhl Cumulative rotation angle

existing moment connections. This study was also the concrete slab may contribute another 16% to the
undertaken to investigate the effects of relatively inex- connection strength and the plastic rotation angles of
pensive and nonintrusive retrofit procedures on connec- composite specimens were more than 0.04 rad. Uang
tion performance. et al. investigated the effectiveness of using RBS and
In this study, which focuses on the presence of a welded haunch for seismic retrofit of pre-Northridge
composite slab which may affect the fracture of the steel moment connections through cyclic testing [6]. A
beam bottom flange in the beam to column connec- test result showed that the composite slab only
tions which occurred in the Kobe earthquake, a frac- increased the beam positive flexural strength and no
ture in the composite beam was reproduced brittle fracture occurred. In addition, it was found that
experimentally and the effects of the presence of floor lateral-torsional buckling was prevented due to the bra-
slabs were investigated. This study also investigated the cing effect of the slab. Civjan et al. stated that the com-
effects of the seismic retrofit methods for the enhance- posite beam connections with floor slabs significantly
ment of deformation capacity of existing composite reduced the severity of local and lateral buckling of the
connections designed prior to the Kobe earthquake. beam and corresponded to the higher-achieved overall
plastic rotations and higher-peak attained moments
compared to bare steel beam connections [7,8]. Other
2. Previous studies of composite beam connections studies of composite connections were reported [9–12].
The tests clearly showed that without early fracture or
Several studies on positive effects of a composite slab detrimental effects, the presence of the slab was ben-
were reported. To enhance the ductility of beam to col- eficial to specimen performance by enhancing beam
umn connections of existing buildings, Chen et al. pro- stability and delaying strength degradation.
posed a simple method which trims the bottom flange On the contrary, some negative effects were noted
of the steel beam slightly [5]. Test results indicated that with composite specimens. A bare steel and two par-
tially composite specimens designed as 35 and 55%
composite were tested by Leon et al. [13] and Hajjar
et al. [14]. According to these tests, the presence of a
composite slab may increase stress and strain demands
on the bottom flange weld and be conjectured that the
slab could cause an earlier fracture at the bottom
flange weld, thereby degrading connection performance
and nullifying any positive effects of the RBS. Okada
et al. [15] and Oh et al. [16] conducted experimental
and analytical studies on the deformation capacity of
the beam to box column connections with and without
slabs under cyclic loading. The results of the tests and
analysis indicated that the deformation capacity of
Fig. 1. Strain distributions of composite beams. composite beams was nearly half of that of steel beams
Y.-J. Kim et al. / Engineering Structures 26 (2004) 1993–2005 1995

Fig. 2. Typical Japanese connection.

without slabs, and these results demonstrated earlier


fractures of bottom flanges of composite beams as
shown in the Kobe Earthquake.

3. Test program

3.1. Test specimen

Modern steel moment resisting frames in Japan are


usually constructed using square tube columns and
wide flange beams known as a ‘‘through-diaphragm Fig. 3. Typical Specimen (SP-2; Standard).
connection’’, due to their excellent cross-sectional
properties to resist biaxial bending loads as shown in action between the beam and the slab, two rows of
Fig. 2 [2,17]. Top and bottom square tube columns studs were welded to the top surface of the top flange
were welded to each other using a 25 mm thick com- at 200 mm spacing. The concrete slab was designed
plete penetration diaphragm. The beam flanges were with common concrete having a design strength of 24
welded to the diaphragms instead of a column flange, MPa, which was 200 mm thick and 2500 mm width.
and a standard web access hole was used. CJP single Also, the concrete slab was provided with longitudinal
bevel groove welds were used to connect the beam flan- and transverse steel reinforcement. For reinforcement,
ges to the diaphragm plates, and fillet-welds were used D13 (13 mm diameter steel reinforcing bars) having a
to connect the beam web to the column. The root of design strength of 400 MPa were placed transversely at
the CJP groove welds was located on the interior side 200 mm spaced over the entire length of the concrete
of both the top and the bottom flange. Gas metal arc slab and were located at both 30 mm from the top and
welding (GMAW) with CO2 shielding was used to fab- from the bottom of the slab. In addition, a mould plate
ricate the welded joints of test specimens. A solid elec- for slip prevention between the beam flange and the
trode designated as ER70S-3 was used in all welding. concrete slab was installed as shown in Fig. 3. The
All subassemblages were designed as an exterior con- mould plate was chosen so that the slab would contrib-
nection. Test specimens were constructed using a built- ute more strength to the connection, thereby simulating
up square tube column Box-45045022 and wide a more severe strain condition. All steel material is
flange beams H-6122021323 with a through- SM490 and a list of material properties used for speci-
diaphragm connection (Fig. 3). A relatively strong col- mens is given in Table 1.
umn was used to ensure that the beams could initiate A total of five specimens were manufactured as
the development of a plastic hinge mechanism during shown in Table 2, and the specimens are largely div-
cyclic loading before damage develops in the column. ided into two series.
Also, incorporating a rigid panel zone Box-
4504502232 may significantly reduce the contri- 3.1.1. Series I—Conventional specimens
bution of panel zone shear deformation to mode of Series I consists of a bare steel specimen (SP-1) and a
failure. composite specimen (SP-2) with concrete floor slab.
To simulate the actual steel building, four side beams They have a conventional type of the weld access hole
were designed at each column web and each side of in their beam-to-column connections (Fig. 2). SP-2 is
loading part, and were fully bonded to the slab using the standard specimen in this study. The detailed objec-
22 mm diameter shear studs. To make fully composite tives of the tests using series I are: (1) to demonstrate
1996 Y.-J. Kim et al. / Engineering Structures 26 (2004) 1993–2005

Table 1
Steel material characteristics

Member Yield strength (Mpa) Tensile strength (Mpa) Yield ratio (%) Elongation (%)
Beam flange (H-6122021323) 364 532 68 27
Beam web (H-6122021323) 390 541 72 26
Column (Box-45045022) 395 563 70 26
Diaphragm (PL-50050025) 378 565 67 27
Panel zone (Box-4504502232) 382 548 69 27

fractures of the conventional type connections that 3.1.2.1. No weld access hole scheme (SP-3). Many stu-
occurred in the Kobe earthquake; (2) to investigate the dies reported the effectiveness of no weld access hole
deformation capacity of composite beams for fracture; (Fig. 4(a)), which could exhibit excellent seismic per-
and, (3) to make clear the effects of slabs on the defor- formance in steel beam connections with or without
concrete floor slabs [3,15,18]. But no testing studied the
mation capacity of composite beams, compared with
effects of this retrofit scheme on existing steel moment
that of bare steel beam connections.
connection. In general, the existence of a weld access
hole is required for CJP welding of the beam flange.
3.1.2. Series II—Retrofit specimens However, it was discovered that it was a primary factor
Series II consists of three composite specimens which
for premature brittle fracture due to the influence of
used the design concept for seismic retrofit methods to the section loss of the web, where the geometry chan-
improve their deformation capacity. As shown in Fig. 4, ges abruptly and the joint efficiency (that is, moment
the three retrofit schemes include no weld access hole transfer efficiency) deceases [19]. To prevent these
(SP-3), horizontal stiffener (SP-4), and cover plate (SP-5). defects, the no weld access hole retrofit was developed.

Table 2
List of specimens

Specimen Composite or bare steel Parameter Connection type Location of retrofit


SP-1 Bare steel Without slab Conventional type –
SP-2 Composite Standard Conventional type –
SP-3 Composite No weld access hole Retrofit type Bottom flange
SP-4 Composite Horizontal stiffener Retrofit type Bottom flange
SP-5 Composite Bottom plate Retrofit type Bottom flange

Fig. 4. Schematic illustrations of retrofit specimens.


Y.-J. Kim et al. / Engineering Structures 26 (2004) 1993–2005 1997

As shown in Fig. 4(b), the welding of a new web plate


without an access hole was involved after the removal
of the beam web part including a weld access hole and
the backing bar. CJP single bevel and square groove
welds were used to connect the beam to the new web
plate.

3.1.2.2. Horizontal stiffener scheme (SP-4). This


scheme was to strengthen the steel beam near the wel-
ded connection by welding a horizontal stiffener to the
beam bottom flange (Fig. 4(c)). Sugimoto et al. proved
that the horizontal stiffener scheme (that is, wing plate
connection, see ref. [20]) can successfully prevent
premature rupture by neutralizing the negative effect of Fig. 5. Test setup.
the weld access hole, backing bars and run-off tabs and
exhibit large deformation capacity. Ideally, the
loaded at an assumed pin at its midspan. The test setup
strengthened section of the beam would remain prim-
is shown in Fig. 5.
arily elastic during plastic hinge movement of the
The loading protocol prescribed a quasi-static cyclic
beam, thereby limiting the stress in the welds.
pattern defined in terms of a rotation angle (h) (Fig. 6).
In Fig. 6, the target rotation angle h is the rotation
3.1.2.3. Cover plate scheme (SP-5). The cover plate
angle of only the pure beam with a displacement d that
scheme effectively strengthens the connections so that
is divided with the distance (L ¼ 3275 mm) from col-
flexural yielding of the beam at the end of the cover
umn face to loading point at the total displacement ddt,
plate can provide the connection ductility [21]. The
excluding displacement V1 and displacement V2 by the
connection was usually used with either top and bot-
tom cover plate or cover plate at the bottom flange connection panel zone deformation angle hpanel. The
only. In this study, a bottom flange only cover plate plastic rotation angle hsp corresponding to the plastic
was considered primarily as a retrofit to existing moment of bare steel beam, Mps , was calculated, and
moment connections. In addition, the specimen, SP-5, this rotation angle was incremented at 2hsp , 4hsp , 6hsp ,
involved slot welding to the beam flange around the and so on after loading at the elastic rotation. This his-
weld access hole as shown in Fig. 4(d). The concept of tory was applied to each specimen until failure
this scheme was to transfer the stress to the bottom occurred.
cover plate through slot welding. Moreover, it was The specimen was equipped with displacement trans-
reinforced with a vertical rib halfway up the beam ducers and strain gauges to measure deformation con-
depth. There was a fundamental difference of retrofit tributions of different parts and measure strain
scheme between this connection and the typical cover distributions, respectively. The measurement position
plate, due to the existence of a slot welding. of the strain gauge was shown in Fig. 7. Four sections,
The concrete slab in existing buildings presents prob- A, B, C and D that are respectively 75, 325, 575 and
lem for economic considerations and work convenience 825 mm distance from the column face are the posi-
in seismic retrofit schemes. Unless the concrete slab tions for strain measurement. In particular, section A
around the column is removed, it is difficult to retrofit
was located in line of the toe of weld access hole so
the top flange and its welded joint. Also, because the
that the stress situation near the weld access hole could
majority of reported damage occurred in the bottom
be investigated in detail.
flange, it was speculated that retrofit only at the bot-
tom flange may be sufficient to significantly improve
the performance of the connections. Therefore, all spe-
cimens included in Series II were retrofitted at only the
bottom flange of the beam.

3.2. Test setup

The test setup was designed to simulate the bound-


ary conditions of a beam-to-column connection sub-
assembly in a moment resisting frame under typical
lateral loading. Thus, the column was assumed to be
pin-supported at midstorey points, and the beam was Fig. 6. Target rotation angle h.
1998 Y.-J. Kim et al. / Engineering Structures 26 (2004) 1993–2005

Fig. 7. Position of strain gauges.

4. Test result 6hsp . The initial crack developed at the center of the
flange from the toe of the weld access hole. The crack
4.1. Global behavior and failure mode progressed outward along the flange width during suc-
cessive loading, followed by a sudden break of the
For the purpose of discussion of the test results,
entire beam flange. The initial crack propagation was
moment versus rotation angle relationships (h) were
ductile, and the final was brittle (Fig. 9(a)).
plotted in Fig. 8, where Mcp (=2173 kN.m) is the cal-
In standard composite specimen (SP-2), although
culated plastic moment for composite beams and Mps
maximum bending moment increased compared with
(=1423 kN.m) is that for bare steel beam without slabs the bare steel beam specimen (SP-1), deformation
[22,23]. Here, h is the rotation angle of only the pure capacity appeared small due to the premature brittle
beam. m, ! and # shows the point where fracture, failure of the beam bottom flange. The initial ductile
local buckling and crack initiation of connections crack was located in the area between the weld fusion
occurred, respectively. A summary of experimental zone on the outside flange surface and the end of the
results for the five tests is given in Table 3. Photo- access hole cut on the inside flange surface, which was
graphs of all specimens after testing are shown in similar to the damage which occurred during the Kobe
Fig. 9. earthquake. After this ductile crack reached its critical
In all specimens with composite beam connections, size, the brittle fracture occurred as shown in Fig. 9(b).
excluding the bare steel beam connection, the bottom SP-3 specimen failed in the bottom flange beneath
flange failed. The bare steel beam connection (SP-1) the weld of the end of the new web plate abruptly, as
showed stable hysteresis behavior and good defor- shown in Fig. 9(c). The reason might be the unsatisfac-
mation capacity, however, the connection failed by tory workmanship of the connection. The interruption
fracture of the top flange upon the negative bending of of the web stiffener near the connections led to the

Fig. 8. Moment- rotation angle relationships (m: fracture; !: local buckling; #: crack initiation).
Y.-J. Kim et al. / Engineering Structures 26 (2004) 1993–2005 1999

Table 3
Test results

Specimen Bending direction Mmax [kN.m] Ki [kN.m/rad.] h smax [rad.] W [KN.m. rad.] Fracture position
SP-1 Positive (+) 1800 148000 0.052 202 Top flange
Negative () 1560 152000 0.036
SP-2 Positive (+) 2490 432000 0.026 134 Bottom flange
Negative () 1900 297000 0.040
SP-3 Positive (+) 2600 552000 0.025 172 Bottom flange
Negative () 1900 294000 0.041
SP-4 Positive (+) 3260 447000 0.037 405 Bottom flange
Negative () 2190 246500 0.057
SP-5 Positive (+) 3010 497000 0.026 195 Bottom flange
Negative () 2110 311000 0.038

complete penetration weld between the beam bottom


flange and the new web plate becoming difficult and
less reliable. Although it was retrofitted with a no weld
access hole, the hysteresis characteristic of the specimen
SP-3 exhibited nearly similar to the specimen SP-2.
Specimen SP-4 exhibited an excellent hysteretic beha-
vior over all other composite specimens through the
prevention of stress concentration of the fuse zone
including the toe of the weld access hole and heat-affec-
ted zone, with the horizontal stiffener remaining elastic.
Moreover, upon the negative bending of 6hsp amplitude,
the local buckling occurred in the horizontal stiffener
end, followed by a degradation of the strength. This
finding implies that, in the horizontal stiffener scheme,
a strengthened area on the beam near the column face
can provide reliable energy dissipation through devel-
oping the plastic hinge in the horizontal stiffener end
even if the concrete floor slab is added to the connec-
tion (Fig. 9(d)).
SP-5 induced stress distribution of the bottom flange
around the connection by the bottom cover plate. But,
eventually, a brittle fracture occurred at the bottom
flange outer edge upon the positive bending of 6hsp
amplitude (Fig. 9(d)). After the fracture of the connec-
tion, the vertical rib was removed for detailed inspection
of the failure mode of the connection and it was exam-
ined. The crack initiated at the welding part between the
diaphragm and beam flange and progressed inward
along the flange width through the slot welding. The
weld was also examined, and a lack of fusion was also
found at the slot welding. Therefore, good workman-
ship and sound welding quality are still required in
order to provide a reliable welded connection.

4.2. Ultimate strength and stiffness

The data in Table 3 showed that the average


maximum strength of composite specimens under posi-
tive bending was 1.39 times the maximum strength
under negative bending. When the concrete slab is
Fig. 9. Photograph of specimens after testing. under positive bending, the maximum strength of the
2000 Y.-J. Kim et al. / Engineering Structures 26 (2004) 1993–2005

Fig. 10. Definition of maximum skeleton rotation angle and skeleton curve.

composite specimens was 1.58 times the maximum composite specimens was 3 times that of the bare
strength of the bare steel beam on average. The ratio of steel beam on average due to the composite action of
attained positive moments to the calculated plastic the floor slab. The increase of the initial stiffness in
capacity of the unreinforced composite specimens (SP-2 composite connections almost developed deformation
and SP-3) was about 1.17 on average. The plastic of the connection in the plastic range rather than the
capacity of the sections of these composite specimens elastic range. For this reason, composite beam con-
was computed assuming an effective concrete stress of nections exhibited a premature fracture due to the
1.3 f’c [22,23]. The results showed that the computed early plastic strain concentration.
plastic capacity of the composite section effectively esti-
mated the actual plastic capacity. However, the average 4.3. Deformation capacity
maximum positive moment of the reinforced composite
specimens (SP-4 and SP-5) was about 1.44 times great- Concepts of a skeleton curve and the Bauschinger
er than the estimated plastic capacity. This showed that curve have been commonly adopted when characteriz-
the contribution of the floor slab added considerable ing the deformation capacity of steel members sub-
extra strength to the ultimate strength of the beam. jected to load reversal in Japan [24]. As shown in
In the previous test, the presence of the concrete slab Fig. 10, the moment versus rotation angle curve of
increased the positive flexural strength of the beam by steel members subjected to cyclic loading can be
about 10% on average [6]. Composite specimens exhib- decomposed into the skeleton part, the Bauschinger
ited a slight increase in initial elastic stiffness and part, and the elastically unloading part. The skeleton
strength to the effect of 10–30% over similar bare steel curve is constructed from moment versus rotation
specimens [7,8]. Another study reported that the peak angle hysteresis loops (i.e. the solid lines in Fig. 10).
load resisted by the composite slab was developed The fundamental hypothesis behind the obtained skel-
between 4 and 17% larger than the corresponding bare eton curve for a cyclic loading test is the same as the
steel counterparts [9]. The results of the previous curve obtained from a monotonic loading test, and the
research indicated that the slab did not, in fact, pro- skeleton is thus useful to compare the ductility capacity
duce a significant increase in the ultimate strength of of hysteresis curves of specimens of various types [24].
the beam. Note, however, that the beams used in their The deformation capacity of each specimen was
studies were relatively deep (i.e. W30 to W36). Thus, compared using the maximum skeleton rotation angle
the influence of the slab on the strength and stiffness of (hsmax ) which is in positive and negative bending state in
the girder was assumed to be relatively small when moment versus rotation relationships. The skeleton
compared to more typical composite beams (i.e. W18 curves under positive bending are shown in Fig. 10,
to W24) similar to specimens used in this study. and hsmax is shown in Table 3. hsmax is a value evaluated
Assuming the thickness of the slab does not decrease at 80% (0.8 Mmax) of the ultimate strength of the speci-
linearly with the depth of the beam, it is speculated men after it reached ultimate strength in skeleton
that shallow beams are potentially more susceptible to curves. hsmax of the composite specimen SP-2 under
composite slab effects because of a great neutral axis positive bending was 50% when compared to the bare
shift. steel specimen (SP-1). Due to the composite action of
The data in Table 3 showed that initial stiffness of the slab, SP-2 had smaller ductility than that of bare
composite specimens under positive bending exhibited a steel specimen, SP-1. hsmax of Series II specimens SP-3,
significant increase to the effect of 45 to 88% over initial SP-4, and SP-5 with retrofit details were 48, 71 and
stiffness under positive bending. When the concrete slab 50% when compared to specimen SP-1. hsmax of SP-4
was under positive bending, the initial stiffness of the was 42% greater than that of the typical composite
Y.-J. Kim et al. / Engineering Structures 26 (2004) 1993–2005 2001

Fig. 11. Plastic neutral axis and strain distributions.

specimen SP-2. When the slab was under tension, the It was found that the strain on the bottom flange was
deformation capacity of the horizontal stiffener speci- several times larger than that of the top flange in the
men SP-4 was also higher than that of the other com- previous studies [5,15]. Focusing on these results, the
posite specimens, and even that of the bare steel beam plastic neutral axis of bending in the beams was esti-
specimen SP-1 without a slab. mated from strain behavior obtained at section A. The
Absorbed energy was also evaluated. Absorbed plastic neutral axis at section A of all specimens under
energy (W) of all specimens is shown in Table 3. the cyclic load reversals is shown in Fig. 11(a). The pos-
energy of the composite specimens was 66–201% when ition of the neutral axis can be obtained by using the
compared to specimen SP-1 without a slab. Especially, distance ratio of the height of the beam depth and the
specimen SP-4 was two times higher than SP-1. strain increment of both bottom and top beam flange.
As shown in Fig. 11(a), the plastic neutral axis of SP-1
is located in the vicinity of the center of the beam web,
5. Discussion but that of SP-2 is shown to be near the top flange
level. Consequently, this caused the strain on the bot-
5.1. Composite effects of slabs (Series I—Conventional tom flange to be much larger than that of the top
specimens) flange (Fig. 11(b)). As shown in Fig. 11(b), while the
strain of SP-1 showed a symmetric balance for the top
Test results exhibited that, while composite connec- and bottom flange, the test result of SP-2 exhibited that
tions developed higher moment than bare steel connec- it was concentrated in the bottom flange. The strain of
tions, composite connections needed more local the bottom flange for SP-1 and SP-2 under positive
deformation capacity than bare steel connections need. bending is shown in Fig. 11(c). At the same cumulative
The effect of the floor slabs was investigated in this sec- rotation angle, Rlhl ¼ 0:1 rad, the strain of the com-
tion based on the results of the measure strain distribu- posite beam (SP-2) was 4.4 times higher than that of
tions. the bare steel beam (SP-1).

5.1.1. Strain concentration and plastic neutral axis 5.1.2. Moment transfer efficiency of beam web
The concrete floor slabs may increase the positive A square tube column had two webs at each side but
flexural capacity, raising the beam neutral axis and, no web at the center where the beam web was connec-
therefore, creating a large strain in the bottom flange. ted. Therefore, the web of the box column was signifi-
2002 Y.-J. Kim et al. / Engineering Structures 26 (2004) 1993–2005

5.1.3. Reduction of plastic zone


Fig. 14(a) shows the distributions of the curvature in
the beam’s longitudinal direction at the completion of
the peak moment, and it was assumed that there was
almost no curvature change from section D to loading
point and it accordingly was simplified into a linear
line. Fig. 14(b) shows the ratio of the curvature of each
section to the summation of those for all sections. SP-1
had a curvature distribution that changed gradually
from section A to section D. But in SP-2, the curvature
distribution from section A to section B changed
exceedingly and the curvatures from section B to sec-
tion D were shown to be very small compared with sec-
tion A. These results also can be seen clearly in
Fig. 14(b).
Fig. 15 shows the absorbed energy in each section of
Fig. 12. Deformation of column flange and strain distribution of all specimens. The energy obtained from moment ver-
connection. sus curvature hysteresis loops. This plot exhibited that,
in the case of SP-2, the ratio of the energy absorbed in
cantly less effective in transferring bending moment due section A to that in all sections was near 80%, while, in
to the out-of-deformation of the column flanges and the case of SP-1, it was a ratio of 59%. Also, while the
the loss of the web sections by the weld access hole energy of SP-1 showed a symmetric balance between
the positive and negative bending, the test result of SP-
(Fig. 12(a)). Stress increase at the end of the beam is
2 exhibited that it was concentrated in the positive
influenced by the efficiency in transmitting the stress in
bending direction.
the web of beam through beam to column joint. More- These results indicated that, for bare steel connec-
over, it was reported that the beam near the connection tions, the deformation was relatively well distributed
developed a smaller strength than the beam away from over the entire section, but, for composite connections,
the connection due to the decrease of the web moment it had higher local ductility demand in a narrow plasiti-
transfer as shown in Fig. 12(b) [19]. fied zone of the beam. In other words, it can be under-
To investigate the effect of web moment transfer, stood that the plastic zone of composite beams was
moment versus curvature relationship was used. The reduced while bare steel beams secured a wide plastic
curvature was obtained from the gross sectional aver- zone.
age strain of a beam flange. Next, the skeleton curve of
a curvature constructed from moment versus curvature 5.2. Effect of seismic retrofit (Series II—Retrofit
relationships and moment versus monotonic curvature specimens)
relationships at each section under positive bending is
In previous studies, no weld access hole connections
shown in Fig. 13. In Fig. 13(a), the moment of section showed outstanding performance in laboratory testing
A in bare steel specimen SP-1 appeared 8, 11, and 13% due to the high efficiency of web moment transfer
slightly smaller than sections B, C and D at the same [15,19]. While typical details for new construction used
curvature, respectively. This means that the web con- no weld access hole scheme in both the top and bottom
nection did not transfer its full share of the beam web, the retrofit of Specimen SP-3 used it only in the
moment, resulting in strain concentration of the beam bottom web. In Fig. 13(c), the moment of section A in
flange. The moment of section A in composite speci- specimen SP-3 exhibited 18, 8, and 7% smaller than
men SP-2 exhibited 35, 30, and 36% significantly smal- sections B, C, and D, at the same curvature, respect-
ler than sections B, C and D at the same curvature, ively. The decrement of the strength of SP-3 was sig-
respectively (Fig. 13(b)). The decrement of the strength nificantly smaller than that of SP-2, exhibiting the ratio
of 30, 36 and 35%. The decrement of the strength of
of SP-2 was about 3 times of that of SP-1, and this
SP-3 was slightly smaller than that of SP-2. To directly
exhibited that composite connection decreased the web
compare moment transfer efficiency of SP-3 with SP-2,
moment transfer compared to bare steel connection moment versus curvature relationship and strain value
due to the composite effect of the slab. Therefore, the was plotted in Fig. 16. Fig. 16 indicated that, at the
deformation was concentrated near the beam bottom same curvature level, SP-2 and SP-3 specimens had dif-
flange where the constraint was minimal. More detailed ferent flexural strength at the critical region, section A.
studies are required for these results. For example, at the curvature of 48 (106/mm), the
Y.-J. Kim et al. / Engineering Structures 26 (2004) 1993–2005 2003

Fig. 13. Moment versus curvature relationships.

strength of the beam for SP-1 already reached 2530


KN.m, while, for SP-2, the strength of the beam was
only 2154 KN.m. As shown in Fig. 17, in the same
cumulative rotation angle, the strain on the bottom
flange of SP-3 was much smaller than that of SP-2 at
section A, while it was slightly larger than that of SP-1.
Also, Fig. 14 showed that in the case of SP-3, the ratio
of the curvature in section A to that in all sections was
about 59%, while, in the case of SP-2, it was a ratio of
83%. In addition, the plastic neutral axis of SP-3 was

Fig. 14. Distribution of curvature along beam length. Fig. 15. Absorbed energy in each section.
2004 Y.-J. Kim et al. / Engineering Structures 26 (2004) 1993–2005

Fig. 16. Effect of no weld access hole scheme.

Fig. 17. Strain distribution.


located slightly lower than that of SP-2 at the same
cumulative rotation angle (Fig. 11(a)). These results
indicated that the no weld access hole scheme was plastic hinge away from the column face and, thus,
effective in transferring the web moment even in com- achieved a more reliable connection performance even
posite connections, so that it developed less ductility in composite connections.
demand on the beam bottom flanges. But, the notch Although the cover plate specimen (SP-5) provides a
caused by the unsatisfactory workmanship developed strengthened zone in the vicinity of the connection that
and, consequently, SP-3 failed in the bottom flange results in a lower level of stress/strain on the weld as
beneath the weld of the new web plate end prior to shown in Figs.13(e), 14 and 17, the proposed connec-
developing a sufficient deformation capacity, suggesting tion scheme exhibited poor performance. As mentioned
that the reliability of the workmanship was needed in in the tests results, good workmanship and sound weld-
doing field constructions of retrofit schemes. ing quality are still required in order to provide a
The horizontal stiffener specimen (SP-4) improved reliable welded connection.
the ductility of composite connections and showed
stable hysteretic characteristics compared to the stan- 6. Conclusion
dard composite specimen (SP-2). This specimen exhib-
ited flange local buckling and reached failure due to a The presence of the concrete slabs had an influence
ductile crack initiated at the tip of the horizontal stiff- on the neutral axis location, the web moment transfer,
ener. Therefore, SP-4 also improved the energy absorp- and the plastic zone of the connection, and these influ-
tion capacity of composite beam connections when ences caused the strain on the bottom flange to be
compared to specimen SP-2. Fig.13(d) shows that for much larger than that of the top flange. Consequently,
SP-4, section A and section B of the beam near the col- the deformation capacity of a composite connection is
umn face stiffened by the horizontal stiffener remained about half that of a bare steel connection. These results
in elastic range or deformed only slightly even under indicated that the detrimental slab effects should be
ultimate state. The force demand in the existing bottom considered in the seismic design of the connection.
flange groove weld and the toe of the weld access hole The no weld access hole detail (SP-3) was effective in
was significantly reduced to a reasonable level, the transferring of the web moment even in composite
although the plastic neutral axis of this specimen connections, such that it developed less ductility
moved forward to the top flange but differed from that demand on the beam bottom flanges. The cover plate
of specimen SP-2, as shown in Fig. 11(a). Fig. 14(a) specimen (SP-5) provided a strengthened zone in the
shows the distributions of curvature in the beam’s vicinity of the connection that can be expected to result
longitudinal direction at completion of the peak in a lower level of stress/strain on the weld. Neverthe-
moment. This plot showed that for SP-4, the curvature less, these proposed connections exhibited poor perform-
was small near the connections and increased from the ance, suggesting that reliability of the workmanship and
horizontal stiffener end. In addition, in Fig. 14(b), the welding quality were required to ensure the ductile per-
ratio of the curvatures in sections A, B, C, and D to formance of the connection.
that in all sections was 7, 8, 50 and 35%, respectively. The horizontal stiffener details (SP-4) showed that an
Similar results can also be seen through the absorbed enlarged plastic zone can be achieved and the defor-
energy of each section. As shown in Fig. 15, the energy mation capacity can be improved. This retrofit scheme
of SP-2 concentrated in section A of 80% compared demonstrated very good potential in improving the duc-
with all sections. But, SP-4 absorbed energy in section tility of composite beam connections in existing build-
C and section D of 50% compared with all sections. ings without removing the floor slabs. Moreover, by
These results may illustrate that moment connections using the horizontal stiffener in retrofit of the existing
retrofitted using the horizontal stiffener moved the building, workmanship as well as excellent performance
Y.-J. Kim et al. / Engineering Structures 26 (2004) 1993–2005 2005

can be expected at the same time. This is because by [11] Roeder CW. Connection performance for seismic design of steel
moment frames. J Struct Eng , ASCE 2001;128(4):517–25.
using the horizontal stiffener retrofit scheme, downward
[12] FEMA. Connection performance state of art report. FEMA-
welding is possible and the design scheme is very simple. 355D. Washington, DC. Federal Emergency Management
Agency, 2000.
[13] Leon RT, Hajjar JF, Gustafson MA. Seismic response of com-
Acknowledgements posite moment-resisting connections. I: Performance. J Struct
Eng, ASCE 1998;124(8):868–76.
The author gratefully acknowledges the support of [14] Hajjar JF, Leon RT, Gustafson MA, Shield CK. Seismic
response of composite moment-resisting connections. II: Beha-
STRESS and POSCO, for financially supporting this
vior. J Struct Eng, ASCE 1998;124(8):877–85.
research. [15] Okada K, et al. Experimental study on deformation capacity of
the composite beams. In: Proceeding of 6th Pacific Structural
Steel Conference (PSSC), Beijing, China, 2001:233–8
References [16] Oh SH, Joh CB, Chang IH, Chen W-F. Slab effects on the seis-
mic behavior of steel moment connections. In: Proceedings of
[1] Miller DK. Lessons learned from the Northridge earthquake. 6th Pacific Struct Steel Conference (PSSC), Beijing, China,
Eng Struct 1998;20(4-6):249–60. 2001:539–44
[2] Nakashima M, Inoue K, Tada M. Classification of damage to [17] Kurobane Y. Connections in tubular structures. Prog Struct Eng
steel buildings observed in the 1995 Hyogoken-Nanbu earth- and Mater 2002;4(1):35–45.
quake. Eng Struct 1998;20(4-6):271–81. [18] Suita K, Tamura T, Morita S, Nakashima M, Engelhardt MD.
[3] FEMA. Recommended seismic Design Criteria For New Steel Plastic rotation capacity of steel beam to column connections
moment Buildings. FEMA-350. Washington DC: Federal using a reduced beam section and no weld access hole design—
Emergency Management Agency, 2000. Full scale tests for improved steel beam to column sub-
[4] Nakashima M, Suita K, Morisako K, Maruoka Y. Tests of wel- assemblies—part 1. J of Struct and Const Eng, AIJ 1999;526(12)
ded beam-column subassemblies. I: Global behavior. J Struct :177–84 (in Japanese).
Eng, ASCE 1998;124(11):1236–44. [19] Okada K, Matsumoto Y, Yamada S. Evaluation of effect of
[5] Chen S-J, Tsao YC, Chao C. Enhancement of ductility of exist- joint efficiency at beam-to-column connection on ductility
ing seismic steel moment connections. J Struct Eng, ASCE capacity of steel beams. J of Struct and Const Eng, AIJ
2001;127(5):538–45. 2003;588(6):131–8 (in Japanese).
[6] Uang C-M, Kent Yu Q-S, Noel S, Gross J. Cyclic testing of steel [20] Sugimoto H, Morita K, Takahashi Y. Prediction of failure mode
moment connections rehabilitated with RBS or welded haunch. of hunched beam to SHS column connections. Steel Struct,
J Struct Eng, ASCE 2000;126(1):57–68. KSSC 2001;1(3):185–99.
[7] Civjan SA, Engelhardt MD, Gross JL. Retrofit of pre-North- [21] Kim T, Whittaker AS, Gilani ASJ, Berto VV, Takhirov SM.
ridge moment-resisting connections. J Struct Eng, ASCE Cover-Plate and Flange-Plate Steel Moment-Resisting Connec-
2000;126(4):445–52. tions. J Struct Eng, ASCE 2002;128(4):474–82.
[8] Civjan SA, Engelhardt MD, Gross JL. Slab effects in SMRF [22] Recommendation for limit state design of steel structure, Archi-
retrofit connection tests. J Struct Eng, ASCE 2001;127(3):230–7. tectural Institute of Japan, 1998.
[9] Jones SL, Fry GT, Engelhardt MD. Experimental evaluation of [23] Design recommendations for composite constructions, Architec-
cyclically loaded reduced beam section moment connections. tural Institute of Japan, 1985
J Struct Eng, ASCE 2001;128(4):441–51. [24] Kato B, Akiyama H. Predictable properties of material under
[10] Roeder CW. General issues influencing connection performance. incremental cyclic loading. Lisbon: IABSE Preliminary Publi-
J Struct Eng, ASCE 2001;128(4):420–8. cation; 1973.

You might also like