Download as pdf or txt
Download as pdf or txt
You are on page 1of 30

PCS-978

Transformer Protection
Instruction Manual Supplement

for Project ECKF 110809

NR Electric Co., Ltd.


Supplement for Project ECKF 110809

Preface
This document is the supplement of the corresponding general instruction manual of the
equipment mentioned on the cover. It is dedicated to the specific project, and can not be used in
other projects. If there are some differences between this supplement and the corresponding
general instruction manual, user must refer to this supplement for the applied-specific project.

Copyright
Version: R1.00 NR ELECTRIC CO., LTD.
69 Suyuan Avenue, Jiangning, Nanjing 211102, China
P/N: EN_YJBH5100.0086.0003.110809 Tel: 86-25-87178185, Fax: 86-25-87178208
Website: www.nari-relays.com
Copyright © NR 2010. All rights reserved Email: nr_techsupport @nari-relays.com

We reserve all rights to this document and to the information


contained herein. Improper use in particular reproduction and
dissemination to third parties is strictly forbidden except where
expressly authorized.

The information in this manual is carefully checked periodically,


and necessary corrections will be included in future editions. If
nevertheless any errors are detected, suggestions for correction or
improvement are greatly appreciated.

We reserve the rights to make technical improvements without


notice.

NR ELECTRIC CO., LTD. i


Supplement for the Project ECKF 110809

ii NR ELECTRIC CO., LTD.


Supplement for Project ECKF 110809

Table of Content
Preface ........................................................................................................................................... i

Table of Content .......................................................................................................................... iii

1 Information about this Application .......................................................................................... 1

2 Introduction................................................................................................................................ 3

2.1 Protective Functions Configuration............................................................................... 3

3 Hardware Description ............................................................................................................... 5

3.1 Plug-in Module Configuration ........................................................................................ 5

3.2 Plug-in Module Configuration ........................................................................................ 5

3.3 Plug-in Module Terminal Definition ................................................................................ 6

3.3.1 PWR Module (NR1301A) ....................................................................................... 6

3.3.2 MON Module (NR 1102D) ...................................................................................... 7

3.3.3 DSP Module 1 and DSP Module 2 (NR1156A) ..................................................... 8

3.3.4 Binary Input Module (NR1504A) ........................................................................... 9

3.3.5 Binary Output Module ......................................................................................... 11

3.3.6 Analog Input Module ........................................................................................... 17

3.4 Tripping Matrix ............................................................................................................... 19

4 Human Machine Interface ....................................................................................................... 21

5 Manual Version History ........................................................................................................... 23

NR ELECTRIC CO., LTD. iii


Supplement for the Project ECKF 110809

iv NR ELECTRIC CO., LTD.


1 Information about this Application

1 Information about this Application


The following table gives the information about the application of this complement which must be
used with corresponding general instruction manual for the applied-specific project.

Project name Philippine LUZON Project


SUBQ SUBQ00090237
Software version PCS-978_R1.00-110809
Corresponding general PCS-978_Instruction Manual_EN_General_X_R1.02_
instruction manual version (EN_YJBH5100.0086.0003)

NR ELECTRIC CO., LTD. 1


1 Information about this Application

2 NR ELECTRIC CO., LTD.


2 Introduction

2 Introduction

2.1 Protective Functions Configuration

According to the requirement of this project, following protective functions are provided in the
protection relay, and the functions which are not mentioned in this section are not equipped in
user’s protection relay.

Table 2.1-1 Protective functions of PCS-978

Protective function overview Function No.


Conventional percent differential protection 87T
Unrestrained instantaneous differential protection 50/87UT
DPFC current differential protection. 7/87DT
Winding differential protection 87W
Overexciation protection 24
Definite-time overcurrent protection of line side
50P,51P
Inverse-time overcurrent protection of line side
Definite-time zero-sequence overcurrent protection of line side
50N, 51N
Inverse-time zero-sequence overcurrent protection of line side
Overload alarm element of line side 49
Definite-time overcurrent protection of end side
50P,51P
Inverse-time overcurrent protection of end side
Definite-time zero-sequence overcurrent protection of end side
50N, 51N
Inverse-time zero-sequence overcurrent protection of end side

Overload alarm element of LV side 49

Voltage element
Current element
CT saturation detection
Harmonic blocking function
VT circuit failure supervision VTS
CT circuit failure supervision CTS

NOTE! Please replace the table 1.2-1 in the section 1.2 of the general instruction manual

with the above table in this section.

NR ELECTRIC CO., LTD. 3


2 Introduction

Bus I

52
Line

VT
PCS-978
Cal
3I0

CT1 * * *
52
Cal
3I0

Shunt 87T 50P, 51P 50N, 51N


52 reactor 7/87DT 87W 49
DT, IDMT DT, IDMT OvLd Alm
50/87UT WdgDiff OC OC
DIFF

Bus II Cal
3I0
CT2
* * *

Figure 2.1-1 Function diagram of PCS-978 applied for protecting a reactor

4 NR ELECTRIC CO., LTD.


3 Hardware Description

3 Hardware Description
3.1 Plug-in Module Configuration

Following figures show of 4U front view and rear view of PCS-978 for the project respectively.

PCS-978
HEALTHY
ALARM TRANSFORMER PROTECTION
TRIP

P
GR
ENT

C
ES

Figure 3.1-1 Front view of PCS-978

NR1102D NR1156A NR1156A NR1401 NR1401 NR1523B NR1504A NR1521A NR1521A NR1523B NR1301A
1 2 3 1 2 3 5V BJ

4 5 6 4 5 6 BJJ BSJ

DANGER DANGER
1 COM1

2 BSJ1

3 BJJ1
4 COM2

5 BSJ2
6 BJJ2

7 24V
8 24 VGND

9
10 DC+

11 DC-

12 FGND

Figure 3.1-2 Rear view of PCS-978

3.2 Plug-in Module Configuration

PCS-978 configurations of plug-in module are as follows:

NR ELECTRIC CO., LTD. 5


3 Hardware Description

BO module 2 for signal


BO module 1 for signal

BO module 1 for signal

BO module 1 for trip


BO module 2 for trip
AC AI module 1

AC AI module 2
MON module

PWR module
DSP module

DSP module

BI module
Slot No.
B01 B02 B03 B04 B05 B06 B07 B08 B09 B10 B11 B12 B13 B14 B15 B00

Figure 3.2-1 Plug-in modules configuration

No. Module description Module ID


B01 MON module NR1102D
B02 DSP Module 1 NR1156A
B03 DSP module 2 NR1156A
B04 AC AI module 1 NR1401
B06 AC AI module 2 NR1401
B11 BO module 1 for signal NR1523B
B12 BI module NR1504A
B13 BO module 1 for trip NR1521A
B14 BO module 2 for trip NR1521A
B15 BO module 2 for signal NR1523B
B00 PWR module NR1301A

3.3 Plug-in Module Terminal Definition

Equipment consists of power supply module, MON module, DSP module, Analog input module,
opto-coupler input module, tripping output module, and signal output module. The definition and
application of each module and its terminal is introduced as follows:

3.3.1 PWR Module (NR1301A)


A power supply module (NR1301A) is equipped at slot B00 position, and the terminals of the PWR
module ant its wiring method is shown in the following figure.

NOTE: Terminal definitions are represents with its slot position and pin number. For

example, contact 1301-1302 means terminal 01-02 of the module at the slot B13, i.e. 13
represents the slot position of module, 01(02) represents the pin number on the module.

6 NR ELECTRIC CO., LTD.


3 Hardware Description

Slot B00

NR1301A

BO_COM1 0001 0001

BO_FAIL 0002 0002

BO_ALM 0003 0003

BO_COM2 0004
0004
BO_FAIL 0005
0005
BO_ALM 0006
0006
OPTO+ 0007

OPTO- 0008

0009

PWR+ 0010

PWR- 0011

GND 0012

Grounding Screw
Grounding Bus

Figure 3.3-1 Pin definition of DC power supply module NR1301A

Pin No. Symbol Description


0001 BO_COM1 Common terminal 1.
0001, 0002 BO_FAIL Binary output 1 of equipment failure.
0001, 0003 BO_ALM Binary output 1 of equipment abnormality alarm.
0004 BO_COM2 Common terminal 2.
0001, 0005 BO_FAIL Binary output 2 of equipment failure.
0001, 0006 BO_ALM Binary output 2 of equipment abnormality alarm.
0007 OPTO+ Pins 0007 and 0008 are 24V power supply output for the
binary input module. Pin 0007 is 24V+ and Pin 0008 is
0008 OPTO-
24V-, the rated current of this power supply is 200mA.
0009 Not used
0010 PWR+ Positive input of power supply for the equipment
0011 PWR- Negative input of power supply for the equipment
0012 GND Grounded connection of this equipment

3.3.2 MON Module (NR 1102D)


A MON module (NR1102D) is equipped at slot B01 position, and the terminals of the MON module
ant its wiring method is shown in the following figure.

Module ID Memory Interface Physical Layer

NR ELECTRIC CO., LTD. 7


3 Hardware Description

Module ID Memory Interface Physical Layer


NR1102D 128M DDR 4 RJ45 Ethernet Twisted pair wire

T
E
Slot B01 N
R
NR1102D E
H
T
E
ETHERNET 1
T
E
N
ETHERNET 2 R
E
H
T
E To SCADA
ETHERNET 3

ETHERNET 4

SYN+ 0101
S
P
SYN- 0102 G
To GPS
SHLD 0103

GND 0104
T
N
I
RTS 0105 R
P
TXD 0106 To PRINT
SGND 0107

Figure 3.3-2 Rear view of MON modules

Pin No. Sign Description


0101 SYN+
0102 CLK SYN- EIA RS-485 standardized interface for clock
0103 SYN SHLD synchronization, PPS and IRIG-B signals are permitted.
0104 GND
0105 RTS
Interface for connecting with a printer, the EPSON®
0106 PRT TXD
LQ-300K printer is recommended.
0107 SGND

3.3.3 DSP Module 1 and DSP Module 2 (NR1156A)


DSP module 1 and DSP module 2 have the same hardware configurations, and they are equipped
at slot B02 and slot B03 positions respectively.

8 NR ELECTRIC CO., LTD.


3 Hardware Description

NR1156A
1 2 3

4 5 6

Figure 3.3-3 Rear view of DSP modules

Module ID Description
NR1156A 48 analog sampling channels, applied for conventional CT/VT.

3.3.4 Binary Input Module (NR1504A)


A binary input module (NR1504A) is equipped at slot B12 position, and the module is a standard
binary input module.

NR ELECTRIC CO., LTD. 9


3 Hardware Description

NR1504A
Opto+ 1201

BI_Pulse_GPS 1202

BI_Print 1203

BI_BlkComm 1204

BI_RstTarg 1205

BI_1 1206

BI_2 1207

COM1- 1208

BI_3 1209

BI_4 1210

EBI_Diff 1211

EBI_WdgDiff 1212

EBI_OvExc 1213

EBI_BakProt 1214

COM2- 1215

BI_9 1216

BI_10 1217

BI_11 1218

BI_12 1219

BI_13 1220

BI_14 1221

COM3- 1222

Figure 3.3-4 Pin definition of binary input module NR1504

Pin No. Symbol Description


1201 Opto+ Positive pole of power supply of the module
1202 BI_Pulse_GPS Binary input of time synchronization pulse
1203 BI_Print Binary input of triggering printing
Binary input of blocking communication between equipment
1204 BI_BlkComm and substation automatic system (SAS) or remote terminal unit
(RTU).
1205 BI_RstTarg Binary input of resetting signal of protective equipment.
1206 BI_1 Configurable binary input 1.
1207 BI_2 Configurable binary input 2.
Common terminal 1 of negative pole of power supply of the
1208 COM1-
module.
1209 BI_3 Configurable binary input 3.
1210 BI_4 Configurable binary input 4.
1211 EBI_Diff Binary input of enabling differential protection.
1212 EBI_WdgDiff Binary input of enabling winding differential protection.

10 NR ELECTRIC CO., LTD.


3 Hardware Description

Pin No. Symbol Description


1213 EBI_OvExc Binary input of enabling overexcitation protection.
1214 EBI_BakProt Binary input of enabling backup protection.
Common terminal 2 of negative pole of power supply of the
1215 COM2-
module.
1216 BI_9 Configurable binary input 9.
1217 BI_10 Configurable binary input 10.
1218 BI_11 Configurable binary input 11.
1219 BI_12 Configurable binary input 12.
1220 BI_13 Configurable binary input 13.
1221 BI_14 Configurable binary input 14.
Common terminal 3 of negative pole of power supply of the
1222 COM3-
module.

3.3.5 Binary Output Module

3.3.5.1 Tripping Output Module (NR1521)

Two tripping output modules (NR1521A) are equipped at slot B13 and slot B14 positions
respectively.

Slot B13 Slot B14

NR1521A NR1521A
BO_Trp_1+ 1301 1301 BO_Trp_1+ 1401 1401
BO_Trp_1 BO_Trp_1
BO_Trp_1- 1302 1302 BO_Trp_1- 1402 1402
BO_Trp_2+ 1303 1303 BO_Trp_2+ 1403 1403
BO_Trp_2 BO_Trp_2
BO_Trp_2- 1304 1304 BO_Trp_2- 1404 1404
BO_Trp_3+ 1305 1305 BO_Trp_3+ 1405 1405
BO_Trp_3 BO_Trp_3
BO_Trp_3- 1306 1306 BO_Trp_3- 1406 1406
BO_Trp_4+ 1307 1307 BO_Trp_4+ 1407 1407
BO_Trp_4 BO_Trp_4
BO_Trp_4- 1308 1308 BO_Trp_4- 1408 1408
BO_Trp_5+ 1309 1309 BO_Trp_5+ 1409 1409
BO_Trp_5 BO_Trp_5
BO_Trp_5- 1310 1310 BO_Trp_5- 1410 1410
BO_Trp_6+ 1311 1311 BO_Trp_6+ 1411 1411
BO_Trp_6 BO_Trp_6
BO_Trp_6- 1312 1312 BO_Trp_6- 1412 1412
BO_Trp_7+ 1313 1313 BO_Trp_7+ 1413 1413
BO_Trp_7- 1314 BO_Trp_7 BO_Trp_7- 1414 BO_Trp_7
1314 1414
BO_Trp_8+ 1315 1315 BO_Trp_8+ 1415 1415
BO_Trp_8- 1316 BO_Trp_8 BO_Trp_8- 1416 BO_Trp_8
1316 1416
BO_Trp_9+ 1317 1317 BO_Trp_9+ 1417 1417
BO_Trp_9- 1318 BO_Trp_9 BO_Trp_9- 1418 BO_Trp_9
1318 1418
BO_Trp_10+ 1319 1319 BO_Trp_10+ 1419 1419
BO_Trp_10- 1320 BO_Trp_10 BO_Trp_10- 1420 BO_Trp_10
1320 1420
BO_Trp_11+ 1321 1321 BO_Trp_11+ 1421 1421
BO_Trp_11- 1322 BO_Trp_11 BO_Trp_11- 1422 BO_Trp_11
1322 1422

Figure 3.3-5 Pin definition of tripping output module

Pin definitions of the tripping output module at slot B13 position are shown as follows.

Pin Original New-defined


Description
No. Symbol Symbol

NR ELECTRIC CO., LTD. 11


3 Hardware Description

Pin Original New-defined


Description
No. Symbol Symbol
1301 BO_Trp_1+ BO_Trp_1-1+
The NO contact 1 of 1st group of signal output.
1302 BO_Trp_1- BO_Trp_1-1-
1303 BO_Trp_2+ BO_Trp_1-2+
The NO contact 2 of 1st group of signal output.
1304 BO_Trp_2- BO_Trp_1-2-
1305 BO_Trp_3+ BO_Trp_1-3+
The NO contact 3 of 1st group of signal output.
1306 BO_Trp_3- BO_Trp_1-3-
1307 BO_Trp_4+ BO_Trp_2-1+
The NO contact 1 of 2nd group of signal output.
1308 BO_Trp_4- BO_Trp_2-1-
1309 BO_Trp_5+ BO_Trp_2-2+
The NO contact 2 of 2nd group of signal output.
1310 BO_Trp_5- BO_Trp_2-2-
1311 BO_Trp_6+ BO_Trp_3-1+
The NO contact 1 of 3rd group of signal output.
1312 BO_Trp_6- BO_Trp_3-1-
1313 BO_Trp_7+ BO_Trp_3-2+
The NO contact 2 of 3rd group of signal output.
1314 BO_Trp_7- BO_Trp_3-2-
1315 BO_Trp_8+ BO_Trp_4-1+
The NO contact 1 of 4th group of signal output.
1316 BO_Trp_8- BO_Trp_4-1-
1317 BO_Trp_9+ BO_Trp_4-2+
The NO contact 2 of 4th group of signal output.
1318 BO_Trp_9- BO_Trp_4-2-
1319 BO_Trp_10+ BO_Trp_5-1+
The NO contact 1 of 5th group of signal output.
1320 BO_Trp_10- BO_Trp_5-1-
1321 BO_Trp_11+ BO_Trp_5-2+
The NO contact 2 of 5th group of signal output.
1322 BO_Trp_11- BO_Trp_5-2-

Pin definitions of the tripping output module at slot B14 position are shown as follows.

Pin Original New-defined


Description
No. Symbol Symbol
1401 BO_Trp_1+ BO_Trp_6-1+
The NO contact 1 of 6th group of signal output.
1402 BO_Trp_1- BO_Trp_6-1-
1403 BO_Trp_2+ BO_Trp_6-2+
The NO contact 2 of 6th group of signal output.
1404 BO_Trp_2- BO_Trp_6-2-
1405 BO_Trp_3+ BO_Trp_6-3+
The NO contact 3 of 6th group of signal output.
1406 BO_Trp_3- BO_Trp_6-3-

12 NR ELECTRIC CO., LTD.


3 Hardware Description

Pin Original New-defined


Description
No. Symbol Symbol
1407 BO_Trp_4+ BO_Trp_7-1+
The NO contact 1 of 7th group of signal output.
1408 BO_Trp_4- BO_Trp_7-1-
1409 BO_Trp_5+ BO_Trp_7-2+
The NO contact 2 of 7th group of signal output.
1410 BO_Trp_5- BO_Trp_7-2-
1411 BO_Trp_6+ BO_Trp_8-1+
The NO contact 1 of 8th group of signal output.
1412 BO_Trp_6- BO_Trp_8-1-
1413 BO_Trp_7+ BO_Trp_8-2+
The NO contact 2 of 8th group of signal output.
1414 BO_Trp_7- BO_Trp_8-2-
1415 BO_Trp_8+ BO_Trp_9-1+
The NO contact 1 of 9th group of signal output.
1416 BO_Trp_8- BO_Trp_9-1-
1417 BO_Trp_9+ BO_Trp_9-2+
The NO contact 2 of 9th group of signal output.
1418 BO_Trp_9- BO_Trp_9-2-
1419 BO_Trp_10+ BO_Trp_10-1+
The NO contact 1 of 10th group of signal output.
1420 BO_Trp_10- BO_Trp_10-1-
1421 BO_Trp_11+ BO_Trp_10-2+
The NO contact 2 of 10th group of signal output.
1422 BO_Trp_11- BO_Trp_10-2-

3.3.5.2 Signal Output Module (NR1523B)

Two signal output modules (NR1523B) are equipped at slot B11 and slot B15 positions
respectively.

NR ELECTRIC CO., LTD. 13


3 Hardware Description

Slot B11 Slot B15

NR1523B NR1523B
BO_Signal_1+ 1101 1101 BO_Signal_1+ 1501 1501
BO_Signal_1 BO_Signal_1
BO_Signal_1- 1102 1102 BO_Signal_1- 1502 1502
BO_Signal_2+ 1103 1103 BO_Signal_2+ 1503 1503
BO_Signal_2 BO_Signal_2
BO_Signal_2- 1104 1104 BO_Signal_2- 1504 1504
BO_Signal_3+ 1105 1105 BO_Signal_3+ 1505 1505
BO_Signal_3 BO_Signal_3
BO_Signal_3- 1106 1106 BO_Signal_3- 1506 1506
BO_Signal_4+ 1107 1107 BO_Signal_4+ 1507 1507
BO_Signal_4 BO_Signal_4
BO_Signal_4- 1108 1108 BO_Signal_4- 1508 1508
BO_Signal_5+ 1109 1109 BO_Signal_5+ 1509 1509
BO_Signal_5 BO_Signal_5
BO_Signal_5- 1110 1110 BO_Signal_5- 1510 1510
BO_Signal_6+ 1111 1111 BO_Signal_6+ 1511 1511
BO_Signal_6 BO_Signal_6
BO_Signal_6- 1112 1112 BO_Signal_6- 1512 1512
BO_Signal_7+ 1113 1113 BO_Signal_7+ 1513 1513
BO_Signal_7- 1114 BO_Signal_7 BO_Signal_7- 1514 BO_Signal_7
1114 1514
BO_Signal_8+ 1115 1115 BO_Signal_8+ 1515 1515
BO_Signal_8 BO_Signal_8
BO_Signal_8- 1116 1116 BO_Signal_8- 1516 1516
BO_Signal_9+ 1117 1117 BO_Signal_9+ 1517 1517
BO_Signal_9 BO_Signal_9
BO_Signal_9- 1118 1118 BO_Signal_9- 1518 1518
BO_Signal_10+ 1119 1119 BO_Signal_10+ 1519 1519
BO_Signal_10- 1120 BO_Signal_10 BO_Signal_10- 1520 BO_Signal_10
1120 1520
BO_Signal_11+ 1121 1121 BO_Signal_11+ 1521 1521
BO_Signal_11- 1122 BO_Signal_11 BO_Signal_11- 1522 BO_Signal_11
1122 1522

Figure 3.3-6 Pin definition of signal output module

Pin definitions of the signal output module at slot B11 position are shown as follows.

Pin Original New-defined


Description
No. Symbol Symbol
1101 BO_Signal_1+
Not used
1102 BO_Signal_1-
1103 BO_Signal_2+
Not used
1104 BO_Signal_2-
1105 BO_Signal_3+ BO_Alm_VTS_1+
The NO contact 1 of VT circuit failure alarm.
1106 BO_Signal_3- BO_Alm_VTS_1-
1107 BO_Signal_4+ BO_Alm_VTS_2+
The NO contact 2 of VT circuit failure alarm.
1108 BO_Signal_4- BO_Alm_VTS_2-
1109 BO_Signal_5+ BO_Alm_CTS_1+
The NO contact 1 of CT circuit failure alarm.
1110 BO_Signal_5- BO_Alm_CTS_1-
1111 BO_Signal_6+ BO_Alm_CTS_2+
The NO contact 2 of CT circuit failure alarm.
1112 BO_Signal_6- BO_Alm_CTS_2-
1113 BO_Signal_7+

14 NR ELECTRIC CO., LTD.


3 Hardware Description

Pin Original New-defined


Description
No. Symbol Symbol
1114 BO_Signal_7-
1115 BO_Signal_8+
Not used
1116 BO_Signal_8-
1117 BO_Signal_9+
Not used
1118 BO_Signal_9-
1119 BO_Signal_10+
Not used
1120 BO_Signal_10-
1121 BO_Signal_11+ BO_Prot+ The magnetic latched NO contact of indicating
1122 BO_Signal_11- BO_Prot- protection operates.

Pin definitions of the signal output module at slot B15 position are shown as follows.

Pin Original New-defined


Description
No. Symbol Symbol
1501 BO_Signal_1+ BO_Diff_1+ The NO contact 1 indicating current differential
1502 BO_Signal_1- BO_Diff_1- protection operates.

1503 BO_Signal_2+ BO_Diff_1+ The NO contact 2 indicating current differential


1504 BO_Signal_2- BO_Diff_1- protection operates.

1505 BO_Signal_3+ BO_WdgDiff_1+ The NO contact 1 indicating restricted earth


1506 BO_Signal_3- BO_WdgDiff _1- fault protection operates.

1507 BO_Signal_4+ BO_WdgDiff _2+ The NO contact 2 indicating restricted earth


1508 BO_Signal_4- BO_WdgDiff _2- fault protection operates.

1509 BO_Signal_5+ BO_OC_1+ The NO contact 1 indicating overcurrent


1510 BO_Signal_5- BO_OC_1- protection operates.

1511 BO_Signal_6+ BO_OC_2+ The NO contact 2 indicating overcurrent


1512 BO_Signal_6- BO_OC_2- protection operates.

1513 BO_Signal_7+ BO_ROC+ The NO contact indicating zero-sequence


1514 BO_Signal_7- BO_ROC- overcurrent protection operates.

1515 BO_Signal_8+
Not used
1516 BO_Signal_8-
1517 BO_Signal_9+
Not used
1518 BO_Signal_9-
1519 BO_Signal_10+ BO_OvExc+ The NO contact indicating overexcitation

NR ELECTRIC CO., LTD. 15


3 Hardware Description

Pin Original New-defined


Description
No. Symbol Symbol
1520 BO_Signal_10- BO_OvExc- protection operates.

1521 BO_Signal_11+ BO_Prot+ The magnetic latched NO contact of indicating


1522 BO_Signal_11- BO_Prot- protection operates.

16 NR ELECTRIC CO., LTD.


3 Hardware Description

3.3.6 Analog Input Module

3.3.6.1 AC Analog Input Module (NR1401)

Two AC analog input modules (NR1401) are equipped at slot B04 and slot B06 positions
respectively.

NR1401 NR1401

I1 0401 I1n 0402 I1 0601 I1n 0602

I2 0403 I2n 0404 I2 0603 I2n 0604

I3 0405 I3n 0406 I3 0605 I3n 0606

I4 0407 I4n 0408 I4 0607 I4n 0608

I5 0409 I5n 0410 I5 0609 I5n 0610

I6 0411 I6n 0412 I6 0611 I6n 0612

U1 0413 U1n 0414 U1 0613 U1n 0614

U2 0415 U2n 0416 U2 0615 U2n 0616

U3 0417 U3n 0418 U3 0617 U3n 0618

U4 0419 U4n 0420 U4 0619 U4n 0620

U5 0421 U5n 0422 U5 0621 U5n 0622

U6 0423 U6n 0424 U6 0623 U6n 0624

Figure 3.3-7 Pin definition of AC analog output module

WARNING: The rated voltages of voltage transformers on the AC analog input module at

slot 04 position are 100V, and those of voltage transformers on the AC analog input
module at slot 06 position are 100V (for the first three VTs) and 200V ( for the last three
VTs).

 For three-winding transformer

Pin definitions of the AC analog input module at slot B04 position are shown as follows.

Pin Original New-defined


Description
No. Symbol Symbol
0401 I1 Ia_Line
The phase A current input of Line side CT.
0402 I1n Ian_Line
0403 I2 Ib_Line
The phase A current input of Line side CT.
0404 I2n Ibn_Line
0405 I3 Ic_Line
The phase A current input of Line side CT.
0406 I3n Icn_Line
0407 I4 Reserved

NR ELECTRIC CO., LTD. 17


3 Hardware Description

Pin Original New-defined


Description
No. Symbol Symbol
0408 I4n
0409 I5
Reserved
0410 I5n
0411 I6
Reserved
0412 I6n
0413 U1 Ua
The phase A voltage input of three-phase VT
0414 U1n Uan
0415 U2 Ub
The phase B voltage input of three-phase VT
0416 U2n Ubn
0417 U3 Uc
The phase C voltage input of three-phase VT
0418 U3n Ucn
0419 U4
Reserved
0420 U4n
0421 U5
Reserved
0422 U5n
0423 U6
Reserved
0424 U6n

Pin definitions of the AC analog input module at slot B06 position are shown as follows.

Pin Original New-defined


Description
No. Symbol Symbol
0601 I1 Ia_End
The phase A current input of end side CT.
0602 I1n Ian_End
0603 I2 Ib_End
The phase B current input of end side CT.
0604 I2n Ibn_End
0605 I3 Ic_End
The phase C current input of end side CT.
0606 I3n Icn_End
0607 I4
Reserved
0608 I4n
0609 I5
Reserved
0610 I5n
0611 I6 Reserved

18 NR ELECTRIC CO., LTD.


3 Hardware Description

Pin Original New-defined


Description
No. Symbol Symbol
0612 I6n
0613 U1
Reserved
0614 U1n
0615 U2
Reserved
0616 U2n
0617 U3
Reserved
0618 U3n
0619 U4
Reserved
0620 U4n
0621 U5
Reserved
0622 U5n
0623 U6
Reserved
0624 U6n

3.4 Tripping Matrix

For the module configuration of PCS-978 in the project, two NR1521A modules are equipped with
being installed adjacently in slot B13 and slot B14, and then tripping output contacts controlled by
logic setting are list in the following table.

Table 6.4-1 Tripping matrix output contact list

Contact
Bit Tripping output group Controlled contacts
amount
1301-1302, 1303-1304,
0 TrpOutp1: the 1st group of tripping output contacts 3
1305-1306

1 TrpOutp2: the 2nd group of tripping output contacts 1307-1308, 1309-1310 2

2 TrpOutp3: the 3rd group of tripping output contacts 1311-1312, 1313-1314 2

3 TrpOutp4: the 4th group of tripping output contacts 1315-1316, 1317-1318 2

4 TrpOutp5: the 5th group of tripping output contacts 1319-1320, 1321-1322 2

1401-1402, 1403-1404
5 TrpOutp6: the 6th group of tripping output contacts 3
1405-1406,

6 TrpOutp7: the 7th group of tripping output contacts 1407-1408 1409-1410, 2

7 TrpOutp8: the 8th group of tripping output contacts 1411-1412, 1413-1414 2

8 TrpOutp9: the 9th group of tripping output contacts 1415-1416 1417-1418 2

NR ELECTRIC CO., LTD. 19


3 Hardware Description

Contact
Bit Tripping output group Controlled contacts
amount

9 TrpOutp10: the 10th group of tripping output contacts 1419-1420 1421-1422 2

10 No definition

11 No definition

12 No definition

13 No definition

14 No definition

15 No definition

20 NR ELECTRIC CO., LTD.


4 Human Machine Interface

4 Human Machine Interface


The definition of configurable LED indicators is list in the following table, which can be configurable
on site according to user requirements.

LED No Display Description

4 Instant Diff Unrestrained instantaneous differential protection operates.

5 Percent Diff Percent differential protection operates.

6 DPFC Diff DPFC percent differential protection operates.

7 Winding Diff Winding differential protection operates.

8 Reserved

9 Reserved

10 DefOvExc1 Stage 1 of definite-time overexcitation protection operates.

11 InvOvExc Stage 2 of definite-time overexcitation protection operates.

12 OC1 of Line Side Stage 1 of overcurrent protection of line side CT operates.

13 OC2 of Line Side Stage 2 of overcurrent protection of line side CT operates.

14 ROC1 of Line Side Stage 1 of zero-sequence overcurrent protection of line side CT operates.

15 ROC2 of Line Side Stage 2 of zero-sequence overcurrent protection of line side CT operates.

16 Reserved

17 Reserved

18 OC1 of End Side Stage 1 of overcurrent protection of end side CT operates.

19 OC2 of End Side Stage 2 of overcurrent protection of end side CT operates.

20 Reserved

NR ELECTRIC CO., LTD. 21


4 Human Machine Interface

22 NR ELECTRIC CO., LTD.


5 Manual Version History

5 Manual Version History


In the latest version of the instruction manual, several descriptions on existing features have been
modified.

Manual version and modification history records

Manual Version Software


Date Description of change
Source New Version
1.00 1.00 2010-08-26 Form the original manual.

NR ELECTRIC CO., LTD. 23


5 Manual Version History

24 NR ELECTRIC CO., LTD.

You might also like