Kohler tp-5982

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 64

Installation

Marine Generator Sets

Models:
5E/4EF
7.3E/6EF
5ECD/4EFCD
7.3ECD/6EFCD
10EG
13EG/EGZ
15EG/EGZ
15C/12.5CF
20C/17.5CF

TP-5982 4/06f
2 TP-5982 4/06
Table of Contents

Safety Precautions and Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5


Section 1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Section 2 Location and Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2.1 General Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2.2 Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
2.3 Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Section 3 Cooling System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.1 Ventilation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.2 Cooling System Components . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.2.1 Intake Through-Hull Strainer (Seacock Cover) . . . . . . . . . . . . . . . . . . . . . 15
3.2.2 Seacock . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3.2.3 Seawater Strainer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
3.2.4 Waterlines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
3.2.5 Closed Heat Exchanger . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Section 4 Exhaust System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4.1 Exhaust Lines . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4.2 Exhaust Systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
4.2.1 Above Waterline Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
4.2.2 Mid/Below Waterline Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Section 5 Fuel System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
5.1 Fuel Tank . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
5.2 Fuel Inlet Line . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
5.3 Fuel Filters or Strainers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
5.3.1 5/7.3E, 4/6EF, 5/7.3ECD, 4/6EFCD, 10/13/15EG, and
13/15EGZ Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
5.3.2 15/20C and 12.5/16CF Models . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
5.4 Antisiphon Device Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
5.5 Fuel Pump Lift and Fuel Consumption . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
5.6 Fuel System Bleed Procedure 5/7.3ECD and 4/6EFCD Models . . . . . . . . . . . . . . 28
Section 6 Electrical System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
6.1 AC Voltage Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
6.2 Circuit Protection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
6.2.1 Circuit Breaker Considerations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
6.2.2 Circuit Breaker Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
6.3 ADC 2100 Continuous Power Mode Jumper (10/13/15EG Models) . . . . . . . . . . . 32
6.4 Installation in Steel or Aluminum Vessels . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
6.5 Installation Regulations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
6.6 Battery . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34
6.7 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
6.8 Remote Start Switch Connection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
Section 7 Installation Drawings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
Section 8 Reconnection/Adjustments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
8.1 Four-Lead Reconnection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
8.2 Voltage Regulator Adjustment (5/7.3E, 4/6EF, 15/20C, and 12.5/16CF Models) 50
8.3 ADC 2100 Adjustment (5/7.3ECD, 4/6EFCD, 10/13/15EG, and
13/15EGZ Models) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
8.3.1 Configuration Mode Time Out . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
8.3.2 Controller Software Version Number . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
8.3.3 Configuration Mode . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 52
8.3.4 Adjusting the Voltage, Gain, Volts/Hz, and Engine Speed . . . . . . . . . . . 54
8.3.5 Voltage Adjustment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 54
Appendix A Generator Selection and Wattage Requirements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
Appendix B Abbreviations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 60
Appendix C Generator Set Output Ratings Procedure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62

TP-5982 4/06 Table of Contents 3


4 TP-5982 4/06
Safety Precautions and Instructions

IMPORTANT SAFETY INSTRUCTIONS. Accidental Starting Battery


Electromechanical equipment,
including generator sets, transfer
switches, switchgear, and accessories, WARNING WARNING
can cause bodily harm and pose
life-threatening danger when
improperly installed, operated, or
maintained. To prevent accidents be
aware of potential dangers and act
safely. Read and follow all safety
precautions and instructions. SAVE Accidental starting.
Can cause severe injury or death. Sulfuric acid in batteries.
THESE INSTRUCTIONS.
Can cause severe injury or death.
Disconnect the battery cables before
This manual has several types of safety working on the generator set. Wear protective goggles and
precautions and instructions: Danger, Remove the negative (--) lead first clothing. Battery acid may cause
Warning, Caution, and Notice. when disconnecting the battery. blindness and burn skin.
Reconnect the negative (--) lead last
when reconnecting the battery. Battery electrolyte is a diluted
DANGER sulfuric acid. Battery acid can cause
Disabling the generator set. severe injury or death. Battery acid
Danger indicates the presence of a can cause blindness and burn skin.
Accidental starting can cause
hazard that will cause severe Always wear splashproof safety
severe injury or death. Before
personal injury, death, or substantial goggles, rubber gloves, and boots
working on the generator set or
property damage. when servicing the battery. Do not
equipment connected to the set,
disable the generator set as follows: open a sealed battery or mutilate the
(1) Place the generator set start/stop battery case. If battery acid splashes in
WARNING the eyes or on the skin, immediately
switch in the STOP position.
(2) Disconnect the power to the battery flush the affected area for 15 minutes
Warning indicates the presence of a charger, if equipped. (3) Remove the with large quantities of clean water.
hazard that can cause severe battery cables, negative (--) lead first. Seek immediate medical aid in the case
personal injury, death, or substantial Reconnect the negative (--) lead last of eye contact. Never add acid to a
property damage. when reconnecting the battery. Follow battery after placing the battery in
these precautions to prevent the service, as this may result in hazardous
starting of the generator set by the spattering of battery acid.
CAUTION remote start/stop switch. Battery acid cleanup. Battery acid
Disabling the generator set. can cause severe injury or death.
Caution indicates the presence of a Battery acid is electrically conductive
hazard that will or can cause minor Accidental starting can cause
severe injury or death. Before and corrosive. Add 500 g (1 lb.) of
personal injury or property damage. bicarbonate of soda (baking soda) to a
working on the generator set or
connected equipment, disable the container with 4 L (1 gal.) of water and
NOTICE mix the neutralizing solution. Pour the
generator set as follows: (1) Move the
Notice communicates installation, generator set master switch to the OFF neutralizing solution on the spilled
operation, or maintenance information position. (2) Disconnect the power to battery acid and continue to add the
that is safety related but not hazard the battery charger. (3) Remove the neutralizing solution to the spilled
related. battery cables, negative (--) lead first. battery acid until all evidence of a
Reconnect the negative (--) lead last chemical reaction (foaming) has
Safety decals affixed to the equipment ceased. Flush the resulting liquid with
when reconnecting the battery. Follow
in prominent places alert the operator water and dry the area.
these precautions to prevent starting of
or service technician to potential
the generator set by an automatic
hazards and explain how to act safely.
transfer switch, remote start/stop
The decals are shown throughout this
switch, or engine start command from a
publication to improve operator
remote computer.
recognition. Replace missing or
damaged decals.

TP-5982 4/06 Safety Precautions and Instructions 5


Battery gases. Explosion can cause Engine Backfire/Flash Engine Fluids and
severe injury or death. Battery gases
can cause an explosion. Do not smoke Fire Chemical Products
or permit flames or sparks to occur near
a battery at any time, particularly when WARNING WARNING
it is charging. Do not dispose of a
battery in a fire. To prevent burns and
sparks that could cause an explosion,
avoid touching the battery terminals
with tools or other metal objects.
Remove all jewelry before servicing the Fire.
equipment. Discharge static electricity Can cause severe injury or death. Handling caustic engine fluids and
from your body before touching chemical products.
batteries by first touching a grounded Do not smoke or permit flames or Can cause severe chemical burns,
metal surface away from the battery. To sparks near fuels or the fuel system. nausea, fainting, or death.
avoid sparks, do not disturb the battery Most chemicals such as used engine
charger connections while the battery Servicing the backfire flame oil, antifreeze/coolant, rustproofing
is charging. Always turn the battery arrester. A sudden backfire can agent, inhibiting oil, degreasing
charger off before disconnecting the cause severe injury or death. Do not agent, spray paint, and adhesives are
battery connections. Ventilate the operate the generator set with the hazardous to health. Read and follow
compartments containing batteries to backfire flame arrester removed. the user information found on the
prevent accumulation of explosive packaging. Avoid inhalation and skin
gases. Combustible materials. A sudden
flash fire can cause severe injury or contact. Use only in well-ventilated
Battery short circuits. Explosion death. Do not smoke or permit flames areas and use a protective mask
can cause severe injury or death. or sparks near the generator set. Keep when spraying. Store engine fluids
Short circuits can cause bodily injury the compartment and the generator set and chemical products in a locked
and/or equipment damage. clean and free of debris to minimize the cabinet. Contact your local recycling
Disconnect the battery before risk of fire. Catch fuels in an approved center for disposal information and
generator set installation or container. Wipe up spilled fuels and locations.
maintenance. Remove all jewelry engine oil.
before servicing the equipment. Use
tools with insulated handles. Remove Combustible materials. A fire can WARNING
the negative (--) lead first when cause severe injury or death.
disconnecting the battery. Reconnect Generator set engine fuels and fuel
the negative (--) lead last when vapors are flammable and explosive.
reconnecting the battery. Never Handle these materials carefully to
connect the negative (--) battery cable minimize the risk of fire or explosion.
to the positive (+) connection terminal Equip the compartment or nearby area Flammable engine solvents and
of the starter solenoid. Do not test the with a fully charged fire extinguisher. cleaners.
Select a fire extinguisher rated ABC or Can cause severe injury or death.
battery condition by shorting the
terminals together. BC for electrical fires or as
recommended by the local fire code or Do not smoke or permit flames or
an authorized agency. Train all sparks near flammable engine
personnel on fire extinguisher solvents and cleaners. Read and
operation and fire prevention follow the user information found on
procedures. the packaging. Use only in well-
ventilated areas. Never use gasoline
or low flash-point solvents as
cleaning agents.

Leaking or accumulated engine


fluids. A fire can cause severe injury
or death. Clean up engine fluids
including fuel, oil, grease, and coolant.
Determine the source of engine leaks
and correct before starting the
generator set. Keep the generator set
area clean and remove combustible
materials.

6 Safety Precautions and Instructions TP-5982 4/06


Used engine oil. Contact with used Carbon monoxide symptoms. Operating the generator set. Carbon
engine oil may cause severe skin Carbon monoxide can cause severe monoxide can cause severe nausea,
irritation. Repeated and prolonged nausea, fainting, or death. Carbon fainting, or death. Carbon monoxide
skin exposure may have other monoxide is a poisonous gas present in is an odorless, colorless, tasteless,
health risks. Used engine oil is a exhaust gases. Carbon monoxide nonirritating gas that can cause death if
suspected carcinogen. Avoid contact poisoning symptoms include but are inhaled for even a short time. Use the
with skin. Thoroughly wash your hands not limited to the following: following precautions when installing
and nails with soap and water shortly D Light-headedness, dizziness and operating the generator set. Do not
after handling used engine oil. Wash or D Physical fatigue, weakness in install the exhaust outlet where exhaust
dispose of clothing or rags containing joints and muscles can be drawn in through portholes,
used engine oil. Dispose of used D Sleepiness, mental fatigue, vents, or air conditioners. Avoid
engine oil in a responsible manner. inability to concentrate overloading the craft. If the generator
Contact your local recycling center for or speak clearly, blurred vision set exhaust discharge outlet is near the
disposal information and locations. D Stomachache, vomiting, nausea waterline, water could enter the
If experiencing any of these symptoms exhaust discharge outlet and close or
Fire-damaged or burned O-rings and carbon monoxide poisoning is restrict the flow of exhaust. Never
may cause the formation of possible, seek fresh air immediately operate the generator set without a
hydrofluoric acid. Contact with and remain active. Do not sit, lie down, functioning carbon monoxide detector.
hydrofluoric acid may cause severe or fall asleep. Alert others to the Be especially careful if operating the
skin irritation and chemical burns. possibility of carbon monoxide generator set when moored or
O-rings and other fluoroelastomer poisoning. Seek medical attention if anchored under calm conditions
seals exposed to fire or temperatures the condition of affected persons does because gases may accumulate. If
above 316_C (600_F) (i.e., during not improve within minutes of breathing operating the generator set dockside,
welding) may decompose forming fresh air. moor the craft so that the exhaust
hydrofluoric acid. Avoid inhalation or discharges on the lee side (the side
skin contact. Do not incinerate O-rings. Inspecting the exhaust system. sheltered from the wind). Always be
Dispose of O-ring waste material in a Carbon monoxide can cause severe aware of others, making sure your
responsible manner. nausea, fainting, or death. For the exhaust is directed away from other
safety of the craft’s occupants, install a boats and buildings.
carbon monoxide detector. Consult the
Exhaust System boat builder or dealer for approved
detector location and installation.
Inspect the detector before each
Fuel System
WARNING generator set use. In addition to routine
exhaust system inspection, test the
carbon monoxide detector per the
WARNING
manufacturer’s instructions and keep
the detector operational at all times.

Carbon monoxide.
Can cause severe nausea,
fainting, or death. Explosive fuel vapors.
Can cause severe injury or death.
The exhaust system must be
leakproof and routinely inspected. Use extreme care when handling,
storing, and using fuels.

WARNING

Explosion.
Gasoline vapors can cause
explosion and severe injury or
death.

Before starting the generator set,


operate the blower 4 minutes and
check the engine compartment for
gasoline vapors.

TP-5982 4/06 Safety Precautions and Instructions 7


Installing the fuel system. Explosive Hazardous Voltage/
WARNING fuel vapors can cause severe injury
or death. Fuel leakage can cause an Electrical Shock
explosion. Do not modify the tank or
the propulsion engine fuel system. WARNING
Equip the craft with a tank that allows
one of the two pickup arrangements
Avoid high pressure fluids. described in the installation section.
Can cause severe injury or death. The tank and installation must conform
Do not work on high pressure fuel or to USCG Regulations.
hydraulic systems without Pipe sealant. Explosive fuel vapors Hazardous voltage. Moving rotor.
protective equipment to protect can cause severe injury or death. Can cause severe injury or death.
hands, eyes, and body. Avoid the Fuel leakage can cause an explosion.
hazard by relieving pressure before Operate the generator set only when
Use pipe sealant on all threaded fittings
disconnecting fuel injection all guards and electrical enclosures
to prevent fuel leakage. Use pipe
pressure lines. Search for leaks are in place.
sealant that resists gasoline, grease,
using a piece of cardboard. Always lubrication oil, common bilge solvents,
protect hands, eyes, and body from salt deposits, and water. Grounding electrical equipment.
high pressure fluids. If an accident Hazardous voltage can cause
occurs, seek medical attention Ignition-protected equipment. severe injury or death. Electrocution
immediately. Explosive fuel vapors can cause is possible whenever electricity is
severe injury or death. Gasoline present. Turn off the main circuit
The fuel system. Explosive fuel vapors can cause an explosion. breakers of all power sources before
vapors can cause severe injury or USCG Regulation 33CFR183 requires servicing the equipment. Configure the
death. Vaporized fuels are highly that all electrical devices (ship-to-shore installation to electrically ground the
explosive. Use extreme care when transfer switch, remote start panel, generator set, transfer switch, and
handling and storing fuels. Store fuels etc.) must be ignition protected when related equipment and electrical
in a well-ventilated area away from used in a gasoline and gaseous-fueled circuits to comply with applicable codes
spark-producing equipment and out of environment. The electrical devices and standards. Never contact
the reach of children. Never add fuel to listed above are not ignition protected electrical leads or appliances when
the tank while the engine is running and are not certified to operate in a standing in water or on wet ground
because spilled fuel may ignite on gasoline and gaseous-fueled because these conditions increase the
contact with hot parts or from sparks. environment such as an engine room or risk of electrocution.
Do not smoke or permit flames or near fuel tanks. Acceptable locations
sparks to occur near sources of spilled are the wheelhouse and other living Disconnecting the electrical load.
fuel or fuel vapors. Keep the fuel lines areas sheltered from rain and water Hazardous voltage can cause
and connections tight and in good splash. severe injury or death. Disconnect
condition. Do not replace flexible fuel the generator set from the load by
lines with rigid lines. Use flexible opening the line circuit breaker or by
sections to avoid fuel line breakage Hazardous Noise disconnecting the generator set output
caused by vibration. Do not operate the leads from the transfer switch and
generator set in the presence of fuel heavily taping the ends of the leads.
leaks, fuel accumulation, or sparks. CAUTION High voltage transferred to the load
Repair fuel systems before resuming during testing may cause personal
generator set operation. injury and equipment damage. Do not
use the safeguard circuit breaker in
Explosive fuel vapors can cause place of the line circuit breaker. The
severe injury or death. Take safeguard circuit breaker does not
additional precautions when using the disconnect the generator set from the
following fuels: Hazardous noise. load.
Can cause hearing loss.
Gasoline—Store gasoline only in
approved red containers clearly Never operate the generator set
marked GASOLINE. without a muffler or with a faulty
exhaust system.
Draining the fuel system. Explosive
fuel vapors can cause severe injury
Engine noise. Hazardous noise can
or death. Spilled fuel can cause an
cause hearing loss. Wear hearing
explosion. Use a container to catch fuel
protection when near an operating
when draining the fuel system. Wipe up
generator set Prolonged exposure to
spilled fuel after draining the system.
noise levels greater than 85 dBA can
cause permanent hearing loss.

8 Safety Precautions and Instructions TP-5982 4/06


Short circuits. Hazardous Hot Parts Servicing the exhaust system. Hot
voltage/current can cause severe parts can cause severe injury or
injury or death. Short circuits can death. Do not touch hot engine parts.
cause bodily injury and/or equipment WARNING The engine and exhaust system
damage. Do not contact electrical components become extremely hot
connections with tools or jewelry while during operation.
making adjustments or repairs.
Remove all jewelry before servicing the
equipment. Moving Parts
Hot coolant and steam.
Testing the voltage regulator. Can cause severe injury or death.
Hazardous voltage can cause WARNING
severe injury or death. High voltage Before removing the pressure cap,
is present at the voltage regulator heat stop the generator set and allow it to
sink. To prevent electrical shock do not cool. Then loosen the pressure cap
touch the voltage regulator heat sink to relieve pressure.
when testing the voltage regulator.
(PowerBoostt, PowerBoostt III, and Hazardous voltage. Moving rotor.
PowerBoostt V voltage regulator WARNING Can cause severe injury or death.
models only)
Operate the generator set only when
Electrical backfeed to the utility. all guards and electrical enclosures
Hazardous backfeed voltage can are in place.
cause severe injury or death.
Connect the generator set to the Hot engine and exhaust system.
building/marina electrical system only Can cause severe injury or death. WARNING
through an approved device and after
the building/marina main switch is Do not work on the generator set until
opened. Backfeed connections can it cools.
cause severe injury or death to utility
personnel working on power lines
and/or personnel near the work area. WARNING
Some states and localities prohibit Rotating parts.
unauthorized connection to the utility Can cause severe injury or death.
electrical system. Install a
Operate the generator set only when
ship-to-shore transfer switch to prevent
all guards, screens, and covers are in
interconnection of the generator set
place.
power and shore power. Hot engine oil.
Can cause severe injury or death.
Testing live electrical circuits.
Hazardous voltage or current can Avoid skin contact with hot oil. Do not WARNING
cause severe injury or death. Have start or operate the generator set with
trained and qualified personnel take the engine oil filler cap removed, as
diagnostic measurements of live hot oil can spray out. Ensure that the
circuits. Use adequately rated test lubrication system is not under
equipment with electrically insulated pressure when servicing. Do not
probes and follow the instructions of the work on the generator set until it
test equipment manufacturer when cools. Airborne particles.
performing voltage tests. Observe the Can cause severe injury or
following precautions when performing blindness.
Checking the coolant level. Hot
voltage tests: (1) Remove all jewelry.
coolant can cause severe injury or Wear protective goggles and clothing
(2) Stand on a dry, approved electrically
death. Allow the engine to cool. when using power tools, hand tools,
insulated mat. (3) Do not touch the
Release pressure from the cooling or compressed air.
enclosure or components inside the
system before removing the pressure
enclosure. (4) Be prepared for the
cap. To release pressure, cover the
system to operate automatically.
pressure cap with a thick cloth and then
(600 volts and under)
slowly turn the cap counterclockwise to
the first stop. Remove the cap after
pressure has been completely
released and the engine has cooled.
Check the coolant level at the tank if the
generator set has a coolant recovery
tank.

TP-5982 4/06 Safety Precautions and Instructions 9


Tightening the hardware. Flying Notice NOTICE
projectiles can cause severe injury Electrostatic discharge damage.
or death. Loose hardware can cause Electrostatic discharge (ESD)
the hardware or pulley to release from NOTICE damages electronic circuit boards.
the generator set engine and can cause Prevent electrostatic discharge
personal injury. Retorque all This generator set has been damage by wearing an approved
crankshaft and rotor hardware after rewired from its nameplate voltage grounding wrist strap when handling
servicing. Do not loosen the crankshaft to electronic circuit boards or integrated
hardware or rotor thrubolt when making circuits. An approved grounding wrist
adjustments or servicing the generator strap provides a high resistance (about
set. Rotate the crankshaft manually in 1 megohm), not a direct short, to
a clockwise direction only. Turning the ground.
crankshaft bolt or rotor thrubolt 246242

counterclockwise can loosen the NOTICE


hardware.
NOTICE Fuse replacement. Replace fuses
Servicing the generator set when it Voltage reconnection. Affix a notice with fuses of the same ampere rating
is operating. Exposed moving parts to the generator set after reconnecting and type (for example: 3AB or 314,
can cause severe injury or death. the set to a voltage different from the ceramic). Do not substitute clear
Keep hands, feet, hair, clothing, and voltage on the nameplate. Order glass-type fuses for ceramic fuses.
test leads away from the belts and voltage reconnection decal 246242 Refer to the wiring diagram when the
pulleys when the generator set is from an authorized service ampere rating is unknown or
running. Replace guards, screens, and distributor/dealer. questionable.
covers before operating the generator
set. NOTICE NOTICE
Hardware damage. The engine and Saltwater damage. Saltwater quickly
Sound shield removal. Exposed
generator set may use both American deteriorates metals. Wipe up saltwater
moving parts can cause severe
Standard and metric hardware. Use on and around the generator set and
injury or death. The generator set
the correct size tools to prevent remove salt deposits from metal
must be operating in order to perform
rounding of the bolt heads and nuts. surfaces.
some scheduled maintenance
procedures. Be especially careful if the
sound shield has been removed, NOTICE
leaving the belts and pulleys exposed. When replacing hardware, do not
(Sound-shield-equipped models only) substitute with inferior grade
hardware. Screws and nuts are
available in different hardness ratings.
To indicate hardness, American
Standard hardware uses a series of
markings, and metric hardware uses a
numeric system. Check the markings
on the bolt heads and nuts for
identification.

10 Safety Precautions and Instructions TP-5982 4/06


Section 1 Introduction

All information in this publication represents data Marine generator set installations must comply with all
available at time of print. Kohler Co. reserves the right to applicable regulations and standards.
change this literature and the products represented
without incurring obligation. The installer is responsible for improper installations
resulting in penalties from noncompliance with CARB or
The safe and successful operation of a marine power EPA emission standards.
system depends primarily on the installation. See
Figure 1-1 or Figure 1-2. Use this manual as a guide to Refer to each model’s specification sheet for details.
install the marine generator set. For operating Use the spec sheets as a guide in planning your
instructions, refer to the operation manual. installation. Use current dimension drawings and wiring
diagrams.
Note: Only qualified persons should install the
generator set.

2
11

9 4
10

8 7

6 5
1. Heat exchanger 7. Fuel line*
2. Coolant recovery tank 8. Worm clamps
3. Seawater strainer* 9. Mounting tray
4. Raw waterline 10. Mounting base
5. Intake through-hull strainer 11. Exhaust line* 598211
6. Seacock* * Indicates components must conform to USCG regulations.

Figure 1-1 Typical Location and Mounting (5/7.3E, 4/6EF, 15/20C, and 12.5/16CF Models)
Note: See text for complete explanation of installation Note: Use two hose clamps on each end of all flexible
requirements. exhaust hose connections.

TP-5982 4/06 Section 1 Introduction 11


1 2 3

16

15

14
4

13

12 5
11

8
10 6

9 7

585711

1. Exhaust mixer elbow (exhaust/water outlet) 10. Fuel supply line *


2. Coolant recovery tank 11. Mounting tray
3. Heat exchanger (not shown) 12. Fuel feed pump (fuel inlet) *
4. Seawater strainer * 13. Battery/battery storage box
5. Seawater pump (seawater inlet) 14. Battery cables
6. Seawater line * 15. Exhaust hose or exhaust line *
7. Seacock * 16. Electrical leads (AC output leads/remote start panel leads)
8. Craft stringers
9. Hose clamps * Indicated components must conform to USCG regulations.

Figure 1-2 Typical Generator Set Location and Mounting (10/13/15EG Model Shown, 13/15EGZ, 5/7.3ECD and
4/6EFCD Models Similar)

Note: See text for complete explanation of installation Note: Use two hose clamps on each end of all flexible
requirements. exhaust hose connections.

12 Section 1 Introduction TP-5982 4/06


Section 2 Location and Mounting

2.1 General Considerations Allow clearance for vibration and cooling during
operation. Allow a minimum of 38 mm (1.5 in.)
The key to installation is location. Before making final clearance on all sides (top, front, rear, and sides) of a
plans for locating a generator set, consider the following generator set without an optional sound shield. Refer to
subsections on this page concerning the set and the the instruction sheet for minimum clearances for
proposed location. sound-shielded units. Also, allow space for the power
takeoff (PTO) option, if equipped.
Installation Location Considerations
1. Choose a location that allows adequate space for 2.3 Mounting
cooling and exhaust system installation, fuel
Craft stringers generally provide the best support for a
system installation, ventilation, and service access
generator set. Ensure that the structural members for
to the generator set (engine and generator).
mounting can support generator set weight and
2. Use craft stringers or other available structural withstand vibration. The generator set includes
members capable of supporting the generator set’s vibration mounts and a mounting tray; if desired, install
weight. additional vibration isolating pads underneath the
generator set’s base. Use the four mounting holes in the
3. Seal the generator set compartment from the cabin mounting tray to mount the generator set securely to the
to prevent exhaust gases and fuel vapors from craft.
entering the cabin.
Position the generator set so it will not adversely alter
See the current generator set specification sheet or the craft’s performance.
Section 7 of this manual for generator set dimensions
and weights. See Figure 1-1 for a typical installation. Mount the generator set as high as possible to avoid
m:is:101:001 contact with bilge splash and lower-lying vapors and to
allow for a downward pitch of the exhaust line toward the
2.2 Location exhaust outlet.

Locate the generator set to allow easy service access to For angular operating limits, consult the operation
the generator set’s engine, controller, cooling, and fuel manual.
system components. The engine compartment is often
the ideal location for the generator set if the propulsion
engine(s) does not obstruct access to the generator set
and controller.

Marine Generator Set Installations in


European Union Member Countries
This generator set is specifically intended and approved
for installation below the deck in the engine
compartment. Installation above the deck and/or
outdoors would constitute a violation of European Union
Directive 2000/14/EC noise emission standard.

TP-5982 4/06 Section 2 Location and Mounting 13


Notes

14 Section 2 Location and Mounting TP-5982 4/06


Section 3 Cooling System

3.1 Ventilation Model Normal Intake Restriction*

Engine combustion, generator cooling, and expulsion of 5/7.3E and 4/6EF


0 03 psi (0.79
0.03 (0 79 in.
in H2O)
flammable and lethal fumes require ventilation. Provide 5/7.3ECD and 4/6EFCD
ventilation compliant with USCG regulations governing 10/13/15EG and 13/15EGZ 0.36 psi (10 in. H2O)
the sizing of vents and other considerations.
15/20C and 12.5/16CF 0.01 psi (0.29 in. H2O)
As a rule, size each inlet- and outlet-vent area to a * Clean backfire flame arrestor.
minimum of 13 sq. cm/30.5 cm (2 sq. in. per ft.) of the Figure 3-1 Intake Restriction
craft’s beam. Should this rule conflict with USCG
regulations, follow USCG regulations. For applications
with screened inlets, double the size of the hull/deck 3.2 Cooling System Components
openings. Extend the vent ducts to bilges to expel
heavier-than-air fumes. Design the marine generator set cooling system to
include the following features.
For generator sets mounted in the engine compartment,
increase the air flow to allow for the generator set’s 3.2.1 Intake Through-Hull Strainer
requirements. Install UL-listed, ignition-protected
(Seacock Cover)
blowers in the outlet vents and wire them to operate
before starting the engine(s). Install optional detection Install a screened intake through-hull strainer to prevent
devices to cause alarm, warning, or engine shutdown entry of foreign objects. Use perforated, slotted-hole, or
should dangerous fumes accumulate in the unrestricted-hole design strainers. See Figure 3-2 for
compartment. examples of typical strainers. The inner diameter of the
strainer opening must be equal to or greater than the
WARNING inner diameter of the waterline hose to the seawater
pump.

Explosion.
Gasoline vapors can cause
explosion and severe injury or 1
death.

Before starting the generator set,


operate the blower 4 minutes and
check the engine compartment for 2
gasoline vapors.

See the current generator set specification sheet for air


requirements. The air intake silencer/cleaner provides 3
combustion air to the engine. Do not compromise the
recommended minimum clearance of 38 mm (1.5 in.) 4
between a duct opening and enclosure wall. The
engine/generator performance will be adversely
affected if the installer neglects these guidelines. Follow
these guidelines to optimize generator set performance.
See Figure 3-1 for allowable intake restriction.
1. Inside packing
5
Note: ISO 3046 derates apply. See Appendix C. 1-789
2. Outside packing
3. Seacock cover
4. Direction of vessel movement
5. Typical intake through-hull strainers

Figure 3-2 Seacock Installation

TP-5982 4/06 Section 3 Cooling System 15


Do not align the strainer (in relation to the direction of 3.2.3 Seawater Strainer
travel) with any other through-hull intakes. See
Figure 3-3. Flush mount the recommended Mount the seawater strainer to the seacock or
through-hull strainer. Install slotted-hole design permanent structure at a point not higher than the
strainers with the slots parallel to the direction of the seawater pump. Ensure that the strainer is accessible
vessel’s movement. for service. See Figure 3-4 for a typical installation.

Note: Some seawater strainers include a seacock and


an intake through-hull strainer.
2

1
4 3

Note: Position the intakes in relation to the vessel’s 3


travel so neither is in the wake of the other.
1-789
1. Generator set intake
2. Intake 1-789
1. Seawater pump
3. Aft (rearward)
2. Seawater strainer
4. Fore (forward)
3. Seacock
Figure 3-3 Intake Strainer Installation Figure 3-4 Seawater Strainer Installation
Do not use a speed scoop or cup design intake
through-hull strainer because it can cause a ramming
effect and force water upward, past the seawater pump,
and into the engine cylinders when the vessel is moving
and the generator set is shut down.

Do not use hull designs incorporating sea chests or


other designs that provide a positive pressure to the raw
water pump for the intake through-hull strainers. A
positive pressure will force water past the raw water
pump and into the engine. A sea chest is a concave
molded-in-the-hull chamber that aligns to the direction
of travel. A sea chest configuration applies a positive
pressure similar to a scoop-type through-hull strainer.

3.2.2 Seacock
Mount the seacock to the hull, assemble it to the intake,
and ensure that it is accessible for operation. Figure 3-2
shows a typical seacock installation.

Avoid overcaulking the seacock. Excess caulk reduces


water flow and, in some cases, develops a barrier that
can force water upward, past the seawater pump, and
into the engine cylinders when the vessel is moving and
the generator set is shut down.

16 Section 3 Cooling System TP-5982 4/06


3.2.4 Waterlines
Waterlines from the seacock to the engine-driven
seawater pump are usually constructed of flexible hose
or copper tubing. Use a flexible section of hose for
connection to the seawater pump to allow for vibrational
motion of the generator set during operation. Support a
nonflexible waterline within 102 mm (4 in.) of its
connection to the flexible section.

Keep the seawater hose as straight and short as


possible. If the hose is too long, usually over 4.6 m
(15 ft.), water draw problems may occur. See Section 7,
Installation Drawings for the inlet waterline hose size
ADV6817-B
and the seawater connection to seawater pump inlet. 1
Avoid running the inlet pipe above the generator. See 1. Seawater inlet
Figure 3-5, Figure 3-6, Figure 3-7, or Figure 3-8 for the
Figure 3-7 Seawater Inlet Connection (10/13/15EG
seawater connection to the seawater pump inlet.
and 13/15EGZ)

ADV6382A-E
1
1
ADV6395A-K

1. Seawater pump inlet (opposite side) 1. Seawater pump inlet

Figure 3-5 Seawater Inlet Connection (5/7.3E) Figure 3-8 Seawater Inlet Connection (15/20C)

3.2.5 Closed Heat Exchanger


Closed heat exchanger cooling is the best alternative for
most applications. See Figure 3-9 for a typical
installation. Provide service accessibility for the heat
exchanger pressure cap.

1
ADV7025A-A

1. Seawater pump inlet (opposite side)

Figure 3-6 Seawater Inlet Connection (5/7.3ECD)

TP-5982 4/06 Section 3 Cooling System 17


2
1
3

8 5

14

10

11

12

Arrow Description
Seawater
13
Freshwater (Coolant/Antifreeze)

TP-5586-6
1. Engine block 8. Thermostat closed
2. Exhaust manifold 9. Heat exchanger
3. Exhaust mixer elbow 10. Engine-driven seawater pump
4. Outlet flapper (exhaust/water discharge) 11. Seawater strainer
5. Silencer (customer-supplied) 12. Seacock
6. Thermostat open 13. Intake strainer
7. Thermostat 14. Engine-driven water pump

Figure 3-9 Typical Closed/Heat Exchanger Cooling System Installation

18 Section 3 Cooling System TP-5982 4/06


Section 4 Exhaust System

Operating the generator set. Carbon monoxide can cause


WARNING severe nausea, fainting, or death. Carbon monoxide is an
odorless, colorless, tasteless, nonirritating gas that can cause
death if inhaled for even a short time. Use the following
precautions when installing and operating the generator set.
Do not install the exhaust outlet where exhaust can be drawn
in through portholes, vents, or air conditioners. Avoid
Carbon monoxide. overloading the craft. If the generator set exhaust discharge
Can cause severe nausea, outlet is near the waterline, water could enter the exhaust
fainting, or death. discharge outlet and close or restrict the flow of exhaust.
Never operate the generator set without a functioning carbon
The exhaust system must be monoxide detector. Be especially careful if operating the
leakproof and routinely inspected. generator set when moored or anchored under calm
conditions because gases may accumulate. If operating the
Carbon monoxide symptoms. Carbon monoxide can generator set dockside, moor the craft so that the exhaust
cause severe nausea, fainting, or death. Carbon monoxide discharges on the lee side (the side sheltered from the wind).
is a poisonous gas present in exhaust gases. Carbon Always be aware of others, making sure your exhaust is
monoxide poisoning symptoms include but are not limited to directed away from other boats and buildings.
the following:
D Light-headedness, dizziness Note: Should any information regarding installation
D Physical fatigue, weakness in conflict with USCG regulations, follow USCG
joints and muscles regulations.
D Sleepiness, mental fatigue,
inability to concentrate
or speak clearly, blurred vision
D Stomachache, vomiting, nausea
4.1 Exhaust Lines
If experiencing any of these symptoms and carbon monoxide
Use water-cooled exhaust lines in all marine
poisoning is possible, seek fresh air immediately and remain
active. Do not sit, lie down, or fall asleep. Alert others to the installations. Use a 51-mm (2-in.) inside diameter hose.
possibility of carbon monoxide poisoning. Seek medical Keep the lines as short and straight as possible.
attention if the condition of affected persons does not improve NFPA 302 Fire Protection Standard for Pleasure and
within minutes of breathing fresh air. Commercial Motor Craft, Clause 4-3 recommends using
Inspecting the exhaust system. Carbon monoxide can two corrosion-resistant hose clamps with a minimum
cause severe nausea, fainting, or death. For the safety of width of 13 mm (1/2 in.) on each end of the flexible
the craft’s occupants, install a carbon monoxide detector. exhaust hose connections. Kohler Co. requires a
Consult the boat builder or dealer for approved detector downward pitch of at least 13 mm per 30.5 cm (0.5 in.
location and installation. Inspect the detector before each per running foot). Use a flexible exhaust hose that
generator set use. In addition to routine exhaust system
inspection, test the carbon monoxide detector per the
conforms to UL Standard 1129 for the engine wet
manufacturer’s instructions and keep the detector operational exhaust components between the mixer elbow and the
at all times. exhaust outlet.

4.2 Exhaust Systems


Mount the silencer independently to eliminate stress on
the exhaust system and the exhaust manifold/mixer
elbow. See Section 7, Installation Drawings for the
mixer elbow waterline hose size. See Figure 4-1,
Figure 4-2, Figure 4-3, or Figure 4-4 for the exhaust
connection to the mixer elbow. Provide an adequate
hose length from the exhaust mixer to the silencer to
allow for generator set movement.

TP-5982 4/06 Section 4 Exhaust System 19


1

1
ADV-6395A-K GX-250000-
1. Water/exhaust outlet located on opposite (nonservice) side 1. Water/exhaust outlet

Figure 4-1 Mixer Elbow/Exhaust Connection Figure 4-4 Mixer Elbow/Exhaust Connection
(5/7.3E) (15/20C)

Locate the exhaust outlet at least 10 cm (4 in.) above the


waterline when the craft is loaded to maximum capacity.
Install an exhaust port with flap at the exhaust (transom)
outlet to prevent water backup in following seas or when
moving astern (backward). A lift in the exhaust piping
before exiting the boat prevents backwash. See
Figure 4-6, Item 1. Support the exhaust lines to prevent
the formation of water pockets.

Exhaust system guidelines for various generator set


locations follow. Information and illustrations of stern-
(rear) exhaust installations also apply to side-exhaust
installations. Where exhaust lines require passage
1
through bulkheads, use port- (left) or starboard- (right)
ADV-7025A-A side exhaust outlets. This is especially true of
1. Water cooled exhaust outlet
applications in which long exhaust lines to the transom
Figure 4-2 Water Cooled Exhaust Outlet (5/7.3ECD) (rear) could cause excessive back pressure. See
Figure 4-5 for allowable back pressures.

1 Allowable Exhaust
Model Back Pressure
5/7.3E and 4/6EF
<1
1.42
42 psi (3 in.
in Hg)
5/7.3ECD and 4/6EFCD

10/13/15EG and 13/15EGZ < 1.47 psi (3 in. Hg)

15/20C and 12.5/16CF < 2.94 psi (6 in. Hg)

Figure 4-5 Allowable Exhaust Back Pressures

ADV6817-B

1. Water/exhaust outlet located on opposite (nonservice) side

Figure 4-3 Mixer Elbow/Exhaust Connection


(10/13/15EG and 13/15EGZ)

20 Section 4 Exhaust System TP-5982 4/06


4.2.1 Above Waterline Installation with drain plug down. Use a pitch of at least 13 mm per
30.5 cm (0.5 in. per running foot). Some silencers
In addition to considerations described earlier, install a require two supporting brackets or hanger straps for
customer-supplied silencer with the silencer’s outlet at a installation to stringers or other suitable structures.
maximum of 3 m (10 ft.) horizontally from the center of Follow the instructions provided with the silencer.
the engine’s exhaust outlet. See Figure 4-6. Mount a Locate any lift in the exhaust line, used to improve
typical silencer with the inlet and outlet horizontal and silencing, below the engine exhaust manifold outlet.

3
4
5

2
1
6

12
8
14
Waterline

15 11

13
10

1. Slight lift improves silencing (keep below level of exhaust 11. Engine-driven seawater pump
manifold outlet) and prevents water backwash into silencer 12. Minimum exhaust hose pitch of 1.3 cm per 30.5 cm (0.5 in. per
2. Silencer (customer supplied) ft.)
3. Exhaust mixer elbow 13. Maximum distance between silencer and exhaust mixer elbow
4. Heat exchanger (locations vary by model) of 3 m (10 ft.)
5. Coolant recovery tank (located on unit on some models) 14. Minimum exhaust hose pitch of 1.3 cm per 30.5 cm (0.5 in. per
6. Locate coolant recovery tank at same height as heat exchanger ft.)
7. Maximum seawater pump lift of 1 m (3 ft.) 15. Minimum exhaust outlet distance above waterline of 10 cm
8. Seawater strainer (4 in.)
9. Seacock
10. Intake strainer NOTE: Data applies to both rear- and side-exhaust installations.

Figure 4-6 Typical Above Waterline Installation

Note: Use two hose clamps on each end of all flexible Note: Read the text for a complete explanation of
exhaust hose connections. dimensions and other installation considerations.

TP-5982 4/06 Section 4 Exhaust System 21


4.2.2 Mid/Below Waterline Installation
1
Follow USCG regulations for installing an antisiphon
provision to prevent raw water entry into the engine.
Use the siphon break if the exhaust manifold outlet is
located less than 23 cm (9 in.) above the waterline when
the craft is loaded to maximum capacity. Install the
siphon break at least 31 cm (1 ft.) above the waterline.
To install, see the instructions provided with the siphon
break kit.

Note: Failure to properly install a siphon break will


cause engine damage and may void the
Nonservice-Side View
warranty.
GM34482D-

Locate the siphon break above the highest point in the 1. Connect siphon break and hardware
exhaust line between the heat exchanger and the
exhaust mixer. See Figure 4-7, Figure 4-8, Figure 4-9, Figure 4-9 Siphon Break Connection (10/13/15EG
or Figure 4-10 for siphon break connection. Support the and 13/15EGZ Model)
siphon break and hoses to maintain their position and
function. Mount the siphon break directly vertical of its 1
connection to the generator set where possible.
Otherwise, allow a slight offset to clear stringers or other
permanent structures. Protect the siphon break air inlet
from dirt and debris.

1
WARNING

carbon monoxide.
Can cause severe
nausea, fainting,
or death.

Completlely seal off


compartment to
maintain vapor tightness
to living space.
See operator’s manual
for complete
installation instructions.
Before removing cap

Fill system before


relieve pressure.
allow to cool and
stop generator,

loosen cap to

starting unit.
WARNING

Can cause severe


Hot coolant and

personal injury.
burns and
steam.

CAUTION
CHECK ZINC ANODE
EVERY 100 HOURS

Generator-End View
OR 3 MONTHS.

Hot engine
and exhaust system.
Can cause severe burns.

Do not work on
GX-250000-
generator set until
unit is allowed to cool.

Top View 1. Connect siphon break and hardware


GY-250000-
1. Connect siphon break and hardware
Figure 4-10 Siphon Break Connection (15/20C Model)
Figure 4-7 Siphon Break Connection (5/7.3E Model)
Mount a typical silencer’s base no more than 1.2 m (4 ft.)
below the highest point in the exhaust line. Attach a
1
separate wood mounting base to the hull stringers or
other suitable structures. Use the silencer
manufacturer’s recommendation for securing the
silencer to the hull. Mount the silencer with outlet not
more than 3 m (10 ft.) horizontally from the engine
exhaust manifold outlet. Use a USCG-type certified
marine exhaust hose.

Top View
GM39685D-

1. Connect siphon break and hardware

Figure 4-8 Siphon Break Connection (5/7.3ECD


Model)
22 Section 4 Exhaust System TP-5982 4/06
2

3 7 8
9
10
1
6
21
5

4 11
Waterline 19

20 16
12

18

15
13

17 14

1. Mounting base 13. Seacock


2. Retaining cap 14. Intake strainer
3. Reed valve assembly 15. Engine-driven seawater pump
4. Maximum silencer vertical lift of 1.2 m (4 ft.) 16. Minimum exhaust hose pitch of 1.3 cm per 30.5 cm (0.5 in. per
5. Exhaust mixer elbow distance above the waterline. If less than ft.)
23 cm (9 in.), a siphon break is required. 17. Maximum distance between silencer and exhaust mixer elbow
6. Minimum siphon break distance above the waterline of 30.5 cm of 3 m (10 ft.)
(1 ft.) 18. Silencer (customer supplied)
7. Siphon break 19. Minimum exhaust hose pitch of 1.3 cm per 30.5 cm (0.5 in. per
8. Exhaust mixer elbow ft.)
9. Heat exchanger (locations vary by model) 20. Minimum exhaust outlet distance above waterline of 10 cm
10. Coolant recovery tank (located on unit on some models) (4 in.)
11. Indicates coolant recovery tank at same height as heat 21. Exhaust hose size: 5cm (2 in.) ID
exchanger
12. Seawater strainer NOTE: Data applies to both rear- and side-exhaust installations.

Figure 4-11 Typical Mid and Below Waterline Installation

Note: Use two hose clamps on each end of all flexible Note: Read the text for a complete explanation of
exhaust hose connections. dimensions and other installation considerations.

TP-5982 4/06 Section 4 Exhaust System 23


Notes

24 Section 4 Exhaust System TP-5982 4/06


Section 5 Fuel System

1
WARNING

Explosive fuel vapors.


Can cause severe injury or death.
Use extreme care when handling, 1. Fuel line to generator set 1-788
storing, and using fuels.
Figure 5-2 Single Dip-Tube Arrangement
Installing the fuel system. Explosive fuel vapors can
Installations with the fuel tank located above the
cause severe injury or death. Fuel leakage can cause an
explosion. Do not modify the tank or the propulsion engine fuel generator set’s carburetor require an auxiliary fuel
system. Equip the craft with a tank that allows one of the two shutoff valve. Close the fuel shutoff valve when not
pickup arrangements described in the installation section. The operating the generator set to prevent fuel leakage.
tank and installation must conform to USCG Regulations.

Note: Fuel systems must conform to USCG 5.2 Fuel Inlet Line
regulations.
Use a flexible hose section to connect the metallic line
from the fuel tank to the engine’s fuel pump. USCG
5.1 Fuel Tank regulations require that metallic lines have a wall
thickness of at least 0.74 mm (0.029 in.). Use seamless
Most marine generator sets draw fuel from the same fuel
annealed copper, copper/nickel, or copper tubing. The
tank as the craft’s propulsion engine(s). If the tank’s fuel
flexible section allows vibrational motion of the
pickup opening allows a multiple dip tube, use a multiple
generator set during operation. Use USCG type-A
dip tube arrangement. See Figure 5-1. The multiple dip
hose, marked and tagged according to regulations, for
tube arrangement incorporates a shorter dip tube for the
the flexible section. Support the metallic line within
generator set and a longer dip tube for the propulsion
102 mm (4 in.) of its connection to the flexible section.
engine. With this arrangement, the generator set runs
out of fuel before the propulsion engine during a low fuel See Figure 5-3 for ID sizes of customer-supplied fuel
supply situation. The alternate tank should have a lines to connect to the fuel pump. Route the fuel lines
smaller, separate pickup opening for a single dip tube. from the fuel tank in a gradual incline to the engine. Do
See Figure 5-2. not exceed the height of the generator set and do not run
the fuel lines above the generator set.
Note: Do not tee into the main propulsion engine.
See Section 7, Installation Drawings for fuel feed pump
inlet connection.

1 Fuel Line ID
Model mm (in.)
2
5/7.3E and 4/6EF
6 (0.25)
(0 25)
5/7.3ECD and 4/6EFCD

10/13/15EG and 13/15EGZ 8 (0.31)


1-788
1. Fuel line to propulsion engine
15/20C and 12.5/16CF 9.5 (0.375)
2. Fuel line to generator set

Figure 5-1 Multiple Dip-Tube Arrangement Figure 5-3 Fuel Line Sizes

TP-5982 4/06 Section 5 Fuel System 25


5.3 Fuel Filters or Strainers

5.3.1 5/7.3E, 4/6EF, 5/7.3ECD, 4/6EFCD,


10/13/15EG, and 13/15EGZ Models
These generator sets are shipped with a fuel filter. No
additional fuel filter or strainer is required.

1 ADV6817-B

1. Fuel filter

Figure 5-6 Fuel Filter Location on 10/13/15EG and


13/15EGZ Models

1
ADV-6395A-K
1. Fuel filter

Figure 5-4 Fuel Filter Location on 5/7.3E and 4/6EF


Models

1
ADV-7025A-A
1. Fuel filter

Figure 5-5 Fuel Filter Location on 5/7.3ECD and


4/6EFCD Models

26 Section 5 Fuel System TP-5982 4/06


5.3.2 15/20C and 12.5/16CF Models 5.5 Fuel Pump Lift and Fuel
Conform to USCG regulations regarding in-line fuel Consumption
filters or strainers. Independently mount the in-line fuel
See Figure 5-7 for fuel pump lift capabilities. Consult
filter or strainer to the craft’s structure. Ensure
current generator set specification sheets for generator
accessibility for servicing without removing permanent
set fuel consumption rates.
structures.

Note: Fuel filter/strainer installation. Support each Fuel Pump


fuel filter and strainer on the engine or boat Lift
structure independent of its fuel-line connections Model m (ft.)
unless the fuel filter or strainer is inside a fuel 5/7.3E and 4/6EF
tank.
5/7.3ECD and 4/6EFCD 0.9 (3)
( )
10/13/15EG and 13/15EGZ
5.4 Antisiphon Device Installation
15/20C and 12.5/16CF 1.2 (4)
Install antisiphon devices when a fuel line section lies
below the highest point of the fuel tank. Install an Figure 5-7 Fuel Pump Lift Capabilities (Max.)
antisiphon device as follows:

D Use a spring-loaded check valve (tested to function


with the installation’s siphon head) or an electrically
operated shutoff valve (UL ignition-protected
tested to USCG regulations) that can operate
manually as the antisiphon device.

D Install the check valve above the fuel tank’s highest


point.

D Secure the check valve to the craft’s structure,


ensuring accessibility without removing permanent
structures.

D Locate the fuel-line section between the tank and


check valve above the fuel tank’s highest point.
Install an electric shutoff valve at the fuel tank’s
fuel-withdrawal fitting.

D Wire the shutoff valve to open whenever cranking


or running the generator set.

Antisiphon holes drilled into fuel dip tubes within the fuel
tank are unreliable antisiphon devices because they
become ineffective when restricted by dirt or gum.

TP-5982 4/06 Section 5 Fuel System 27


5.6 Fuel System Bleed Procedure 1
5/7.3ECD and 4/6EFCD Models
Before placing the generator set into service for the first
time, bleed air from the fuel system in order to reduce
rough running or vapor lock.

WARNING

Fire.
Can cause severe injury or death.
Do not smoke or permit flames or
sparks near fuels or the fuel system.

Servicing the fuel system. A flash fire can cause severe


injury or death. Do not smoke or permit flames or sparks near
the carburetor, fuel line, fuel filter, fuel pump, or other potential
sources of spilled fuels or fuel vapors. Catch fuels in an
approved container when removing the fuel line or carburetor.

Fuel System Bleed Procedure

1. Press and hold the Select button on the ADC. See


Figure 5-8.

2. While holding the Select button, move the


generator set master switch into the RUN position.
See Figure 5-8.
2
3. Keep holding the Select button until step 6. The
ADC software version and then FUEL will appear
on the ADC’s LED display. See Figure 5-8. 1. Bleed point (with the cap removed)
2. Bleed tool (with fuel drain hose attached)

1
Figure 5-9 Bleed Location

4. Remove the cap from the location shown in


FUEL Figure 5-9.

5. Hold the bleed tool (part number GM46327) onto


the bleed point to remove air from the line.
2
6. When fuel begins to drip from the hose (on the
bleed tool) release the Select button and replace
the cap.

Note: Use a container at the end of the bleed tool’s hose


to catch the fuel. Dispose of fuel in an
environmentally safe manner.

3 GM28707A-C
1. LED display
2. Select button (use for setup and adjustment only)
3. Generator set master switch

Figure 5-8 ADC 2100 Control

28 Section 5 Fuel System TP-5982 4/06


Section 6 Electrical System

WARNING 6.1 AC Voltage Connections


Make AC connections to the generator set inside the
controller box (5/7.3E, 4/6EF, 15/20C, and 12.5/16CF
models) or inside the junction box (5/7.3ECD, 4/6EFCD,
10/13/15EG, and 13/15EGZ models). Typically, the
Explosion. generator set connects to a ship-to-shore transfer
Gasoline vapors can cause switch that allows the use of shore/utility power when
explosion and severe injury or
docked or generator set power when docked or at sea.
death.
The wiring then connects to a main circuit breaker box
Before starting the generator set, (panel board) that distributes branch circuits throughout
operate the blower 4 minutes and the craft. See Figure 6-1 for AC voltage connections to
check the engine compartment for
the generator set. See Section 8 for reconnection of the
gasoline vapors.
generator set.
Ignition-protected equipment. Explosive fuel vapors can
cause severe injury or death. Gasoline vapors can cause an
1 2
explosion. USCG Regulation 33CFR183 requires that all
electrical devices (ship-to-shore transfer switch, remote start
panel, etc.) must be ignition protected when used in a gasoline
and gaseous-fueled environment. The electrical devices
listed above are not ignition protected and are not certified to
operate in a gasoline and gaseous-fueled environment such
as an engine room or near fuel tanks. Acceptable locations are
the wheelhouse and other living areas sheltered from rain and 3
water splash.

WARNING

4
Hazardous voltage. Moving rotor.
Can cause severe injury or death. 1. Line side connections from generator TP-5811-6
2. AC circuit breaker
Operate the generator set only when 3. L1/L2 phase (black) leads. Load side customer
all guards and electrical enclosures connection points.
are in place. 4. LO neutral (white) lead
5. GRD. ground (green) lead

Electrical backfeed to the utility. Hazardous backfeed Figure 6-1 AC Voltage Connections in
voltage can cause severe injury or death. Connect the Controller Box
generator set to the building/marina electrical system only
through an approved device and after the building/marina
main switch is opened. Backfeed connections can cause
severe injury or death to utility personnel working on power
6.2 Circuit Protection
lines and/or personnel near the work area. Some states and The AC circuit breakers protect the generator set from
localities prohibit unauthorized connection to the utility
electrical system. Install a ship-to-shore transfer switch to extreme overload. AC circuit breakers (optional) trip
prevent interconnection of the generator set power and shore when they detect a fault in the output circuit.
power.
For circuit breaker application and selection
information, contact an authorized distributor/dealer.

After correcting the fault, reset AC circuit breaker(s) by


placing them in the ON position. Restart the unit. The
unit’s voltage configuration determines circuit breaker
selection.

TP-5982 4/06 Section 6 Electrical System 29


Note: Circuit breaker ampere rating and availability are
subject to change.
WARNING

6.2.1 Circuit Breaker Considerations


Mounting location. Mount the circuit breakers in the
Hazardous voltage. Moving rotor.
generator set controller (5/7.3E, 4/6EF, 15/20C, and Can cause severe injury or death.
12.5/16CF models) or inside the junction box
(5/7.3ECD, 4/6EFCD, 10/13/15EG, and 13/15EGZ Operate the generator set only when
models). all guards and electrical enclosures
are in place.
Sizing. Use the generator set voltage/frequency
configuration to determine the circuit breaker Grounding electrical equipment. Hazardous voltage can
cause severe injury or death. Electrocution is possible
amperage. If the circuit breaker was sized for one
whenever electricity is present. Turn off the main circuit
voltage configuration and later the generator set is breakers of all power sources before servicing the equipment.
reconnected to a different voltage, change the circuit Configure the installation to electrically ground the generator
breaker accordingly to provide optimum protection. set, transfer switch, and related equipment and electrical
circuits to comply with applicable codes and standards. Never
Note: Ignition-protected circuit breakers. Use only contact electrical leads or appliances when standing in water
ignition-protected circuit breakers on marine or on wet ground because these conditions increase the risk of
gasoline generator sets. See CFR 33, Part electrocution.
183.410 for ignition-protection requirements. Do Short circuits. Hazardous voltage/current can cause
not use standard circuit breakers. severe injury or death. Short circuits can cause bodily injury
and/or equipment damage. Do not contact electrical
Have a qualified electrician or technician install circuit connections with tools or jewelry while making adjustments or
breakers and reconnect the generator set. Comply with repairs. Remove all jewelry before servicing the equipment.
all governing standards and codes. Electrical backfeed to the utility. Hazardous backfeed
voltage can cause severe injury or death. Connect the
WARNING generator set to the building/marina electrical system only
through an approved device and after the building/marina
main switch is opened. Backfeed connections can cause
severe injury or death to utility personnel working on power
lines and/or personnel near the work area. Some states and
localities prohibit unauthorized connection to the utility
Accidental starting. electrical system. Install a ship-to-shore transfer switch to
Can cause severe injury or death. prevent interconnection of the generator set power and shore
power.
Disconnect the battery cables before
working on the generator set. Note: Voltage/frequency adjustable. Some four-lead
Remove the negative (--) lead first generator sets are not voltage/frequency
when disconnecting the battery. adjustable. To determine adjustment
Reconnect the negative (--) lead last
possibilities, check the model’s specification
when reconnecting the battery.
sheet or service manual. If you are reconnecting
the generator set from a single voltage to a
Disabling the generator set. Accidental starting can dual-voltage configuration (example: from 120
cause severe injury or death. Before working on the volt to 120/240 volt) or a dual voltage to a single
generator set or equipment connected to the set, disable the
voltage (example: from 120/240 volt to 120 volt)
generator set as follows: (1) Place the generator set start/stop
switch in the STOP position. (2) Disconnect the power to the with the same primary voltage, do not adjust the
battery charger, if equipped. (3) Remove the battery cables, voltage/frequency adjustment. Adjust the
negative (--) lead first. Reconnect the negative (--) lead last voltage/frequency for frequency changes or
when reconnecting the battery. Follow these precautions to setting changes of the primary voltage (example:
prevent the starting of the generator set by the remote from 120 volt to 100 volt).
start/stop switch.

30 Section 6 Electrical System TP-5982 4/06


6.2.2 Circuit Breaker Installation breaker marked LINE. Do not use a jumper lead
(see Section 8). Attach stator leads 2 and 3 to L0.
1. Turn the generator set off and disconnect the
generator set engine starting battery, negative (−) Models without ADC 2100:
lead first. Single-pole circuit breaker with a 240-volt,
2-wire, single-voltage system. Attach the stator
2. Remove the controller cover screws and remove lead marked 2 to the side of the circuit breaker
the access cover. marked LINE (see Section 8). Bolt together leads 1
and 4 and tape the leads to insulate them from
3. Remove screws and nuts to remove the circuit
ground. Attach the stator lead marked 3 to L0.
breaker cover plate. Save the mounting hardware.

4. Install the circuit breaker from the inside of the Models with ADC 2100:
cutout panel and mount it using existing screws. Single-pole circuit breaker with a 240-volt,
Position the circuit breaker with ON in the normal 2-wire, single-voltage system. Attach the stator
upright position or to the left side. Cover the cutout lead marked 1 to the side of the circuit breaker
opening, if applicable, with the circuit breaker marked LINE (see Section 8). Bolt together leads
coverplate. Use existing screws and nuts. 2 and 3 and tape to insulate from ground. Attach
the stator lead marked 4 to L0.
5. See Section 8 for voltage reconnection.
8. Connect the stator lead(s) used for neutral
Note: Voltage reconnection. Some four-lead connection to the L0 stud. See the illustrations in
generator sets are not voltage adjustable. Section 8.
To determine adjustment possibilities,
check the model specification sheet. 9. Connect the side of the circuit breaker marked
LOAD to the ship-to-shore switch or craft wiring.
6. Install insulation boots over stator lead terminals if Attach insulation boots to black leads if the kit
the kit includes insulation boots. includes insulation boots. With a single-pole circuit
breaker, use one black lead (L1). With a two-pole
Note: See Section 8 for wiring instructions. circuit breaker use two black leads, L1 and L2.
Connect the neutral white lead to the L0 stud.
Note: 10/13/15EG and 13/15EGZ models are Connect the equipment ground green lead to GRD.
available with a two-pole circuit breaker with stud.
a dual-voltage system (120/240 volt, 60 Hz,
3-wire configuration). Note: Wire material. Use stranded copper for all
The 10EG model is also available with a wiring. Use wire gauges and insulation,
single-pole circuit breaker (120 volt, 60 Hz, conductor temperature ratings, sheath
2-wire configuration). stripping, conductor support and protection,
conductor terminals and splices, and
7. Make the recommended connections for the overcurrent protection (circuit breakers,
following reconnection systems using circuit fuses) that conform to standards and codes.
breakers.
Note: Conform to USCG Regulations CFR33, Part
Two-pole circuit breaker with a single-voltage 183 (Pleasurecraft) and CFR46
system (example: 120 volt, 3-wire). Attach stator (Commercial Craft) for Marine applications.
leads marked 2 and 4 to the side of the circuit
breaker marked LINE. Install the jumper lead Note: Wire protection. Use rubber grommets
across the LINE side of circuit breaker terminals and cable ties as necessary to protect and
(see Section 8). Attach stator leads 1 and 3 to L0. secure wiring from sharp objects, the
exhaust system, and any moving parts.
Single-pole circuit breaker with a
single-voltage system (example: 120 volt, 10. Replace the controller cover or circuit breaker box
2-wire). Attach stator leads marked 2 and 4 to the access panel.
side of the circuit breaker marked LINE (see
11. Reconnect the generator set engine starting
Section 8). Attach stator leads 1 and 3 to L0.
battery, negative (−) lead last.
Two-pole circuit breaker with a dual-voltage 12. Make voltage or frequency adjustments according
system (example: 120/240 volt, 3-wire). Attach to Section 8.
stator leads marked 1 and 4 to the side of the circuit

TP-5982 4/06 Section 6 Electrical System 31


6.3 ADC 2100 Continuous Power b. Remove the cover screws and remove the
controller’s back cover. See Figure 6-2.
Mode Jumper (10/13/15EG
Models) 4. Locate the P7 connector near the top of the
Note: This procedure does not apply to 5/7.3ECD, controller. See Figure 6-2. Remove the jumper
4/6EFCD, and 13/15EGZ models (equipped with from pins 1 and 2 of the P7 connector. If the P7
the ADC 2100). connector has three pins, connect the jumper
across pins 2 and 3 for storage.
A jumper on connector P7 on the back of the controller
2
causes the controller to remain powered at all times.
Controllers are shipped from the factory with the jumper 1
connected. Disconnecting the jumper causes the
controller to auto power down 48 hours after the
generator set shuts down. See the wiring diagram and
schematic drawing in the operation manual.

Note: Be advised that the ADC consumes 250 mA


when the master switch is in the AUTO position
with the jumper connected. If you do not plan to
use your generator set for a long period of time,
Kohler recommends moving the master switch to
the OFF/RESET position (0 mA draw). Remote
communications require an active (powered-up)
controller.

Note: For most applications, it is not necessary to


disconnect the continuous power mode jumper.

Procedure to disconnect the continuous power


mode jumper (optional).
5 4 3
1. Prevent the generator set from starting. tp6195
1. Engine wiring harness connector plug (P1)
a. Move the generator set master switch to the 2. Continuous power mode jumper location (P7)
3. J15 connector
OFF/RESET position. 4. J16 connector
5. Generator set master switch connectors
b. Disconnect power to the battery charger, if
equipped. Figure 6-2 Advanced Digital Control Connections
(Shown with the Back Cover Removed)
c. Disconnect the generator set engine starting
battery, negative (--) lead first. 5. Replace the controller’s back cover and secure the
cover screws.
2. Remove the controller from the generator set. 6. Reconnect the three pink connectors to the
generator set master switch.
a. Disconnect the engine wiring harness
connector P1 plug (35-pin) from the controller. 7. Reconnect the J15 and J16 connectors.
Disconnect the J15 and J16 connectors. See
Figure 6-2. 8. Reconnect the engine wiring harness connector
P1 plug (35-pin) to the controller.
b. Remove the controller from the generator set
housing in order to access the back of the 9. Reconnect the generator set engine starting
controller. battery, negative (--) lead last.

3. Remove the controller’s back cover to access the 10. Reconnect power to the battery charger, if
jumper. equipped.
a. Note the labels on the three leads connected to 11. Place the generator set master switch in the AUTO
the generator set master switch for position.
reconnection later. Disconnect the leads at the
pink connectors. See Figure 6-2.

32 Section 6 Electrical System TP-5982 4/06


6.4 Installation in Steel or 6.5 Installation Regulations
Aluminum Vessels The U.S. Coast Guard governs generator set
Installation of a generator set in a vessel constructed of installation in U.S. pleasurecraft and commercial
a material capable of conducting current (e.g., steel or vessels. Refer to the applicable regulations below:
aluminum) is subject to considerations not normally
encountered in fiberglass or wood vessels. These U.S. Pleasurecraft Installation
differences include equipment grounding, grounding of Regulations
neutral conductors, ground-fault protection, and
isolation of galvanic currents. Title 33CFR, Chapter I, U.S. Coast Guard, Part 183

The scope of these topics is too extensive to be fully 1. Subpart I—Electrical Equipment
discussed here. Consult your local marine authority for
more information. 2. Subpart J—Fuel Systems

Before installing the generator set, check the available U.S. Commercial Vessel Installation
wiring diagrams in the operation manual to become
Regulations
familiar with the electrical system.
Title 46CFR, Chapter I, U.S. Coast Guard

1. Part 111—Electrical Systems

2. Part 182—Machinery Installation


m:sc:001:001

TP-5982 4/06 Section 6 Electrical System 33


6.6 Battery Required
Battery Cable
Batteries and their installation must conform to USCG AWG Gage
Regulations 183.420 (a) through (g). Provide generator (Minimum)
sets with batteries separate from the propulsion engines 2.5 m 5m
Distance (from battery to generator set)
whenever possible. The starting/charging systems of (8.3 ft.) (16.4 ft.)
both the generator set and the engine must have a 5--7.3E/4--6EF, 5--7.3ECD/4--6EFCD 6 4
common negative (−) ground. 10--15EG, 13/15EGZ 6 2
15--20C/12.5--16CF 4 2
USCG Regulation 183.415, Grounding requires
connection of a common conductor to each grounded Figure 6-3 Battery Cable Sizing Recommendations
cranking motor circuit. Size the conductor to match the
larger of the engine’s two battery cables. Figure 6-3 lists 12-Volt Starting Battery Size CCA
recommended minimum cable sizes for generator set (at --18°C (0°F) or 100 Amp Hr)
battery connections at various generator set-to-battery Models CCA
distances. Connecting a common conductor to each
5/7.3E and 4/6EF
grounded cranking motor circuit prevents the starting 260
motor current from using alternative electrical paths 5/7.3ECD and 4/6EFCD
should the cranking motor ground circuit be restricted or 10/13/15EG and 13/15EGZ 600
open because of oxidation or loose hardware.
15/20C and 12.5/16CF 630
Alternative electrical paths include metallic fuel lines
that can pose a hazard. See Section 7, Installation
Figure 6-4 Battery Recommendations
Drawings for battery connections to the generator set.

See Figure 6-4 for minimum cold cranking amps (CCA)


recommendations.

34 Section 6 Electrical System TP-5982 4/06


6.7 Wiring Non-Service Side
1
Use only stranded copper wire. Conform to USCG
Regulations 183.425 through 183.460 for wire gauges
and insulation, conductor temperature ratings, sheath
stripping, conductor support and protection, conductor
terminals and splices, and overcurrent protection
(circuit breakers, fuses). Use rubber grommets and
cable ties as necessary to protect and secure the wire
from sharp objects, the exhaust system, and moving
parts.

6.8 Remote Start Switch


Connection ADV6843b-a
1. Remote interface connector
Kohler Co. offers several remote panels for connection
to the generator set. Contact your local Kohlerr Figure 6-6 Remote Interface Connector,
distributor/dealer for further detailed descriptions. See 10/13/15EG and 13/15EGZ Model
Figure 6-5, Figure 6-6, or Figure 6-7 for the location of Shown
the remote start panel connection to the generator set
controller. Kohler Co. also offers wiring harnesses in 1
various lengths with a connector keyed to the controller
box connector. A “pigtail” harness is also offered which
includes the appropriate connector on one end and has
pigtails that the installer can use to connect to a
customer-supplied start/stop switch or separate lights
and hourmeter. Consult current wiring diagrams, ADVs,
and instruction sheets for connection information and
details.

5/7.3ECD, 4/6EFCD, 10/13/15EG, and 13/15EGZ


Models. These models use a 12-pin connector for the ADV7025A-A
remote interface connection. See Figure 6-6 or 1. Remote interface connector (located on the non-service side)
Figure 6-7 for the connector’s location. See Figure 6-8
for the correct customer-supplied plug and pin part Figure 6-7 Remote Interface Connector, 5/7.3ECD
numbers. Model Shown

Component Amp Part No. Kohler Part No.


1 Plug 350735-1 229998
Pin 350218-6 241618
Cable Seal 794280-1 GM29252
Interface Seal 794279-1 GM29507
Cavity Plug 770377-1 GM28769

Figure 6-8 Connector Components


(5/7.3ECD, 4/6EFCD, 10/13/15EG, and
13/15EGZ Models)

Note: Gauge senders. Gauge senders are available


DA-250000-H
1. Controller remote connector for most generator sets. If using gauges, be sure
they are compatible with generator set senders.
Figure 6-5 Controller Remote Connector (Typical) Gauges/senders are available as a service item
5/7.3E, 4/6EF, 15/20C, and 12.5/16CF from authorized Kohler service
Models distributors/dealers.

TP-5982 4/06 Section 6 Electrical System 35


Notes

36 Section 6 Electrical System TP-5982 4/06


Section 7 Installation Drawings

Use the drawings in this section for installation Model No. Drawing Page
purposes. Consult the supplier and verify that the
5/7.3ECD and 4/6EFCD ADV-7025A 38
drawings are the most current for your specification.
with Sound Shield ADV-7025B 39
Installation drawings show exhaust outlet locations, fuel
5/7.3E and 4/6EF ADV-6395A 40
inlet connections, siphon break locations, and battery
connections. See Figure 7-1 for installation drawing with Sound Shield ADV-6395B 41
identification. 15/20C and 12.5/16CF ADV-6382A 42
15/20C and 12.5/16CF
ADV-6382B 43
PTO Kit
10/13/15EG ADV-6817A 44
13/15EGZ with PTO ADV-6817B 45

Figure 7-1 Installation Drawings

TP-5982 4/06 Section 7 Installation Drawings 37


ADV-7025A-A
Note: Dimensions in [ ] are inch equivalents.

Figure 7-2 Dimension Drawing—5/7.3ECD and 4/6EFCD


38 Section 7 Installation Drawings TP-5982 4/06
ADV-7025B-A
Note: Dimensions in [ ] are inch equivalents.

Figure 7-3 Dimension Drawing—Sound Shield 5/7.3ECD and 4/6EFCD


TP-5982 4/06 Section 7 Installation Drawings 39
ADV-6395A-L
Note: Dimensions in [ ] are inch equivalents.

Figure 7-4 Dimension Drawing—5/7.3E and 4/6EF


40 Section 7 Installation Drawings TP-5982 4/06
ADV-6395B-L
Note: Dimensions in [ ] are inch equivalents.

Figure 7-5 Dimension Drawing—Sound Shield 5/7.3E and 4/6EF


TP-5982 4/06 Section 7 Installation Drawings 41
Note: Dimensions in [ ] are inch equivalents. ADV-6382A-F

Figure 7-6 Dimension Drawing—15/20C and 12.5/16CF


42 Section 7 Installation Drawings TP-5982 4/06
ADV-6382B-F
Note: Dimensions in [ ] are inch equivalents.

Figure 7-7 Hydraulic Pump PTO—15/20C and 12.5/16CF (Note: Kohler Co. does not furnish hydraulic pumps.)

TP-5982 4/06 Section 7 Installation Drawings 43


ADV-6817A-D
Note: Dimensions in [ ] are inch equivalents.

Figure 7-8 Dimension Drawing—10/13/15EG

44 Section 7 Installation Drawings TP-5982 4/06


ADV-6817B-D
Note: Dimensions in [ ] are inch equivalents.

Figure 7-9 Dimension Drawing—13/15EGZ with PTO

TP-5982 4/06 Section 7 Installation Drawings 45


Notes

46 Section 7 Installation Drawings TP-5982 4/06


Section 8 Reconnection/Adjustments

WARNING WARNING

Hazardous voltage. Moving rotor.


Accidental starting. Can cause severe injury or death.
Can cause severe injury or death.
Operate the generator set only when
Disconnect the battery cables before all guards and electrical enclosures
working on the generator set. are in place.
Remove the negative (--) lead first
when disconnecting the battery.
Reconnect the negative (--) lead last Grounding electrical equipment. Hazardous voltage can
when reconnecting the battery. cause severe injury or death. Electrocution is possible
whenever electricity is present. Turn off the main circuit
breakers of all power sources before servicing the equipment.
Disabling the generator set. Accidental starting can Configure the installation to electrically ground the generator
cause severe injury or death. Before working on the set, transfer switch, and related equipment and electrical
generator set or equipment connected to the set, disable the circuits to comply with applicable codes and standards. Never
generator set as follows: (1) Place the generator set start/stop contact electrical leads or appliances when standing in water
switch in the STOP position. (2) Disconnect the power to the or on wet ground because these conditions increase the risk of
battery charger, if equipped. (3) Remove the battery cables, electrocution.
negative (--) lead first. Reconnect the negative (--) lead last
when reconnecting the battery. Follow these precautions to
prevent the starting of the generator set by the remote
start/stop switch.
Disabling the generator set. Accidental starting can
cause severe injury or death. Before working on the
generator set or connected equipment, disable the generator
set as follows: (1) Move the generator set master switch to the
OFF position. (2) Disconnect the power to the battery charger.
(3) Remove the battery cables, negative (--) lead first.
Reconnect the negative (--) lead last when reconnecting the
battery. Follow these precautions to prevent starting of the
generator set by an automatic transfer switch, remote
start/stop switch, or engine start command from a remote
computer.

TP-5982 4/06 Section 8 Reconnection/Adjustments 47


8.1 Four-Lead Reconnection
L0 (Neutral)
The following information illustrates the reconnection of L0
four-lead generator sets. In all cases, conform to the GRD.
Ground
National Electrical Code (NEC). L1
L2
Load
NOTICE Side
Voltage reconnection. Affix a notice to the generator set after Two-Pole
reconnecting the set to a voltage different from the voltage on Line Circuit
the nameplate. Order voltage reconnection decal 246242 Side Breaker
from an authorized service distributor/dealer.

100--120-Volt Configurations
Jumper
If the installation requires a factory two-pole circuit
Lead
breaker, do not connect the load-side terminals of the
circuit breaker. See Figure 8-1. If the installation
4 3 2 1
requires a 100--120-volt, 2-wire system, use a Stator Leads
single-pole circuit breaker. See Figure 8-2. When
connecting stator phase leads together, size the output
lead (L1) to handle the amperage. Use a jumper lead on Figure 8-1 100--120-Volt, 3-Wire Configuration
the line side of the circuit breaker to balance the load of (Not released for 10/13/15EG and
the generator set. 13/15EGZ models)

L0 (Neutral)
L0
GRD.
Ground

L1
Load
Side
Single-Pole
Circuit
Line Breaker
Side

4 3 2 1
Stator Leads

60 Hz 50 Hz
L0-L1 100--120 Volt 100--120 Volt
L0-L2 100--120 Volt 100--120 Volt

Figure 8-2 100--120-Volt, 2-Wire Configuration


(Not released for 13/15EG and
13/15EGZ models)

48 Section 8 Reconnection/Adjustments TP-5982 4/06


100--120/200--240-Volt Configurations L0 (Neutral)
L0
The 100--120/200--240-volt configuration does not use Ground GRD.
a jumper lead. If the unit was originally wired for straight L1
Load
100--120 volt, 3 wire, remove the jumper lead (see
Side
Figure 8-1 for location). Select a two-pole circuit
breaker. Application of two single-pole circuit breakers Line Single-Pole
does not conform to NEC requirements for supplying a Side Circuit
Breaker
200--240-volt load—even if the breakers are
mechanically attached. Leads L1 and L2 are for
Tape to insulate
different phases—never connect them. from ground

L0 (Neutral)
L0 4 3 2 1
200-220-240 Volt,
Ground GRD. Stator Leads 2 Wire
L2
L1 60 Hz 50 Hz
Load
Side L0-L1 not used 200-220-240 Volt
Factory
Two-Pole Figure 8-4 200--220--240-Volt, 2-Wire Configuration
Circuit Models without ADC 2100
Line
Side Breaker (Not released for 10/13/15EG and
13/15EGZ models)

100-120/200-240 Volt, L0 (Neutral)


3 Wire L0
4 3 2 1
Ground GRD.
Stator Leads
L1
60 Hz 50 Hz Load
Side
L0-L1 100-120 Volt 100-120 Volt
L0-L2 100-120 Volt 100-120 Volt Line Single-Pole
L1-L2 200-240 Volt 200-240 Volt Side Circuit
Breaker
Figure 8-3 100--120/200--240-Volt,
3-Wire Configuration Tape to insulate
from ground
200--240-Volt Configurations
4 1 3 2
The 200--240-volt configuration does not use a jumper 200--220--240 Volt
lead. If the unit was originally wired for straight 100--120 Stator Leads 2 Wire
volt, 3 wire, remove the jumper lead (see Figure 8-1 for
60 Hz 50 Hz
location). See Figure 8-4 for models without the
L0--L1 200-240 Volt 200--220--240 Volt
ADC 2100 or Figure 8-5 for models equipped with the
ADC 2100, Figure 8-5 200--220--240-Volt, 2-Wire Configuration
Models with ADC 2100

TP-5982 4/06 Section 8 Reconnection/Adjustments 49


8.2 Voltage Regulator Adjustment
(5/7.3E, 4/6EF, 15/20C, and
12.5/16CF Models)
WARNING

Hazardous voltage. Moving rotor.


Can cause severe injury or death.
Operate the generator set only when
all guards and electrical enclosures 1
are in place. 2
3 TT-875-11
1. Voltage adjustment potentiometer
Testing the voltage regulator. Hazardous voltage can 2. Stability adjustment potentiometer
cause severe injury or death. High voltage is present at the 3. Volts/Hz adjustment potentiometer
voltage regulator heat sink. To prevent electrical shock do not
touch the voltage regulator heat sink when testing the voltage Figure 8-6 PowerBoost™ IIIE Voltage Regulator
regulator. (5/7.3E and 4/6EF Models)
(PowerBoostt, PowerBoostt III, and PowerBoostt V
voltage regulator models only)

The voltage regulator is typically located in the


controller. Adjustments can be made without removing
the voltage regulator. The voltage regulator adjustment
procedure applies to both the PowerBoost™ IIIE
(Figure 8-6) and PowerBoost™ V (Figure 8-7) voltage
regulators. 8
7
Note: Broadrange generator sets. The following
adjustment procedure is for readjustment of the STAB 6
voltage regulator and governor for broadrange 5
generator sets with mechanical governors. V/HZ VOLTS
4

Note: Special tool. Use a frequency meter 50/60 Hz. 3


2 3 1 2
Note: Rheostat connection. Connect a
1
customer-provided rheostat across regulator
leads/terminals 33 and 66 to adjust the generator
TT-875-11
output voltage from a location remote from the 1. Voltage adjustment potentiometer
set. The rheostat (10K ohms, 1/2 watt minimum) 2. Stability adjustment potentiometer
provides a 5-volt adjustment range. 3. Volts/Hz adjustment potentiometer

Figure 8-7 PowerBoost™ V Voltage Regulator


(15/20C and 12.5/16CF Models)

50 Section 8 Reconnection/Adjustments TP-5982 4/06


Stabilizer Potentiometer (Pot)—Fine-tunes the 6. Rotate the stability pot clockwise to minimize
regulator circuitry to reduce light flicker. light flicker.

Voltage Adjustment Potentiometer (Pot)—Adjusts 7. Readjust the voltage adjustment pot, if


the generator voltage output within a range of necessary.
approximately 100--130 volts.
8. Adjust the engine speed to desired cut-in
Volts/Hz Potentiometer (Pot)—Determines the engine frequency (factory setting 57.5-58 Hz for 60 Hz
speed (Hz) at which the generator output voltage begins models or 47.5-48 Hz for 50 Hz models) as
to drop. measured on the frequency meter.

Note: For optimum results, apply full load for voltage 9. Rotate the volts/Hz adjustment pot clockwise
regulator adjustment. until the voltage level (as measured on voltmeter)
begins to drop. When set to these specifications,
the generator attempts to maintain normal output
Voltage Regulator Adjustment Procedure
until the engine speed drops below the frequency
1. With the generator set off, turn the remote set in step 5 (as load is applied).
rheostat, if equipped, to midpoint.
10. Readjust the engine speed to normal (63 Hz/
2. Turn voltage, volts/Hz, and stability pots fully 1890 RPM for 60 Hz or 52.5 Hz/1575 RPM for
counterclockwise. 50 Hz).

3. Connect the voltmeter and the frequency meter to 11. Readjust the voltage adjustment pot, if
the AC circuit or an electrical outlet. necessary.

4. Start the generator set. 12. Readjust the stability pot, if necessary.

5. Rotate the voltage adjustment pot clockwise to 13. Use the remote rheostat, if equipped, to make final
increase the voltage (counterclockwise to voltage adjustments.
decrease the voltage) to the desired output
14. Stop the generator set.
voltage.

TP-5982 4/06 Section 8 Reconnection/Adjustments 51


8.3 ADC 2100 Adjustment 8.3.2 Controller Software Version
(5/7.3ECD, 4/6EFCD, Number
10/13/15EG, and 13/15EGZ The application software for controller operation is
Models) factory-loaded onto the Advanced Digital Control. At
times, it may be necessary to check the software version
number for troubleshooting purposes.
The controller’s application software version number is
displayed on the LED screen during the key sequence to
enter the configuration mode, after the Select button has
been pressed and held for about five seconds. For
example, 01.00 will be displayed for software
version 1.00.

Note: The unit configuration (UC), engine type (EC),


and engine data input type (ED) are factory set
and should only be changed by an authorized
Kohler dealer/distributor. Incorrect settings will
make your unit non-functional.

8.3.3 Configuration Mode


Figure 8-8 Advanced Digital Control (ADC 2100)
Follow the instructions in Figure 8-11 to enter the
The controller is factory-set for the generator set voltage configuration mode. The settings are shown in
and frequency and normally does not require Figure 8-9. An X in the Display column in Figure 8-11
adjustment. If adjustment is necessary, follow the indicates a number from 0 to 9.
procedures in this section. Set the system voltage and
frequency and then adjust the voltage, gain, and engine Press the Select button to step through to the Save
speed. mode as shown in Figure 8-13. When SAVE is
displayed, press the up arrow to save the new settings or
the down arrow to discard the changes and exit the
8.3.1 Configuration Mode Time Out configuration mode without saving.
The controller will automatically exit the configuration Pressing the Select button when SAVE is displayed
mode without saving any changes after about 1 minute if returns to the first parameter, system voltage/frequency
no buttons are pressed. Start the configuration (Uu).
procedure over again from the beginning if the controller
exits the configuration mode before the settings have
been saved.

52 Section 8 Reconnection/Adjustments TP-5982 4/06


Parameter Setting Definition Connect
Unit’s system
y voltage
g Single phase, 2W, 60 Hz, 120 VAC 1 Ph, 2W
and
d frequency
f * Uu00
Single phase, 3W, 60 Hz, 120 VAC 1 Ph, 3W
Uu01 Single phase, 3W, 60 Hz, 120/240 VAC 1 Ph, 3W
Single phase, 3W, 50 Hz, 115/230 VAC 1 Ph, 3W
Uu02
Single phase, 2W, 50 Hz, 230 VAC 1 Ph, 2W
Single phase, 2W, 50 Hz, 110 VAC 1 Ph, 2W
Uu05 Single phase, 3W, 50 Hz, 110 VAC 1 Ph, 3W
Single phase, 2W, 50 Hz, 115 VAC 1 Ph, 2W
Uu07 Single phase, 3W, 50 Hz, 110/220 VAC 1 Ph, 3W
Uu08 Single phase, 3W, 60 Hz, 100/200 VAC 1 Ph, 3W
Uu09 Single phase, 3W, 50 Hz, 100/200 VAC 1 Ph, 3W
Uu12 Single phase, 2W, 50 Hz, 220 VAC 1 Ph, 2W
Uu13 Single phase, 2W, 50 Hz, 240 VAC 1 Ph, 2W
Unit configuration Uc00 Marine generator set
Engine
g type
yp Ec03 10/13/15EG
Ec04 5/7.3ECD and 4/6EFCD
Ec10 [ 13/15EGZ with PTO
Engine data input types Ed00 All digital inputs. Required for 5/7.3ECD and 4/6EFCD.
((No magnetic
g p p) w
pick-up) Default setting for 10/13/15EG and 13/15EGZ with PTO.
Ed01 Digital: Low coolant level and low oil pressure
Analog: Low coolant temperature
Ed02 Digital: Low coolant level and low coolant temperature
Analog: Low oil pressure
Ed03 Digital: Low coolant level
Analog: Low coolant temperature and low oil pressure
Ed08 Digital: Low coolant temperature and low oil pressure
Analog: Low coolant level
Ed09 Digital: Low oil pressure
Analog: Low coolant level and low coolant temperature
Ed10 Digital: Low coolant temperature
Analog: Low coolant level and low oil pressure
Ed11 All analog inputs
Battery Voltage Bt12 Battery voltage 12 VDC
Communications Cn00 No CAN communications
Cn01 SAE J1939 (Used for ADC remote digital gauge)
Cn02 ] SmartCraftt CAN compatible (Required for 5/7.3ECD and 4/6EFCD models)
* Check the generator set spec sheet for voltage configurations applicable to each model.
Use voltage/frequency parameters Uu05--Uu13 only with ADC application program version 1.20 or higher.
[ 13/15EGZ models with PTO require application program version 1.21 or higher.
w Setting the Ec parameter automatically selects the appropriate Ed parameter for the standard data input types for that engine.
Change this parameter if optional senders are installed.
] Smartcraftr settings for ADC code version 2.xx only, for models 5/7.3ECD and 4/6EFCD
SmartCraftt is a trademark of Mercury Marine, a division of Brunswick Corporation.

Figure 8-9 Controller Parameters

TP-5982 4/06 Section 8 Reconnection/Adjustments 53


8.3.4 Adjusting the Voltage, Gain, Voltage Adjustment Procedure
Volts/Hz, and Engine Speed 1. With the generator set off, connect a digital
After setting the system voltage, check the output voltmeter to the output leads or an electrical outlet
voltage and adjust, if necessary, using the following on the load side of the generator set. Set the meter
to measure voltage.
procedures. Follow the instructions in Figure 8-14 to
adjust the voltage, gain, volts/Hz, and governor gain 2. Start the generator set by moving the generator set
while the engine is running. An X in the Display column master switch to the RUN position.
in Figure 8-14 indicates a number from 0 to 9. Use the
up arrow to increase a setting or the down arrow to 3. Use the ADC controller to adjust the voltage
decrease the setting. Pressing the Select button when (parameter 1P) until the output voltage reaches the
SAVE is displayed returns to the first parameter, voltage desired value. See Figure 8-10.
adjust (1P).
Measured Approximate
Note: A digital multimeter that measures voltage and g , VAC
Voltage, Voltage Change per Step, VAC
frequency is required for these adjustments. Coarse Adjust Fine Adjust
85--132 5 0.5
8.3.5 Voltage Adjustment 180--251 7 0.7
Figure 8-10 Voltage Adjustment
WARNING
4. Adjust the voltage stability (gain, parameter 2P) to
minimize light flicker.

5. Readjust the voltage, if necessary.


Hazardous voltage. Moving rotor. 6. Adjust the volts/Hz (parameter 3P) until the voltage
Can cause severe injury or death.
level measured by the voltmeter begins to drop.
Operate the generator set only when When the volts/Hz is set correctly, the generator
all guards and electrical enclosures (as load is applied) attempts to maintain normal
are in place. output until the engine speed drops below the
cut-in frequency.
Short circuits. Hazardous voltage/current can cause
severe injury or death. Short circuits can cause bodily injury 7. Readjust the voltage stability (gain, parameter 2P),
and/or equipment damage. Do not contact electrical if necessary.
connections with tools or jewelry while making adjustments or
repairs. Remove all jewelry before servicing the equipment. 8. Readjust the voltage (parameter 1P), if necessary.
Grounding electrical equipment. Hazardous voltage can
cause severe injury or death. Electrocution is possible 9. Stop the generator set.
whenever electricity is present. Turn off the main circuit
breakers of all power sources before servicing the equipment.
Configure the installation to electrically ground the generator
set, transfer switch, and related equipment and electrical
circuits to comply with applicable codes and standards. Never
contact electrical leads or appliances when standing in water
or on wet ground because these conditions increase the risk of
electrocution.

54 Section 8 Reconnection/Adjustments TP-5982 4/06


Controller Configuration Mode (Use with Figure 8-9, Controller Parameters):

Hold the Select button: Display:


Move the generator set master switch to the RUN . 0
position. (The generator set engine will not start.)

Wait about 5 seconds until the display shows the


program version number. (The number may be 1 0 4
different than the one shown here.)

Press the down arrow key and then the up arrow


key 3 times to enter the configuration mode.
(This is the controller “password.”)
Uu 0 x

Now release the Select button.


Press:

To set the voltage/frequency setting see Figure 8-9. Uu 0 x


or

To step to the next parameter, unit configuration


Uc.

To set the unit configuration setting to Uc00, if


or
necessary.
Uc 0 0

To step to the next parameter, engine type Ec.

or To set the engine type, if necessary.


E c 0 x
To step to the next parameter, advanced Ad n c
configuration mode or save mode selection.

Now either save your settings or enter the Advanced Configuration Mode to
set the engine data inputs, battery voltage, and communications.

Press:
To enter advanced configuration mode. E d 0 x
Go to Figure 8-12.
OR:
or To proceed to the save mode without
entering the advanced configuration mode. S AV E
Go to Figure 8-13.

Note: Shaded boxes show which number in the controller display changes when the up or down arrow
key is pressed. “x” denotes any number from 0 to 9.

Figure 8-11 Configuration Mode (system voltage/frequency, unit configuration, and engine type parameters)

TP-5982 4/06 Section 8 Reconnection/Adjustments 55


Pressing the up arrow key at the Adnc display (See Figure 8-11) puts you
into the Advanced Configuration Mode.
Press:

or To set the engine data input type. E d 0 x

To enter battery voltage selection mode.

or To toggle between 12 and 24 VDC. 12-volt models B t 1 2

To enter communications selection mode.

or
To set the communications parameter. C n 0 x

To enter SAVE mode. Go to Figure 8-13.


S AV E
Note: Shaded boxes show which number in the controller display changes when the up or down arrow
key is pressed. “x” denotes any number from 0 to 9.
Figure 8-12 Advanced Configuration Mode (engine data input types, battery voltage, and engine
communications)

There are 3 options when the display says SAVE: S AV E


Press:
To return to the first parameter, system voltage/frequency
Uu, to check or change settings before saving. See Uu 0 x
Figure 8-11.
or

To save changes. Y E S
or
To discard changes without saving. n o

“Yes”or “no” flashes when the up or down arrow is pressed and then
the controller exits the configuration mode. The display returns to
the runtime hours.
x x x x
Note: Be sure to save your settings before exiting the configuration mode. The controller reverts to the
last saved settings when the master switch is moved to the OFF/RESET position.

* x in the runtime hours display above denotes any number from 0 to 9.

Figure 8-13 Save Mode (after configuring generator set parameters)

56 Section 8 Reconnection/Adjustments TP-5982 4/06


Output Voltage Adjustment Mode: Display :*
Move the generator set master switch to the RUN position. The generator set x x x x
engine starts and the controller display shows the engine runtime hours.
Hold:
Wait about 5 seconds until the display changes from runtime hours
to the program version number.
x. x x
Press the down arrow key and then the up arrow key 3 times to enter the
adjustment mode. (This is the controller “password.”)
1 P x x

The controller is now in the voltage coarse adjustment mode.

Press:

or
To raise or lower the voltage in large increments 1 P x x
(approximately 5--7 volts per step).

To enter fine voltage adjustment mode.


1 P x x
To raise or lower the voltage in smaller increments
or
(approximately 0.5--0.7 volts per step).

To enter coarse voltage stability (gain) adjustment mode.


2 P x x
To raise or lower the voltage stability (gain) in large
or increments.

To enter fine voltage stability (gain) adjustment mode.


2 P x x
or To raise or lower the voltage stability (gain) in smaller
increments.

To enter volts/Hz adjustment mode.


3 P 0 x
or To raise or lower the volts/Hz: 00=low; 09= high

See Figure 8-13 to save.


* Shaded boxes show which character in the controller display changes for each adjustment. “x” in the
examples above denotes any number from 0 to 9. The actual values may vary from model-to-model. TP6196

Figure 8-14 Output Voltage Adjustments

TP-5982 4/06 Section 8 Reconnection/Adjustments 57


Notes

58 Section 8 Reconnection/Adjustments TP-5982 4/06


Appendix A Generator Selection and Wattage Requirements

General Wattage Requirements Appliance Loads


Consider total wattage requirements (lights, motors, Generator sets often furnish AC for appliances such as
appliances) when selecting a generator set, or when TVs, stereos, and electric water heaters. Except for
sizing wattage usage in which available space and resistance-type loads such as the water heater,
construction limit the size of the generator set. requirements for appliances are usually low. Do not
overlook such loads when figuring total requirements.
Motor Loads Allow reserve capacity for anticipated appliance loads to
avoid overloading a generator set.
When figuring generator set capacity requirements for
loads that include electric motors, consider the high Lighting Load
current demanded by the motors during startup. The
inrush or starting current is typically 2 to 3 times higher To calculate the lighting load, add the wattage of each
than that required when the motor reaches normal generator set-operated lamp. Note that not all of the
operating speed. Allow reserve for inrush demands plus lights or lamps are on the generator set AC
other loads that could be on the line as the electric motor circuit—some are DC powered by a 12-volt battery.
starts. Use Figure 1 as a guide when selecting Ensure that the calculated total wattage includes only
generator set capacity requirements involving motor lights actually on the generator set AC circuit.
loads.
Air Conditioners
Starting
Motor (Inrush) Running The starting characteristics of air conditioners vary
HP Watts Watts greatly—for example, one 12,000 Btu unit has lower
1/4 750 330 starting requirements than a 10,000 Btu unit of another
1/3 1000 400 variety. When using only one unit, there is usually no
1/2 1500 600 starting problem provided that the lighting and appliance
3/4 2000 750 load is not too high when starting the generator set.
1 3300 1100
2 4000 2000 Simultaneous starting of two air conditioning units,
3 5000 3000 however, can present problems if the generator set
capacity is marginal. Because of the variation in starting
Figure 1 Motor Requirements characteristics among air conditioners, this publication
makes no statements regarding multiple-motor starting
capabilities of the generator set covered. Consider
delayed starting or the use of easy-starting devices on
air conditioner units whenever simultaneously starting
more than one motor.

See Figure 2 for typical air conditioner requirements.


The requirements vary among different manufacturers.

Air Conditioner Size (Btu)


7,000 9,000 12,000 16,000 24,000
Voltage 115 230 115 230 115 230 115 230 230
Full load amps 9.3 4.8 9.9 5.0 11.8 6.3 16.3 8.0 11.6
Rated load amps 7.7 4.0 7.0 3.5 8.9 4.8 13.0 6.2 10.2
Locked rotor amps 34.0 20.0 40.0 20.0 50.0 31.0 75.0 36.0 56.0
Starting (inrush) watts 3910 4600 4600 4600 5750 7130 8630 8280 12,900
Running watts 886 920 805 805 1020 1100 1500 1430 2350

Figure 2 Typical Marine Air Conditioner Requirements (60 Hz)

TP-5982 4/06 Appendix 59


Appendix B Abbreviations

The following list contains abbreviations that may appear in this publication.
A, amp ampere CG center of gravity fglass. fiberglass
ABDC after bottom dead center CID cubic inch displacement FHM flat head machine (screw)
AC alternating current CL centerline fl. oz. fluid ounce
A/D analog to digital cm centimeter flex. flexible
ADC analog to digital converter CMOS complementary metal oxide freq. frequency
adj. adjust, adjustment substrate (semiconductor) FS full scale
ADV advertising dimensional cogen. cogeneration ft. foot, feet
drawing Com communications (port) ft. lbs. foot pounds (torque)
AHWT anticipatory high water conn. connection ft./min. feet per minute
temperature cont. continued g gram
AISI American Iron and Steel CPVC chlorinated polyvinyl chloride ga. gauge (meters, wire size)
Institute crit. critical
ALOP anticipatory low oil pressure gal. gallon
CRT cathode ray tube gen. generator
alt. alternator CSA Canadian Standards
Al aluminum genset generator set
Association GFI ground fault interrupter
ANSI American National Standards CT current transformer
Institute Cu copper GND, ground
(formerly American Standards gov. governor
Association, ASA) cu. in. cubic inch
cw. clockwise gph gallons per hour
AO anticipatory only
CWC city water-cooled gpm gallons per minute
API American Petroleum Institute
cyl. cylinder gr. grade, gross
approx. approximate, approximately
D/A digital to analog GRD equipment ground
AR as required, as requested
DAC digital to analog converter gr. wt. gross weight
AS as supplied, as stated, as
suggested dB decibel HxWxD height by width by depth
ASE American Society of Engineers dBA decibel (A weighted) HC hex cap
ASME American Society of DC direct current HCHT high cylinder head temperature
Mechanical Engineers DCR direct current resistance HD heavy duty
assy. assembly deg., ° degree HET high exhaust temperature
ASTM American Society for Testing dept. department hex hexagon
Materials dia. diameter Hg mercury (element)
ATDC after top dead center DI/EO dual inlet/end outlet HH hex head
ATS automatic transfer switch DIN Deutsches Institut fur Normung HHC hex head cap
auto. automatic e. V. HP horsepower
aux. auxiliary (also Deutsche Industrie hr. hour
A/V audiovisual Normenausschuss) HS heat shrink
avg. average DIP dual inline package hsg. housing
AVR automatic voltage regulator DPDT double-pole, double-throw HVAC heating, ventilation, and air
AWG American Wire Gauge DPST double-pole, single-throw conditioning
AWM appliance wiring material DS disconnect switch HWT high water temperature
bat. battery DVR digital voltage regulator Hz hertz (cycles per second)
BBDC before bottom dead center E, emer. emergency (power source) IC integrated circuit
BC battery charger, battery EDI electronic data interchange ID inside diameter, identification
charging EFR emergency frequency relay IEC International Electrotechnical
BCA battery charging alternator e.g. for example (exempli gratia) Commission
BCI Battery Council International EG electronic governor IEEE Institute of Electrical and
BDC before dead center EGSA Electrical Generating Systems Electronics Engineers
BHP brake horsepower Association IMS improved motor starting
blk. black (paint color), block EIA Electronic Industries in. inch
(engine) Association in. H2O inches of water
blk. htr. block heater EI/EO end inlet/end outlet in. Hg inches of mercury
BMEP brake mean effective pressure EMI electromagnetic interference in. lbs. inch pounds
bps bits per second emiss. emission Inc. incorporated
br. brass eng. engine ind. industrial
BTDC before top dead center EPA Environmental Protection int. internal
Agency int./ext. internal/external
Btu British thermal unit
EPS emergency power system I/O input/output
Btu/min. British thermal units per minute
ER emergency relay IP iron pipe
C Celsius, centigrade
ES engineering special, ISO International Organization for
cal. calorie engineered special
CARB California Air Resources Board Standardization
ESD electrostatic discharge J joule
CB circuit breaker est. estimated
cc cubic centimeter JIS Japanese Industry Standard
E-Stop emergency stop k kilo (1000)
CCA cold cranking amps etc. et cetera (and so forth)
ccw. counterclockwise K kelvin
exh. exhaust kA kiloampere
CEC Canadian Electrical Code
cfh cubic feet per hour
ext. external KB kilobyte (210 bytes)
F Fahrenheit, female
cfm cubic feet per minute

60 Appendix TP-5982 4/06


kg kilogram MW megawatt rms root mean square
kg/cm2 kilograms per square mW milliwatt rnd. round
centimeter μF microfarad ROM read only memory
kgm kilogram-meter N, norm. normal (power source) rot. rotate, rotating
kg/m3 kilograms per cubic meter NA not available, not applicable rpm revolutions per minute
kHz kilohertz nat. gas natural gas RS right side
kJ kilojoule NBS National Bureau of Standards RTV room temperature vulcanization
km kilometer NC normally closed SAE Society of Automotive
kOhm, kΩ kilo-ohm NEC National Electrical Code Engineers
kPa kilopascal NEMA National Electrical scfm standard cubic feet per minute
kph kilometers per hour Manufacturers Association SCR silicon controlled rectifier
kV kilovolt NFPA National Fire Protection s, sec. second
kVA kilovolt ampere Association SI Systeme international d’unites,
kVAR kilovolt ampere reactive Nm newton meter International System of Units
kW kilowatt NO normally open SI/EO side in/end out
kWh kilowatt-hour no., nos. number, numbers sil. silencer
kWm kilowatt mechanical NPS National Pipe, Straight SN serial number
L liter NPSC National Pipe, Straight-coupling SPDT single--pole, double--throw
LAN local area network NPT National Standard taper pipe SPST single--pole, single--throw
L x W x H length by width by height thread per general use spec, specs
lb. pound, pounds NPTF National Pipe, Taper-Fine specification(s)
lbm/ft3 pounds mass per cubic feet NR not required, normal relay sq. square
LCB line circuit breaker ns nanosecond sq. cm square centimeter
LCD liquid crystal display OC overcrank sq. in. square inch
ld. shd. load shed OD outside diameter SS stainless steel
LED light emitting diode OEM original equipment std. standard
manufacturer stl. steel
Lph liters per hour
OF overfrequency tach. tachometer
Lpm liters per minute
opt. option, optional TD time delay
LOP low oil pressure
OS oversize, overspeed TDC top dead center
LP liquefied petroleum OSHA Occupational Safety and Health
LPG liquefied petroleum gas TDEC time delay engine cooldown
Administration TDEN time delay emergency to
LS left side OV overvoltage normal
Lwa sound power level, A weighted oz. ounce TDES time delay engine start
LWL low water level p., pp. page, pages TDNE time delay normal to
LWT low water temperature PC personal computer emergency
m meter, milli (1/1000) PCB printed circuit board TDOE time delay off to emergency
M mega (106 when used with SI pF picofarad TDON time delay off to normal
units), male PF power factor temp. temperature
m3 cubic meter
ph., ∅ phase term. terminal
m3/min. cubic meters per minute TIF telephone influence factor
mA milliampere PHC Phillips head crimptite (screw)
PHH Phillips hex head (screw) TIR total indicator reading
man. manual tol. tolerance
max. maximum PHM pan head machine (screw)
PLC programmable logic control turbo. turbocharger
MB megabyte (220 bytes)
PMG permanent-magnet generator typ. typical (same in multiple
MCM one thousand circular mils locations)
MCCB molded-case circuit breaker pot potentiometer, potential
ppm parts per million UF underfrequency
meggar megohmmeter UHF ultrahigh frequency
MHz megahertz PROM programmable read-only
memory UL Underwriter’s Laboratories, Inc.
mi. mile psi pounds per square inch UNC unified coarse thread (was NC)
mil one one-thousandth of an inch pt. pint UNF unified fine thread (was NF)
min. minimum, minute PTC positive temperature coefficient univ. universal
misc. miscellaneous PTO power takeoff US undersize, underspeed
MJ megajoule PVC polyvinyl chloride UV ultraviolet, undervoltage
mJ millijoule qt. quart V volt
mm millimeter VAC volts alternating current
qty. quantity
mOhm, mΩ VAR voltampere reactive
milliohm R replacement (emergency)
power source VDC volts direct current
MOhm, MΩ rad. radiator, radius VFD vacuum fluorescent display
megohm
MOV metal oxide varistor RAM random access memory VGA video graphics adapter
MPa megapascal RDO relay driver output VHF very high frequency
mpg miles per gallon ref. reference W watt
mph miles per hour rem. remote WCR withstand and closing rating
MS military standard RFI radio frequency interference w/ with
m/sec. meters per second RH round head w/o without
MTBF mean time between failure RHM round head machine (screw) wt. weight
MTBO mean time between overhauls rly. relay xfmr transformer
mtg. mounting

TP-5982 4/06 Appendix 61


Appendix C Generator Set Output Ratings Procedure

General correct for environmental variables encountered in a


genset installation. Figure 3 outlines the calculations.
Kohler Co. develops the kilowatt output rating of a Figure 4 contains examples of how heat variables affect
Kohler marine genset based upon the calculations genset ratings.
specified in ISO 3046 and ISO 8528-1. The calculations

Generator Output corrected = Generator Output observed x Correction Factor


Output power is expected to be within ±5% of the specified rating when corrected to reference conditions.
Correction factors are determined using the following formulas:
1. For naturally aspirated spark-ignition engines using gaseous fuel:
C.F. = [1.175 (29.2 / Dry Barometer in. Hg)0.86 (Temperature _F + 460/537)0.55 − 0.175]
x Alternator Efficiency Reference / Alternator Efficiency Observed
2. For naturally aspirated spark-ignition engines burning gasoline:
C.F. = [1.175 (29.2 / Dry Barometer in. Hg)1 (Temperature _F + 460/537)0.5 − 0.175]
x Alternator Efficiency Reference / Alternator Efficiency Observed

Reference conditions:
Temperature: 77_F; Pressure: 29.2 in. Hg dry barometer.
Kohler sound shield increases ambient intake air approx. 12_F.
Approximate derates:
Temperature: approximately 1% per 10_F (turbocharged engines have a greater derate);
Pressure (altitude): approximately 4% per 1000 ft. (1 in. Hg)

Figure 3 Generator Output

KEY

60 Hz 8.0
50 Hz 7.9
7.8
7.7
7.6
7.5
7.4
7.3
7.2
7.1
7.0
Power Output 6.9
(kW) 6.8
6.7
6.6
6.5
6.4
6.3
6.2
6.1
6.0
5.9
5.8
5.7
5.6
5.5
75 77 80 85 90 95 100 105 110 115 120
Temperature (_F)

Figure 4 Example: 8EOZ/6.5EFOZ kW Derates (ISO 3046/ISO 8258-1)

62 Appendix TP-5982 4/06


TP-5982 4/06 63
KOHLER CO. Kohler, Wisconsin 53044
Phone 920-565-3381, Fax 920-459-1646
For the nearest sales/service outlet in the
US and Canada, phone 1-800-544-2444
KohlerPowerSystems.com
Kohler Power Systems
Asia Pacific Headquarters
TP-5982 4/06f 7 Jurong Pier Road
Singapore 619159
E 1998, 2001, 2002, 2004, 2005, and 2006 by Kohler Co. All rights reserved. Phone (65)6264-6422, Fax (65)6264-6455

You might also like