Commercial Air Conditioners: Water Cooled Screw Chiller
Commercial Air Conditioners: Water Cooled Screw Chiller
ty
e
em
cupational
Envir
Assessment
ent
Add.: Midea Headquarters Building, 6 Midea Avenue, Shunde, Foshan, Guangdong, China
Midea CAC After-service Application Midea CAC News Application
Postal code: 528311
cac.midea.com global.midea.com
Note: Product specifications change from time to time as product improvements and
iOS Version Android Version iOS Version developments are released and may vary from those in this document.
Midea CAC
Midea CAC is a key division of the Midea Group, a leading producer of consumer appliances and provider of heating, There are three production bases: Shunde, Chongqing and Hefei.
ventilation and air conditioning solutions. Midea CAC has continued with the tradition of innovation upon which it was MCAC Shunde: 38 product lines focusing on VRF, Split Products, Heat Pump Water Heaters, and AHU/FCU.
founded, and emerged as a global leader in the HVAC industry. A strong drive for advancement has created a MCAC Chongqing: 14 product lines focusing on Water Cooled Centrifugal/Screw/Scroll Chillers, Air Cooled Screw/Scroll
groundbreaking R&D department that has placed Midea CAC at the forefront of a competitive field. Through these Chillers, and AHU/FCU.
independent efforts and joint cooperation with other global enterprises, Midea has supplied thousands of innovative MCAC Hefei: 11 product lines focusing on VRF, Chillers, and Heat Pump Water Heaters.
solutions to customers worldwide.
Contents
Contents
Midea water cooled screw chiller is a classic products that operates on a flooded type
evaporator and high efficiency compressor. Optimized system design and enhanced heat
exchange efficiency mean the unit works best under both full load and partial load. Every
05 Nomenclature
chiller is fully factory tested and gas charged before shipment. It's an ideal choice for hotels,
shopping malls, hospitals, factories, cinemas and other civil architecture air conditioning 06 Features and benefits
system. Its uses also extend into the plastic industry, electroplating industry, food processing,
10 Specifications
chemical industry and other processing facilities that require large amounts of chilled water.
13 Dimensions
21 Selection software
22 Reference projects
03 04
R134a Flooded (410 to 1690kW)
Evaporator Condenser
Gas refrigerant inlet
Gas refrigerant
Chilled Filter Filter Cooling
water outlet water outlet
Chilled
water inlet
Cooling
Liquid water inlet
EXV Liquid refrigerant outlet
refrigerant Tube
High efficiency shell and tube heat exchanger, 2 pass, straight water pipe, easy to clean. Both two side cover can be
exchanged to meet customer’s requirement for condenser.
05 06
R134a Flooded (410 to 1690kW)
Strategies to address problems When powered-down, the chiller will maintain previous running mode and parameter set point.
Temperature sensor
Cooling tower
07 08
R134a Flooded (410 to 1690kW)
Circuit A Quantity 1 1 1 1 1
Circuit B Quantity -- -- -- -- --
Oil recharge
Circuit A L 18 20 23 28 40
Self-diagnosis is always performed prior to start-up to enable safe operation. Only after all the requirements are met, the Max. pressure kPa 1000 1000 1000 1000 1000
chiller will start. If any malfunction occurs, it will be displayed on the screen. Connection type Victaulic coupling
Multiple protection features guarantee the safety and stability of the unit. Unit length mm 3496 3496 3521 3521 3521
Anti-freeze protection under cooling mode Protects the evaporators' copper pipes from damage caused by water freeze Net weight kg 2460 2830 3400 3900 4000
09 10
R134a Flooded (410 to 1690kW)
460-3-60 Chilled
Power supply V-Ph-Hz Cooling water inlet
water outlet
Semi-hermetic screw compressor Cooling Chilled
C
water inlet water outlet
Circuit A Quantity 1 1 1 1 1
G
K
Circuit B Quantity -- 1 1 1 1
L
F
Oil recharge
H D
J
Circuit A L 40 23 23 40 40 E A
B
Circuit B L 23 23 40 40
Max. pressure kPa 1000 1000 1000 1000 1000 LSBLG750/MCF 3521 1400 2026 2850 1300 441 300 350 700 300 591 DN200
Connection type Victaulic coupling LSBLG860/MCF 3521 1400 2026 2850 1300 441 300 350 700 300 591 DN200
Water inlet/outlet pipe dim. mm DN200 DN200 DN200 DN200 DN200 LSBLG1070/MCF 3588 1500 2168 2850 1400 443 350 375 750 375 618 DN200
Cooling Chilled
Water inlet/outlet pipe dim. DN200 DN200 DN200 DN200 DN200 water inlet
water outlet
Chilled
C
Unit length mm 3588 4593 4593 4611 4611 Cooling water outlet
water inlet
Unit width mm 1500 1500 1500 1600 1600
G
K
Unit height mm 2150 2002 2002 2132 2132
L
D
F
Packing length mm 3950 5050 5050 5050 5050 H
A
J
E
Packing width mm 1660 2080 2080 2180 2180 B
Note: LSBLG1290/MCF 4593 1500 2002 3850 1400 443 350 375 750 350 618 DN200
1. Nominal cooling capacities are based on following conditions: Chilled water inlet/outlet temperature 12/7°C(53.6°F /44.6°F);
Cooling water inlet/outlet temperature 30/35°C(86°F /95°F). LSBLG1420/MCF 4593 1500 2002 3850 1400 443 350 375 750 350 618 DN200
2. The design fouling factor for evaporator is 0.0176m2•°C/kW(0.0001ft2 F.hr/Btu) and for condenser is 0.044m2•°C/kW(0.00025ft2 F.hr/Btu).
3. The voltage range is 414V~506V. LSBLG1560/MCF 4820 1600 2230 3850 1500 468 350 400 800 350 643 DN200
4. All these models will be customized in the factory, please contact with the manufacture firstly.
LSBLG1690/MCF 4820 1600 2230 3850 1500 468 350 400 800 350 643 DN200
11 12
R134a Flooded (410 to 1690kW)
30 60
20 40
20
10
0
0 0.0 50.0 100.0 150.0 200.0 250.0 300.0 350.0 400.0
0.0 50.0 100.0 150.0 200.0 250.0 Water flow (m3/h)
Water flow (m3/h)
120
2
50 100 to avoid noise and vibration. Consulting the building designer before 3
2 Chiller Frame Base
40 80
conducting installation is recommended. 4 3 Rubber Pad
30 60
20 40
A drainage ditch should surround the base to ensure dewatering occurs. 5 4 Steel Base Plate
10 20 Anti-vibration pad is to be placed between the base frame and founda- 5 Concrete Base
0
0.0 50.0 100.0 150.0 200.0 250.0 300.0
0 tion in order to avoid vibrations and unnecessary noise, and make sure
0.0 100.0 200.0 300.0 400.0 500.0
Water flow (m3/h) Water flow (m3/h)
the unit is aclinic during installation. Typical isolation structure
LSBLG410/MCF LSBLG530/MCF LSBLG650/MCF LSBLG1290/MCF LSBLG14200/MCF
LSBLG755/MCF LSBLG860/MCF LSBLG1070/MCF LSBLG1560/MCF LSBLG1690/MCF
Notes:
Application Range The maximum altitude difference (levelness) should be within 3mm for the chiller base.
Items Application range The base should be raised 100mm.
Condenser water entering temperature 25°C~35°C
The installation base of the unit must be concrete or steel structure, which can bear the running weight of the
Evaporator water leaving temperature 5°C~15°C
Water flow volume Flow volume rating ±20% machine. The top should be horizontal. It is ideal to prepare a drainage ditch around installation base.
Temperature difference 4~8°C Put the steel plate and anti-vibration pad in the correct position. Finish the installation of the unit and the
Fouling factor (m2.°C/kW) Evaporator: 0.0176, condenser: 0.044
foundation bolt before secondary concreting. The foundation bolt should protrude 100mm.
Voltage tolerance Voltage rating ±10%
Phase tolerance ±2% Spring isolators are specified on the sales order as an option.
Power supply frequency Frequency rating ±2%
Unit bottom
Evaporator max. working pressure on water side 1.0MPa Unit bottom
Environment quality Highly corrosive environments and high humidity should be avoided.
Steel plate
Spring shock (thickness ≥ 5mm)
Drainage system The height of water drainage should not be higher than the base of the unit. absorber Rubber pad
Storage and transport temperature -25°C~55°C Foundation
Foundation
RH(relative humidity) In + 40°C does not exceed 50%, + 25°C no more than 90%
13 14
R134a Flooded (410 to 1690kW)
Position the absorbers under the unit saddles before final positioning of the unit. The quantity of absorption used for each
Drainage ditch
unit is always decided by the elasticity or durometer value of the absorber. Below please refer to the typical isolation pad
and vibration isolator for selection. A
E+500
L R
E
B
Cond Centre Line F
180mm 22mm
Front side of chiller
D
70mm
D+500
200mm
100
45°
Isolation pad Vibration Isolator
400
300
Model
Minimum load Minimum Minimum load
bearing (kg/EA) Quantity bearing (kg/EA) Quantity
LSBLG1070/MCF 2000 4 2000 4 Dimensions 410 530 650 750 860 1070 1290 1420 1560 1690
LSBLG1290/MCF 2200 4 2200 4 D(mm) 2850 2850 2850 2850 2850 2850 3850 3850 3850 3850
LSBLG1420/MCF 2200 4 2200 4
E(mm) 1100 1100 1300 1300 1300 1400 1400 1400 1500 1500
LSBLG1560/MCF 2200 4 2200 4
Note:
(1) Pads have to extend the full length of the saddle when isolation pads are used.
(2) Level the unit to within 5mm over its length and width after absorbers are installed.
15 16
R134a Flooded (410 to 1690kW)
Water flow switch is required and should be installed on the straight line (5 times the pipe diameter) of
the Chilled/Cooling water outlet. Vibration damper reduces
It is recommended to install a thermometer and pressure gauge to measure the units’ operational condition. vibration and noise by
1 Vibration damper SHA series isolating the supports from the 4
Notes: The diagram is the recommended water system schematic, some changes may be required to accommodate local
floor.
conditions.
Automatic Watering
To Drain
ExpansionTank
Can be installed in the control
room through the cable
connected to the unit touch
Collector
screen. It can display all status
2 Remote control cabinet YCKZ-P 1
Distributer
information and complete all
the unit
operations(startup/shutdown,
error confirm, etc.)
Stop Valve Water Pump Temperature gauge Water Flow Switch 3-Way Valve
Optional items
Suggestion for energy conservation: Name Content
Power supply 380V 3Ph 50Hz is standard and 400/415/460V is optional. 60Hz product is also available.
1. Choose the right pressure head for chilled water pump and cooling water pump.
Water inlet/outlet connection Victaulic type connection is standard for the condenser and evaporator. Flange type connection is optional.
Choose proper pipe diameter and water velocity.
High pressure water box Standard water box can sustain 1.0Mpa pressure .1.6Mpa or 2.0Mpa pressure is optional.
Minimize pipe joint, reducing joints, pipe reducers, manifolds, and valves unnecessary to reduce local resistance loss.
Chiller vibration isolator Spring isolator and rubber pad are the optional accessories from the factory.
Choose proper water strainer (structure/meshes) and periodically clean.
2. Using a variable frequency water pump is recommended as it can reduce energy consumption by 30%-45%. Four steps compressor control Stepless compressor control is standard and capacity adjust in four steps is optional.
3. Using a water distributor and valves between floors or terminal SV to prevent chilled water from High entering condenser water temperature High entering condenser water entering temperature up to 35°C.
circulating in non-working terminals is recommended. Multi unit centralized control Multiple units centralized control is optional (Chiller plant manager).
17 18
Selection software Reference projects
Professional selection software makes the product selection process much easier and more efficient than conventional
manual selection. Simple operating interface and smart arithmetic greatly improves selection efficiency. The user simply
needs to provide several basic parameters, such as cooling capacity, fouling factor, power supply, etc. The program will then
display all suitable models for easy selection.This software can be conveniently updated online. If you have any questions
Selection software
Reference projects
Beijing Airport T3 Terminal
Country: China
City: Beijing
Total Capacity: 9556RT
Outdoor Unit: Centrifugal Chiller & Water-cooled screw chiller
Indoor Unit: FCU
Control System: BMS
Completion Year: 2007
Total Floor Area: 900,000 m²
We reserve the right to make change in design and construction at any time without notice.
19 20
Reference projects
Reference projects
Guangzhou Huadu Asian Games Stadium
Country: China
City: Guangzhou
Outdoor Unit: Water-cooled screw chiller
Indoor Unit: AHU
Total capacity: 3,650 kW
21 22
Reference projects
Reference projects
The 27th Southeast Asian Games Stadium
Country: Myanmar
City: Nay Pyi Taw
Total Capacity: 4100RT
Outdoor Unit: Water-cooled screw chiller (Heat Recovery)
Indoor Unit: MAHU
Completion Year: 2012
Total Floor Area: 40,000 m²
23 24
Reference projects
Reference projects
Midea Headquarter Building
Country: China
City: Shunde
Total Capacity: 3,700 RT
Outdoor Unit: Centrifugal chiller & Water-cooled screw chiller
& Air-cooled scroll chiller & DC Inverter VRF
Indoor Unit: AHU & Cassette & Wall Mounted & Duct
Control System: BMS
Completion Year: 2010
25 26
Reference projects
Reference projects
Hilton Hotel in Foshan (Five Star) Salarieh Trade Center
Country: China Country: Iran
City: Foshan City: Qom
Total Capacity: 3,700 RT Capacity: 800Ton
Outdoor Unit: Centrifugal chiller & Water-cooled screw chiller
Outdoor Unit: Water screw chiller
Indoor Unit: AHU & FCU
Control System: BMS Indoor Unit: FCU
Completion Year: 2013 Completion Year: 2013
Total Floor Area: 90,000 m²
27 28
Reference projects
Reference projects
The Prime Minister Office Building
Country: Tajikistan
City: Dushanbe
Total Capacity: 2880kW
Outdoor Unit: Water-cooled screw chiller
Indoor Unit: Cassette & Duct FCU
Control System: Wired Control & Remote Control
Completion Year: 2015