Professional Documents
Culture Documents
ZP31K5E PFV Compressor
ZP31K5E PFV Compressor
ZP31K5E PFV Compressor
Performance Mechanical
Number of Cylinders: 0 Displ(in^3/Rev): 1.80
Evap(°F)/Cond(°F) 45 / 130 50 / 100
Bore Size(in): 0.00 Displ(ft^3/hr): 218.75
RG(°F)/Liq(°F) 65.0 / 115.0 70.0 / 85.0 Stroke(in): 0.00
Capacity (Btu/hr) 31100 42500
Power (Watts): 3070 2020 Overall Length (in): 9.56 Mounting Length (in): 7.50
Current (Amps): 13.50 9.10 Overall Width (in): 9.56 Mounting Width (in): 7.50
EER (Btu/Wh): 10.10 21.10 Overall Height (in): 15.27 Mounting Height (in): 16.02 *
Mass Flow (lbs/hr): 459 525
Sound Data 45 / Suction Size (in): 3/4 Stub
Sound Power (dBA): 68 Avg 73 Max Discharge Size (in): 1/2 Stub
Oil Recharge (oz): 21
Vibration (mils(peak-peak)): 2.0 Avg 3.0 Max Initial Oil Charge (oz): 25
Record Date: 2015-10-06 Net Weight (lbs): 49.6
Internal Free Volume (in^3): 119.4
Horse Power:
*Overall compressor height on Copeland Brand Product's specified
mounting grommets.
Electrical
LRA-High*: 79.0 MCC (Amps): 26.0 UL File No: SA-2337
LRA-Half Winding: RPM: 3500 UL File Date: 16-Dec-2003
LRA Low*: Max Operating Current: 17.8
RLA(=MCC/1.4;use for contactor selection): 18.6
RLA(=MCC/1.56;use for breaker & wire size 16.7
*Low and High refer to the low and high nominal voltage ranges for which the motor is approved.
Alternate Applications
Refrigerant Freq (Hz) Phase Voltage Application
Rating Conditions
11.1 K Superheat
8.3 K Subcooling
35 °C Ambient Air Over
Compressor Information
Inputs
Results
Notes: Net Refrigeration Capacity is the amount of useful cooling delivered to refrigerated space.
Discharge Temperature Estimation Accuracy ± 5.6 °C.
Electrical
Median Voltage High Voltage Phase Frequency RPM
Mechanical
Overall Dimensions Mounting Dimensions Suction Connection Discharge Connection
Length (mm) Width (mm) Height (mm) Length (mm) Width (mm) Height (mm) Size (in) Type Size (mm) Type
242.95 242.95 387.99 190.50 190.50 407.04 0.75 ST 12.700 ST
Displacement
No. of Cylinders Bore (mm) Stroke (mm) Displacement Displacement Horse Power Drawing Weight (kg)
(cm³/Revolution) (m³/hr) (HP)
68 73 0.051 0.076 1 1
60 Hz Operation
Condensing Temperature °C
(Sat. Dew Pt. Pressure, bar) Evaporating Temperature °C (Sat. Dew Pt. Pressure, bar)
0.0 (8) 2.0 (8.5) 4.0 (9) 6.0 (9.6) 8.0 (10.2) 10.0 (10.8)
62.0 C 6,350 6,950 7,550 8,200 8,850
(40.1) P 3,850 3,810 3,770 3,740 3,710
A 16.7 16.6 16.4 16.3 16.1
M 45 49 53 57 62
E 1.7 1.8 2.0 2.2 2.4
% 54.1 56.9 59.5 61.8 63.9
C 6,050 6,650 7,250 7,850 8,500 9,200
3,690 3,640 3,610 3,570 3,540 3,520
60.0 P
A 16.0 15.9 15.7 15.6 15.4 15.3
Condensing Temp. / Gas Cooler Outlet Temp. °F (Sat. Dew Pt. Pressure, psig)
(38.3) M 42 46 50 54 58 62
E 1.6 1.8 2.0 2.2 2.4 2.6
% 53.6 56.4 59.0 61.5 63.6 65.5
C 6,750 7,350 7,950 8,600 9,300 10,000
3,220 3,180 3,160 3,130 3,110 3,090
55.0 P
A 14.1 13.9 13.8 13.7 13.6 13.5
(34.3) M 44 47 51 55 59 63
E 2.1 2.3 2.5 2.8 3.0 3.2
% 59.1 61.6 63.9 65.9 67.6 69.1
C 7,350 8,000 8,650 9,350 10,050 10,800
2,810 2,790 2,770 2,750 2,740 2,720
50.0 P
A 12.4 12.3 12.2 12.1 12.1 12.0
(30.6) M 45 49 52 56 60 64
E 2.6 2.9 3.1 3.4 3.7 4.0
% 63.8 66.0 67.8 69.3 70.5 71.4
C 7,950 8,600 9,300 10,000 10,750 11,500
2,470 2,460 2,440 2,430 2,420 2,410
45.0 P
A 11.0 10.9 10.8 10.8 10.7 10.7
(27.3) M 46 49 53 57 61 65
E 3.2 3.5 3.8 4.1 4.4 4.8
% 67.6 69.2 70.5 71.5 72.0 72.2
C 8,500 9,200 9,900 10,600 11,350 12,150
2,180 2,170 2,160 2,150 2,140 2,130
40.0 P
A 9.8 9.7 9.7 9.6 9.6 9.5
(24.2) M 47 50 54 58 61 66
E 3.9 4.2 4.6 4.9 5.3 5.7
% 70.0 71.1 71.8 72.1 71.9 71.3
C 9,050 9,700 10,450 11,200 12,000 12,800
1,930 1,910 1,900 1,900 1,890 1,880
35.0 P
A 8.7 8.7 8.6 8.6 8.5 8.5
(21.4) M 47 51 54 58 62 66
E 4.7 5.1 5.5 5.9 6.4 6.8
% 71.1 71.5 71.5 71.0 70.0 68.6
C 9,500 10,250 11,000 11,750 12,550 13,450
1,700 1,690 1,680 1,670 1,660 1,650
30.0 P
A 7.8 7.8 7.7 7.7 7.6 7.6
(18.8) M 48 51 55 58 62 66
E 5.6 6.1 6.6 7.1 7.6 8.2
% 70.7 70.3 69.4 68.1 66.2 63.7
C: Capacity (W), P: Power (W), A: Current (Amps), M: Mass Flow (gm/s), E: COP, %: Isentropic Efficiency (%)
Nominal Performance Values (±5%) based on 72 hours run-in. Subject to change without notice. Current @ 230 V
Note: Subcooling is included only in Subcritical calculations.