Professional Documents
Culture Documents
RC12-installation Manual
RC12-installation Manual
Series Grasso 12
Legal Notice
This publication has been written in good faith.
However, Grasso cannot be held responsible, neither for
any errors occurring in this publication nor for their
consequences.
Safety
This manual is written with great care, but the
contractor/installer is held responsible to examine this
information and to take care of possible additional and/
or deviated safety measures.
Safety instructions
It is the task of the contractor/installer to inform and
explain to his client the operation of the compressor
(Package).
Do respect all federal, state or local safety
regulations/legislations during installing, connecting and
operating this compressor (package).
Construction changes
Contents
Description of (re)assembling, inspection, repair and part
or total overhaul of the bare shaft compressor. This
manual should be used together with the 'Installation
and Maintenance Manual'.
Legend
1, 2, 3, ... Cylinder numbers
T Top view of compressor
M Motor/Drive end of compressor
O Oil pump of compressor
NOTES:
Oil discharge - running in - filter Red coloured filter element Factory mounted; to be replaced after max. 100
running hours by permanent oil discharge filter
element
Oil discharge - permanent - filter Grey filter element Supplied loose; replacement for factory
mounted running in filter
Direction of rotation of compressor drive shaft Counterclockwise when facing shaft end
1.1 INSTALLATION
Every precaution must be taken while moving the
package to its final location. Pushing, pulling or climbing
The compressor is not charged with oil, therefore, DO on any package component or piping, can easily create
NOT start the compressor before it has been installed damage.
and prepared according to Grasso’s instructions.
This section contains instructions for the proper 1.1.2 STORAGE
installation of a Grasso compressor (package). Before The compressor (package) is filled with dry nitrogen.
the compressor (package) is ready for the initial start up, Keep the system closed until the package is installed. If
the installation instructions in the following paragraphs the compressor (package) is stored, it should be kept at
must be followed: all times in a dry location to prevent corrosion damage.
1. The Compressor (Package) should be levelled and If the compressor (package) is to be stored for a
securely anchored to the foundation. prolonged period of time, it should be checked weekly to
2. All piping should be completed. ensure that the holding charge of dry nitrogen remains
3. The system and the compressor are to be pressure above atmospheric pressure.
tested for leaks (see. Section 1.2.1)
4. The system should be evacuated to remove air and 1.1.3 HOISTING AND MOVING INSTRUCTIONS
moisture.
5. The electric wiring should be completed as per wiring
diagrams. Do not energise the main power control
cabinet until oil is added and the direction of
rotation1 has been checked.
6. The compressor is to be filled with the correct type
and amount of lubricating oil and has to be
pre-lubricated before the first start.
7. ‘Open compressors’ only;
1 Open compressors;
The drive system should be installed.
2 (Semi) hermitic compressors;
Mark R-S-T-N power supply in the terminal box of
the motor.
8. The system should be charged with the correct
amount of refrigerant.
9. The oil should be warmed up above minimum start
up oil temperature (see "Product Information").
10.The control cabinet should be energised to check the
package controls. Fig. 1.1-1 Hoisting a compressor package
DO NOT use the compressor or motor or oil separator Refer to “Product Information“ for minimum
hoisting eyes to move the package! These hoisting eyes requirements.
are intended for lifting loose components only and not
for the entire package! 1.1.5 FOUNDATION REQUIREMENTS
Table 1.1-1
Legend
A Chemical anchor
B Grouted anchor, grounded to reinforcing steel
Legend
1 Self-levelling grout
2 Adjusting bolts (4x) Fig. 1.1-6 Grouting details of bare compressor on concrete block
3 Washer
4 Temporary barrier strip around and inside frame Legend
Legend
Refer to separate user manuals, in case an electrionic
control device is installed. 1 Lubricating oil pressure regulator
2 Control oil pressure regulator
1.2.5.2 REFRIGERANTS R717 AND HALOCARBONS A Oil suction filter
Oil discharge filter
Pressure safety limit switches for R717 and halocarbons REMARK: A running in filter is factory mounted; to
B be replaced after max. 100 running
5oC below design
Setting hours by permanent oil discharge filter
Suction pressure a evaporating temp.
element
Precondition Min. =0.3 bar(a)
Oil charge valve for lubrication circuit.
Max.= depends on C
Suction and
rotational speed, REMARK: This connection to be used for
intermediate Setting pre-lubrication of the oil circuit
refer to Product
pressure
Information (PI)
Oil charge plug for oil suction filter (Hand operarated oil
D
Setting 5oC above design pump and stop valve are not included)
Discharge pressure condensing temp.
E Connection to measure oil control pressure
Precondition Max. =24 bar(a)
F Hand operated oil charge pump (optional).
Lubrication oil
Setting Min. =1.3 bar
pressure difference
Re-adjustment procedure:
a. Settings Pdischarge - Psuction must never exceed max. value as
mentioned in Product Information
REMARK: For settings, refer Table 1.
Oil pressure regulators for R717 and halocarbons
i) Run the compressor for 15 minutes until the
crankcase oil is at its stable operating temperature
Setting 2.0 bar [Toil] of 50 oC at which:
Lubrication oil # The lubricating oil pressure difference should be (A)
pressure
differencea Precondition, Min. =1.3 bar according to Table 1.
at 50 oC oil temp. Max. =4.5 bar # The control oil pressure difference should be
approx. (B) according to Table 1.
Control oil
pressure difference
Setting 8.0 bar After the initial run the oil pressure differences should
be slightly higher.
a. The oil pressure regulator is adjusted at the works, but it may occur ii) Determine the lubricating oil pressure difference
that this setting should be corrected during the initial run and also if
the value <1.5 or >2.5 bar. The re-adjustment procedure is given in
(difference between the pressure gauges of the oil
section “Re-adjustment of oil pressure regulator. and suction or [dOil]).
iii) Determine the control oil pressure difference
1.2.5.3 RE-ADJUSTMENT OF OIL PRESSURE (difference between the pressure gauges of oil pump
REGULATOR discharge 1 and suction.
iv) Remove the cap nut of both oil pressure regulators if
It is possible that after the compressor(package) has the pressures need to be re-adjusted.
been installed, the lubrication oil pressure regulator v) Turn the slotted pin with a screwdriver clockwise or
(located on the left side of the pump) needs to be counter clockwise for a higher or lower oil pressure
re-adjusted. respectively, until the required control & lubricating
Inside the oil pump two regulators are factory preset and oil pressure differences have been achieved 2.
installed; One control oil pressure regulator (right) to vi) Replace both cap nuts.
control the valve lifting mechanisms and one lubricating REMARK: If the valve lifting fails, check the control oil
oil pressure regulator for lubrication. pressure regulator!
monthly
weekly
daily
CHECK
POINTSa FREQUENCY REMARKS
monthly
weekly
Adjustment
daily
Note:
Fig. 2.4-1 Oil level in compressor sight glass The job isn't finished until the paper work is done!
Complete the service report, e.g. Grasso report
2.5 EVACUATION, LEAK TESTING AND 00.89.062.
START-UP OF THE
COMPRESSOR/PACKAGE 2.6 DRAINING AND CHANGE OF OIL
To evacuate the refrigeration system refer to Section To top up oil see Section 2.4.1, Oil changing procedure:
1.2.2, i) Evacuate the compressor (refer to Section 2.5).
ii) Drain the oil via the oil charging/drain valve. Remove
Use always a vacuum pump or pump-down unit to the cover of one or more service openings on the
evacuate the refrigerant from the compressor. compressor side.
iii) Clean the inside of the crankcase with a non-fibrous
2.5.1 EVACUATION OF REFRIGERANT BEFORE cloth (do not use cotton waste!).
SERVICING iv) Replace the service cover(s) with a new seal.
Procedure to evacuate the compressor: v) Charge crankcase with clean oil in accordance with
1. Switch off main control panel the procedure.
2. Remove main fuses
3. Close shut-off valves
4. Remove the refrigerant by means of a vacuum pump
or pump-down unit, via the evacuation/purging
valve(s) as prescribed by local safety regulations. For
the location of these valves refer to the "Product
Information".
5. Drain the oil from the compressor and oil separator,
oil return /oil rectifier system if present.
2.5.2 LEAK-TIGHTNESS AFTER SERVICING
The necessary safety precautions should be taken before
carrying out the leak-tightness test. To check
leak-tightness use dry nitrogen at a positive pressure
2.6.1 DRAINING OIL REVERVOIR FOR MARINE USE 2.9 DISMANTLING, INSPECTION AND
(OPTIONAL) RE-ASSEMBLY OF SUCTION AND
DISCHARGE VALVES
In case an oil reservoir for marine use is applied, this oil
reservoir has also to be drained via the oil drain plug of
the oil reservoir. A high working temperature and rapid temperature
variations shorten the life time of the valves, which, for
this reason, require regular inspection.
2.7 REPLACEMENT OF OIL FILTERS The suction and discharge valves of a refrigeration
compressor are parts that are heavily loaded both
mechanically and thermally. Wear and life time of the
Tools; Use the ring spanner for (dis)mounting the oil valves strongly depend on the working conditions of the
filter cups (included in set of special Grasso tools) compressor. It is recommended that valve condition is
regularly checked.For dismantling, inspection and
Evacuate (refer to Section 2.5) the compressor prior to re-assembly of the valves, refer to the relevant
exchange the filter(s). paragraph of the Compressor Service Instruction
Facts: Manual.
Oil suction filter = BLUE coloured
Oil discharge - running-in - filter = RED coloured
Oil discharge - permanent - filter= GREY coloured. In order to reduce the downtime involved in the valve
inspection, it is recommended to have as many complete
2.7.1 OIL DISCHARGE FILTER valve assemblies in stock as there are cylinders on the
compressor.These valves can be exchanged with the
original valves; in this case, these original valves can be
An oil discharge (running-in) filter is factory mounted. inspected and repaired or replaced if necessary later.
This filter must be exchanged after max. 100 running
hours. Oil filters can not be cleaned!
Replace this filter according to the schedule in Section
2.10 COMPRESSOR PURGING
2.2.2 and to the replacement instructions included in the Procedure to purge the compressor(after maintenance
filter set (GREY = permanent) or in case of a modified jobs):
plant (RED = running-in).
9. Water cooling is not Repair 3. No return from oil Check the operation of
working properly separatorb float valve in oil separator
G Too high oil
1. Capacity control consumption 4. Restriction plug at
does not operate Repair the bottom of suction Clean plug
chamber in cylinder
2. Compressor capacity Refer to plant design clogged
too small
C Suction 5. Worn out oil scraper
ring(s) Replace ring(s)
pressure too high 3. Suction pressure Repair or renew
gauge defective
6. Loss of oil due to
leakage Repair
4. One or more suction Renew suction valve rings
valves defective
7. Leaking shaft seal
5. One or more (max. 1 cc/hr) Repair shaft seal
discharge valves Repair or renew (Not for Grasso 7S and Refer to Section 2.2
defective 8S)()
6. Pressure relief valve 8. Oil level in crankcase Drain/Refill with oil
Repair or renew too high
is leaking
1. Suction stop valve 9. Oil separator is not Refer to section “Initial oil
not fully open Open fully initially filled with oil charge”
2. Suction gas strainer 1. Lubricating oil
Renew H Too high oil pressure regulator not Re-adjust or renew
blocked
pressure during adjusted properly or
D Suction 3. Injection control not normal defective
pressure too low adjusted correctly Re-adjust control
operation at
working 2. Defective oil
4. Too little refrigerant temperature pressure and/or
Top-up with refrigerant Repair or replace
in installation suction pressure gauge
(if present)
5. Suction pressure
gauge defective Renew
3. MAINTENANCE
After the refrigerating system has been modified, the These operations cover routine maintenance and are
suction gas filter(s). the oil filters and the oil should be
changed. meant as a guide only. Lack of maintenance, frequency
of stop/starting, extreme operating conditions etc could
lead to accelerated wear.
Maintenance Number of operating hours
100a > 100
Inspect/clean suction gas filter X
General;
refer to Service and
The service and maintenance schedules use the codes as
Renewal oil discharge filter X
Maintenance explained in the table below;
Inspect/clean oil suction filter Schedules (SMS)
X
(strainer) Table 3.4-1 Actions
Oil analysis bc X Legend for service and maintenance schedules (SMS)
a. Time dependent on pollution. Item Code/Actions Description
b. Take an oil sample every 3,000 running hours or once a year and renew if any
sign of discoloration and if the system is contaminated. Inspection / Alternatively renewal - correcting
c. Consult your oil supplier. 1 IC
/ Testing
Inspection Visual / Alternatively electrical
2 IV
testing
3 RE Renewal
4 ME Measure
5 CL Clean
3.4.1 GRASSO 12
Description Checkpoint
15 - 18 -
0.1 YEARLY
21 - - 24 - -
27 30 - - -
33 - - - 36
1 CL RE CL RE RE RE RE RE Oil suction filter
2 REb RE RE RE RE RE RE RE Oil discharge filterc
3 Oil - ME ME ME ME ME ME ME Oil analysis
Oil refreshment (If hygroscopical oil is used replace this
4 RE RE - RE RE RE RE RE always after each opening of compressor or
installation)
5 - IC/CL - IC/CL IC/CL IC/CL IC/CL IC/CL Housing and element
Oil pump
6 - IC/CL - IC/CL IC/CL IC/CL IC/CL IC/CL Control and lubrication oil pressure regulator
7a - - - - - - IC/ME IC/ME Main and intermediate bearing bushes
Description Checkpoint
15 - 18 -
0.1 YEARLY
21 - - 24 - -
27 30 - - -
33 - - - 36
31 IC IC IC IC IC IC CL/IC CL/IC Oil level switch
32 IC IC IC IC IC IC IC IC Safety switches
33 IC IC IC IC IC IC IC IC Gauges
34 IC IC IC IC IC IC IC IC Thermostats
35 IC IC IC IC IC IC IC IC Thermometers
36 IC IC IC IC IC IC IC IC Electrical control system
37 IC IC IC IC IC IC CL/IC CL/IC Valve oil return protection
38 IV IV IV IV IV IV IV IV Thermistors
39 Optionals IC IC IC IC IC IC IC IC Vibration dampers and bolts
40 IC/ME IC/ME IC/ME IC/ME IC/ME IC/ME IC/ME IC/ME Intermediate cooler and injection valve
Oil separator refreshing oil and cleaning/testing of float
41 CL CL - CL CL CL CL CL
valve
42 - IC IC IC IC RE IC IC Heavy duty thrust bearing
43 CL CL CL CL CL CL CL CL Oil cooler, air side
44 RE RE - RE RE RE RE RE Oil cooler, oil side, refrigeration oil
45 Refer to specifications of motor manufacturer Oil cooler, electic motor (fan)
46 ME ME/CL ME/CL ME/CL ME/CL ME/CL ME/CL ME/CL Cylinder head water cooling system
a. Check after every maintenance job the settings and working of all safety devices, regulators and the running conditions according to the Service Instruction Manual
(SIM)
b. A running-in oil discharge filter is factory mounted. This running-in filter has to be replaced after max. 100 running hours by a permanent filter. One permanent filter
is supplied togehter with the compressor.
c. Oil discharge filter change every 3000 hours or check optional pressure drop indicator
d. A running-in suction gas filter is factory mounted. This running-in filter has to be replaced after max. 100 running hours by a permanent filter. One permanent filter
is supplied together with the compressor
3.4.2 CHECKLIST
A Compressor type
B Machine number
C Date
D Running hours
E Refrigerant
E Evaporating temperature/pressure To/Po
F Intermediate temperature/pressure Tm/Pm
G Discharge temperature/pressure Tc/Pc
H Oil lubricating pressure
I Oil control pressure
J General Notes
18 Crankcase heater
19 Crankcase
20 Compressor Non return valves LP/HP
housing
21 Relief valves
22 Suction gas filter
23 Discharge Valves, springs and damper rings
valves
24 Stroke limitor/Discharge valve seat
25 Suction valves Valves, springs and damper rings
26 Cap. Control lifting mechanism
Cylinder liners
27 Dimension and running profile
28 Alignment
Drive
29 V-belts
30 Electric motor Consult motor manufacturer
31 Oil level switch
32 Safety switches
33 Gauges
34 Thermostats
35 Thermometers
36 Electrical control system
37 Valve oil return protection
38 Thermistors
Optionals
39 Vibration dampers and bolts
40 Intermediate cooler and injection valve
41 Oil separator refreshing oil and cleaning/testing of float valve
42 Heavy duty thrust bearing
43 Oil cooler, air side
44 Oil cooler, oil side, refrigeration oil
45 Consult motor manufacturer Oil cooler, electric motor (fan)
46 Cylinder head water cooling system
4. PARTS COMPRESSOR
1A SUCTION GAS FILTER SET RC12-2000 2038130 - 1 piece for RC2112(E) / 4212(E) - 2 for RC212(E)
/ 312(E) / 412(E) / 3112(E) / 5112(E) / 612(E)
1A.1 OILIT SEALING RING 170x230x1.5 0903168 1
1A.2 GAUZE FILTER ELEMENT 2000 * 1
1B SUCTION GAS FILTER SET RC12-3000 2038131 - 1 piece for RC6312(E) / 8412(E) - 2 for RC912(E)
/ 7212(E) / 1212(E) / 9312(E) / 10212(E)
1B.1 OILIT SEALING RING 195x255x1.5 0903195 1
1B.2 GAUZE FILTER ELEMENT 3000 * 1
1.3 O-RING 2.65x13.95 0952269 1
1.4 CIRCLIP RING 14 1103014 1
2A.1 SUCTION HOUSING COVER 236x118 0530240 2 2x for RC312(E) / 612(E) / 5112(E) and 1 for
RC2112(E) / 4212(E)
2A.2 SUCTION HOUSING COVER 236x74.5 0530239 2 For RC212(E) / 412(E) / 3112(E)
2A.3 SUCTION HOUSING COVER 236 0530241 1 For RC211(2)E / 4212(E)
2B.1 SUCTION HOUSING COVER 260x118 0530263 - 1 piece for RC6312(E) / 8412(E) - 2 for RC912(E)
/ 7212(E) / 1212(E) / 9312(E) / 10212(E)
2B.2 SUCTION HOUSING COVER 260 0530262 1
3 SPRING RETAINER 14.5x45 4836015 -
4 PRESSURE SPRING 6x40x2.7x42 1131601 -
5A HEXAGON HEAD BOLT M16x40 0185840 8
5B HEXAGON HEAD BOLT M16x45 0185845 8
aaaaaaaaaa aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa
aaaaaaaaaa aaaaaaaaaa
aaaaaaaaaa
1.a GASKET 106x120x2 0904106 1 RC12(E) 212/ 312/ 4212/ 5112/ 6312/ 7212/
8412/ 9312/ 10212/ 412
RC12(E) 412/ 4212/ 6312/ 7212/ 8412/ 9312/
1.b GASKET 129x149x2 0904129 1
10212/ 612/ 912/ 1212
1.c GASKET 155x175x2 0904155 1 RC12(E) 612/ 912/ 1212/ 5112
RC12(E) 2112/ 3112/ 4212/ 5112/ 6312/ 7212/
1.d GASKET 95x109x2 0904095 1
8412/ 9312/ 10212
2.a GASKET 61x75x2 0904061 1 RC12(E) 2112/ 3112
2.b GASKET 95x109x2 0904095 1 RC12(E) 2112/ 3112/ 4212/ 5112/ 6312/ 7212/
8412/ 9312/ 10212
3.a GASKET 73x87x2 0904073 1 RC12(E) 2112/ 3112
3.b GASKET 106x120x2 0904106 1 RC12(E) 212/ 312/ 4212/ 5112/ 6312/ 7212/
8412/ 9312/ 10212/ 412
RC12(E) 2112/ 3112/ 4212/ 5112/ 6312/ 7212/
4.a GASKET 95x109x2 0904095 1
8412/ 9312/ 10212
4.b GASKET 106x120x2 0904106 1 RC12(E) 212/ 312/ 4212/ 5112/ 6312/ 7212/
8412/ 9312/ 10212/ 412
4.c GASKET 129x149x2 0904129 1 RC12(E) 412/ 4212/ 6312/ 7212/ 8412/ 9312/
10212/ 612/ 912/ 1212
4.d GASKET 73x87x2 0904073 1 RC12(E) 2112/ 3112
5. SUPPLEMENTARY PARTS
6.1 GENERAL LIMITS AND FIELDS OF The diagrams overleaf represent the overall fields of
application in which the individual operation limits are
OPERATION GRASSO 12 taken into account.
When operating the compressor, none of the limits of
operation as stated in the table below must be Table 6.1-1 General limits and fields of operation
exceeded.1 1. In practice, it is not so much the individual operation limits as combinations of
them that are decisive for the conditions under which a compressor may
operate. To check the various possibilities in this respect, use should be made
of the "fields of application" ).
h. The standard built-in overflow safety valve(s) between suction and discharge side has been factory-set to 22.0 1.5 bar to prevent opening during normal operation
at 'p = (pc - po) 17.5 bar.
i. Indicated minimum value is the lowest oil temperature at which the compressor is allowed to be started. The maximum oil temperature depends on the operating
conditions of the compressor, the oil type used and (for halocarbon refrigerants only) the solubility of the refrigerant in the oil. A minimum actual oil viscosity of 10
cSt is always required.
General
Electric capacity control is compulsory in the standard
scope of supply for two stage compressors.
Legend
A Top view of compressor
B Valve lifting mechanism
C Oil return from valve lifting mechanisms to crankcase
D Oil pump
E Electrical wiring, refer Section 1.2.9.2
H Supply of oil (control pressure)
NO Normally Open; 3-way solenoid valve for unloaded starting
NC Normally Closed; 3-way solenoid valve for capacity control
6.3.2 DIAGRAMS
Solenoid
FPDb UNLd No. 1 No. 2 No. 3 No. 4
Compressor NC c
NOe
NC NC NC NC
typea
Cylinder number / solenoid valves
4 - - 1+2 3 4 - -
6
- - 1+3 6 4 5 2
Single stage
2+3+
6 Booster - - 6 4 1 -
5
9 1+2+ 4+7+
Single stage - - 3 8 5+6 9 -
9 1+3+ 4+7+
Booster - - 5+8 2+6 9 - -
12 1+2+ 4 + 10 6 + 7 +
Single stage - - 3 11 5+8 + 12 9
1+2+
12 7 + 10
Booster - - 3+4+ 5+8 6 + 11 + 12 -
9
31 2 - 2 1+3 4 - -
31 + FPD 2 1 2 3 4 - -
42 3+6 - 3 1+2 5 4+6 -
42 + FPD 3+6 6 3 1+2 5 4 -
51 3 - 3 1+2 6 5 4
51 + FPD 3 1 3 2 6 5 4
3+6 5+8+ 4+7+
63 - 3 1+2 -
+9 9 6
3 + 6 1 +92 +
10 + 7+8+
102 3+6 - 4+5
12 11
Capacity %a
Solenoids
Capacity %a
Compressor
Solenoids
type Remarks Cylinders Mb
Compressor
type Remarks Cylinders M b
25 - 1+2+3 - -
50 - 1+2 - - 33 - 1 + 2 + 3 + 11 1 -
4
single stage & 75 - 1+2+3 1 - 1+2+3+5
Booster 42 - +8 2 -
100 - 1+2+3+4 1+2 -
1+2+3+5
33 - 1+3 - - 50 - + 8 + 11
1+2 -
50 - 1+3+6 1 - 1+2+3+4
67 - 1+3+4+6 1+2 - 58 - + 10 + 11 + 1+3 -
6 12
single stage 1+3+4+5 1+2+
83 - - 1+2+3+4
+6 3
67 - + 5 + 8 + 10 + 2+3 -
1+2+3+4 1+2+ 12 12
100 - - single stage
+5+6 3+4
1+2+3+5
1+2+
50 - 2+3+5 - - 75 - +6+7+8+ -
9 + 11 4
67 - 2+3+5+6 1 -
1+2+3+4
6 2+3+4+5 83 - + 6 + 7 + 9 + 1 +43 + -
Booster 83 - +6 1+2 - 10 + 11 + 12
1+2+3+4 1+2+ 1+2+3+4 2+3+
100 - - 92 - +6+7+8+ -
+5+6 3 4
9 + 10 + 12
33 - 1+2+3 - -
1+2+3+4
44 - 1+2+3+8 1 - +5+6+7+ 1+2+
100 - -
8 + 9 + 10 + 3 + 4
1+2+3+5 11 + 12
56 - 2 -
+6
42 - 1+2+3+4 - -
1+2+3+5 +9
67 - 1+2 -
+6+8
9 1+2+3+4
single stage 1+2+3+4 58 - 1 -
78 - 1+3 - +5+8+9
+7+8+9
12 1+2+3+4
1+2+3+4 booster 75 - +5+6+8+ 1+2 -
89 - +5+6+7+ 2+3 - 9 + 11
9
1+2+3+4
1+2+3+4 1+2+ +5+6+7+ 1+2+
100 - +5+6+7+ - 100 - 8 + 9 + 10 + 3 -
3
8+9 11 + 12
44 - 1+3+5+8 - - 0 Starting only 2 - 0.0
1+2+3+5 31 67 - 1+2+3 1 2.0
9 67 - 1 -
+6+8
Booster 100 - 1+2+3+4 1+2 3.0
1+2+3+4
100 - +5+6+7+ 1+2 - 0 Starting only 2 - 0.0
8+9
33 Starting only 1+2 FPD 1.0
31 + FPD 1+
67 - 1+2+3 2.0
FPD
1 + 2 + 3 + 4 1 FPD
+2+
100 - 3.0
Capacity %a
Capacity %a
Solenoids
Solenoids
Compressor Remarks Cylinders Mb
Compressor
Remarks Cylinders Mb
type type
Capacity %a
Capacity %a
Solenoids
Solenoids
Compressor Remarks Cylinders Mb
Compressor
Remarks Cylinders Mb
type type
6.4 LUBRICATING OILS (CHOICE AND a. to,max is the saturated temperature, corresponding to maximum crankcase
RECOMMENDATIONS) pressure where at the usual oil temperatures the oil/refrigerant mixture has a
viscosity of > 10 cSt.
b. Refer to Section 6.4.1.1.
NH3 - vb v vb SHELL
Clavus S-68 /
Refrigeration Oil S2 FR-Aa
-50 v
a. Old name resp. new name; old name will be phased-out during 2010.
-30 v v
HCFC’s -20 v
(R22) -10 v v
0 v
+10 v
-50 v v
-30 v v
HFC’s -20 v v
(R134a, R507,
R404A) -10 v v
0 v
+10 v
For all other refrigerants contact Grasso
Legend v Approved by Grasso
6.4.3 ACCEPTED NH3 AND HCFC OIL TYPES 6.4.4 ACCEPTED HFC OIL TYPES
Table 6.4-3 Accepted NH3 and HCFC (e.g. R22) oil types for Grasso Table 6.4-4 Accepted HFC (e.g. R134a, R404A, R407c, R507) oil types
reciprocating compressors for Grasso reciprocating compressors