A C D E F B: Level 00 Fire Alarm System Layout 1
A C D E F B: Level 00 Fire Alarm System Layout 1
A C D E F B: Level 00 Fire Alarm System Layout 1
KEYPLAN :
( B103 )
ﺍﻟﻣﺎﻧﻊ
AL MANA
P.O.Tel no. 44539888 Fax 44960734 P.O.Box 23300 Doha Qatar
www.rcalmana.com
TECHNICAL DEPARTMENT
A B C D E F Qetaifan Island North at Lusail Qatar
-WaterPark-Package 3
Reviewed by:_________________
Date:_____________
Approval Stamp
00-ST-01
STAIRCASE (ST-01) FIRE ALARM REPEATER PANEL
B103/00/HS/APS4/L1/02
B103/00/MP/P01/L1/218
B103/00/HS/APS4/L1/03
50 mm(W) x50 mm(D) B.O.T:3880 mm
550
B103/00/HS/APS4/L1/05 FIRE ALARM TRUNKING
1430 B103/00/HS/APS4/L1/04
70 Cd 00-ST-02
70 Cd W/P
400 3840 250
00-GA-01
General Notes:
STAIRCASE (ST-02)
1. THE PROPOSED FIRE ALARM SYSTEM IS UL LISTED, QCDD APPROVED AND COMPLIES
1
W/P GAS SUPPRESSION ROOM WITH NFPA STANDARDS.
380
FARP
F 2. FOR EXACT DIMENSIONS OF PROPOSED EQUIPMENT, REFER TO EQUIPMENT
810
B103/00/CR/P01/L1/208 CATALOGUE SHEETS.
W/P 00-LB-01 CM FOR MSFD-B103-00-03 3. ISOLATOR BASE OR MODULE SHALL BE PROVIDED EVERY 15 TO 20 DEVICES AND
00-LT-01 70 Cd LOBBY B103/00/CT1/P01/L1/209 WHEN THE LOOP TRAVELS BETWEEN FLOORS OR ZONES.
CR FOR MSFD-B103-00-03 4. FIRE ALARM PANELS AND AUXULIARY POWER SUPPLIES SHALL BE FED FROM
LIFT FIRE RATED FIBER OPTIC NETWORK CABLE B103/00/CT1/P01/L1/217 DEDICATED BRANCH CIRCUITS.
1880 1980
B103/00/HS/APS4/L1/01 FROM FACP1 IN B100 MM FOR CLEAN AGENT SYSTEM 5. FUSED CONNECTION UNIT FOR FIRE ALARM PANELS AND AUXILIARY POWER
W/P
FIRE L1 TO LEVEL 01 B103/00/CT2/P01/L1/215 SUPPLIES SHALL BE "UNSWITCHED" TYPE.
70 Cd
6. CLASS A CIRCUITS SHALL FOLLOW NFPA 72 CLAUSE 12.3.8 WHICH DISCUSSES
4500
30 Cd B103/00/CT2/P01/L1/216
CT1 PATHWAY SEPARATION.
W/P W/P MM FOR CLEAN AGENT SYSTEM 7. ALL FIRE ALARM DEVICES INSTALLED ABOVE FALSE CEILING SHALL BE ACCESSIBLE.
900
CT2
B103/00/CT2/P01/L1/213
1050
70 Cd B103/00/HS/APS4/L1/07 70 Cd 8. ALL ABOVE FALSE CEILING DETECTORS SHALL BE CONNECTED TO AN LED
CT2
370 1710 B103/00/CT2/P01/L1/214 INDICATOR ON THE CEILING.
300 B103/00/HS/APS4/L1/06 MM FOR CLEAN AGENT SYSTEM
1490
S 770 1100 9. LOCATION OF ALL DEVICES SHALL BE COORDINATED. SMOKE/HEAT DETECTOR
B103/00/SD/P01/L1/088
P B103/00/CR/P01/L1/207 SHALL NOT BE LOCATED IN A DIRECT AIRFLOW NOR CLOSER THAN 1 METER
B103/00/IM/P01/L1/091 IB FROM AN AIR SUPPLY DIFFUSER OR RETURN AIR GRILLE.
S S B103/00/MP/P01/L1/210 10. CONTROL RELAY MODULES SHALL BE 1M AWAY FROM 3RD PARTY SYSTEM
F
B103/00/SD/P01/L1/090 CONTROLLERS.
2
CR CT1
P P
POWER SUPPLY CABLE BACK TO APS3
CT1 CR
M
11. FINAL LABELING OF FIRE ALARM SYSTEM DEVICES WILL BE BASED ON SYSTEM
50 mm(W) x50 mm(D) B.O.T:2920 mm B103/00/SD/P01/L1/089 PROGRAMMING.
12. ALL FIRE ALARM DEVICES INSTALLATION DETAILS SHALL BE SUBMITTED
FIRE ALARM TRUNKING 2050 140 15 Cd SEPARATELY.REFER TO TYPICAL INSTALLATION DETAILS DRAWING.
3080 1010 4130 2170 6160
B103/00/SH/P01/L1/087 M
B103/00/HS/APS4/L1/08
3420
00-EL-04
CR CT1
B103/00/CC2A/P01/L1/107 W/P
3000
1130
B103/00/CT1/P01/L1/203 ICT
B103/00/CC2A/P01/L1/204 MM FOR BMS PANEL
00-EC-02 F B103/00/MP/P01/L1/211
400
00-SG-03
ELEC. CUPD S H B103/00/MP/P01/L1/212
CT1
S H
CR
STORE ROOM
500
490
M
3
300
Project Title:
Architect/Engineer of Record:
2Cx2.5mm² FIRE RATED CABLE FOR 24VDC POWER SUPPLY
QINWP-QEM-B103-00-SD-EE-0001-05 00