Grid Solutions

Multilin C60
Breaker Monitoring and Control for Protection and Control
Substation and Industrial Automation • Breaker failure & Synchronism check
• Autoreclose and open pole detector
The MultilinTM C60 Breaker Protection System is a substation hardened controller that provides a
complete integrated package for the protection, control, and monitoring of circuit breakers. The C60 • Phase, neutral and auxiliary overvoltage
supports dual-breaker busbar configurations such as breaker-and-a-half or ring bus arrangements. • Sensitive directional power & dual breaker control
Signals from up to 4 sets of CT’s can be brought into the C60 via convetional wiring or process bus for
• High density inputs/outputs to support the
internal summation, which is advantageous by still having the individual currents available for metering
control of many switchyard assets – all from
and the additional protection elements that operate on individual currents.
one powerful device
The C60 provides fast and deterministic execution of programmable logic and extensive I/O options that • Integrated large, full color display, for real-time
are necessary for substation automation applications. All of the necessary control logic functions are visualization and control of the protected bay
available for creating automated breaker control schemes, such as the popular main-tie-main scheme
using a single C60 device.

Using high-speed peer-to-peer communications for inter-device messaging, the C60 can also accept
Advanced Communications
breaker opening, closing and lock-out commands from other devices at a fraction of the cost of • 3 independent Ethernet ports for simultaneous
hardwiring these signals. & dedicated network connections with
IEEE  1588 support
• Phasor Measurement Unit (Synchrophasor)
Key Benefits according to IEEE® C37.118 (2011) and
• Complete breaker control, protection, monitoring and integration in a single platform IEC 61850-90-5
• Advanced automation capabilities for providing customized protection and control solutions • IEC 61850-9-2LE/IEC 61869 networked or
• Modular hardware architecture allows for flexibility in device configurations to cover most breaker IEC61850-9-2 Hardfiber process bus support
applications
• An integrated large, full color display, provides real-time visualization and control of the protected bay,
via a bay mimic as well as annunciator functionality and graphical visualization of phasors
Cyber Security
• CyberSentry™ provides high-end cyber
• Advanced IEC 61850 Ed. 1 and Ed. 2 certified implementation, complete settings via SCL files and
security aligned to industry standards and
comprehensive process bus support (IEC 61850-9-2LE or IEC 61869 or IEC 61850-9-2 Hardfiber)
services (NERC® CIP, AAA, Radius, RBAC, Syslog)
ensures interoperability, device managing optimization and reduced cost of ownership
• Routable GOOSE (R-GOOSE) enables GOOSE messages going beyond the substation, which enables
wide area protection and control applications Monitoring & Metering
• Increased network availability via failover time reduced to zero through IEC 62439-3 “PRP” support
®
• P & M Class Synchrophasors of voltage,
• Supports latest edition of waveform capture (COMTRADE 2013) simplifying fault records management current and sequence components
• Fault Locator
Applications • Advanced recording capabilities with high-
• Stand-alone breaker monitoring and control capacity event recorder, configurable and
extended waveform capture and data logger
• Automatic bus transfer scheme using a single device
• Metering: current, voltage, power, energy,
• Multiple breaker configuration control including breaker-and-a-half and ring bus
frequency, and harmonics
• As part of a distributed bay controller
C60 Breaker Protection System

Protection and Control C60 - Protection, Metering, Monitoring and Control


As part of the UR family of Protection & Control
devices, the Multilin C60 Breaker Protection
System offers a high degree of modularity in
its design and functionality, providing superior
performance while meeting the toughest
requirements of the marketplace.

Advanced protection and control features of this


relay includes:

Breaker Failure
The breaker failure functions included in the C60
are available to detect breaker failure conditions
for both single and three-pole tripping schemes.
The C60 provides two independent breaker
failure functions, and all of the current source
inputs, digital inputs and digital outputs need
to perform breaker failure functions on dual
breaker schemes, such as breaker-and-a-half or The C60 is the single point for protection, control, metering, and monitoring in one integrated device
ring bus arrangements. Breaker failure initiation that can easily be connected directly into DCS or SCADA monitoring and control systems like Viewpoint
and transfer tripping signals can be done using Monitoring as shown.
hardwired contacts or through communications
(IEC 61850 and direct I/O).
users to select the reclosure mode to suit elements can be dynamically blocked or
Autorecloser specific applications. The autoreclose modes unblocked by other elements or user logic,
can be dynamically changed by any internal allowing coordination with other C60 protection
The C60 provides multi-shot autoreclosing
FlexLogic™ digital operand, allowing flexibility settings and groups. The C60 provides additional
on all types of faults for single or three-pole
with changing system conditions. enhancements in synchronizing by checking
applications with independent dead time for
dead source conditions for synchronism bypass
each shot . The protection settings can be Synchrocheck under these conditions.
changed between shots (typical application
The C60 provides ten synchrocheck elements that
being an accelerated zone 1 extension scheme). Overcurrent and Thermal Elements
monitor voltage difference, phase angle difference
Autoreclosure can also be dynamically blocked
and slip frequency taking the CB closing time into Overcurrent protection is delivered through
by user-programmable logic. Four different
account to ensure proper breaker closure as per instantaneous and time overcurrent elements
autoreclose modes are available, enabling
user requirements. Any of the ten synchrocheck available for phase, neutral, ground and

Functional Block Diagram


ANSI® Device Numbers & Functions
DEVICE
FUNCTION
59P NUMBER
59N 25 Synchrocheck
27P Phase Undervoltage
50P 51P 50BF 32 49 50NBF 27 25 27X Auxiliary Undervoltage
32 Sensitive Directional Power
49 Thermal Overload Protection
50BF Breaker Failure
Trip
50DD Disturbance Detector
59X 27X 81O 50G Ground Instantaneous Overcurrent
52 Close 50N Neutral Instantaneous Overcurrent
50N BF Neutral Instantaneous Overcurrent, Breaker
Failure
79 Metering + PMU 50P Phase Instantaneous Overcurrent
51G Ground Time Overcurrent
Close 51N Neutral Time Overcurrent
52
TM Transducer 51P Phase Time Overcurrent
FlexElement input
Trip 52 AC Circuit Breaker
59N Neutral Overvoltage
59P Phase Overvoltage
59X Auxiliary Overvoltage
50P 51P 50BF 32 50NBF 27 25 79 Autoreclose
81O Overfrequency
59N Harmonic/Inrush detection

C60 Breaker Protection System


834777A1.CDR

2 GEGridSolutions.com
C60 Breaker Protection System

sensitive ground protection. Most of the FlexLogic Designer


standard protection curves are provided.
Thermal overload elements as per the IEC 255-8
standard are also available.

Sensitive Directional Power


Two separate directional power elements are
provided to detect reverse and low forward
power conditions for use in IEEE 1547 DG
interconnection anti-islanding protection.

Breaker Control
The C60 allows for control of up to two breakers
through commands given to it from either
local or remote users. The C60 front panel can
have 16 user-configurable pushbuttons that
can be used to select and operate the breaker
functions. Each button can be customized
and labeled for easy operator identification.
The C60 can also accept breaker operation
commands from remote users through one of
the many available communication protocols
including Modbus, DNP 3.0, IEC 61850, and FlexLogic allows for the creation of customized C60 breaker control schemes, including the receipt of trip and
IEC  60870-5-104. close commands from other devices, and the creation of logic to replace the need for external lockout relays.

Harmonic/Inrush detection
Topologies:
The Harmonic detection element monitors Station Bus
PRP Start
the selected 2nd to 5th harmonic or Total Hot-Stanby
Harmonics Distortion (THD), which is present
in the phase currents. The relay provides six
identical Harmonic Detection elements.
Integrated Station and
During transformer energization or motor starts, Process bus (available)
the inrush current present in phase currents
can impact some sensitive elements, such as
negative sequence overcurrent . Therefore, Topologies: Process Bus:
the ratio of the second harmonic to the HSR ring IEC 61850-9-2LE or 61869* SV
fundamental magnitude per phase is monitored, PRP start IEEE 1588 Grand Master or
while exceeding the settable pickup level, an P-2-P Process Bus slave 61850-9-1 GOOSE
operand is asserted, which can be used to block
such sensitive elements.

IEC 61869 and 61850-9-2LE Merging units


Process Bus
Three UR process bus modules enable
Conventional or
communicating to Merging Units “MU” that Optical CT/VTs
comply to either IEC 61869 standard or
IEC 61850-9-2LE technical report. MUs connect
to the primary asset and translate analog signals
and digital status/commands to standard
clock (61850-9-3 profile) or a 1588 Grand Master IEC 61850-9-2 HardFiber
clock which removes the need of external time
sample values “SV” data and GOOSE messages.
sources connected to the process bus network.
Process Bus
Flexibility for connecting to different network size The IEC 61850 Process Bus module is designed
Customers who may not be using GE MU
and topology is granted through 100Mbps and/ to interface with the GE Multilin HardFiber
devices, could use MU from other vendors.
or 1Gbps Ethernet port support, plus IEC 62439 System, allowing bi-directional IEC 61850 fiber
Interoperability with MU from other vendors is
PRP or HSR standard redundancy, plus Star, Ring optic communications. The HardFiber System is
expected when they comply to the mentioned
and Point-to-point network support. designed to integrate seamlessly with existing
standards.
Universal Relay (UR) applications, including
For time synchronization purposes, this Process protection functions, FlexLogic, metering and
bus module can become an IEEE 1588 slave communications.

GEGridSolutions.com 3
C60 Breaker Protection System

The GE Multilin HardFiber System offers the control schemes, minimizing the need and parameters are available as total RMS
following benefits: associated costs of auxiliary components and magnitude, and as fundamental frequency
wiring. With 1024 lines of FlexLogic, the C60 magnitude and angle.
• Communicates using open standard
can be programmed to provide the required
IEC 61850 messaging
logic for performing complete breaker control in Fault and Disturbance Recording
• Drastically reduces P&C design, installation schemes that may include simple single breaker The advanced disturbance and event recording
and testing labor by eliminating individual
management, equipment backup protection as features within the C60 can significantly reduce
copper terminations
well as sophisticated automatic transfer schemes. the time needed for postmortem analysis
• Integrates with existing C60’s by replacing of power system events and the creation of
traditional CT/VT inputs with the IEC 61850 Scalable Hardware regulatory reports. Recording functions include:
Process Bus module
The C60 is available with a multitude of I/O
• Sequence of Event (SOE)
• Does not introduce new cyber security configurations to suit the most demanding
- 1024 time stamped events
concerns application needs. The expandable modular
• Oscillography
Visit the HardFiber System product page on the design allows for easy configuration and future
- Supports IEEE C37.111-1999/2013,
GE Multilin web site for more details. upgrades.
IEC 60255-24 Ed 2.0 COMTRADE standard
• Multiple CT/VT configurations allow for the - 128 digital & up to 56 analog channels
Advanced Automation implementation of many different schemes, - Events up to 45s in length
including single and dual breaker applications
The C60 incorporates advanced automation • Data Logger and Disturbance Recording
• Flexible, modular high density I/O covering - 16 channels up to 1 sample/cycle/channel
features including powerful FlexLogic
a broad range of input signals and tripping
programmable logic, communication, and • Fault Reports
schemes
SCADA capabilities that far surpass what is - Powerful summary report of pre-fault and
found in the average breaker relay or controller. • RTDs and DCmA inputs are available to fault values
The C60 integrates seamlessly with other UR monitor equipment parameters such as
The very high sampling rate and large amounts
relays for complete breaker management temperature and pressure
of storage space available for data recording
including reclosing, load shedding, and in the C60 can eliminate the need for installing
synchronism applications. Monitoring and Metering costly stand-alone recording equipment.
The C60 includes high accuracy metering and
FlexLogic Advanced Device Health Diagnostics
recording for all AC signals. Voltage, current,
FlexLogic is the powerful UR-platform and power metering are built into the relay The C60 performs comprehensive device health
programming logic engine that provides the as a standard feature. Current and voltage diagnostic tests at startup and continuously
ability to create customized protection and

Power System Troubleshooting


The C60 contains tools that allow for the early detection of impending breaker problems and allow for maintenance to be performed before serious damage occurs.

Triggering a waveform on each breaker operation


can identify changes in the length of time each part
or mechanism in the breaker takes to perform its
function.
Breaker Latch Release Time:
Indicates how long it took for the breaker
latch to release from the time the trip coil was
energized by the relay.

Arc Extinguish Time:


Indicates the length of time that was required
for the breaker to extinguish the arc and finally
clear the fault.

Breaker Mechanism Travel Time:


Indicates time interval required for the breaker
mechanism to travel to its rest position.

4 GEGridSolutions.com
C60 Breaker Protection System

during run-time to test its own major functions roles for up to eight configurable users with standard protocols enabling easy, direct
and critical hardware. These diagnostic tests independent passwords. The standard “Remote integration into DCS and SCADA systems.
monitor for conditions that could impact security Authentication Dial In User Service” (Radius) is • IEC 61850 Ed. 1 and Ed. 2 Station Bus,
and availability of protection, and present device used for authentication. IEC 61850-2-2LE / IEC 61869 networked or
status via SCADA communications and front IEC 61850-9-2 HardFiber Process Bus, and
panel display. Providing continuous monitoring Event Recorder (Syslog for SEM) IEC 61850-90-5 PMU over GOOSE support
and early detection of possible issues help Capture all cyber security related events within • DNP 3.0 (serial & TCP/IP)
improve system uptime. a SOE element (login, logout, invalid password • Ethernet Global Data (EGD)
• Comprehensive device health diagnostic attempts, remote/local access, user in session, • IEC 60870-5-103 and IEC 60870-5-104
performed at startup settings change, FW update, etc), and then • Modbus RTU, Modbus TCP/IP
serve and classify data by security level using
• Monitors the CT/VT input circuitry to validate • HTTP, TFTP, SFTP and MMS file transfer
standard Syslog data format. This will enable
the integrity of all signals • IEEE1588 and redundant SNTP for time
integration with established SEM (Security Event
synchronization
Management) systems.
Cyber Security – CyberSentry UR • PRP as per IEC 62439-3

CyberSentry UR enabled UR devices deliver full • Supports Routable GOOSE (R-GOOSE)


Communications
cyber security features that help customers to
The C60 provides advanced commun-ications Interoperability with Embedded
comply with NERC CIP and NIST® IR 7628 cyber
technologies for remote data and engineering IEC 61850 Ed. 1 and Ed. 2
security requirements. This software option
delivers the following core features: access, making it easy and flexible to use and The new IEC 61850 implementation in the UR
integrate into new and existing infrastructures. Family positions GE as an industry leader in this
AAA Server Support (Radius/LDAP) Direct support for fiber optic Ethernet provides standard.
high-bandwidth communications allowing
Enables integration with centrally managed • Implements, user selectable, Ed. 1 and Ed. 2
for low-latency controls and high-speed
authentication and accounting of all user of the standard across the entire UR Family
file transfers of relay fault and event record
activities and uses modern industry best • Provides full relay setting management via
information. The available three independent
practices and standards that meet and exceed standard SCL files (ICD, CID and IID)
Ethernet ports, redundant Ethernet option
NERC CIP requirements for authentication and
and the embedded managed Ethernet switch • Enables automated relay setting
password management.
provide the means to create fault tolerant management using 3rd party tools through
communication architectures in an easy, standard file transfer services (MMS and SFTP)
Role Based Access Control (RBAC)
cost-effective manner without the need for • Increases the number of Logical Devices and
Efficiently administrate users and roles within
intermediary communication hardware. data mapped to them, GOOSE messages
UR devices. The new and advanced access
from up to 64 remote devices, and reports
functions allow users to configure up to five The C60 supports the most popular industry
to support different organizational needs for
data transfer and reduce dependency on
generic logical nodes
Simplifying Fault and Disturbance Analysis
• Configures GE Systems based on IEC 61850
using universal 3rd party tools
• Multicast IEEE C37.118 synchrophasor
data between PMU and PDC devices using
IEC  91850-90-5
• R-GOOSE enable customer to send GOOSE
messages beyond the substation, which
enables WAPC and more cost effective
communication architectures for wide area
applications

Direct I/O Messaging


Direct I/O allows for the sharing of high-speed
digital information between multiple UR
relays via direct back-to-back connections or
multiplexed through a standard DS0 multiplexer
channel bank. Regardless of the connection
method, direct I/O provides continuous real-time
channel monitoring that supplies diagnostics
information on channel health.

Direct I/O provides superior relay-to-relay


The events recorded in multiple GE devices can be collected and merged into a single station-wide SOE communications that can be used in advanced
record to simplify the tracking of substation operations.

GEGridSolutions.com 5
C60 Breaker Protection System

interlocking, generation rejection and other setup software within Launchpad allows for Viewpoint Maintenance
special protection schemes. the configuration of devices in real-time by
Viewpoint Maintenance provides tools that
communicating using serial, Ethernet, or modem
• Communication with up to 16 UR relays will create reports on the operating status of
connections, or offline by creating setting files
in single or redundant rings rather than the relay, simplify the steps to download fault
strictly limited to simplistic point-to-point to be sent to devices at a later time.Included
and event data, and reduce the work required
configurations between two devices in Launchpad is a document archiving and
for cyber security compliance audits. Tools
management system that ensures critical
• Connect to standard DS0 channel banks available in Viewpoint Maintenance include:
documentation is up-to-date and available when
through standard RS422, G.703 or IEEE • Settings Security Audit Report
needed. Documents made available include:
C37.94 interfaces or via direct fiber optic
• Device Health Report
connections • Manuals
• Single-Click Fault Data Retrieval
• No external or handheld tester required to • Application Notes
provide channel diagnostic information • Guideform Specifications EnerVista Integrator
LAN Redundancy • Brochures EnerVista Integrator is a toolkit that allows
• Wiring Diagrams seamless integration of GE Multilin devices into
Substation LAN redundancy has been
new or existing automation systems. Included in
traditionally accomplished by reconfiguring • FAQ’s
EnerVista Integrator is:
the active network topology in case of failure. • Service Bulletins
Regardless of the type of LAN architecture (tree, • OPC/DDE Server Retrieval
mesh, etc), reconfiguring the active LAN requires Viewpoint Monitoring • GE Multilin Drivers • Automatic
time to switchover, during which the LAN is Viewpoint Monitoring is a simple-to-use and Waveform Retrieval
• Automatic Event
unavailable. UR devices deliver redundancy as full-featured monitoring and data recording
specified by PRP-IEC 62439-3, which eliminates software package for small systems. Viewpoint
the dependency on LAN reconfiguration and the Monitoring provides a complete HMI package
User Interface
associated switchover time. The UR becomes a with the following functionality: The C60 front panel provides extensive local
dual attached node that transmits data packets HMI capabilities. The local display is used for
over both main and redundant networks • Plug-&-Play Device Monitoring
monitoring, status messaging, fault diagnosis,
simultaneously, so in case of failure, one of the • System Single-Line Monitoring & Control and device configuration. User-configurable
data packets will reach the receiving device with • Annunciator Alarm Screens messages that combine text with live data can be
no time delay. displayed when user-defined conditions are met.
• Trending Reports
Multi-Language • Automatic Event Retrieval A 7” color, graphic HMI is optionally available that
allows users to have customizable bay diagrams
UR devices support multiple languages: English, • Automatic Waveform Retrieval
with local monitoring of status, values and control
French, Russian, Chinese, Turkish, German,
Polish and Japanese. These language options
Viewpoint UR Engineer functionality. The alarm annunciator panel
provides the configuration of up to 96 signals
are available on the front panel, in the EnerVista Viewpoint UR Engineer is a set of powerful
(alarms and status) with full text description.
setup software, and in the product manuals. tools that allows the configuration and testing
Easily switch between English and an additional of GE relays at a system level in an easy-to-
language on the local displays without use graphical drag-and-drop environment .
uploading new firmware. Viewpoint UR Engineer provides the following
configuration and commissioning utilities:

EnerVista Software • Graphical Logic Designer

The EnerVist suite is an industry-leading set of • Graphical System Designer


software programs that simplifies every aspect • Graphical Logic Monitor
of using the C60 relay. The EnerVista suite
• Graphical System Monitor
provides all the tools to monitor the status of
the protected asset, maintain the relay, and
integrate information measured by the C60 into LED indicators 7” large color graphic HMI
DCS or SCADA monitoring systems. Convenient
COMTRADE and SOE viewers are an integral part 8 user
of the UR setup software included with every UR programmable
relay, to carry out postmortem event analysis to pushbuttons
ensure proper protection system operation.

EnerVista Launchpad
EnerVista Launchpad is a powerful software
package that provides users with all of the
setup and support tools needed for configuring 10 side screen
and maintaining GE Multilin products. The pushbuttons

6 GEGridSolutions.com
C60 Breaker Protection System

Typical Wiring
A
B
C

VA F5a
VA F5c

Voltage inputs
Open delta VB F6a
VT connection (ABC) VB F6c
TYPICAL CONFIGURATION VC F7a
The AC signal path is configurable
VC F7c

P1a VA F5a
Form-C

6G
Voltage and
I
P1b output P1 VA
current supervision V F5c
TC1 P1c
VB

Voltage inputs
P2a F6a
Form-C
I
P2b VB F6c
V output P2
Voltage supervision P2c VC F7a
TC2 P3a
Form-C
I
VC F7c
P3b output P3
V
P3c VX F8a
P4a VX F8c
Form-C
I
P4b output P4 IA5
V F1a
P4c
P5a Contact input P5a IA F1b

Contact input and output module


P5c Contact input P5c IA1 F1c
P6a Contact input P6a IB5 F2a
P6c Contact input P6c
( DC only )

IB

Current inputs
P5b Common P5b F2b
IB1 F2c
P7a Contact input P7a
Contact input P7c IC5 F3a
P7c
P8a Contact input P8a IC F3b
P8c Contact input P8c IC1
CT/VT module
F3c
P7b Common P7b 52
IG5 F4a
P8b Surge IG F4b
Connection as
H1a IG1 F4c
Form-C required
6G

I
H1b output H1
V VA M5a
H1c
VA M5c
H2a 52
Form-C
I
H2b VB
Voltage inputs

output H2 M6a
V
H2c VB M6c
H3a
Form-C
I
VC M7a
H3b Connection as
V output H3
H3c VC M7c required
H4a VX M8a
Form-C
I
H4b output H4 VX
V M8c
H4c
H5a Contact input H5a IA5 M1a
Contact input and output module

H5c Contact input H5c IA M1b


H6a Contact input H6a IA1 M1c
H6c Contact input H6c
IB5 M2a
H5b Common H5b
IB
Current inputs

M2b
H7a Contact input H7a
Contact input H7c IB1 M2c
H7c
H8a Contact input H8a IC5 M3a
H8c Contact input H8c IC M3b
H7b Common H7b
IC1
CT/VT module

M3c
H8b Surge IG5 M4a
B1b IG M4b
B1a Critical failure IG1 M4c
B2b
DC B3a
48 V DC output
B3b
B5b HI
Power supply

AC or DC B6b LO Control power


B6a
B8a Surge C60 C60 Computer
B8b Filter Breaker Protection 1 1 8
Fibre Tx1 100BaseFX System TXD 2 2 3 RXD
optic Port 1
T

Rx1
RXD 3 3 2 TXD
Tx2 100BaseFX 4 4 20
Rx2
Port 2
SGND 5 5 7 SGND
Tx3 100BaseFX Contacts shown
Shielded Port 3 6 6 6
Rx3 with no
twisted pairs
Ground at control power 7 7 4
D1a
UR RS485 8 8 5
D2a
device COM 2
D3a com 9 9 22
D4b RS232 (front)
D4a IRIG-B 9-pin 25-pin
Input
DB-9 connector
connector
Co-axial BNC
CPU

Computer
Module arrangement 834773A2.CDR

No. 10AWG X W V U T S R P N M L K J H G F D B
minimum Modules must be
Input/ Input/ Power grounded if terminal
CPU
output CT/VT output CT/VT supply is provided
Ground bus
(Rear view)

Copyright GE Multilin Inc. All rights reserved.

GEGridSolutions.com 7
Ordering
C60 - * ** - H * * - F ** - H ** - M ** - P ** - U ** - W ** For Full Sized Horizontal Mount
C60 - * ** - V F * - F ** - H ** - M ** # ** For Reduced Size Vertical Mount
Base Unit C60 Base Unit
CPU E RS485 + RS485 (IEC 61850 option not available)
J RS485 + multimode ST 100BaseFX
K RS485 + multimode ST Redundant 100BaseFX
N RS485 + 10/100BaseT
T RS485 + three multimode SFP LC 100BaseFX. Req FW v7xx or higher
U RS485 + two multimode SFP LC 100BaseFX + one SFP RJ45 100BaseT. Req FW v7xx or higher
V RS485 + three SFP RJ45 100BaseT. Req FW v7xx or higher
W RS485 + two 100BaseFx Eth, Multimode ST + one 10/100BaseT Eth, RJ-453
Software Options1 00 No Software Options
01 Ethernet Global Data
03 IEC 61850
04 Ethernet Global Data
14 2 x PMU
15 IEC 61850 + 2 x PMU
A0 CyberSentry UR Lvl 1. Req UR FW 7.xx or higher
B0 IEEE 1588. Req UR FW 7.xx or higher
C0 PRP
D0 IEEE 1588 + CyberSentry UR. Req UR FW 7.xx or higher
M2 IEC 61850 + 2 x PMU + 61850-90-5
Mount H Horizontal (19" rack) - Standard
A Horizontal (19" rack) - Harsh Chemical Environment Option
V Vertical (3/4 size) - Standard
B Vertical (3/4 size) - Harsh Chemical Environment Option
User Interface E 7” Graphical display, USB front port & programmable pushbuttons - Multi-Language (FW 7.6x or higher)
F Vertical Front Panel with English Display
I Enhanced German Front Panel
J Enhanced German Front Panel with User-Programmable Pushbuttons
K Enhanced English Front Panel
L Enhanced English Front Panel with User-Programmable Pushbuttons
M Enhanced French Front Panel
N Enhanced French Front Panel with User-Programmable Pushbuttons
Q Enhanced Russian Front Panel
T Enhanced Russian Front Panel with User-Programmable Pushbuttons
U Enhanced Chinese Front Panel
V Enhanced Chinese Front Panel with User-Programmable Pushbuttons
W Enhanced Turkish Front Panel
Y Enhanced Turkish Front Panel with User-Programmable Pushbuttons
H Enhanced Polish Front Panel3
O Enhanced Polish Front Panel with User-Programmable Pushbuttons3
Z Enhanced Japanese Front Panel3
X Enhanced Japanese Front Panel with User-Programmable Pushbuttons3
Power Supply2 H 125 / 250 V AC/DC
H RH 125/250 V AC/DC with redundant 125/250 V AC/DC power supply
L 24 - 48 V (DC only)
CT/VT DSP 8L 8L Standard 4CT/4VT w/ enhanced diagnostics
8M 8M Sensitive Ground 4CT/4VT w/ enhanced diagnostics
8N 8N Standard 8CT w/ enhanced diagnostics
8R 8R Sensitive Ground 8CT w/ enhanced diagnostics
IEC 61850 Process Bus4, 5 81 8 Port IEC 61850 Process Bus Module
85 -9-2LE & 61869 Process Bus, 2 x 1000BaseF
86 -9-2LE & 61869 Process Bus, 4 x 1000BaseF + 4 x 100BaseFx
87 -9-2LE & 61869 Process Bus, 4 x 100BaseFx
Digital I/O XX XX XX XX XX No module
4A 4A 4A 4A 4A 4 Solid State (No Monitoring) MOSFET Outputs
4C 4C 4C 4C 4C 4 Solid State (Current w/opt Voltage) MOSFET Outputs
4L 4L 4L 4L 4L 14 Form-A (No Monitoring) Latchable Outputs
67 67 67 67 67 8 Form-A (No Monitoring) Outputs
6C 6C 6C 6C 6C 8 Form-C Outputs
6D 6D 6D 6D 6D 16 Digital Inputs
6E 6E 6E 6E 6E 4 Form-C Outputs, 8 Digital Inputs
6F 6F 6F 6F 6F 8 Fast Form-C Outputs
6K 6K 6K 6K 6K 4 Form-C & 4 Fast Form-C Outputs
6L 6L 6L 6L 6L 2 Form-A (Current w/ opt Voltage) & 2 Form-C Outputs, 8 Digital Inputs
6M 6M 6M 6M 6M 2 Form-A (Current w/ opt Voltage) & 4 Form-C Outputs, 4 Digital Inputs
6N 6N 6N 6N 6N 4 Form-A (Current w/ opt Voltage) Outputs, 8 Digital Inputs
6P 6P 6P 6P 6P 6 Form-A (Current w/ opt Voltage) Outputs, 4 Digital Inputs
6R 6R 6R 6R 6R 2 Form-A (No Monitoring) & 2 Form-C Outputs, 8 Digital Inputs
6S 6S 6S 6S 6S 2 Form-A (No Monitoring) & 4 Form-C Outputs, 4 Digital Inputs
6T 6T 6T 6T 6T 4 Form-A (No Monitoring) Outputs, 8 Digital Inputs
6U 6U 6U 6U 6U 6 Form-A (No Monitoring) Outputs, 4 Digital Inputs
6V 6V 6V 6V 6V 2 Form-A (Cur w/ opt Volt) 1 Form-C Output, 2 Latching Outputs, 8 Digital Inputs
6W 6W 6W 6W 6W 30 Contact Inputs - Pin Terminals3
6X 6X 6X 6X 6X 18 Form-A (No Monitoring) Outputs - Pin Terminals3
Transducer I/O 5A 5A 5A 5A 5A 4 dcmA Inputs, 4 dcmA Outputs
5C 5C 5C 5C 5C 8 RTD Inputs
5D 5D 5D 5D 5D 4 RTD Inputs, 4 dcmA Outputs
5E 5E 5E 5E 5E 4 dcmA Inputs, 4 RTD Inputs
5F 5F 5F 5F 5F 8 dcmA Inputs
Inter-Relay Communications 2B IEEE C37.94, 1300nm, singlemode, ELED, 2 Channel
2I Channel 1 - IEEE C37.94, 820nm, multimode fiber, 64/128 kbps;
Channel 2 - 1300 nm, singlemode, LASER
2J Channel 1 - IEEE C37.94, 820nm, multimode fiber, 64/128 kbps;
Channel 2 - 1550 nm, singlemode, LASER
7A 820 nm, multimode, LED, 1 Channel
7B 1300 nm, multimode, LED, 1 Channel
7C 1300 nm, singlemode, ELED, 1 Channel
7H 820 nm, multimode, LED, 2 Channels
7I 1300 nm, multimode, LED, 2 Channels
7J 1300 nm, singlemode, ELED, 2 Channels
7S G.703, 2 Channels
7W RS422, 2 Channels
77 IEEE C37.94, 820 nm, multimode, LED, 2 Channel
Ordering Notes:
1. To view all the options available for C60, please visit GE’s On-Line Store at
http://store.gedigitalenergy.com/viewprod.asp?model=C60 GEGridSolutions.com
2. Redundant power supply only available in horizontal unit. If redundant is chosen, must be same
type. Maximum 2 per chassis IEC is a registered trademark of Commission Electrotechnique Internationale. IEEE is a registered
3. Option available soon trademark of the Institute of Electrical Electronics Engineers, Inc. Modbus is a registered trademark of
4. Process bus module requires empty slots next to it. Schneider Automation. NERC is a registered trademark of North American Electric Reliability Council.
5. Conventional DSP and Process Bus modules cannot run simultaneously NIST is a registered trademark of the National Institute of Standards and Technology.
GE, the GE monogram, Multilin, FlexLogic, EnerVista and CyberSentry are trademarks of General Electric
Company. GE reserves the right to make changes to specifications of products described at any time
without notice and without obligation to notify any person of such changes.
Copyright 2020, General Electric Company. All Rights Reserved. GEA-12654J(EN)