HFP AP-AS Features

Analogue Addressable
1-2 Loop Control Panels  16 zonal LED indicators
 2 programmable sounder circuits
 5 programmable inputs
 3 programmable relays
 3A power supply
 Large graphic display
 Real time clock
 Expandable from 1 to 2 loops*
 Certified to EN54-2/ EN54-4
 Up to 512 additional programmable I/O
via HFP I/O modules *
 Powerful, network wide cause and
effects *
 Sensitivity adjustment and Drift
Compensation
 Can be networked with HFP control
panels *
 Compatible with HFP and HFP AP-CRL
repeaters *
 Stores 500 last events in event log
 Dial up modem connection available
 Compact, stylish enclosure
 Installer friendly, removable equipment
chassis
 Different language and character set
variants available
 Fully EN54-2 and EN54-4 compliant
improved front loading Printer option * **

*These items not available on HFP ASL panel


** Can be fitted to M3 size enclosure only

Product Overview
The HFP AP-AS is a powerful and versatile Single or two Loop Analogue
Addressable Fire Control Panel.

HFP AP-AS supports Hochiki ESP loop drivers, which are all capable of providing up to 400 milliamps of
loop current for the most demanding applications.

An integral 3 Amp power supply and temperature compensated battery charger provides ample power for the two, 1 Amp rated standard
sounder outputs, loop powered sounders and other devices.

HFP AP-AS is also available as a HFP AP-ASL version offering a very cost effective solution for smaller standalone installations requiring
only one detection loop.

The HFP AP-ASL version does not support the following: Second loop, Printer output, Networking and connection of I/O boards or the
HFP AP-CRL repeater.

Product Number Description Extras


HFP AP-1ASLS 1Lp Panel c/w 16 zones, non networkable, surface Keyswitch

Flush Mounting, Large Enclosure, Network Card, Printer,


HFP AP-1ASS 1Lp Panel c/w 16 zones, surface
Keyswitch.

Flush Mounting, Large Enclosure, Network Card, Printer,


HFP AP-2ASS 2Lp Panel c/w 16 zones, surface
Keyswitch

The Manufacturer reserves the right to amend specification without prior notice.
For further information visit www.hochikieurope.com>
Analogue Photoelectric Smoke
Sensor
ALN-E(HFP)
Features
 Removable, High Performance chamber
 Twin LEDs allow 360 viewing – green when
polling, turn red in fire
 Locking mechanism (sensor to base)
 Variable sensitivity
 Electronically addressed
 Pulsing/non-pulsing controlled from panel*
 Approved by LPCB & VdS
 SIL Level 2 approved variants available

Description
Model ALN-E(HFP) is a Photoelectric Smoke Sensor, which is fully compatible with
Hochiki's ESP Analogue Addressable Protocol.
The ALN-E(HFP) incorporates Hochiki's newest High Performance Chamber Technology
removing the need to use Ionisation Smoke Sensors in the majority of applications.
This also allows the sensor threshold level to be increased, thereby improving the signal
to noise ratio and reducing susceptibility to false alarms.
The ALN-E(HFP) smoke chamber is easily removed or replaced for cleaning and utilises
a unique improved baffle design which allows smoke to enter the chamber whilst
keeping out ambient light.

Specification
Ordering Code ALN-E(HFP)
Operating Voltage 17 – 41 V d.c.
Low Power Mode (typ) 120 A
Quiescent Current (typ) 400 A
Alarm Current (controlled by CIE) 9.1 mA (excluding remote indicator)
Transmission Method Digital Communications Using ESP
Operating Temperature Range -10 °C to + 50 °C
Operating Humidity 95% RH - Non Condensing (at 40 °C)
Storage Temperature Range -30 °C to +60 °C
Storage Humidity <80% RH at 60 °C
Colour / Case Material White / ABS
Weight (g) 95
Diameter (mm) / Height (mm) 100 / 45
YBN-R/3, YBO-R/SCI, YBO-BS, YBO-BSB, YBN-
Compatible Bases
R/3(SCI)
Base Fixing Centres (mm) 48 ~ 74
Approvals LPCB & VdS
*Control Panel compatibility required

Hochiki Europe (UK) Ltd. reserves the right to alter the specification of its products from time to time without notice. Although
every effort has been made to ensure the accuracy of the information contained in this document it is not warranted or
represented by Hochiki Europe (UK) Ltd. to be a complete and up-to-date description.
Technical
Construction 1.2mm mild sheet steel
IP Rating IP30
Finish Epoxy powder coated
Colour - lid & box BS 00 A 05 grey - fine texture
Colour - controls plate & labels RAL 7047 light grey - satin
Weight 6kg (standard panel)
Display 8 lines of 40 characters graphic LCD
Mains voltage supply 110 or 230V AC 50 or 60 Hz. (Specify when ordering, default is 230V)
Mains supply fuse 1.6A 250V
Power supply DC rating 24V 3 Amps
Aux 24V supply Fused at 500 milliamps
Maximum Battery size 9Ah 12V (2 per panel) (non-networked)
Fault contact rating 30V DC1 Amp
Fire contact rating 30V DC1 Amp
Alarm contact rating 30V DC1 Amp
Sounder output rating Fused at 1 Amp each
Detection loop 400 milliamp output
Dimensions (mm) 385 x 310 x 90

The Manufacturer reserves the right to amend specification without prior notice.
For further information visit www.hochikieurope.com>
Multi-Heat Sensor
ATJ-E(HFP)
Features

 User selectable modes


 Incorporates Fixed Temperature and Rate
Of Rise Heat elements
 Twin LEDs allow 360 viewing – green
when polling, turn red in fire
 Pulsing/non-pulsing controlled from
panel*
 Electronically addressed
 LPCB & VdS approved to Classes A1, B &
C
 SIL Level 2 approved variants available

Description
Model ATJ-E(HFP) is a Multi-Heat Sensor, which is fully compatible with Hochiki’s ESP
Analogue Addressable Protocol.
The ATJ-E(HFP) incorporates a Variable Temperature heat element and a Rate Of Rise
heat element, both of which are controlled from the Control Panel, allowing either
thermal element or both elements simultaneously to be active in making the fire
decision. The sensor polling LEDs can also be controlled via the Control Panel
(pulsing/non-pulsing)*.

Specification
Ordering Code ATJ-E(HFP)
Operating Voltage 17 – 41 V d.c.
Low Power Mode (typ) 110 A
Quiescent Current (typ) 350 A
Alarm Current (controlled by CIE) 9.1 mA (excluding remote indicator)
Transmission Method Digital Communications Using ESP
Operating Temperature Range -10 °C to +50 °C
Operating Humidity 95% RH - Non Condensing (at 40 C)
Storage Temperature Range -30 °C to +60 °C
Storage Humidity <80% RH at 70 °C
Colour / Case Material White / Polycarbonate
Weight (g) 90
Diameter (mm) / Height (mm) 100 / 45
Compatible Bases YBN-R/3, YBO-R/SCI, YBO-BS, YBO-BSB,
YBN-R/3(SCI)
Base Fixing Centres (mm) 48 ~ 74
Approvals LPCB & VdS approved to Classes A1, B & C
*Control Panel compatibility required

Hochiki Europe (UK) Ltd. reserves the right to alter the specification of its products from time to time without notice. Although
every effort has been made to ensure the accuracy of the information contained in this document it is not warranted or
represented by Hochiki Europe (UK) Ltd. to be a complete and up-to-date description.
Analogue Multi-Sensor
ACC-E(HFP)
Features
 User selectable modes
 Incorporates Optical & Heat elements
 Removable, High Performance Chamber
 Twin LEDs allow 360 viewing – green
when polling, turn red in fire
 Pulsing/non-pulsing controlled from
panel*
 Variable sensitivity
 Electronically Addressed
 LPCB & VdS approved to classes A1 & C
 SIL Level 2 approved variants available
 Available in white

Description
Model ACC-E(HFP) is a Multi-Sensor, which is fully compatible with Hochiki’s ESP
Analogue Addressable Protocol, and incorporates a thermal element and High
Performance photoelectric smoke chamber.
The ACC-E(HFP) has three modes, which are controlled from the Control Panel,
allowing either the optical element or thermal element or both elements to be active
in making the fire decision. The sensor polling LEDs can be controlled via the Control
Panel (pulsing/non-pulsing). The ACC-E(HFP) smoke chamber can easily be removed
or replaced for easy maintenance.

Specification
Ordering Code ACC-E(HFP)
Operating Voltage 17 – 41 V d.c.
Low Power Mode (typ) 120 A
Quiescent Current (typ) 400 A
Alarm Current (controlled by CIE) 9.1 mA (excluding remote indicator)
Transmission Method Digital Communications Using ESP
Operating Temperature Range -10 °C to + 50 °C
Operating Humidity 95%RH - Non Condensing (at 40 °C)
Storage Temperature Range -30 °C to +60 °C
Storage Humidity <80% RH at 60 °C
Colour / Case Material White / Polycarbonate
Weight (g) 95
Diameter (mm) / Height (mm) 100 / 45
Compatible Bases YBN-R/3, YBO-R/SCI, YBO-BS, YBO-BSB,
YBN-R/3(SCI)
Base Fixing Centres (mm) 48 ~ 74
Approvals LPCB & VdS approved to classes A1 & C
*Control Panel compatibility required

Hochiki Europe (UK) Ltd. reserves the right to alter the specification of its products from time to time without notice. Although
every effort has been made to ensure the accuracy of the information contained in this document it is not warranted or
represented by Hochiki Europe (UK) Ltd. to be a complete and up-to-date description.
YBN-R/3
ANALOGUE COMMON MOUNTING BASE

Features

Electronics free

Stainless steel contacts

Takes 2.5mm2 cables

Slim profile - only 8 mm

Rugged wiring contacts

Facility for remote indicator

Quick connection via square cable clamps

Also available in white.

Description
Model YBN-R/3 is a Common Mounting Base, which is fully compatible with
Hochiki’s ESP range of sensors. It is supplied with square cable clamps for
secure and reliable cable termination and is also capable of driving a remote
LED if required.

Specification

Ordering Code YBN-R/3 YBN-R/3(WHT)

Operating Temperature Range -10 °C to + 50 °C

Storage Temperature Range -30 °C to + 70 °C

Maximum Humidity 95% RH - Non Condensing (at 40 °C)

Colour / Material Ivory or White / ABS

Weight (g) / Diameter (mm) / Height (mm) 50 / 100 / 8

Fixing Centres (mm) 48 ~ 74

Maximum Wire Thickness 2.5 mm2 Cables

Operating Humidity RH 95% non-condensing

Operating Temperature -20°C to +40°C

Ingress Protection Rating IP20

Ordering Information
Product Part Number
SCI Sensor Mounting Base (Ivory) YBV-R/4
SCI Sensor Mounting Base (White) YBV-R/4(WHT)

For further information visit www.hochikieurope.com/esp


Hochiki Europe (UK) Ltd. Reserves the right to alter the specification of its products from time to time without notice.
Although every effort has been made to ensure the accuracy of the information contained in this document it is not
ISS1NOV18 warranted or represented by Hochiki Europe (UK) Ltd. To be a complete and up-to-date description.
Your Safety, Our Technology

HCP-E(SCI)
Analogue Addressable Manual Call Point with Short-Circuit Isolator

Features
 Fast response
 Integral short-circuit isolator
 Bi-coloured status LED
 Non-frangible element fitted as standard (conforms to EN54)
 Addressed with TCH-B200 Hand Held Programmer
 Flush or surface mounted (with separate back box)
 LPCB Approved to EN54

Description
Model HCP-E(SCI) is a Manual Call Point with integral short-circuit isolator, which is fully compatible with Hochiki’s ESP analogue addressable protocol.
The unit incorporates a bi-coloured LED, which can be selected as pulsing/non-pulsing*1 for communications polling and is continuously lit when the device is
operated – in these two states the LED will show red. The LED will show amber when a short-circuit is present but will switch to red if the unit is activated. A built in
test function initiated by the control panel ensures the integrity of the device at all times and the device can be tested by insertion of a test key in the underside of
the unit. Two terminal blocks are provided for easy connection to the loop wiring.

The unit is addressed using the TCH-B200 Hand Held Programmer for quick and reliable addressing. The unit is surface mounted using the included back box.
An optional glass element is also available.

Specification

Operating Voltage 17 – 41 VDC

Low Power Mode (typ) 180 µA (max), 100 µA (typ)

Quiescent Current 350 µA (max), 250 µA (typ)

Alarm Current 10.0 mA (max), 5 mA (typ)

Resistance in positive 100 mΩ when closed (max), 100 kΩ when open (min)

Short-circuit threshold (typ) 430 Ω

Transmission Method Digital Communication Using ESP

Operating Temperature Range -10 °C to + 50 °C

Storage Temperature Range -30 °C to + 70 °C

Maximum Humidity 95% RH - Non Condensing (at 40 °C)

Ingress Protection Rating IP24

Colour / Case Material Red / Modified Polyphenylene Oxide

(Flush Unit) 110 / W 89 x H 93 x D 27.5


Weight (g) / Dimensions (mm)
(With Surface Mount Back Box) 161 / W 89 x H 93 x D 59.5

*1 Fire alarm control panel compatibility is required for this feature.

Ordering Codes
Product Part Number

Analogue Addressable Manual Call Point with Short-Circuit Isolator HCP-E(SCI)


Flush or surface mounted (with separate back box) SR Back Box

For further information visit www.hochikieurope.com/esp


Hochiki Europe (UK) Ltd. reserves the right to alter the specification of its products from time to time without notice.
Although every effort has been made to ensure the accuracy of the information contained in this document it is not
ISS1/APR19 warranted or represented by Hochiki Europe (UK) Ltd. to be a complete and up-to-date description.
ESPintelligent

CHQ-WSB2
Analogue Wall Sounder Beacon

Features

Auto-Shutdown feature prevents noise pollution*1  or 1Hz flash frequency*1
0.5

Sounder and Beacon can operated independently*1 
High Intensity LED technology

Fits Hochiki Standard or Isolator Base 
Fits Hochiki Standard or Isolator Base
 User-Selectable Tones (all tones EN54-3 approved)
51  Rated Beacon to EN54-23
O’

Single Loop Address - addressed via the TCH-B200 
Available with Red or White LEDs
Hand Held Programmer 
Available with Red or White case

Variable Sound Output 90 ~ 102 dB(A) (±2 dB(A)) 
Weatherproof Kit available
output at 1 metre  Level 2 approved variant available
SIL

Description
Model CHQ-WSB2 is an addressable loop powered Wall Sounder Beacon Also incorporates an auto shutdown mode*1 which allows the user to set a fixed
innovatively designed to provide a range of tones and volumes with a time within which the sounder will operate, before automatically silencing
maximum output of up to 102dB(A) (±2dB(A)) with low current consumption. itself, ideal for minimising noise pollution.
The unit features an integral beacon within the horn utilising high intensity LED
technology and is designed to fit to the Standard Base (CHQ-WPK) & YBOR/
SCI(WHT)) or the Isolator Base (YBO-R/SCI(RED) & YBO-R/SCI(WHT)). The
sounder is IP rated to IP21 for internal use but it can be made weatherproof by
utilising the WS2-WPK Weatherproof Kit, which consists of a specialised back
box and gasket set.

Specification

Operating Voltage 17 ~ 41 Vdc

150 μA (with YBO-R/3(RED) & YBO-R/3(WHT))


Quiescent Current (typ)
200 μA (with YBO-R/SCI(RED) & YBO-R/SCI(WHT))

Sounding Current (typ) 2 mA (90 dB(A) (±2 dB(A)) @ 1 m) ~ 8 mA (102 dB(A) (±2 dB(A)) @ 1 m)

Additional Current when Beacon active + 7 mA

Sound Output (at 1 metre) 90 ~ 102 dB(A) (±2 dB(A)) @ 24 Vdc or above

Number of Tones 51

Tone Frequency Range 300 Hz ~ 2850 Hz

Operating Temperature Range -10 °C to +50 °C

Storage Temperature Range -30 °C to +70 °C

Maximum Humidity 95% RH - Non Condensing (at 40 °C)

Colour/Case Material Red or White / PC ABS

Lens Material Translucent PC

Ingress Protection Rating IP21 (IP65 with WS2-WPK)

Weight (g)/Dimensions (mm) 164 / H112 x W112 x D67

Base Fixing Centres (mm) 48 ~ 74

For further information visit www.hochikieurope.com/esp


Note: Although the TCH-B100 Hand Held Programmer will allow addresses between 128 and 255 to be programmed into the YBO-BSB2, addresses 1 to 127
ONLY should be used.

How to choose your Hochiki VAD


Our VAD ratings comprise three parts, X-Y-Z


Where X denotes the category, either “O” for Open, “W” for Wall or “C” for ceiling

Where Y denotes the maximum mounting height (m)

Where Z is the width and length (m) of the coverage floor area

For example C-3-5 means the VAD is in the Ceiling category, can be mounted at a maximum ceiling height of 3 metres and produces a 5 metre diameter
coverage.

What type of VAD? Which case colour? Which LED colour? Product EN54-23 Ratings*3
White LEDs YBO-BSB2/WL
Ivory case
Red LEDs YBO-BSB2/RL
Base Sounder
Beacon
White LEDs YBO-BSB2(WHT)/WL
White case
Red LEDs YBO-BSB2(WHT)/RL ‘O’ Rated

White LEDs CHQ-WSB2/WL


Red case
Red LEDs CHQ-WSB2/RL
Wall Sounder
Beacon
White LEDs CHQ-WSB2(WHT)/WL
White case
Red LEDs CHQ-WSB2(WHT)/RL

0 1 2
Red LEDs CHQ-CB/RL C-3-1.5 C-3-8.6 C-3-10
Ivory Case CHQ-CB/WL C-3-6.5 C-3-7.9 C-3-10
White LEDs
CHQ-CB/WL-15 ‘O’ C-3-11.4 C-3-15.1

Red LEDs CHQ-CB(WHT)/RL C-3-1.5 C-3-8.6 C-3-10


Ceiling Beacon White Case CHQ-CB(WHT)/WL C-3-6.5 C-3-7.9 C-3-10
White LEDs
CHQ-CB(WHT)/WL-15 ‘O’ C-3-11.4 C-3-15.1

Red LEDs CHQ-CB(RED)/RL C-3-1.5 C-3-8.6 C-3-10


Red Case CHQ-CB(RED)/WL C-3-6.5 C-3-7.9 C-3-10
White LEDs
CHQ-CB(RED)/WL-15 ‘O’ C-3-11.4 C-3-15.1

Red LEDs CHQ-WB/RL ‘O’ W-2.4-5 W-2.4-5.5


Ivory Case
White LEDs CHQ-WB/WL W-2.4-5 W-2.4-5.5 W-2.4-7

Red LEDs CHQ-WB(WHT)/RL ‘O’ W-2.4-5 W-2.4-5.5


Wall Beacon White Case
White LEDs CHQ-WB(WHT)/WL W-2.4-5 W-2.4-5.5 W-2.4-7

Red LEDs CHQ-WB(RED)/RL ‘O’ W-2.4-5 W-2.4-5.5


Red Case
White LEDs CHQ-WB(RED)/WL W-2.4-5 W-2.4-5.5 W-2.4-7

For CHQ-CB/WL & RL Default setting is C-3-7.5, for CHQ-CB/WL-15 Default setting is C-3-15

*3
All ratings are all based on 0.5Hz frequency.

*4
Full ‘O’ rating data available in our Application Notes (see below).

For further information visit www.hochikieurope.com/esp


Current when Beacon Active

CHQ-CB/WL&RL & CHQ-WB/WL & RL mA 6 12 17

CHQ-CB/WL-15 mA 6 17 38

CHQ-WSB2/WL&RL mA (Beacon Only) 7 (one setting only)

YBO-BSB2/WL&RL mA (Beacon Only) 7 (one setting only)

Note: Our VAD product codes feature “WL” which means white LEDs and “RL” which means red LEDs.

Ceiling Beacon and Wall Beacon Application Note AP131

For details of ‘O’ Rating data for Wall Sounder Beacon See Application Note AP132

Base Sounder Beacon Application Note AP133

All Application Notes are available to download from our web site.

Ordering Codes

Product Part Number

RED Case
Wall Sounder Beacon - Red Case, White LEDS CHQ-WSB2/WL
Wall Sounder Beacon - Red Case, Red LEDS CHQ-WSB2/RL

White Case
Wall Sounder Beacon - White Case, White LEDS CHQ-WSB2(WHT)/WL
Wall Sounder Beacon - White Case, Red LEDS CHQ-WSB2(WHT)/RL

For further information visit www.hochikieurope.com/esp


Hochiki Europe (UK) Ltd. reserves the right to alter the specification of its products from time to time without notice.
Although every effort has been made to ensure the accuracy of the information contained in this document it is not
warranted or represented by Hochiki Europe (UK) Ltd. to be a complete and up-to-date description.
YBO-R/3
Intelligent Wall Sounder Mounting Base

Features

Electronics free

Stainless steel contacts

Takes 2.5 mm2 cables

Slim profile - only 13 mm

Rugged wiring contacts

Quick Connection via square cable clamps

Also available in white.

Description
Model YBO-R/3 is a Sounder Mounting Base, which is fully compatible with It is supplied with square cable clamps for secure and reliable cable
Hochiki’s ESP range of sensors and designed specifically for the Hochiki range termination.
of wall sounders, the CHQ-WS2 Wall Sounder and the CHQ-WSB2 Wall Sounder
Beacon. 

Specification
Operating Temperature Range -10 °C to +50 °C

Storage Temperature Range -30 °C to + 70 °C

Maximum Humidity 95% RH - Non Condensing (at 40 °C)

Colour / Material Red or White / ABS

Weight (g) / Diameter (mm) / Height (mm) 60 / 100 / 13

Beam Head ± 0.3 °


Fixing Centres (mm)
Reflector ± 2 ° (static not auto-aligning)

Alarm Sensitivity Levels 48 ~ 74

Maximum Wire Thickness 2.5 mm2 Cables

Ordering Codes
Product Part Number

Wall Sounder Mounting Base (Red) YBO-R/3(RED)

Wall Sounder Mounting Base (White) YBO-R/3(WHT)

For further information visit www.hochikieurope.com/esp


Hochiki Europe (UK) Ltd. reserves the right to alter the specification of its products from time to time without notice. Although every effort has been
made to ensure the accuracy of the information contained in this document it is not warranted or represented by Hochiki Europe (UK) Ltd. to be a
ISS2AUG19 complete and up-to-date description. Check online for current version at store.hochikieurope.com
CHQ-SIM
SINGLE INPUT MODULE

Features

Includes a single monitored input

Small design for simple provision of a monitored input onto an ESP loop

Flying leads for easy installation

Addressed with TCH-200 Hand Held Programmer

Approved by LPCB & VdS.

Description
The CHQ-SIM has been designed to allow a single monitored input to be connected to the ESP loop. This provides a compact, low-cost option where the installation
of the larger CHQ ‘Smart-Fix’ Range of Modules might be difficult.

The CHQ-SIM features flying leads as well as a wiring terminal block for loop connection, making installation quick and easy. The unit is addressed with the
TCH-B200 Hand Held Programmer utilising the onboard programming connector and a PL-3 lead.

Specification

Ordering Codes CHQ-SIM

Operating voltage 17 – 41 VDC

Quiescent Current / Alarm Current 150 μA (at 41 V) max

Open Circuit >100 kΩ

Normal State 10 kΩ (EOL resistor provided)


Input Ratings
Input Activation 470 Ω (EOL resistor provided)

Short Circuit 50 Ω

Operating temperature range -10 °C to + 50 °C

Storage temperature range -20 °C to + 60 °C

Maximum humidity 95% RH - Non condensing (at 40 °C)

Colour / Case material Ivory / ACS

Weight (g) / Length / Width / Depth (mm) 25 / 65 / 42 / 15

Approvals

For further information visit www.hochikieurope.com/esp


Hochiki Europe (UK) Ltd. reserves the right to alter the specification of its products from time to time without notice.
Although every effort has been made to ensure the accuracy of the information contained in this document it is not
ISS1SEP19 warranted or represented by Hochiki Europe (UK) Ltd. to be a complete and up-to-date description.
Single Output Module
CHQ-SOM
Features
 Includes a single monitored output
 Small design for simple provision of
a monitored output onto an ESP
loop
 Flying leads for easy installation
 Addressed with TCH-B100 Hand
Held Programmer
 Approved by LPCB

Description
The CHQ-SOM has been designed to allow a single relay output to be connected to the ESP loop.
The unit incorporates a volt-free relay contact that can be configured as either N/O or N/C, the
relay contact is rated to 30 V dc (max), 1 A (resistive load). The CHQ-SOM features three colour-
coded flying leads, the unit also features a wiring terminal block for loop connection.
NOTE: The state of the relay contacts will be indeterminate until the unit is powered.
To maintain LPCB approval the device must be mounted in an SMB-1 enclosure (or an equivalent
enclosure made from polycarbonate or a similar material which is impact resistant as per EN54-
18:2005 Clause 5.9) in conjunction with the SMB-ADAPTOR plate, using two M3 screws or two
M3 nuts and bolts.
NOTE: If the PCB is removed from the protective outer casing the EN54 approval is voided.

Specification
Ordering code CHQ-SOM*
Operating voltage 17 – 41 V dc
Quiescent Current / Alarm Current 150 μA (at 41 V) max
Max voltage 30 V dc
Output Ratings
Max current 1 A (resistive load)
Operating temperature range -10 °C to + 50 °C
Storage temperature range -20 °C to + 60 °C
Maximum humidity 95% RH - Non condensing (at 40 C)
Colour / Case material Ivory / ACS
Weight (g) / Length / Width / Depth (mm) 25 / 65 / 42 / 15
Approval LPCB

*Fire alarm control panel compatibility is required for this product

Hochiki Europe (UK) Ltd. reserves the right to alter the specification of its products from time to time without notice. Although
every effort has been made to ensure the accuracy of the information contained in this document it is not warranted or
represented by Hochiki Europe (UK) Ltd. to be a complete and up-to-date description.

You might also like