Oil Analysi s Report

Location : PT DSSP POWER KENDARI Fluid Manufacturer : TOTAL


Sampling Date : 07 Desember, 2021 Fluid Type : Preslia VG 32
Subject : Outlet Purifier (unit 2) Measure.Equipment : FCU1310-4-U-AS-1
Code sample : LAB OIL-0003 Type Measurement : Sampling

NO PARAMETER UNIT RESULT REQUIREMENT


1 WATER CONTENT 1 %sat 85.51% <30%
2 SOLID PARTICLE (Size particles)
>4 µm Particle/100ml 25.000 (SAE 5A)
>6 µm Particle/100ml 38.900 (SAE 7B)
>14 µm Particle/100ml 27.700 (SAE 9C)
>21 µm Particle/100ml 19.600 (SAE 11D)
ISO CODE 4406: 1999 2 15/15/15 18/15/12
2
NAS 1638 4 7
3 Temperature °C 27.47 -

4 MPC (dE) 3 Index - Not Available < 15


2
5 Viscosity 40 ℃ mm /s

Evaluation Code
No action is required
warning
Action is required

Conclusion :
1 need dewatering treatment. Water saturation > 50%. It means Oil and water blend (emulsified water)
2 continous filtration.
3 Varnish removal is needed.
APPENDIX

RECORD ANALYSIS

1. Data Visual :

Export data :

Date Time ISO 4 ISO 6 ISO 14 SAE A SAE B SAE C SAE D SatLevel, % Temp, °C

07/12/2021 11:11 15 15 15 5 7 9 11 84,9 29,55

07/12/2021 11:12 21 21 20 11 12 14 14 83,88 28,27

07/12/2021 11:12 15 15 15 5 7 9 11 85,51 27,47

Analyst by Approval by

( Fitria Nur Salima ) ( Agus Cahyono )