2. Determine the steam leak rate of the new steam traps that
are being purchased per the following leak rate standards:
a. PTC-39
b. ISO 7841
6. Expand the tube/pipe diameter after the discharge connec- 15. Develop and maintain installation standards for all applica-
tion of the steam trap. For example, a 1 in. (connection) steam tions.
trap discharge tubing/piping should be increased to 1.25 in or
1.5 in. 16. Codes:
7. Steam traps with a connection size of 1 in. or smaller should a. Material test reports on all components (steam
be connected to the tubing or piping with universal mounts. traps, connection devices, etc.)
The universal mount provides the ability to connect the steam
b. B31.1 Piping code
trap to the application with two bolts, thus dramatically reduc-
ing the time for installation of a steam trap.
12. Locate the steam trap below the lowest condensate dis- Follow us
charge point of the equipment.