Reporte de Simulacion Alt2
Reporte de Simulacion Alt2
PVsyst TRIAL
Project: PV_Renovables_Alt2
Variant: Simulacion1 Alt2_simulacion 2
No 3D scene defined, no shadings
System power: 17.50 MWp
El Cruce de La Loma - Colombia
PVsyst TRIAL
PVsyst TRIAL
PVsyst V7.2.8
VC0, Simulation date:
04/12/21 15:21
with v7.2.8
Project summary
Geographical Site Situation Project settings
El Cruce de La Loma Latitude 9.60 °N Albedo 0.20
Colombia Longitude -73.63 °W
Altitude 43 m
PVsyst TRIAL
Time zone UTC-5
Meteo data
El Cruce de La Loma
NASA-SSE satellite data 1983-2005 - Sintético
System summary
Grid-Connected System No 3D scene defined, no shadings
System information
PVsyst TRIAL
PV Array Inverters
Nb. of modules 37632 units Nb. of units 3 units
Pnom total 17.50 MWp Pnom total 15.00 MWac
Pnom ratio 1.167
Results summary
Produced Energy 2942 MWh/year Specific production 168 kWh/kWp/year Perf. Ratio PR 8.12 %
Table of contents
Project and results summary 2
General parameters, PV Array Characteristics, System losses 3
Main results 4
Loss diagram 5
PVsyst TRIAL
Special graphs 6
PVsyst TRIAL
04/12/21 PVsyst Evaluation mode Page 2/6
Project: PV_Renovables_Alt2
Variant: Simulacion1 Alt2_simulacion 2
PVsyst V7.2.8
VC0, Simulation date:
04/12/21 15:21
with v7.2.8
General parameters
Grid-Connected System No 3D scene defined, no shadings
PV Field Orientation
Orientation Sheds configuration Models used
PVsyst TRIAL
Fixed plane No 3D scene defined Transposition Perez
Tilt/Azimuth 10 / 0 ° Diffuse Perez, Meteonorm
Circumsolar separate
PV Array Characteristics
PV module Inverter
Manufacturer Generic Manufacturer Generic
Model Q.Peak-Duo-XL-G9.2-465 Model Sinacon PV5000
(Custom parameters definition) (Original PVsyst database)
Unit Nom. Power 465 Wp Unit Nom. Power 5000 kWac
Number of PV modules 37632 units Number of inverters 6 * MPPT 50% 3 units
PVsyst TRIAL
Nominal (STC)
Modules
At operating cond. (50°C)
Pmpp
U mpp
I mpp
17.50 MWp
1344 Strings x 28 In series
15.99 MWp
1066 V
14999 A
Total power
Operating voltage
Pnom ratio (DC:AC)
15000
1006-1500
1.17
kWac
V
Array losses
PVsyst TRIAL
Thermal Loss factor DC wiring losses Module Quality Loss
Module temperature according to irradiance Global array res. 1.2 mΩ Loss Fraction 1.5 %
Uc (const) 20.0 W/m²K Loss Fraction 1.5 % at STC
Uv (wind) 0.0 W/m²K/m/s
PVsyst TRIAL
04/12/21 PVsyst Evaluation mode Page 3/6
Project: PV_Renovables_Alt2
Variant: Simulacion1 Alt2_simulacion 2
PVsyst V7.2.8
VC0, Simulation date:
04/12/21 15:21
with v7.2.8
Main results
System Production
Produced Energy 2942 MWh/year Specific production 168 kWh/kWp/year
Performance Ratio PR 8.12 %
PVsyst TRIAL
Normalized productions (per installed kWp) Performance Ratio PR
PVsyst TRIAL
January
GlobHor
kWh/m²
178.9
DiffHor
kWh/m²
44.02
Balances and main results
T_Amb
°C
25.51
GlobInc
kWh/m²
197.5
GlobEff
kWh/m²
194.1
EArray
MWh
2879
E_Grid
MWh
202.4
PR
ratio
0.059
February 163.5 48.44 26.88 174.7 171.5 2529 139.1 0.045
March 186.0 62.00 27.64 190.6 186.8 2746 115.2 0.035
April 170.4 67.20 26.10 168.0 164.0 2449 217.3 0.074
May 167.4 67.89 25.39 159.5 155.4 2348 309.9 0.111
June 166.5 62.40 25.34 156.2 151.9 2301 249.6 0.091
July 182.0 62.62 25.45 171.5 166.9 2522 245.6 0.082
August 179.5 66.03 25.51 174.3 170.0 2554 261.2 0.086
PVsyst TRIAL
September 163.2 65.10 24.90 164.4 160.7 2382 287.5 0.100
October 156.9 62.31 24.53 163.6 160.1 2407 327.3 0.114
November 152.1 51.90 24.46 165.5 161.8 2437 313.4 0.108
December 164.9 45.88 24.43 183.2 179.8 2690 273.1 0.085
Year 2031.2 705.79 25.50 2069.0 2023.0 30244 2941.5 0.081
Legends
GlobHor Global horizontal irradiation EArray Effective energy at the output of the array
DiffHor Horizontal diffuse irradiation E_Grid Energy injected into grid
T_Amb Ambient Temperature PR Performance Ratio
GlobInc Global incident in coll. plane
GlobEff Effective Global, corr. for IAM and shadings
PVsyst TRIAL
04/12/21 PVsyst Evaluation mode Page 4/6
Project: PV_Renovables_Alt2
Variant: Simulacion1 Alt2_simulacion 2
PVsyst V7.2.8
VC0, Simulation date:
04/12/21 15:21
with v7.2.8
Loss diagram
2031 kWh/m² Global horizontal irradiation
+1.9% Global incident in coll. plane
PVsyst TRIAL
-2.22% IAM factor on global
PVsyst TRIAL
30328 MWh Array virtual energy at MPP
PVsyst TRIAL
0.00% Inverter Loss over nominal inv. voltage
-0.05% Inverter Loss due to power threshold
-2.76% Inverter Loss due to voltage threshold
-0.07% Night consumption
2942 MWh Available Energy at Inverter Output
2942 MWh Energy injected into grid
PVsyst TRIAL
04/12/21 PVsyst Evaluation mode Page 5/6
Project: PV_Renovables_Alt2
Variant: Simulacion1 Alt2_simulacion 2
PVsyst V7.2.8
VC0, Simulation date:
04/12/21 15:21
with v7.2.8
Special graphs
Diagrama entrada/salida diaria
PVsyst TRIAL
PVsyst TRIAL
Distribución de potencia de salida del sistema
PVsyst TRIAL
PVsyst TRIAL
04/12/21 PVsyst Evaluation mode Page 6/6