TABLE OF CONTENTS
1. INTRODUCTION ................................................................................................................................. 3
1.1 Objective ......................................................................................................................................... 3
1.2 Scope ............................................................................................................................................... 3
1.3 Definition ......................................................................................................................................... 3
2. REFERENCE ........................................................................................................................................ 3
2.1 Standard and Codes ......................................................................................................................... 3
2.2 Contractor Document ...................................................................................................................... 3
2.3 Abbreviations .................................................................................................................................. 4
3. AIR CONDITIONING CALCULATION ............................................................................................. 5
3.1 Design Input .................................................................................................................................... 5
3.2 Outdoor Design Condition .............................................................................................................. 6
3.3 Indoor Design Condition .................................................................................................................. 7
3.4 U-Value and Shading Coefficient ................................................................................................... 7
3.5 Electrical Equipment Heat Dissipation ............................................................................................ 7
4. VENTILATION REQUIREMENT CALCULATION ......................................................................... 8
4.1 Exhaust Air ...................................................................................................................................... 8
4.2 Fresh Air for People ........................................................................................................................ 8
4.3 Air Pressure Calculation ................................................................................................................... 8
4.4 Fresh Air Requirement .................................................................................................................... 9
4.5 Electrical Duct Heater Calculation ................................................................................................... 9
5. SUMMARY OF AIR CONDITIONING SYSTEM ........................................................................... 10
6. HVAC EQUIPMENT SELECTION ................................................................................................... 11
6.1 AC Equipment Selection ............................................................................................................... 11
6.2 Fan Equipment Selection ............................................................................................................... 11
7. APPENDIX ......................................................................................................................................... 12
7.1 Space Input ..................................................................................................................................... 12
7.2 Cooling Load Panel House Wellpad A .......................................................................................... 36
7.3 Cooling Load Panel House Wellpad B ........................................................................................... 42
7.4 Cooling Load Panel House Wellpad D .......................................................................................... 48
7.5 Cooling Load Panel House Wellpad E ........................................................................................... 54
7.6 Cooling Load Panel House Wellpad F ........................................................................................... 60
7.7 Cooling Load Panel House Wellpad H .......................................................................................... 66
7.8 Building Architectural Drawings ................................................................................................... 72
Page 2 of 72
1. INTRODUCTION
1.1. Objective
This report describes conceptually the proposed system and performance requirements for
Heating, Ventilating and Air Conditioning (HVAC) services for SGS Panel House at MUARA
LABOH Geothermal Power Plant. This report is minimum cooling load and ventilation
requirements for sizing to HVAC equipment. The cooling load has been calculated in
accordance with ASHRAE FUNDAMENTALS using the Software/Program E-20 HAP System
Design Load version 4.9
1.2. Scope
This spesification covers the requirements for engineering, procurement, construction (EPC) of
air conditioning and ventilating facilities to be used for HVAC WORK MUARA LABOH
GEOTHERMAL POWER PLANT SOLOK WEST SUMATERA
Definition
Term Definition
EMPLOYER PT. SUPREME ENERGI
CONTRACTOR PT. REKAYASA INDUSTRI
SUBCONTRACTOR/VENDOR/ PT. BAYU SUKSES PRATAMA
SUPPLIER
MANUFACTURE TRANE
2. REFERENCE
2.1 Standards and Codes
ASHRAE Standard 62.1-2007 Ventilation for Acceptable Indoor Air Quality
ASHRAE Handbook Fundamental 2009 (SI)
ASHRAE Handbook HVAC Application
SNI 03 – 6572 – 2001
SNI 03 – 6389 - 2000
2.2 Contractor Document
Design Criteria for Heating and Air Conditioning (HVAC) System
Panel House Building Architecture Drawing
Page 3 of 72
2.3 Abbreviations
Term Definition
ACH Air Change per Hour
American Society of Heating, Refrigerating and Air Conditioning
ASHRAE
Engineers
°C degrees Celsius
CMH Cubic meters per hour
H Enthalpy
hr Hour
kg Kilogram
kW Kilowatt
L/s Liters per second
MAX Maximum
m Meters
m2 Square meters
3
m Cubic meters
MIN Minimum
N/C Not Conditioned
Pa Pascal
RH Relative Humidity
TEMP Temperature
VENT Ventilation
W Watt
% Percent
∆ Delta
NE North East
NW North West
SE South East
SW South West
Page 4 of 72
Reference:
Architecture Panel House Operation Floor Plan
Page 5 of 72
Lighting
No Room Power
Watt
1. BATTERY ROOM 72
2. PANEL ROOM 216
1)
Refer to ASHRAE Standard 90.1]
Average 78 %
Temperature
Min. 10.7°C
Max. 21.8°C
Temperature
Min. 14.8°C
Max. 27.0°C
Plant Located :
Latitude : 9819986
Longitude : 737037
Elevation :
a. Wellpad A : 1421.8 masl
b. Wellpad B : 1388.3 masl
c. Wellpad D : 1093.3 masl
d. Wellpad E : 1212.3 masl
e. Wellpad F : 1460.3 masl
f. Wellpad H : 1562.3 masl
Page 6 of 72
Min.
Temperature Humidity Min. Vent
Pressurized
No Room
Min. Max. Min. Max.
(Pa) (ACH)
(°C) (°C) % %
1 BATTERY ROOM 24 26 50 60 Negative(*) 5
2 PANEL ROOM 21 25 50 60 Positive
Note :
(*): refer to HVAC Design Criteria
Min. U-Value
Shading Coefficient Remarks
(W/m2.°K)
Roof 0.606 -
Wall 0.702 -
Door 0.650 -
Page 7 of 72
* Refer to ASHRAE Standard 62.1 2007, Ventilation for Acceptable Indoor Air Quality
Q CD * A 2P
........ refer to ASHRAE Handbook Fundamental 2009 (SI) page 16.13
Where
3
Q air flow rate, m
s
C D discharge coefficient for opening, dimensionless, ( C D 0.40 0.0045 Ti To )
A cross-sectional area of opening, m 2
Page 8 of 72
air density, kg
m3
P pressure difference across opening, Pa
X X
Y
Y Y Y
A ∆P ρ Q Q
NO Room Door CD
(m2) (Pa) (kg/m3) (m3/s) (CMH) L/s
PANEL HOUSE
1 BATTERY ROOM SD 0.4 0.0252 15 1.204 0.0503 181.08 50.2
2 PANEL ROOM DD 0.4 0.045 15 1.204 0.089 323.46 89.8
Note:
SD: Single Door, DD: Double Door
Where :
Page 9 of 72
Where :
Q = airflow (m3/s)
v = specific air volume (0.858 m3/kg) (From Psychometric)
Page 10 of 72
External
Air Flow
Qty. Static
No Building Capacity Remark
(unit) Pressure
(L/s)
(Pa)
Explosion
1. Battery Room 2x100% 125 38
Proof
Page 11 of 72
Battery Room
1. General Details:
Floor Area 17.5 m²
Avg. Ceiling Height 5.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 50.2 L/s
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 72.0 Watts Activity Level User defined
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule Schedule Latent 60.1 W/person
Schedule None
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
E 27.5 0 0 0
N 19.3 0 0 1
S 19.3 0 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 17.5 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Unconditioned Space
Floor Area 17.5 m²
Total Floor U-Value 0.568 W/(m²-°K)
Unconditioned Space Max Temp. 23.9 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 23.9 °C
Ambient at Space Min Temp. 12.8 °C
7. Partitions:
(No partition data).
Panel Room
1. General Details:
Floor Area 27.5 m²
Avg. Ceiling Height 4.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 89.8 L/s
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 216.0 Watts Activity Level Medium Work
Ballast Multiplier 1.00 Sensible 86.5 W/person
Schedule Schedule Latent 133.3 W/person
Schedule None
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
N 22.0 0 0 1
W 20.0 0 0 0
S 22.0 0 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 27.5 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Unconditioned Space
Floor Area 27.5 m²
Total Floor U-Value 0.568 W/(m²-°K)
Unconditioned Space Max Temp. 23.9 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 23.9 °C
Ambient at Space Min Temp. 12.8 °C
7. Partitions:
(No partition data).
Battery Room
1. General Details:
Floor Area 17.5 m²
Avg. Ceiling Height 5.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 50.2 L/s
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 72.0 Watts Activity Level User defined
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule Schedule Latent 60.1 W/person
Schedule None
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
E 19.3 0 0 1
W 19.3 0 0 0
S 27.5 0 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 17.5 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Unconditioned Space
Floor Area 17.5 m²
Total Floor U-Value 0.568 W/(m²-°K)
Unconditioned Space Max Temp. 23.9 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 23.9 °C
Ambient at Space Min Temp. 12.8 °C
7. Partitions:
(No partition data).
6. Floors:
Type Floor Above Unconditioned Space
Floor Area 27.5 m²
Total Floor U-Value 0.568 W/(m²-°K)
Unconditioned Space Max Temp. 23.9 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 23.9 °C
Ambient at Space Min Temp. 12.8 °C
7. Partitions:
(No partition data).
6. Floors:
Type Floor Above Unconditioned Space
Floor Area 17.5 m²
Total Floor U-Value 0.568 W/(m²-°K)
Unconditioned Space Max Temp. 23.9 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 23.9 °C
Ambient at Space Min Temp. 12.8 °C
7. Partitions:
(No partition data).
Panel Room
1. General Details:
Floor Area 27.5 m²
Avg. Ceiling Height 4.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 89.8 L/s
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 216.0 Watts Activity Level Medium Work
Ballast Multiplier 1.00 Sensible 86.5 W/person
Schedule Schedule Latent 133.3 W/person
Schedule None
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
N 20.0 0 0 0
W 22.0 0 0 0
E 22.0 0 0 1
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 27.5 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Unconditioned Space
Floor Area 27.5 m²
Total Floor U-Value 0.568 W/(m²-°K)
Unconditioned Space Max Temp. 23.9 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 23.9 °C
Ambient at Space Min Temp. 12.8 °C
7. Partitions:
(No partition data).
Battery Room
1. General Details:
Floor Area 17.5 m²
Avg. Ceiling Height 5.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 50.2 L/s
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 72.0 Watts Activity Level User defined
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule Schedule Latent 60.1 W/person
Schedule None
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
W 19.3 0 0 1
N 27.5 0 0 0
E 19.3 0 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 17.5 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Unconditioned Space
Floor Area 17.5 m²
Total Floor U-Value 0.568 W/(m²-°K)
Unconditioned Space Max Temp. 23.9 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 23.9 °C
Ambient at Space Min Temp. 12.8 °C
7. Partitions:
(No partition data).
Panel Room
1. General Details:
Floor Area 27.5 m²
Avg. Ceiling Height 4.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 89.8 L/s
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 216.0 Watts Activity Level Medium Work
Ballast Multiplier 1.00 Sensible 86.5 W/person
Schedule Schedule Latent 133.3 W/person
Schedule None
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
W 22.0 0 0 1
E 22.0 0 0 0
S 20.0 0 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 27.5 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Unconditioned Space
Floor Area 27.5 m²
Total Floor U-Value 0.568 W/(m²-°K)
Unconditioned Space Max Temp. 23.9 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 23.9 °C
Ambient at Space Min Temp. 12.8 °C
7. Partitions:
(No partition data).
Battery Room
1. General Details:
Floor Area 17.5 m²
Avg. Ceiling Height 5.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 50.2 L/s
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 72.0 Watts Activity Level User defined
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule Schedule Latent 60.1 W/person
Schedule None
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
N 19.3 0 0 1
E 27.5 0 0 0
S 19.3 0 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 17.5 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Unconditioned Space
Floor Area 17.5 m²
Total Floor U-Value 0.568 W/(m²-°K)
Unconditioned Space Max Temp. 23.9 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 23.9 °C
Ambient at Space Min Temp. 12.8 °C
7. Partitions:
(No partition data).
Panel Room
1. General Details:
Floor Area 27.5 m²
Avg. Ceiling Height 4.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 89.8 L/s
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 216.0 Watts Activity Level Medium Work
Ballast Multiplier 1.00 Sensible 86.5 W/person
Schedule Schedule Latent 133.3 W/person
Schedule None
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
N 22.0 0 0 1
W 20.0 0 0 0
S 22.0 0 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 27.5 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Unconditioned Space
Floor Area 27.5 m²
Total Floor U-Value 0.568 W/(m²-°K)
Unconditioned Space Max Temp. 23.9 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 23.9 °C
Ambient at Space Min Temp. 12.8 °C
7. Partitions:
(No partition data).
Battery Room
1. General Details:
Floor Area 17.5 m²
Avg. Ceiling Height 5.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 50.2 L/s
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 72.0 Watts Activity Level User defined
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule Schedule Latent 60.1 W/person
Schedule None
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
W 19.3 0 0 0
E 19.3 0 0 1
S 27.5 0 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 17.5 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Unconditioned Space
Floor Area 17.5 m²
Total Floor U-Value 0.568 W/(m²-°K)
Unconditioned Space Max Temp. 23.9 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 23.9 °C
Ambient at Space Min Temp. 12.8 °C
7. Partitions:
(No partition data).
Panel Room
1. General Details:
Floor Area 27.5 m²
Avg. Ceiling Height 4.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 89.8 L/s
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 216.0 Watts Activity Level Medium Work
Ballast Multiplier 1.00 Sensible 86.5 W/person
Schedule Schedule Latent 133.3 W/person
Schedule None
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
W 22.0 0 0 0
N 20.0 0 0 0
E 22.0 0 0 1
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 27.5 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Unconditioned Space
Floor Area 27.5 m²
Total Floor U-Value 0.568 W/(m²-°K)
Unconditioned Space Max Temp. 23.9 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 23.9 °C
Ambient at Space Min Temp. 12.8 °C
7. Partitions:
(No partition data).
Battery Room
1. General Details:
Floor Area 17.5 m²
Avg. Ceiling Height 5.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 50.2 L/s
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 72.0 Watts Activity Level User defined
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule Schedule Latent 60.1 W/person
Schedule None
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
W 19.3 0 0 1
N 27.5 0 0 0
E 19.3 0 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 17.5 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Unconditioned Space
Floor Area 17.5 m²
Total Floor U-Value 0.568 W/(m²-°K)
Unconditioned Space Max Temp. 23.9 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 23.9 °C
Ambient at Space Min Temp. 12.8 °C
7. Partitions:
(No partition data).
Panel Room
1. General Details:
Floor Area 27.5 m²
Avg. Ceiling Height 4.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 89.8 L/s
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007
2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 216.0 Watts Activity Level Medium Work
Ballast Multiplier 1.00 Sensible 86.5 W/person
Schedule Schedule Latent 133.3 W/person
Schedule None
Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
W 22.0 0 0 0
E 22.0 0 0 0
S 20.0 0 0 0
4. Roofs, Skylights:
Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 27.5 0 0
5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.
6. Floors:
Type Floor Above Unconditioned Space
Floor Area 27.5 m²
Total Floor U-Value 0.568 W/(m²-°K)
Unconditioned Space Max Temp. 23.9 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 23.9 °C
Ambient at Space Min Temp. 12.8 °C
7. Partitions:
(No partition data).
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' Battery Room '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 2000 HEATING DATA AT DES HTG
COOLING OA DB / WB 22.3 °C / 20.6 °C HEATING OA DB / WB 14.8 °C / 10.7 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 18.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 61 m² 385 - 61 m² 137 -
Roof Transmission 18 m² 157 - 18 m² 34 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 5 m² 5 - 5 m² 10 -
Floor Transmission 18 m² 29 - 18 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 72 W 72 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 1500 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 2147 0 - 182 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' Battery Room '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
E EXPOSURE
WALL 28 0.702 - 182 - 62
N EXPOSURE
WALL 14 0.702 - 43 - 32
DOOR 5 0.650 - 5 - 10
S EXPOSURE
WALL 19 0.702 - 160 - 43
H EXPOSURE
ROOF 18 0.606 - 157 - 34
TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' Panel Room '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 2100 HEATING DATA AT DES HTG
COOLING OA DB / WB 21.2 °C / 20.3 °C HEATING OA DB / WB 14.8 °C / 10.7 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 18.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 59 m² 400 - 59 m² 133 -
Roof Transmission 28 m² 238 - 28 m² 53 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 5 m² 2 - 5 m² 10 -
Floor Transmission 28 m² 45 - 28 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 216 W 216 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 4650 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 5551 0 - 196 0
TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' Panel Room '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 17 0.702 - 54 - 38
DOOR 5 0.650 - 2 - 10
W EXPOSURE
WALL 20 0.702 - 162 - 45
S EXPOSURE
WALL 22 0.702 - 185 - 49
H EXPOSURE
ROOF 28 0.606 - 238 - 53
0.016
0.014
0.008
0.006
0.004
0.002
0.000
0 5 10 15 20 25 30 35
Temperature ( °C )
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' Battery Room '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 2100 HEATING DATA AT DES HTG
COOLING OA DB / WB 21.2 °C / 20.3 °C HEATING OA DB / WB 14.8 °C / 10.7 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 18.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 61 m² 479 - 61 m² 137 -
Roof Transmission 18 m² 151 - 18 m² 34 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 5 m² 2 - 5 m² 10 -
Floor Transmission 18 m² 29 - 18 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 72 W 72 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 1500 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 2233 0 - 182 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' Battery Room '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
E EXPOSURE
WALL 14 0.702 - 92 - 32
DOOR 5 0.650 - 2 - 10
W EXPOSURE
WALL 19 0.702 - 156 - 43
S EXPOSURE
WALL 28 0.702 - 231 - 62
H EXPOSURE
ROOF 18 0.606 - 151 - 34
TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' Panel Room '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Feb 2100 HEATING DATA AT DES HTG
COOLING OA DB / WB 21.2 °C / 20.3 °C HEATING OA DB / WB 14.8 °C / 10.7 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 18.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 59 m² 357 - 59 m² 133 -
Roof Transmission 28 m² 245 - 28 m² 53 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 5 m² 2 - 5 m² 10 -
Floor Transmission 28 m² 45 - 28 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 216 W 216 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 4750 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 5616 0 - 196 0
TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' Panel Room '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 20 0.702 - 64 - 45
W EXPOSURE
WALL 22 0.702 - 182 - 49
E EXPOSURE
WALL 17 0.702 - 112 - 38
DOOR 5 0.650 - 2 - 10
H EXPOSURE
ROOF 28 0.606 - 245 - 53
0.016
0.014
0.008
0.006
0.004
0.002
0.000
0 5 10 15 20 25 30 35
Temperature ( °C )
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' Battery Room '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Feb 2100 HEATING DATA AT DES HTG
COOLING OA DB / WB 21.2 °C / 20.2 °C HEATING OA DB / WB 14.8 °C / 10.7 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 18.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 61 m² 333 - 61 m² 137 -
Roof Transmission 18 m² 156 - 18 m² 34 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 5 m² 2 - 5 m² 10 -
Floor Transmission 18 m² 29 - 18 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 72 W 72 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 1500 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 2091 0 - 182 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' Battery Room '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
W EXPOSURE
WALL 14 0.702 - 118 - 32
DOOR 5 0.650 - 2 - 10
N EXPOSURE
WALL 28 0.702 - 88 - 62
E EXPOSURE
WALL 19 0.702 - 127 - 43
H EXPOSURE
ROOF 18 0.606 - 156 - 34
TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' Panel Room '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 2000 HEATING DATA AT DES HTG
COOLING OA DB / WB 22.3 °C / 20.5 °C HEATING OA DB / WB 14.8 °C / 10.7 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 18.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 59 m² 438 - 59 m² 133 -
Roof Transmission 28 m² 246 - 28 m² 53 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 5 m² 5 - 5 m² 10 -
Floor Transmission 28 m² 45 - 28 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 216 W 216 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 4650 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 5600 0 - 196 0
TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' Panel Room '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
W EXPOSURE
WALL 17 0.702 - 127 - 38
DOOR 5 0.650 - 5 - 10
E EXPOSURE
WALL 22 0.702 - 145 - 49
S EXPOSURE
WALL 20 0.702 - 166 - 45
H EXPOSURE
ROOF 28 0.606 - 246 - 53
0.016
0.014
34 5 0.010
0.008
0.006
0.004
0.002
0.000
0 5 10 15 20 25 30 35
Temperature ( °C )
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' Battery Room '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 2000 HEATING DATA AT DES HTG
COOLING OA DB / WB 22.3 °C / 20.5 °C HEATING OA DB / WB 14.8 °C / 10.7 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 18.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 61 m² 385 - 61 m² 137 -
Roof Transmission 18 m² 157 - 18 m² 34 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 5 m² 5 - 5 m² 10 -
Floor Transmission 18 m² 29 - 18 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 72 W 72 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 1500 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 2147 0 - 182 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' Battery Room '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 14 0.702 - 43 - 32
DOOR 5 0.650 - 5 - 10
E EXPOSURE
WALL 28 0.702 - 182 - 62
S EXPOSURE
WALL 19 0.702 - 160 - 43
H EXPOSURE
ROOF 18 0.606 - 157 - 34
TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' Panel Room '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 2100 HEATING DATA AT DES HTG
COOLING OA DB / WB 21.2 °C / 20.2 °C HEATING OA DB / WB 14.8 °C / 10.7 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 18.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 59 m² 400 - 59 m² 133 -
Roof Transmission 28 m² 238 - 28 m² 53 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 5 m² 2 - 5 m² 10 -
Floor Transmission 28 m² 45 - 28 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 216 W 216 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 4650 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 5551 0 - 196 0
TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' Panel Room '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 17 0.702 - 54 - 38
DOOR 5 0.650 - 2 - 10
W EXPOSURE
WALL 20 0.702 - 162 - 45
S EXPOSURE
WALL 22 0.702 - 185 - 49
H EXPOSURE
ROOF 28 0.606 - 238 - 53
0.016
0.014
0.008
0.006
0.004
0.002
0.000
0 5 10 15 20 25 30 35
Temperature ( °C )
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' Battery Room '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 2100 HEATING DATA AT DES HTG
COOLING OA DB / WB 21.2 °C / 20.3 °C HEATING OA DB / WB 14.8 °C / 10.7 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 18.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 61 m² 479 - 61 m² 137 -
Roof Transmission 18 m² 151 - 18 m² 34 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 5 m² 2 - 5 m² 10 -
Floor Transmission 18 m² 29 - 18 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 72 W 72 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 1500 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 2233 0 - 182 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' Battery Room '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
W EXPOSURE
WALL 19 0.702 - 156 - 43
E EXPOSURE
WALL 14 0.702 - 92 - 32
DOOR 5 0.650 - 2 - 10
S EXPOSURE
WALL 28 0.702 - 231 - 62
H EXPOSURE
ROOF 18 0.606 - 151 - 34
TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' Panel Room '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Feb 2100 HEATING DATA AT DES HTG
COOLING OA DB / WB 21.2 °C / 20.3 °C HEATING OA DB / WB 14.8 °C / 10.7 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 18.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 59 m² 357 - 59 m² 133 -
Roof Transmission 28 m² 245 - 28 m² 53 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 5 m² 2 - 5 m² 10 -
Floor Transmission 28 m² 45 - 28 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 216 W 216 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 4650 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 5516 0 - 196 0
TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' Panel Room '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
W EXPOSURE
WALL 22 0.702 - 182 - 49
N EXPOSURE
WALL 20 0.702 - 64 - 45
E EXPOSURE
WALL 17 0.702 - 112 - 38
DOOR 5 0.650 - 2 - 10
H EXPOSURE
ROOF 28 0.606 - 245 - 53
0.016
0.014
0.008
0.006
0.004
0.002
0.000
0 5 10 15 20 25 30 35
Temperature ( °C )
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' Battery Room '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Feb 2100 HEATING DATA AT DES HTG
COOLING OA DB / WB 21.2 °C / 20.3 °C HEATING OA DB / WB 14.8 °C / 10.7 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 18.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 61 m² 333 - 61 m² 137 -
Roof Transmission 18 m² 156 - 18 m² 34 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 5 m² 2 - 5 m² 10 -
Floor Transmission 18 m² 29 - 18 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 72 W 72 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 1500 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 2091 0 - 182 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' Battery Room '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
W EXPOSURE
WALL 14 0.702 - 118 - 32
DOOR 5 0.650 - 2 - 10
N EXPOSURE
WALL 28 0.702 - 88 - 62
E EXPOSURE
WALL 19 0.702 - 127 - 43
H EXPOSURE
ROOF 18 0.606 - 156 - 34
TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' Panel Room '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 2100 HEATING DATA AT DES HTG
COOLING OA DB / WB 21.2 °C / 20.3 °C HEATING OA DB / WB 14.8 °C / 10.7 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 18.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 64 m² 488 - 64 m² 144 -
Roof Transmission 28 m² 238 - 28 m² 53 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 28 m² 45 - 28 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 216 W 216 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 4650 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 5637 0 - 197 0
TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' Panel Room '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
W EXPOSURE
WALL 22 0.702 - 178 - 49
E EXPOSURE
WALL 22 0.702 - 142 - 49
S EXPOSURE
WALL 20 0.702 - 168 - 45
H EXPOSURE
ROOF 28 0.606 - 238 - 53
0.016
0.014
0.008
0.006
0.004
0.002
0.000
0 5 10 15 20 25 30 35
Temperature ( °C )
x
x
x
x
x
x
x
B
x
x
x
x
x
x
x x x x x x x x x x x x x x x x x x x x x x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
x
E 735500
E 736000
E 736500
E 737000
E 737500
E 738000
E 738500
E 739000
E 739500
x
x
x
x
x
x
x
x
x
x
x
x
x
x
C
x
x
x
x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x
x
x
x
x
x
x
x
x
x
x
x
D
E
F
G
ISSUED FOR REVIEW
ATTACHED XREF FILES PROJECT TITLE
H supremeenergy
DRAWN DRAFT. CHECK REVIEWED APPROVED
SCALE DRAWING No REV
REV DATE DESCRIPTION DRAWN REV'D APP'D
SUPREME ENERGY MUARA LABOH CONT. DWG No DESIGNED DESGN. REVIEW
DATE DATE
1 2 3 4 5 6 7 8 9 10 11 12 A3