Download as pdf or txt
Download as pdf or txt
You are on page 1of 74

HVAC COOLING LOAD CALCULATION PANEL HOUSE WELLPADS BUILDING

Document No : Origin Rev No. Contract No :

ML-PRD01-CEG-CCAL-0082 RH 0 14000011-OS-10101

PROJECT : MUARA LABOH GEOTHERMAL POWER PROJECT


STAGE 1 DEVELOPMENT EPC CONTRACT

OWNER : PT. SUPREME ENERGY MUARA LABOH (SEML)

LOCATION : MUARA LABOH, SOLOK SELATAN, SUMATERA


BARAT, INDONESIA

0 Issued For Use 19-Mar-2018 TB APS AS


Rev Description Date Prepared Checked Approved

Consortium of Sumitomo Corporation and PT REKAYASA INDUSTRI


HVAC COOLING LOAD CALCULATION PANEL HOUSE WELLPADS BUILDING

Document No : .Origin Rev No. Contract No :


ML-PRD01-CEG-CCAL-0082 RH 0 14000011-OS-10101

TABLE OF CONTENTS
1. INTRODUCTION ................................................................................................................................. 3
1.1 Objective ......................................................................................................................................... 3
1.2 Scope ............................................................................................................................................... 3
1.3 Definition ......................................................................................................................................... 3
2. REFERENCE ........................................................................................................................................ 3
2.1 Standard and Codes ......................................................................................................................... 3
2.2 Contractor Document ...................................................................................................................... 3
2.3 Abbreviations .................................................................................................................................. 4
3. AIR CONDITIONING CALCULATION ............................................................................................. 5
3.1 Design Input .................................................................................................................................... 5
3.2 Outdoor Design Condition .............................................................................................................. 6
3.3 Indoor Design Condition .................................................................................................................. 7
3.4 U-Value and Shading Coefficient ................................................................................................... 7
3.5 Electrical Equipment Heat Dissipation ............................................................................................ 7
4. VENTILATION REQUIREMENT CALCULATION ......................................................................... 8
4.1 Exhaust Air ...................................................................................................................................... 8
4.2 Fresh Air for People ........................................................................................................................ 8
4.3 Air Pressure Calculation ................................................................................................................... 8
4.4 Fresh Air Requirement .................................................................................................................... 9
4.5 Electrical Duct Heater Calculation ................................................................................................... 9
5. SUMMARY OF AIR CONDITIONING SYSTEM ........................................................................... 10
6. HVAC EQUIPMENT SELECTION ................................................................................................... 11
6.1 AC Equipment Selection ............................................................................................................... 11
6.2 Fan Equipment Selection ............................................................................................................... 11
7. APPENDIX ......................................................................................................................................... 12
7.1 Space Input ..................................................................................................................................... 12
7.2 Cooling Load Panel House Wellpad A .......................................................................................... 36
7.3 Cooling Load Panel House Wellpad B ........................................................................................... 42
7.4 Cooling Load Panel House Wellpad D .......................................................................................... 48
7.5 Cooling Load Panel House Wellpad E ........................................................................................... 54
7.6 Cooling Load Panel House Wellpad F ........................................................................................... 60
7.7 Cooling Load Panel House Wellpad H .......................................................................................... 66
7.8 Building Architectural Drawings ................................................................................................... 72

Page 2 of 72

Consortium of Sumitomo Corporation and PT REKAYASA INDUSTRI


HVAC COOLING LOAD CALCULATION PANEL HOUSE WELLPADS BUILDING

Document No : .Origin Rev No. Contract No :


ML-PRD01-CEG-CCAL-0082 RH 0 14000011-OS-10101

1. INTRODUCTION
1.1. Objective
This report describes conceptually the proposed system and performance requirements for
Heating, Ventilating and Air Conditioning (HVAC) services for SGS Panel House at MUARA
LABOH Geothermal Power Plant. This report is minimum cooling load and ventilation
requirements for sizing to HVAC equipment. The cooling load has been calculated in
accordance with ASHRAE FUNDAMENTALS using the Software/Program E-20 HAP System
Design Load version 4.9

1.2. Scope
This spesification covers the requirements for engineering, procurement, construction (EPC) of
air conditioning and ventilating facilities to be used for HVAC WORK MUARA LABOH
GEOTHERMAL POWER PLANT SOLOK WEST SUMATERA

Definition

Term Definition
EMPLOYER PT. SUPREME ENERGI
CONTRACTOR PT. REKAYASA INDUSTRI
SUBCONTRACTOR/VENDOR/ PT. BAYU SUKSES PRATAMA
SUPPLIER
MANUFACTURE TRANE

2. REFERENCE
2.1 Standards and Codes
 ASHRAE Standard 62.1-2007 Ventilation for Acceptable Indoor Air Quality
 ASHRAE Handbook Fundamental 2009 (SI)
 ASHRAE Handbook HVAC Application
 SNI 03 – 6572 – 2001
 SNI 03 – 6389 - 2000
2.2 Contractor Document
 Design Criteria for Heating and Air Conditioning (HVAC) System
 Panel House Building Architecture Drawing

Page 3 of 72

Consortium of Sumitomo Corporation and PT REKAYASA INDUSTRI


HVAC COOLING LOAD CALCULATION PANEL HOUSE WELLPADS BUILDING

Document No : .Origin Rev No. Contract No :


ML-PRD01-CEG-CCAL-0082 RH 0 14000011-OS-10101

2.3 Abbreviations
Term Definition
ACH Air Change per Hour
American Society of Heating, Refrigerating and Air Conditioning
ASHRAE
Engineers
°C degrees Celsius
CMH Cubic meters per hour
H Enthalpy
hr Hour
kg Kilogram
kW Kilowatt
L/s Liters per second
MAX Maximum
m Meters
m2 Square meters
3
m Cubic meters
MIN Minimum
N/C Not Conditioned
Pa Pascal
RH Relative Humidity
TEMP Temperature
VENT Ventilation
W Watt
% Percent
∆ Delta
NE North East
NW North West
SE South East
SW South West

Page 4 of 72

Consortium of Sumitomo Corporation and PT REKAYASA INDUSTRI


HVAC COOLING LOAD CALCULATION PANEL HOUSE WELLPADS BUILDING

Document No : .Origin Rev No. Contract No :


ML-PRD01-CEG-CCAL-0082 RH 0 14000011-OS-10101

3. AIR CONDITIONING CALCULATION


3.1 Design Input
The components that contribute to room heat gains and losses consist of external load (solar
transmissions, radiations, wall transmissions, floor transmissions, ceiling transmissions,
ventilations load and infiltration loads) and internal load (equipment heat dissipation, people and
lighting heat gain).
 General Info

Floor Room Wall Area (m2)


No Room Area Height Facing to the sun
m2 m W N E S
A PANEL HOUSE WELLPAD A
1 BATTERY ROOM 17.5 5.5 - 19.3 27.5 19.3
2 PANEL ROOM 27.5 4.0 20.0 22.0 - 22.0

B PANEL HOUSE WELLPAD B


1 BATTERY ROOM 17.5 5.5 19.3 - 19.3 27.5
2 PANEL ROOM 27.5 4.0 22.0 20.0 22.0 -

C PANEL HOUSE WELLPAD D


1 BATTERY ROOM 17.5 5.5 19.3 27.5 19.3 -
2 PANEL ROOM 27.5 4.0 22.0 - 22.0 20.0

D PANEL HOUSE WELLPAD E


1 BATTERY ROOM 17.5 5.5 - 19.3 27.5 19.3
2 PANEL ROOM 27.5 4.0 20.0 22.0 - 22.0

E PANEL HOUSE WELLPAD F


1 BATTERY ROOM 17.5 5.5 19.3 - 19.3 27.5
2 PANEL ROOM 27.5 4.0 22.0 20.0 22.0 -

F PANEL HOUSE WELLPAD H


1 BATTERY ROOM 17.5 5.5 19.3 27.5 19.3 -
2 PANEL ROOM 27.5 4.0 22.0 - 22.0 20.0

Reference:
Architecture Panel House Operation Floor Plan

Page 5 of 72

Consortium of Sumitomo Corporation and PT REKAYASA INDUSTRI


HVAC COOLING LOAD CALCULATION PANEL HOUSE WELLPADS BUILDING

Document No : .Origin Rev No. Contract No :


ML-PRD01-CEG-CCAL-0082 RH 0 14000011-OS-10101

 People and Lighting Heat Gain (Typical For Cluster A to Cluster F)

Lighting
No Room Power
Watt
1. BATTERY ROOM 72
2. PANEL ROOM 216

1)
Refer to ASHRAE Standard 90.1]

3.2 Outdoor Design Condition


Outdoor design conditions used for the cooling load calculations are per the external design
conditions reference in MUARA LABOH Geothermal Power Plant
Relative Humidity
Relative Humidity %

Average 78 %

Temperature

Temperature Wet Bulb °C

Min. 10.7°C
Max. 21.8°C

Temperature

Temperature Dry Bulb °C

Min. 14.8°C
Max. 27.0°C

 Plant Located :
 Latitude : 9819986
 Longitude : 737037
 Elevation :
a. Wellpad A : 1421.8 masl
b. Wellpad B : 1388.3 masl
c. Wellpad D : 1093.3 masl
d. Wellpad E : 1212.3 masl
e. Wellpad F : 1460.3 masl
f. Wellpad H : 1562.3 masl

Page 6 of 72

Consortium of Sumitomo Corporation and PT REKAYASA INDUSTRI


HVAC COOLING LOAD CALCULATION PANEL HOUSE WELLPADS BUILDING

Document No : .Origin Rev No. Contract No :


ML-PRD01-CEG-CCAL-0082 RH 0 14000011-OS-10101

3.3 Indoor Design Condition


Indoor design conditions used for the cooling load calculation as per reference in Muara Laboh
Geothermal Power Plant.

Min.
Temperature Humidity Min. Vent
Pressurized
No Room
Min. Max. Min. Max.
(Pa) (ACH)
(°C) (°C) % %
1 BATTERY ROOM 24 26 50 60 Negative(*) 5
2 PANEL ROOM 21 25 50 60 Positive
Note :
(*): refer to HVAC Design Criteria

3.4 U-Value and Shading Coefficient

Min. U-Value
Shading Coefficient Remarks
(W/m2.°K)
Roof 0.606 -
Wall 0.702 -
Door 0.650 -

3.5 Electrical Equipment Heat Dissipation

Room Heat Dissipation (Watt)


NO

1 BATTERY ROOM 0.0

2 PANEL ROOM 4650

Page 7 of 72

Consortium of Sumitomo Corporation and PT REKAYASA INDUSTRI


HVAC COOLING LOAD CALCULATION PANEL HOUSE WELLPADS BUILDING

Document No : .Origin Rev No. Contract No :


ML-PRD01-CEG-CCAL-0082 RH 0 14000011-OS-10101

4. VENTILATION REQUIREMENT CALCULATION


4.1 Exhaust Air for Panel House
Exhaust Air from room specified with following formula:
Q = V x ACH
Where :
Q = Air Flow (m3/h)
V = Volume Room (m3)
ACH = Air Change per Hour
Exhaust air required for Panel House Building tabulated as below
Min.
Area High Volume Ventilated
No Room Ventilation
(m²) (m) (m³) (ACH) CMH L/s
1 BATTERY ROOM 17.5 5 87.5 5 437.5 121.5
27.5 4 110 N/A N/A N/A
2 PANEL ROOM

* Refer to ASHRAE Standard 62.1 2007, Ventilation for Acceptable Indoor Air Quality

4.2 Fresh Air for People


Fresh air required for People tabulated as below:

Occupant Requirement Area Total FA


No Room
(Persons) L/s.m2 (m2) L/s
1 BATTERY ROOM 0,3 17.5 5.25
2 PANEL ROOM 0,3 27.5 8.25

4.3 Air Pressure Calculation


Fresh air required for room pressure

Q  CD * A 2P
 ........ refer to ASHRAE Handbook Fundamental 2009 (SI) page 16.13
Where
3
Q  air flow rate, m
s
C D  discharge coefficient for opening, dimensionless, ( C D  0.40  0.0045 Ti  To )
A  cross-sectional area of opening, m 2

Page 8 of 72

Consortium of Sumitomo Corporation and PT REKAYASA INDUSTRI


HVAC COOLING LOAD CALCULATION PANEL HOUSE WELLPADS BUILDING

Document No : .Origin Rev No. Contract No :


ML-PRD01-CEG-CCAL-0082 RH 0 14000011-OS-10101

  air density, kg
m3
P  pressure difference across opening, Pa
X X

Y
Y Y Y

Single Door (2X x a ) + ( 2Y x a ) Double Door (2X x a) + (3Y x a)


Where:
A = (2X x a ) + ( 2Y x a ) or (2X x a) + (3Y x a)
a = Gaps, m
Fresh Air for Pressurized tabulated as below:

A ∆P ρ Q Q
NO Room Door CD
(m2) (Pa) (kg/m3) (m3/s) (CMH) L/s
PANEL HOUSE
1 BATTERY ROOM SD 0.4 0.0252 15 1.204 0.0503 181.08 50.2
2 PANEL ROOM DD 0.4 0.045 15 1.204 0.089 323.46 89.8
Note:
SD: Single Door, DD: Double Door

4.4 Fresh Air Requirement


FA for FA for
FA selected
No Room person Pressurized
(L/s)
(L/s) (L/s)
Ground Floor

1 BATTERY ROOM 5.25 50.2 50.2

2 PANEL ROOM 8.25 89.8 89.8


Total 140
1) Refer to ASHRAE Handbook Fundamental 2009 (SI) page 2.1

4.5 Electric Duct Heater Calculation

Where :
Page 9 of 72

Consortium of Sumitomo Corporation and PT REKAYASA INDUSTRI


HVAC COOLING LOAD CALCULATION PANEL HOUSE WELLPADS BUILDING

Document No : .Origin Rev No. Contract No :


ML-PRD01-CEG-CCAL-0082 RH 0 14000011-OS-10101

= mass flow (kg/s)


c = specific heat (kJ/kg.K.)
∆T = temperature (°K)

Where :
Q = airflow (m3/s)
v = specific air volume (0.858 m3/kg) (From Psychometric)

Duct Heater Capacity tabulated as below:


Mass Air Duct Heater
Air Flow c
No Room Supply ∆T (°K) Capacity
(m3/s) (kJ/kg.K)
(kg/s) (kW)
1 Panel House Wellpad A 0.757 0.882 1 4 3.52
2 Panel House Wellpad B 0.769 0.847 1 4 3.38
3 Panel House Wellpad D 0.726 0.846 1 4 3.38
4 Panel House Wellpad E 0.738 0.860 1 4 3.44
5 Panel House Wellpad F 0.765 0.891 1 4 3.56
6 Panel House Wellpad H 0.773 0.900 1 4 3.60

5. SUMMARY OF AIR CONDITIONING SYSTEM


Accordance to result of E-20 calculation, cooling load capacity for Panel House Building
tabulated as below:
Total Maximum Maximum
Cooling Cooling Cooling Supply Air Fresh Air
No Service Load Sensible Latent
(kW) (kW) (kW) (L/s) (L/s)
1. Panel House Wellpad A 10.8 8.1 2.7 140
757
2. Panel House Wellpad B 11.0 8.3 2.7 140
769
3. Panel House Wellpad D 10.9 8.1 2.8 140
726
4. Panel House Wellpad E 10.8 8.1 2.7 140
738
5. Panel House Wellpad F 10.8 8.0 2.8 140
765
6. Panel House Wellpad H 10.8 8.1 2.7 140
773

Page 10 of 72

Consortium of Sumitomo Corporation and PT REKAYASA INDUSTRI


HVAC COOLING LOAD CALCULATION PANEL HOUSE WELLPADS BUILDING

Document No : .Origin Rev No. Contract No :


ML-PRD01-CEG-CCAL-0082 RH 0 14000011-OS-10101

6. HVAC EQUIPMENT SELECTION


6.1 AC Equipment Selection
Cooling Air Flow
Qty.
No Building Capacity Capacity
(unit)
(kW) (L/s)
1. Panel House Wellpad A 2x100% 12.4 757
2. Panel House Wellpad B 2x100% 12.6 769
3. Panel House Wellpad D 2x100% 12.5 726
4. Panel House Wellpad E 2x100% 12.4 738
5. Panel House Wellpad F 2x100% 12.4 765
6. Panel House Wellpad H 2x100% 12.4 773

6.2 Fan Equipment Selection

External
Air Flow
Qty. Static
No Building Capacity Remark
(unit) Pressure
(L/s)
(Pa)
Explosion
1. Battery Room 2x100% 125 38
Proof

Page 11 of 72

Consortium of Sumitomo Corporation and PT REKAYASA INDUSTRI


Space Input Data
Muara Laboh Geothermal Panel House Wellpad A 03/22/2018
PT.Bayu Sukses Pratama 04:00PM

Battery Room

1. General Details:
Floor Area 17.5 m²
Avg. Ceiling Height 5.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 50.2 L/s
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 72.0 Watts Activity Level User defined
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule Schedule Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 1500 W
Schedule Schedule Schedule Schedule
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.00 W/m²
Schedule None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
E 27.5 0 0 0
N 19.3 0 0 1
S 19.3 0 0 0

3.1. Construction Types for Exposure E


Wall Type Wall

3.2. Construction Types for Exposure N


Wall Type Wall
Door Type Door

3.3. Construction Types for Exposure S


Wall Type Wall

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 17.5 0 0

4.1. Construction Types for Exposure H


Roof Type Built-up Roof + 203mm LW Concrete

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

Hourly Analysis Program v4.90 Page 1 of 2


Space Input Data
Muara Laboh Geothermal Panel House Wellpad A 03/22/2018
PT.Bayu Sukses Pratama 04:00PM

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 17.5 m²
Total Floor U-Value 0.568 W/(m²-°K)
Unconditioned Space Max Temp. 23.9 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 23.9 °C
Ambient at Space Min Temp. 12.8 °C

7. Partitions:
(No partition data).

Hourly Analysis Program v4.90 Page 2 of 2


Space Input Data
Muara Laboh Geothermal Panel House Wellpad A 03/20/2018
PT.Bayu Sukses Pratama 10:00AM

Panel Room

1. General Details:
Floor Area 27.5 m²
Avg. Ceiling Height 4.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 89.8 L/s
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 216.0 Watts Activity Level Medium Work
Ballast Multiplier 1.00 Sensible 86.5 W/person
Schedule Schedule Latent 133.3 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 4650 W
Schedule Schedule Schedule Schedule
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule Schedule

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
N 22.0 0 0 1
W 20.0 0 0 0
S 22.0 0 0 0

3.1. Construction Types for Exposure N


Wall Type Wall
Door Type Door

3.2. Construction Types for Exposure W


Wall Type Wall

3.3. Construction Types for Exposure S


Wall Type Wall

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 27.5 0 0

4.1. Construction Types for Exposure H


Roof Type Built-up Roof + 203mm LW Concrete

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

Hourly Analysis Program v4.90 Page 1 of 2


Space Input Data
Muara Laboh Geothermal Panel House Wellpad A 03/20/2018
PT.Bayu Sukses Pratama 10:00AM

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 27.5 m²
Total Floor U-Value 0.568 W/(m²-°K)
Unconditioned Space Max Temp. 23.9 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 23.9 °C
Ambient at Space Min Temp. 12.8 °C

7. Partitions:
(No partition data).

Hourly Analysis Program v4.90 Page 2 of 2


Space Input Data
Muara Laboh Geothermal Panel House Wellpad B 03/22/2018
PT.Bayu Sukses Pratama 04:01PM

Battery Room

1. General Details:
Floor Area 17.5 m²
Avg. Ceiling Height 5.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 50.2 L/s
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 72.0 Watts Activity Level User defined
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule Schedule Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 1500 W
Schedule Schedule Schedule Schedule
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.00 W/m²
Schedule None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
E 19.3 0 0 1
W 19.3 0 0 0
S 27.5 0 0 0

3.1. Construction Types for Exposure E


Wall Type Wall
Door Type Door

3.2. Construction Types for Exposure W


Wall Type Wall

3.3. Construction Types for Exposure S


Wall Type Wall

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 17.5 0 0

4.1. Construction Types for Exposure H


Roof Type Built-up Roof + 203mm LW Concrete

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

Hourly Analysis Program v4.90 Page 1 of 2


Space Input Data
Muara Laboh Geothermal Panel House Wellpad B 03/22/2018
PT.Bayu Sukses Pratama 04:01PM

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 17.5 m²
Total Floor U-Value 0.568 W/(m²-°K)
Unconditioned Space Max Temp. 23.9 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 23.9 °C
Ambient at Space Min Temp. 12.8 °C

7. Partitions:
(No partition data).

Hourly Analysis Program v4.90 Page 2 of 2


Space Input Data
Muara Laboh Geothermal Panel House Wellpad A 03/20/2018
PT.Bayu Sukses Pratama 10:00AM

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 27.5 m²
Total Floor U-Value 0.568 W/(m²-°K)
Unconditioned Space Max Temp. 23.9 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 23.9 °C
Ambient at Space Min Temp. 12.8 °C

7. Partitions:
(No partition data).

Hourly Analysis Program v4.90 Page 2 of 2


Space Input Data
Muara Laboh Geothermal Panel House Wellpad B 03/22/2018
PT.Bayu Sukses Pratama 04:01PM

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 17.5 m²
Total Floor U-Value 0.568 W/(m²-°K)
Unconditioned Space Max Temp. 23.9 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 23.9 °C
Ambient at Space Min Temp. 12.8 °C

7. Partitions:
(No partition data).

Hourly Analysis Program v4.90 Page 2 of 2


Space Input Data
Muara Laboh Geothermal Panel House Wellpad B 03/20/2018
PT.Bayu Sukses Pratama 10:01AM

Panel Room

1. General Details:
Floor Area 27.5 m²
Avg. Ceiling Height 4.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 89.8 L/s
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 216.0 Watts Activity Level Medium Work
Ballast Multiplier 1.00 Sensible 86.5 W/person
Schedule Schedule Latent 133.3 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 4750 W
Schedule Schedule Schedule Schedule
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule Schedule

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
N 20.0 0 0 0
W 22.0 0 0 0
E 22.0 0 0 1

3.1. Construction Types for Exposure N


Wall Type Wall

3.2. Construction Types for Exposure W


Wall Type Wall

3.3. Construction Types for Exposure E


Wall Type Wall
Door Type Door

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 27.5 0 0

4.1. Construction Types for Exposure H


Roof Type Built-up Roof + 203mm LW Concrete

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

Hourly Analysis Program v4.90 Page 1 of 2


Space Input Data
Muara Laboh Geothermal Panel House Wellpad B 03/20/2018
PT.Bayu Sukses Pratama 10:01AM

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 27.5 m²
Total Floor U-Value 0.568 W/(m²-°K)
Unconditioned Space Max Temp. 23.9 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 23.9 °C
Ambient at Space Min Temp. 12.8 °C

7. Partitions:
(No partition data).

Hourly Analysis Program v4.90 Page 2 of 2


Space Input Data
Muara Laboh Geothermal Panel House Wellpad D 03/22/2018
PT.Bayu Sukses Pratama 04:05PM

Battery Room

1. General Details:
Floor Area 17.5 m²
Avg. Ceiling Height 5.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 50.2 L/s
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 72.0 Watts Activity Level User defined
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule Schedule Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 1500 W
Schedule Schedule Schedule Schedule
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.00 W/m²
Schedule None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
W 19.3 0 0 1
N 27.5 0 0 0
E 19.3 0 0 0

3.1. Construction Types for Exposure W


Wall Type Wall
Door Type Door

3.2. Construction Types for Exposure N


Wall Type Wall

3.3. Construction Types for Exposure E


Wall Type Wall

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 17.5 0 0

4.1. Construction Types for Exposure H


Roof Type Built-up Roof + 203mm LW Concrete

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

Hourly Analysis Program v4.90 Page 1 of 2


Space Input Data
Muara Laboh Geothermal Panel House Wellpad D 03/22/2018
PT.Bayu Sukses Pratama 04:05PM

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 17.5 m²
Total Floor U-Value 0.568 W/(m²-°K)
Unconditioned Space Max Temp. 23.9 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 23.9 °C
Ambient at Space Min Temp. 12.8 °C

7. Partitions:
(No partition data).

Hourly Analysis Program v4.90 Page 2 of 2


Space Input Data
Muara Laboh Geothermal Panel House Wellpad D 03/20/2018
PT.Bayu Sukses Pratama 10:02AM

Panel Room

1. General Details:
Floor Area 27.5 m²
Avg. Ceiling Height 4.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 89.8 L/s
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 216.0 Watts Activity Level Medium Work
Ballast Multiplier 1.00 Sensible 86.5 W/person
Schedule Schedule Latent 133.3 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 4650 W
Schedule Schedule Schedule Schedule
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule Schedule

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
W 22.0 0 0 1
E 22.0 0 0 0
S 20.0 0 0 0

3.1. Construction Types for Exposure W


Wall Type Wall
Door Type Door

3.2. Construction Types for Exposure E


Wall Type Wall

3.3. Construction Types for Exposure S


Wall Type Wall

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 27.5 0 0

4.1. Construction Types for Exposure H


Roof Type Built-up Roof + 203mm LW Concrete

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

Hourly Analysis Program v4.90 Page 1 of 2


Space Input Data
Muara Laboh Geothermal Panel House Wellpad D 03/20/2018
PT.Bayu Sukses Pratama 10:02AM

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 27.5 m²
Total Floor U-Value 0.568 W/(m²-°K)
Unconditioned Space Max Temp. 23.9 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 23.9 °C
Ambient at Space Min Temp. 12.8 °C

7. Partitions:
(No partition data).

Hourly Analysis Program v4.90 Page 2 of 2


Space Input Data
Muara Laboh Geothermal Panel House Wellpad E 03/22/2018
PT.Bayu Sukses Pratama 04:08PM

Battery Room

1. General Details:
Floor Area 17.5 m²
Avg. Ceiling Height 5.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 50.2 L/s
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 72.0 Watts Activity Level User defined
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule Schedule Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 1500 W
Schedule Schedule Schedule Schedule
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.00 W/m²
Schedule None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
N 19.3 0 0 1
E 27.5 0 0 0
S 19.3 0 0 0

3.1. Construction Types for Exposure N


Wall Type Wall
Door Type Door

3.2. Construction Types for Exposure E


Wall Type Wall

3.3. Construction Types for Exposure S


Wall Type Wall

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 17.5 0 0

4.1. Construction Types for Exposure H


Roof Type Built-up Roof + 203mm LW Concrete

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

Hourly Analysis Program v4.90 Page 1 of 2


Space Input Data
Muara Laboh Geothermal Panel House Wellpad E 03/22/2018
PT.Bayu Sukses Pratama 04:08PM

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 17.5 m²
Total Floor U-Value 0.568 W/(m²-°K)
Unconditioned Space Max Temp. 23.9 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 23.9 °C
Ambient at Space Min Temp. 12.8 °C

7. Partitions:
(No partition data).

Hourly Analysis Program v4.90 Page 2 of 2


Space Input Data
Muara Laboh Geothermal Panel House Wellpad E 03/20/2018
PT.Bayu Sukses Pratama 10:03AM

Panel Room

1. General Details:
Floor Area 27.5 m²
Avg. Ceiling Height 4.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 89.8 L/s
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 216.0 Watts Activity Level Medium Work
Ballast Multiplier 1.00 Sensible 86.5 W/person
Schedule Schedule Latent 133.3 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 4650 W
Schedule Schedule Schedule Schedule
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule Schedule

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
N 22.0 0 0 1
W 20.0 0 0 0
S 22.0 0 0 0

3.1. Construction Types for Exposure N


Wall Type Wall
Door Type Door

3.2. Construction Types for Exposure W


Wall Type Wall

3.3. Construction Types for Exposure S


Wall Type Wall

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 27.5 0 0

4.1. Construction Types for Exposure H


Roof Type Built-up Roof + 203mm LW Concrete

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

Hourly Analysis Program v4.90 Page 1 of 2


Space Input Data
Muara Laboh Geothermal Panel House Wellpad E 03/20/2018
PT.Bayu Sukses Pratama 10:03AM

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 27.5 m²
Total Floor U-Value 0.568 W/(m²-°K)
Unconditioned Space Max Temp. 23.9 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 23.9 °C
Ambient at Space Min Temp. 12.8 °C

7. Partitions:
(No partition data).

Hourly Analysis Program v4.90 Page 2 of 2


Space Input Data
Muara Laboh Geothermal Panel House Wellpad F 03/20/2018
PT.Bayu Sukses Pratama 10:04AM

Battery Room

1. General Details:
Floor Area 17.5 m²
Avg. Ceiling Height 5.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 50.2 L/s
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 72.0 Watts Activity Level User defined
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule Schedule Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 200 W
Schedule Schedule Schedule Schedule
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.00 W/m²
Schedule None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
W 19.3 0 0 0
E 19.3 0 0 1
S 27.5 0 0 0

3.1. Construction Types for Exposure W


Wall Type Wall

3.2. Construction Types for Exposure E


Wall Type Wall
Door Type Door

3.3. Construction Types for Exposure S


Wall Type Wall

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 17.5 0 0

4.1. Construction Types for Exposure H


Roof Type Built-up Roof + 203mm LW Concrete

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

Hourly Analysis Program v4.90 Page 1 of 2


Space Input Data
Muara Laboh Geothermal Panel House Wellpad F 03/20/2018
PT.Bayu Sukses Pratama 10:04AM

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 17.5 m²
Total Floor U-Value 0.568 W/(m²-°K)
Unconditioned Space Max Temp. 23.9 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 23.9 °C
Ambient at Space Min Temp. 12.8 °C

7. Partitions:
(No partition data).

Hourly Analysis Program v4.90 Page 2 of 2


Space Input Data
Muara Laboh Geothermal Panel House Wellpad F 03/20/2018
PT.Bayu Sukses Pratama 10:04AM

Panel Room

1. General Details:
Floor Area 27.5 m²
Avg. Ceiling Height 4.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 89.8 L/s
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 216.0 Watts Activity Level Medium Work
Ballast Multiplier 1.00 Sensible 86.5 W/person
Schedule Schedule Latent 133.3 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 4650 W
Schedule Schedule Schedule Schedule
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule Schedule

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
W 22.0 0 0 0
N 20.0 0 0 0
E 22.0 0 0 1

3.1. Construction Types for Exposure W


Wall Type Wall

3.2. Construction Types for Exposure N


Wall Type Wall

3.3. Construction Types for Exposure E


Wall Type Wall
Door Type Door

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 27.5 0 0

4.1. Construction Types for Exposure H


Roof Type Built-up Roof + 203mm LW Concrete

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

Hourly Analysis Program v4.90 Page 1 of 2


Space Input Data
Muara Laboh Geothermal Panel House Wellpad F 03/20/2018
PT.Bayu Sukses Pratama 10:04AM

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 27.5 m²
Total Floor U-Value 0.568 W/(m²-°K)
Unconditioned Space Max Temp. 23.9 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 23.9 °C
Ambient at Space Min Temp. 12.8 °C

7. Partitions:
(No partition data).

Hourly Analysis Program v4.90 Page 2 of 2


Space Input Data
Muara Laboh Geothermal Panel House Wellpad H 03/22/2018
PT.Bayu Sukses Pratama 04:17PM

Battery Room

1. General Details:
Floor Area 17.5 m²
Avg. Ceiling Height 5.5 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 50.2 L/s
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 72.0 Watts Activity Level User defined
Ballast Multiplier 1.00 Sensible 71.8 W/person
Schedule Schedule Latent 60.1 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 1500 W
Schedule Schedule Schedule Schedule
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.00 W/m²
Schedule None

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
W 19.3 0 0 1
N 27.5 0 0 0
E 19.3 0 0 0

3.1. Construction Types for Exposure W


Wall Type Wall
Door Type Door

3.2. Construction Types for Exposure N


Wall Type Wall

3.3. Construction Types for Exposure E


Wall Type Wall

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 17.5 0 0

4.1. Construction Types for Exposure H


Roof Type Built-up Roof + 203mm LW Concrete

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

Hourly Analysis Program v4.90 Page 1 of 2


Space Input Data
Muara Laboh Geothermal Panel House Wellpad H 03/22/2018
PT.Bayu Sukses Pratama 04:17PM

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 17.5 m²
Total Floor U-Value 0.568 W/(m²-°K)
Unconditioned Space Max Temp. 23.9 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 23.9 °C
Ambient at Space Min Temp. 12.8 °C

7. Partitions:
(No partition data).

Hourly Analysis Program v4.90 Page 2 of 2


Space Input Data
Muara Laboh Geothermal Panel House Wellpad H 03/20/2018
PT.Bayu Sukses Pratama 10:05AM

Panel Room

1. General Details:
Floor Area 27.5 m²
Avg. Ceiling Height 4.0 m
Building Weight 341.8 kg/m²
1.1. OA Ventilation Requirements:
Space Usage User-Defined
OA Requirement 1 89.8 L/s
OA Requirement 2 0.00 L/(s-m²)
Space Usage Defaults ASHRAE Standard 62.1-2007

2. Internals:
2.1. Overhead Lighting: 2.4. People:
Fixture Type Recessed (Unvented) Occupancy 0.0 Person
Wattage 216.0 Watts Activity Level Medium Work
Ballast Multiplier 1.00 Sensible 86.5 W/person
Schedule Schedule Latent 133.3 W/person
Schedule None

2.2. Task Lighting: 2.5. Miscellaneous Loads:


Wattage 0.00 W/m² Sensible 4650 W
Schedule Schedule Schedule Schedule
Latent 0 W
Schedule None
2.3. Electrical Equipment:
Wattage 0.0 Watts
Schedule Schedule

3. Walls, Windows, Doors:

Exp. Wall Gross Area (m²) Window 1 Qty. Window 2 Qty. Door 1 Qty.
W 22.0 0 0 0
E 22.0 0 0 0
S 20.0 0 0 0

3.1. Construction Types for Exposure W


Wall Type Wall

3.2. Construction Types for Exposure E


Wall Type Wall

3.3. Construction Types for Exposure S


Wall Type Wall

4. Roofs, Skylights:

Exp. Roof Gross Area (m²) Roof Slope (deg.) Skylight Qty.
H 27.5 0 0

4.1. Construction Types for Exposure H


Roof Type Built-up Roof + 203mm LW Concrete

5. Infiltration:
Design Cooling 0.00 L/s
Design Heating 0.00 L/s
Energy Analysis 0.00 L/s
Infiltration occurs at all hours.

Hourly Analysis Program v4.90 Page 1 of 2


Space Input Data
Muara Laboh Geothermal Panel House Wellpad H 03/20/2018
PT.Bayu Sukses Pratama 10:05AM

6. Floors:
Type Floor Above Unconditioned Space
Floor Area 27.5 m²
Total Floor U-Value 0.568 W/(m²-°K)
Unconditioned Space Max Temp. 23.9 °C
Ambient at Space Max Temp. 35.0 °C
Unconditioned Space Min Temp. 23.9 °C
Ambient at Space Min Temp. 12.8 °C

7. Partitions:
(No partition data).

Hourly Analysis Program v4.90 Page 2 of 2


Air System Sizing Summary for Panel House Wellpad A
Project Name: Muara Laboh Geothermal Panel House Wellpad A 03/22/2018
Prepared by: PT.Bayu Sukses Pratama 04:09PM

Air System Information


Air System Name Panel House Wellpad A Number of zones 1
Equipment Class SPLT AHU Floor Area 45.0 m²
Air System Type SZCAV Location Solok Selatan, Indonesia

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 10.8 kW Load occurs at Jan 1700
Sensible coil load 8.1 kW OA DB / WB 26.0 / 21.5 °C
Coil L/s at Jan 1700 757 L/s Entering DB / WB 22.5 / 16.3 °C
Max block L/s 757 L/s Leaving DB / WB 12.0 / 11.4 °C
Sum of peak zone L/s 757 L/s Coil ADP 10.8 °C
Sensible heat ratio 0.752 Bypass Factor 0.100
m²/kW 4.2 Resulting RH 51 %
W/m² 239.5 Design supply temp. 11.0 °C
Water flow @ 5.6 °K rise N/A Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 757 L/s Fan motor BHP 0.18 BHP
Standard L/s 638 L/s Fan motor kW 0.14 kW
Actual max L/(s-m²) 16.82 L/(s-m²) Fan static 125 Pa

Outdoor Ventilation Air Data


Design airflow L/s 140 L/s L/s/person 0.00 L/s/person
L/(s-m²) 3.11 L/(s-m²)

Hourly Analysis Program v4.90 Page 1 of 6


Zone Sizing Summary for Panel House Wellpad A
Project Name: Muara Laboh Geothermal Panel House Wellpad A 03/22/2018
Prepared by: PT.Bayu Sukses Pratama 04:09PM

Air System Information


Air System Name Panel House Wellpad A Number of zones 1
Equipment Class SPLT AHU Floor Area 45.0 m²
Air System Type SZCAV Location Solok Selatan, Indonesia

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 7.7 757 757 Jan 2000 0.4 45.0 16.82

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
Battery Room 1 2.1 Jan 2000 211 0.2 17.5 12.06
Panel Room 1 5.6 Jan 2100 546 0.2 27.5 19.85

Hourly Analysis Program v4.90 Page 2 of 6


Air System Design Load Summary for Panel House Wellpad A
Project Name: Muara Laboh Geothermal Panel House Wellpad A 03/22/2018
Prepared by: PT.Bayu Sukses Pratama 04:09PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jan 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 26.0 °C / 21.5 °C HEATING OA DB / WB 14.8 °C / 10.7 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 120 m² 572 - 120 m² 270 -
Roof Transmission 45 m² 342 - 45 m² 87 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 10 m² 24 - 10 m² 21 -
Floor Transmission 45 m² 74 - 45 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 288 W 288 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 6150 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 7450 0 - 378 0
Zone Conditioning - 7359 0 - 6 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 757 L/s 0 - 757 L/s 0 -
Ventilation Load 140 L/s 610 2671 140 L/s 146 0
Supply Fan Load 757 L/s 139 - 757 L/s -139 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 8108 2671 - 12 0
Central Cooling Coil - 8108 2672 - 0 0
>> Total Conditioning - 8108 2672 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 3 of 6


Space Design Load Summary for Panel House Wellpad A
Project Name: Muara Laboh Geothermal Panel House Wellpad A 03/22/2018
Prepared by: PT.Bayu Sukses Pratama 04:09PM

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' Battery Room '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 2000 HEATING DATA AT DES HTG
COOLING OA DB / WB 22.3 °C / 20.6 °C HEATING OA DB / WB 14.8 °C / 10.7 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 18.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 61 m² 385 - 61 m² 137 -
Roof Transmission 18 m² 157 - 18 m² 34 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 5 m² 5 - 5 m² 10 -
Floor Transmission 18 m² 29 - 18 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 72 W 72 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 1500 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 2147 0 - 182 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' Battery Room '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
E EXPOSURE
WALL 28 0.702 - 182 - 62
N EXPOSURE
WALL 14 0.702 - 43 - 32
DOOR 5 0.650 - 5 - 10
S EXPOSURE
WALL 19 0.702 - 160 - 43
H EXPOSURE
ROOF 18 0.606 - 157 - 34

Hourly Analysis Program v4.90 Page 4 of 6


Space Design Load Summary for Panel House Wellpad A
Project Name: Muara Laboh Geothermal Panel House Wellpad A 03/22/2018
Prepared by: PT.Bayu Sukses Pratama 04:09PM

TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' Panel Room '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 2100 HEATING DATA AT DES HTG
COOLING OA DB / WB 21.2 °C / 20.3 °C HEATING OA DB / WB 14.8 °C / 10.7 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 18.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 59 m² 400 - 59 m² 133 -
Roof Transmission 28 m² 238 - 28 m² 53 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 5 m² 2 - 5 m² 10 -
Floor Transmission 28 m² 45 - 28 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 216 W 216 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 4650 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 5551 0 - 196 0

TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' Panel Room '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 17 0.702 - 54 - 38
DOOR 5 0.650 - 2 - 10
W EXPOSURE
WALL 20 0.702 - 162 - 45
S EXPOSURE
WALL 22 0.702 - 185 - 49
H EXPOSURE
ROOF 28 0.606 - 238 - 53

Hourly Analysis Program v4.90 Page 5 of 6


Psychrometric Analysis for Panel House Wellpad A
Project Name: Muara Laboh Geothermal Panel House Wellpad A 03/22/2018
Prepared by: PT.Bayu Sukses Pratama 04:09PM

Location: Solok Selatan, Indonesia


Altitude: 1421.8 m.
Data for: January DESIGN COOLING DAY, 1700
0.020
1. Outdoor Air
2. Mixed Air
3. Central Cooling Coil Outlet
4. Supply Fan Outlet 1 0.018
5. Room Air

0.016

0.014

Specific Humidity ( kg/kg )


2 0.012
34 5
0.010

0.008

0.006

0.004

0.002

0.000
0 5 10 15 20 25 30 35
Temperature ( °C )

Hourly Analysis Program v4.90 Page 6 of 6


Air System Sizing Summary for Panel House Wellpad B
Project Name: Muara Laboh Geothermal Panel House Wellpad B 03/22/2018
Prepared by: PT.Bayu Sukses Pratama 05:03PM

Air System Information


Air System Name Panel House Wellpad B Number of zones 1
Equipment Class SPLT AHU Floor Area 45.0 m²
Air System Type SZCAV Location Solok Selatan, Indonesia

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 11.0 kW Load occurs at Jan 1600
Sensible coil load 8.3 kW OA DB / WB 26.7 / 21.7 °C
Coil L/s at Jan 1600 769 L/s Entering DB / WB 22.5 / 16.2 °C
Max block L/s 769 L/s Leaving DB / WB 11.9 / 11.3 °C
Sum of peak zone L/s 769 L/s Coil ADP 10.7 °C
Sensible heat ratio 0.755 Bypass Factor 0.100
m²/kW 4.1 Resulting RH 51 %
W/m² 244.8 Design supply temp. 11.0 °C
Water flow @ 5.6 °K rise N/A Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 769 L/s Fan motor BHP 0.18 BHP
Standard L/s 650 L/s Fan motor kW 0.14 kW
Actual max L/(s-m²) 17.08 L/(s-m²) Fan static 125 Pa

Outdoor Ventilation Air Data


Design airflow L/s 140 L/s L/s/person 0.00 L/s/person
L/(s-m²) 3.11 L/(s-m²)

Hourly Analysis Program v4.90 Page 1 of 6


Zone Sizing Summary for Panel House Wellpad B
Project Name: Muara Laboh Geothermal Panel House Wellpad B 03/22/2018
Prepared by: PT.Bayu Sukses Pratama 05:03PM

Air System Information


Air System Name Panel House Wellpad B Number of zones 1
Equipment Class SPLT AHU Floor Area 45.0 m²
Air System Type SZCAV Location Solok Selatan, Indonesia

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 7.8 769 769 Jan 2100 0.4 45.0 17.08

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
Battery Room 1 2.2 Jan 2100 219 0.2 17.5 12.50
Panel Room 1 5.6 Feb 2100 550 0.2 27.5 20.00

Hourly Analysis Program v4.90 Page 2 of 6


Air System Design Load Summary for Panel House Wellpad B
Project Name: Muara Laboh Geothermal Panel House Wellpad B 03/22/2018
Prepared by: PT.Bayu Sukses Pratama 05:03PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jan 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 26.7 °C / 21.7 °C HEATING OA DB / WB 14.8 °C / 10.7 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 120 m² 483 - 120 m² 270 -
Roof Transmission 45 m² 291 - 45 m² 87 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 10 m² 27 - 10 m² 21 -
Floor Transmission 45 m² 74 - 45 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 288 W 288 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 6250 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 7413 0 - 378 0
Zone Conditioning - 7438 0 - 6 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 769 L/s 0 - 769 L/s 0 -
Ventilation Load 140 L/s 742 2696 140 L/s 147 0
Supply Fan Load 769 L/s 141 - 769 L/s -141 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 8321 2696 - 12 0
Central Cooling Coil - 8321 2697 - 0 0
>> Total Conditioning - 8321 2697 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 3 of 6


Space Design Load Summary for Panel House Wellpad B
Project Name: Muara Laboh Geothermal Panel House Wellpad B 03/22/2018
Prepared by: PT.Bayu Sukses Pratama 05:03PM

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' Battery Room '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 2100 HEATING DATA AT DES HTG
COOLING OA DB / WB 21.2 °C / 20.3 °C HEATING OA DB / WB 14.8 °C / 10.7 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 18.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 61 m² 479 - 61 m² 137 -
Roof Transmission 18 m² 151 - 18 m² 34 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 5 m² 2 - 5 m² 10 -
Floor Transmission 18 m² 29 - 18 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 72 W 72 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 1500 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 2233 0 - 182 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' Battery Room '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
E EXPOSURE
WALL 14 0.702 - 92 - 32
DOOR 5 0.650 - 2 - 10
W EXPOSURE
WALL 19 0.702 - 156 - 43
S EXPOSURE
WALL 28 0.702 - 231 - 62
H EXPOSURE
ROOF 18 0.606 - 151 - 34

Hourly Analysis Program v4.90 Page 4 of 6


Space Design Load Summary for Panel House Wellpad B
Project Name: Muara Laboh Geothermal Panel House Wellpad B 03/22/2018
Prepared by: PT.Bayu Sukses Pratama 05:03PM

TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' Panel Room '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Feb 2100 HEATING DATA AT DES HTG
COOLING OA DB / WB 21.2 °C / 20.3 °C HEATING OA DB / WB 14.8 °C / 10.7 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 18.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 59 m² 357 - 59 m² 133 -
Roof Transmission 28 m² 245 - 28 m² 53 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 5 m² 2 - 5 m² 10 -
Floor Transmission 28 m² 45 - 28 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 216 W 216 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 4750 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 5616 0 - 196 0

TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' Panel Room '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 20 0.702 - 64 - 45
W EXPOSURE
WALL 22 0.702 - 182 - 49
E EXPOSURE
WALL 17 0.702 - 112 - 38
DOOR 5 0.650 - 2 - 10
H EXPOSURE
ROOF 28 0.606 - 245 - 53

Hourly Analysis Program v4.90 Page 5 of 6


Psychrometric Analysis for Panel House Wellpad B
Project Name: Muara Laboh Geothermal Panel House Wellpad B 03/22/2018
Prepared by: PT.Bayu Sukses Pratama 05:03PM

Location: Solok Selatan, Indonesia


Altitude: 1388.3 m.
Data for: January DESIGN COOLING DAY, 1600
0.020
1. Outdoor Air
2. Mixed Air
3. Central Cooling Coil Outlet
4. Supply Fan Outlet 1 0.018
5. Room Air

0.016

0.014

Specific Humidity ( kg/kg )


2 0.012
34 5 0.010

0.008

0.006

0.004

0.002

0.000
0 5 10 15 20 25 30 35
Temperature ( °C )

Hourly Analysis Program v4.90 Page 6 of 6


Air System Sizing Summary for Panel House Wellpad D
Project Name: Muara Laboh Geothermal Panel House Wellpad D 03/22/2018
Prepared by: PT.Bayu Sukses Pratama 04:11PM

Air System Information


Air System Name Panel House Wellpad D Number of zones 1
Equipment Class SPLT AHU Floor Area 45.0 m²
Air System Type SZCAV Location Solok Selatan, Indonesia

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 10.9 kW Load occurs at Dec 1700
Sensible coil load 8.1 kW OA DB / WB 25.4 / 21.5 °C
Coil L/s at Dec 1700 726 L/s Entering DB / WB 22.3 / 16.2 °C
Max block L/s 726 L/s Leaving DB / WB 11.7 / 11.2 °C
Sum of peak zone L/s 726 L/s Coil ADP 10.5 °C
Sensible heat ratio 0.745 Bypass Factor 0.100
m²/kW 4.1 Resulting RH 50 %
W/m² 242.5 Design supply temp. 11.0 °C
Water flow @ 5.6 °K rise N/A Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 726 L/s Fan motor BHP 0.17 BHP
Standard L/s 637 L/s Fan motor kW 0.13 kW
Actual max L/(s-m²) 16.14 L/(s-m²) Fan static 125 Pa

Outdoor Ventilation Air Data


Design airflow L/s 140 L/s L/s/person 0.00 L/s/person
L/(s-m²) 3.11 L/(s-m²)

Hourly Analysis Program v4.90 Page 1 of 6


Zone Sizing Summary for Panel House Wellpad D
Project Name: Muara Laboh Geothermal Panel House Wellpad D 03/22/2018
Prepared by: PT.Bayu Sukses Pratama 04:11PM

Air System Information


Air System Name Panel House Wellpad D Number of zones 1
Equipment Class SPLT AHU Floor Area 45.0 m²
Air System Type SZCAV Location Solok Selatan, Indonesia

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 7.7 726 726 Jan 2100 0.4 45.0 16.14

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
Battery Room 1 2.1 Feb 2100 198 0.2 17.5 11.29
Panel Room 1 5.6 Jan 2000 529 0.2 27.5 19.23

Hourly Analysis Program v4.90 Page 2 of 6


Air System Design Load Summary for Panel House Wellpad D
Project Name: Muara Laboh Geothermal Panel House Wellpad D 03/22/2018
Prepared by: PT.Bayu Sukses Pratama 04:11PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Dec 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 25.4 °C / 21.5 °C HEATING OA DB / WB 14.8 °C / 10.7 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 120 m² 523 - 120 m² 270 -
Roof Transmission 45 m² 324 - 45 m² 87 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 10 m² 21 - 10 m² 21 -
Floor Transmission 45 m² 74 - 45 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 288 W 288 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 6150 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 7380 0 - 378 0
Zone Conditioning - 7416 0 - 5 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 726 L/s 0 - 726 L/s 0 -
Ventilation Load 140 L/s 583 2781 140 L/s 147 0
Supply Fan Load 726 L/s 134 - 726 L/s -134 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 8132 2781 - 19 0
Central Cooling Coil - 8132 2781 - 0 0
>> Total Conditioning - 8132 2781 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 3 of 6


Space Design Load Summary for Panel House Wellpad D
Project Name: Muara Laboh Geothermal Panel House Wellpad D 03/22/2018
Prepared by: PT.Bayu Sukses Pratama 04:11PM

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' Battery Room '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Feb 2100 HEATING DATA AT DES HTG
COOLING OA DB / WB 21.2 °C / 20.2 °C HEATING OA DB / WB 14.8 °C / 10.7 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 18.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 61 m² 333 - 61 m² 137 -
Roof Transmission 18 m² 156 - 18 m² 34 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 5 m² 2 - 5 m² 10 -
Floor Transmission 18 m² 29 - 18 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 72 W 72 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 1500 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 2091 0 - 182 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' Battery Room '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
W EXPOSURE
WALL 14 0.702 - 118 - 32
DOOR 5 0.650 - 2 - 10
N EXPOSURE
WALL 28 0.702 - 88 - 62
E EXPOSURE
WALL 19 0.702 - 127 - 43
H EXPOSURE
ROOF 18 0.606 - 156 - 34

Hourly Analysis Program v4.90 Page 4 of 6


Space Design Load Summary for Panel House Wellpad D
Project Name: Muara Laboh Geothermal Panel House Wellpad D 03/22/2018
Prepared by: PT.Bayu Sukses Pratama 04:11PM

TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' Panel Room '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 2000 HEATING DATA AT DES HTG
COOLING OA DB / WB 22.3 °C / 20.5 °C HEATING OA DB / WB 14.8 °C / 10.7 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 18.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 59 m² 438 - 59 m² 133 -
Roof Transmission 28 m² 246 - 28 m² 53 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 5 m² 5 - 5 m² 10 -
Floor Transmission 28 m² 45 - 28 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 216 W 216 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 4650 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 5600 0 - 196 0

TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' Panel Room '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
W EXPOSURE
WALL 17 0.702 - 127 - 38
DOOR 5 0.650 - 5 - 10
E EXPOSURE
WALL 22 0.702 - 145 - 49
S EXPOSURE
WALL 20 0.702 - 166 - 45
H EXPOSURE
ROOF 28 0.606 - 246 - 53

Hourly Analysis Program v4.90 Page 5 of 6


Psychrometric Analysis for Panel House Wellpad D
Project Name: Muara Laboh Geothermal Panel House Wellpad D 03/22/2018
Prepared by: PT.Bayu Sukses Pratama 04:11PM

Location: Solok Selatan, Indonesia


Altitude: 1093.3 m.
Data for: December DESIGN COOLING DAY, 1700
0.020
1. Outdoor Air
2. Mixed Air
3. Central Cooling Coil Outlet
4. Supply Fan Outlet
1
0.018
5. Room Air

0.016

0.014

Specific Humidity ( kg/kg )


0.012
2

34 5 0.010

0.008

0.006

0.004

0.002

0.000
0 5 10 15 20 25 30 35
Temperature ( °C )

Hourly Analysis Program v4.90 Page 6 of 6


Air System Sizing Summary for Panel House Wellpad E
Project Name: Muara Laboh Geothermal Panel House Wellpad E 03/22/2018
Prepared by: PT.Bayu Sukses Pratama 05:28PM

Air System Information


Air System Name Panel House Wellpad E Number of zones 1
Equipment Class SPLT AHU Floor Area 45.0 m²
Air System Type SZCAV Location Solok Selatan, Indonesia

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 10.8 kW Load occurs at Jan 1700
Sensible coil load 8.1 kW OA DB / WB 26.0 / 21.5 °C
Coil L/s at Jan 1700 738 L/s Entering DB / WB 22.5 / 16.3 °C
Max block L/s 738 L/s Leaving DB / WB 12.0 / 11.4 °C
Sum of peak zone L/s 738 L/s Coil ADP 10.8 °C
Sensible heat ratio 0.754 Bypass Factor 0.100
m²/kW 4.2 Resulting RH 51 %
W/m² 239.4 Design supply temp. 11.0 °C
Water flow @ 5.6 °K rise N/A Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 738 L/s Fan motor BHP 0.17 BHP
Standard L/s 638 L/s Fan motor kW 0.14 kW
Actual max L/(s-m²) 16.39 L/(s-m²) Fan static 125 Pa

Outdoor Ventilation Air Data


Design airflow L/s 140 L/s L/s/person 0.00 L/s/person
L/(s-m²) 3.11 L/(s-m²)

Hourly Analysis Program v4.90 Page 1 of 6


Zone Sizing Summary for Panel House Wellpad E
Project Name: Muara Laboh Geothermal Panel House Wellpad E 03/22/2018
Prepared by: PT.Bayu Sukses Pratama 05:28PM

Air System Information


Air System Name Panel House Wellpad E Number of zones 1
Equipment Class SPLT AHU Floor Area 45.0 m²
Air System Type SZCAV Location Solok Selatan, Indonesia

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 7.7 738 738 Jan 2000 0.4 45.0 16.39

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
Battery Room 1 2.1 Jan 2000 206 0.2 17.5 11.75
Panel Room 1 5.6 Jan 2100 532 0.2 27.5 19.35

Hourly Analysis Program v4.90 Page 2 of 6


Air System Design Load Summary for Panel House Wellpad E
Project Name: Muara Laboh Geothermal Panel House Wellpad E 03/22/2018
Prepared by: PT.Bayu Sukses Pratama 05:28PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Jan 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 26.0 °C / 21.5 °C HEATING OA DB / WB 14.8 °C / 10.7 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 120 m² 572 - 120 m² 270 -
Roof Transmission 45 m² 342 - 45 m² 87 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 10 m² 24 - 10 m² 21 -
Floor Transmission 45 m² 74 - 45 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 288 W 288 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 6150 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 7450 0 - 378 0
Zone Conditioning - 7360 0 - 5 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 738 L/s 0 - 738 L/s 0 -
Ventilation Load 140 L/s 628 2650 140 L/s 147 0
Supply Fan Load 738 L/s 136 - 738 L/s -136 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 8124 2650 - 17 0
Central Cooling Coil - 8124 2651 - 0 0
>> Total Conditioning - 8124 2651 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 3 of 6


Space Design Load Summary for Panel House Wellpad E
Project Name: Muara Laboh Geothermal Panel House Wellpad E 03/22/2018
Prepared by: PT.Bayu Sukses Pratama 05:28PM

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' Battery Room '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 2000 HEATING DATA AT DES HTG
COOLING OA DB / WB 22.3 °C / 20.5 °C HEATING OA DB / WB 14.8 °C / 10.7 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 18.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 61 m² 385 - 61 m² 137 -
Roof Transmission 18 m² 157 - 18 m² 34 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 5 m² 5 - 5 m² 10 -
Floor Transmission 18 m² 29 - 18 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 72 W 72 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 1500 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 2147 0 - 182 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' Battery Room '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 14 0.702 - 43 - 32
DOOR 5 0.650 - 5 - 10
E EXPOSURE
WALL 28 0.702 - 182 - 62
S EXPOSURE
WALL 19 0.702 - 160 - 43
H EXPOSURE
ROOF 18 0.606 - 157 - 34

Hourly Analysis Program v4.90 Page 4 of 6


Space Design Load Summary for Panel House Wellpad E
Project Name: Muara Laboh Geothermal Panel House Wellpad E 03/22/2018
Prepared by: PT.Bayu Sukses Pratama 05:28PM

TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' Panel Room '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 2100 HEATING DATA AT DES HTG
COOLING OA DB / WB 21.2 °C / 20.2 °C HEATING OA DB / WB 14.8 °C / 10.7 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 18.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 59 m² 400 - 59 m² 133 -
Roof Transmission 28 m² 238 - 28 m² 53 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 5 m² 2 - 5 m² 10 -
Floor Transmission 28 m² 45 - 28 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 216 W 216 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 4650 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 5551 0 - 196 0

TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' Panel Room '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
N EXPOSURE
WALL 17 0.702 - 54 - 38
DOOR 5 0.650 - 2 - 10
W EXPOSURE
WALL 20 0.702 - 162 - 45
S EXPOSURE
WALL 22 0.702 - 185 - 49
H EXPOSURE
ROOF 28 0.606 - 238 - 53

Hourly Analysis Program v4.90 Page 5 of 6


Psychrometric Analysis for Panel House Wellpad E
Project Name: Muara Laboh Geothermal Panel House Wellpad E 03/22/2018
Prepared by: PT.Bayu Sukses Pratama 05:28PM

Location: Solok Selatan, Indonesia


Altitude: 1212.3 m.
Data for: January DESIGN COOLING DAY, 1700
0.020
1. Outdoor Air
2. Mixed Air
3. Central Cooling Coil Outlet
4. Supply Fan Outlet 1
0.018
5. Room Air

0.016

0.014

Specific Humidity ( kg/kg )


2
0.012
34 5 0.010

0.008

0.006

0.004

0.002

0.000
0 5 10 15 20 25 30 35
Temperature ( °C )

Hourly Analysis Program v4.90 Page 6 of 6


Air System Sizing Summary for Panel House Wellpad F
Project Name: Muara Laboh Geothermal Panel House Wellpad F 03/22/2018
Prepared by: PT.Bayu Sukses Pratama 05:30PM

Air System Information


Air System Name Panel House Wellpad F Number of zones 1
Equipment Class SPLT AHU Floor Area 45.0 m²
Air System Type SZCAV Location Solok Selatan, Indonesia

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 10.8 kW Load occurs at Dec 1700
Sensible coil load 8.0 kW OA DB / WB 25.4 / 21.5 °C
Coil L/s at Dec 1700 765 L/s Entering DB / WB 22.3 / 16.2 °C
Max block L/s 765 L/s Leaving DB / WB 12.0 / 11.4 °C
Sum of peak zone L/s 765 L/s Coil ADP 10.8 °C
Sensible heat ratio 0.745 Bypass Factor 0.100
m²/kW 4.2 Resulting RH 51 %
W/m² 239.2 Design supply temp. 11.0 °C
Water flow @ 5.6 °K rise N/A Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 765 L/s Fan motor BHP 0.18 BHP
Standard L/s 642 L/s Fan motor kW 0.14 kW
Actual max L/(s-m²) 17.01 L/(s-m²) Fan static 125 Pa

Outdoor Ventilation Air Data


Design airflow L/s 140 L/s L/s/person 0.00 L/s/person
L/(s-m²) 3.11 L/(s-m²)

Hourly Analysis Program v4.90 Page 1 of 6


Zone Sizing Summary for Panel House Wellpad F
Project Name: Muara Laboh Geothermal Panel House Wellpad F 03/22/2018
Prepared by: PT.Bayu Sukses Pratama 05:30PM

Air System Information


Air System Name Panel House Wellpad F Number of zones 1
Equipment Class SPLT AHU Floor Area 45.0 m²
Air System Type SZCAV Location Solok Selatan, Indonesia

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 7.7 765 765 Jan 2100 0.4 45.0 17.01

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
Battery Room 1 2.2 Jan 2100 221 0.2 17.5 12.61
Panel Room 1 5.5 Feb 2100 545 0.2 27.5 19.81

Hourly Analysis Program v4.90 Page 2 of 6


Air System Design Load Summary for Panel House Wellpad F
Project Name: Muara Laboh Geothermal Panel House Wellpad F 03/22/2018
Prepared by: PT.Bayu Sukses Pratama 05:30PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Dec 1700 HEATING DATA AT DES HTG
COOLING OA DB / WB 25.4 °C / 21.5 °C HEATING OA DB / WB 14.8 °C / 10.7 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 120 m² 539 - 120 m² 270 -
Roof Transmission 45 m² 324 - 45 m² 87 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 10 m² 21 - 10 m² 21 -
Floor Transmission 45 m² 74 - 45 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 288 W 288 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 6150 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 7396 0 - 378 0
Zone Conditioning - 7337 0 - 6 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 765 L/s 0 - 765 L/s 0 -
Ventilation Load 140 L/s 539 2748 140 L/s 146 0
Supply Fan Load 765 L/s 141 - 765 L/s -141 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 8018 2748 - 11 0
Central Cooling Coil - 8018 2748 - 0 0
>> Total Conditioning - 8018 2748 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 3 of 6


Space Design Load Summary for Panel House Wellpad F
Project Name: Muara Laboh Geothermal Panel House Wellpad F 03/22/2018
Prepared by: PT.Bayu Sukses Pratama 05:30PM

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' Battery Room '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 2100 HEATING DATA AT DES HTG
COOLING OA DB / WB 21.2 °C / 20.3 °C HEATING OA DB / WB 14.8 °C / 10.7 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 18.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 61 m² 479 - 61 m² 137 -
Roof Transmission 18 m² 151 - 18 m² 34 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 5 m² 2 - 5 m² 10 -
Floor Transmission 18 m² 29 - 18 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 72 W 72 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 1500 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 2233 0 - 182 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' Battery Room '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
W EXPOSURE
WALL 19 0.702 - 156 - 43
E EXPOSURE
WALL 14 0.702 - 92 - 32
DOOR 5 0.650 - 2 - 10
S EXPOSURE
WALL 28 0.702 - 231 - 62
H EXPOSURE
ROOF 18 0.606 - 151 - 34

Hourly Analysis Program v4.90 Page 4 of 6


Space Design Load Summary for Panel House Wellpad F
Project Name: Muara Laboh Geothermal Panel House Wellpad F 03/22/2018
Prepared by: PT.Bayu Sukses Pratama 05:30PM

TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' Panel Room '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Feb 2100 HEATING DATA AT DES HTG
COOLING OA DB / WB 21.2 °C / 20.3 °C HEATING OA DB / WB 14.8 °C / 10.7 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 18.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 59 m² 357 - 59 m² 133 -
Roof Transmission 28 m² 245 - 28 m² 53 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 5 m² 2 - 5 m² 10 -
Floor Transmission 28 m² 45 - 28 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 216 W 216 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 4650 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 5516 0 - 196 0

TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' Panel Room '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
W EXPOSURE
WALL 22 0.702 - 182 - 49
N EXPOSURE
WALL 20 0.702 - 64 - 45
E EXPOSURE
WALL 17 0.702 - 112 - 38
DOOR 5 0.650 - 2 - 10
H EXPOSURE
ROOF 28 0.606 - 245 - 53

Hourly Analysis Program v4.90 Page 5 of 6


Psychrometric Analysis for Panel House Wellpad F
Project Name: Muara Laboh Geothermal Panel House Wellpad F 03/22/2018
Prepared by: PT.Bayu Sukses Pratama 05:30PM

Location: Solok Selatan, Indonesia


Altitude: 1460.3 m.
Data for: December DESIGN COOLING DAY, 1700
0.020
1. Outdoor Air
2. Mixed Air
3. Central Cooling Coil Outlet 1
4. Supply Fan Outlet 0.018
5. Room Air

0.016

0.014

Specific Humidity ( kg/kg )


2 0.012
34 5
0.010

0.008

0.006

0.004

0.002

0.000
0 5 10 15 20 25 30 35
Temperature ( °C )

Hourly Analysis Program v4.90 Page 6 of 6


Air System Sizing Summary for Panel House Wellpad H
Project Name: Muara Laboh Geothermal Panel House Wellpad H 03/22/2018
Prepared by: PT.Bayu Sukses Pratama 05:30PM

Air System Information


Air System Name Panel House Wellpad H Number of zones 1
Equipment Class SPLT AHU Floor Area 45.0 m²
Air System Type SZCAV Location Solok Selatan, Indonesia

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Central Cooling Coil Sizing Data


Total coil load 10.8 kW Load occurs at Feb 1500
Sensible coil load 8.1 kW OA DB / WB 27.0 / 21.8 °C
Coil L/s at Feb 1500 773 L/s Entering DB / WB 22.5 / 16.2 °C
Max block L/s 773 L/s Leaving DB / WB 12.0 / 11.4 °C
Sum of peak zone L/s 773 L/s Coil ADP 10.8 °C
Sensible heat ratio 0.751 Bypass Factor 0.100
m²/kW 4.2 Resulting RH 51 %
W/m² 240.3 Design supply temp. 11.0 °C
Water flow @ 5.6 °K rise N/A Zone T-stat Check 1 of 1 OK
Max zone temperature deviation 0.0 °K

Supply Fan Sizing Data


Actual max L/s 773 L/s Fan motor BHP 0.18 BHP
Standard L/s 640 L/s Fan motor kW 0.14 kW
Actual max L/(s-m²) 17.18 L/(s-m²) Fan static 125 Pa

Outdoor Ventilation Air Data


Design airflow L/s 140 L/s L/s/person 0.00 L/s/person
L/(s-m²) 3.11 L/(s-m²)

Hourly Analysis Program v4.90 Page 1 of 6


Zone Sizing Summary for Panel House Wellpad H
Project Name: Muara Laboh Geothermal Panel House Wellpad H 03/22/2018
Prepared by: PT.Bayu Sukses Pratama 05:30PM

Air System Information


Air System Name Panel House Wellpad H Number of zones 1
Equipment Class SPLT AHU Floor Area 45.0 m²
Air System Type SZCAV Location Solok Selatan, Indonesia

Sizing Calculation Information


Calculation Months Jan to Dec Zone L/s Sizing Sum of space airflow rates
Sizing Data Calculated Space L/s Sizing Individual peak space loads

Zone Sizing Data

Maximum Maximum Zone


Cooling Design Minimum Heating Floor
Sensible Airflow Airflow Time of Load Area Zone
Zone Name (kW) (L/s) (L/s) Peak Load (kW) (m²) L/(s-m²)
Zone 1 7.7 773 773 Jan 2100 0.4 45.0 17.18

Zone Terminal Sizing Data


No Zone Terminal Sizing Data required for this system.

Space Loads and Airflows

Cooling Time Air Heating Floor


Zone Name / Sensible of Flow Load Area Space
Space Name Mult. (kW) Load (L/s) (kW) (m²) L/(s-m²)
Zone 1
Battery Room 1 2.1 Feb 2100 209 0.2 17.5 11.95
Panel Room 1 5.6 Jan 2100 564 0.2 27.5 20.50

Hourly Analysis Program v4.90 Page 2 of 6


Air System Design Load Summary for Panel House Wellpad H
Project Name: Muara Laboh Geothermal Panel House Wellpad H 03/22/2018
Prepared by: PT.Bayu Sukses Pratama 05:30PM

DESIGN COOLING DESIGN HEATING


COOLING DATA AT Feb 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 27.0 °C / 21.8 °C HEATING OA DB / WB 14.8 °C / 10.7 °C
Sensible Latent Sensible Latent
ZONE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 125 m² 400 - 125 m² 281 -
Roof Transmission 45 m² 238 - 45 m² 87 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 5 m² 14 - 5 m² 10 -
Floor Transmission 45 m² 74 - 45 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 288 W 288 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 6150 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 7164 0 - 379 0
Zone Conditioning - 7208 0 - 6 0
Plenum Wall Load 0% 0 - 0 0 -
Plenum Roof Load 0% 0 - 0 0 -
Plenum Lighting Load 0% 0 - 0 0 -
Return Fan Load 773 L/s 0 - 773 L/s 0 -
Ventilation Load 140 L/s 773 2689 140 L/s 145 0
Supply Fan Load 773 L/s 142 - 773 L/s -142 -
Space Fan Coil Fans - 0 - - 0 -
Duct Heat Gain / Loss 0% 0 - 0% 0 -
>> Total System Loads - 8123 2689 - 9 0
Central Cooling Coil - 8123 2689 - 0 0
>> Total Conditioning - 8123 2689 - 0 0
Key: Positive values are clg loads Positive values are htg loads
Negative values are htg loads Negative values are clg loads

Hourly Analysis Program v4.90 Page 3 of 6


Space Design Load Summary for Panel House Wellpad H
Project Name: Muara Laboh Geothermal Panel House Wellpad H 03/22/2018
Prepared by: PT.Bayu Sukses Pratama 05:30PM

TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' Battery Room '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Feb 2100 HEATING DATA AT DES HTG
COOLING OA DB / WB 21.2 °C / 20.3 °C HEATING OA DB / WB 14.8 °C / 10.7 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 18.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 61 m² 333 - 61 m² 137 -
Roof Transmission 18 m² 156 - 18 m² 34 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 5 m² 2 - 5 m² 10 -
Floor Transmission 18 m² 29 - 18 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 72 W 72 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 1500 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 2091 0 - 182 0

TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' Battery Room '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
W EXPOSURE
WALL 14 0.702 - 118 - 32
DOOR 5 0.650 - 2 - 10
N EXPOSURE
WALL 28 0.702 - 88 - 62
E EXPOSURE
WALL 19 0.702 - 127 - 43
H EXPOSURE
ROOF 18 0.606 - 156 - 34

Hourly Analysis Program v4.90 Page 4 of 6


Space Design Load Summary for Panel House Wellpad H
Project Name: Muara Laboh Geothermal Panel House Wellpad H 03/22/2018
Prepared by: PT.Bayu Sukses Pratama 05:30PM

TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' Panel Room '' IN ZONE '' Zone 1 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 2100 HEATING DATA AT DES HTG
COOLING OA DB / WB 21.2 °C / 20.3 °C HEATING OA DB / WB 14.8 °C / 10.7 °C
OCCUPIED T-STAT 21.0 °C OCCUPIED T-STAT 18.0 °C
Sensible Latent Sensible Latent
SPACE LOADS Details (W) (W) Details (W) (W)
Window & Skylight Solar Loads 0 m² 0 - 0 m² - -
Wall Transmission 64 m² 488 - 64 m² 144 -
Roof Transmission 28 m² 238 - 28 m² 53 -
Window Transmission 0 m² 0 - 0 m² 0 -
Skylight Transmission 0 m² 0 - 0 m² 0 -
Door Loads 0 m² 0 - 0 m² 0 -
Floor Transmission 28 m² 45 - 28 m² 0 -
Partitions 0 m² 0 - 0 m² 0 -
Ceiling 0 m² 0 - 0 m² 0 -
Overhead Lighting 216 W 216 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 0W 0 - 0 0 -
People 0 0 0 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 4650 0 - 0 0
Safety Factor 0% / 0% 0 0 0% 0 0
>> Total Zone Loads - 5637 0 - 197 0

TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' Panel Room '' IN ZONE '' Zone 1 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(m²) (W/(m²-°K)) Coeff. (W) (W) (W)
W EXPOSURE
WALL 22 0.702 - 178 - 49
E EXPOSURE
WALL 22 0.702 - 142 - 49
S EXPOSURE
WALL 20 0.702 - 168 - 45
H EXPOSURE
ROOF 28 0.606 - 238 - 53

Hourly Analysis Program v4.90 Page 5 of 6


Psychrometric Analysis for Panel House Wellpad H
Project Name: Muara Laboh Geothermal Panel House Wellpad H 03/22/2018
Prepared by: PT.Bayu Sukses Pratama 05:30PM

Location: Solok Selatan, Indonesia


Altitude: 1562.3 m.
Data for: February DESIGN COOLING DAY, 1500
0.020
1. Outdoor Air
2. Mixed Air
3. Central Cooling Coil Outlet 1
4. Supply Fan Outlet 0.018
5. Room Air

0.016

0.014

Specific Humidity ( kg/kg )


2 0.012
34 5
0.010

0.008

0.006

0.004

0.002

0.000
0 5 10 15 20 25 30 35
Temperature ( °C )

Hourly Analysis Program v4.90 Page 6 of 6


1 2 3 4 5 6 7 8 9 10 11 12
A
B H-6
x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x

x
x
x
x
x
x
x
B

x
x
x
x
x
x
x x x x x x x x x x x x x x x x x x x x x x

x
x

x
x

x
x

x
x

x
x

x
x

x
x

x
x

x
x

x
x

x
x
x

x
x

E 735500

E 736000

E 736500

E 737000

E 737500

E 738000

E 738500

E 739000

E 739500
x

x
x

x
x

x
x

x
x

x
x

x
x

x
C

x
x
x
x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x

x
x

x
x

x
x

x
x

x
x

x
D
E
F
G
ISSUED FOR REVIEW
ATTACHED XREF FILES PROJECT TITLE
H supremeenergy
DRAWN DRAFT. CHECK REVIEWED APPROVED
SCALE DRAWING No REV
REV DATE DESCRIPTION DRAWN REV'D APP'D
SUPREME ENERGY MUARA LABOH CONT. DWG No DESIGNED DESGN. REVIEW
DATE DATE
1 2 3 4 5 6 7 8 9 10 11 12 A3

You might also like