Automatic Transfer Switch With Auxiliary Power System For Cadet Hostel

You might also like

Download as docx, pdf, or txt
Download as docx, pdf, or txt
You are on page 1of 6

Automatic Transfer Switch with Auxiliary Power System

for Cadet Hostel


Hein Htet Aung
Department of Electrical Power Engineering, Defence Services Technological Academy, Myanmar
Abstract - This paper focus on the development of
auxiliary power system that allow user to use electric power
without breaking. The main objective is to design a simple,
reliable and cost effective system using control theory, basic
electrical calculation and electrical appliances. . The
system adapts serial connection of the cables with electrical
appliances from grid power system and auxiliary power
system. Generally, module case circuit breaker (MCCB)
and miniature circuit breaker (MCB) are used for short
circuit protection in this system. To receive power demand The total lighting power demand for this hostel is about
enough for five-storey cadet hostel, suitable batteries, 9275 W. When there is no power on the national grid,
battery chargers and inverters are used in auxiliary power
system.

Keywords –Battery, inverter/charger, automatic transfer


switch, connection cable, circuit breaker.

I .INTRODUCTION

Auxiliary power supply system plays as an vital


role in the developing countries. When the grid power is
shut down due to environmental effects and human
errors, auxiliary power is needed. According to the
power system of Myanmar, backup power systems are this power is used for a limit time. This period is 12
the most essential requirement to the vital areas such as hours that is 6 hours per day for two days.
hospitals, control stations, power transmission
substations, airports etc.

Fig. 1 Backup power system

Fig. 2 Backup power system for lighting load

The elementary unit for backup power system are as


follows:
There are many technologies for backup power 1. Loads(total power demand)
system. They are generator used backup power system,
solar power used backup power system, bioenergy used 2. Electrical appliances(cable and circuit breaker)
backup power system, wind power used backup power
3. Auxiliary power supply
system and grid power charging backup power
system.For lighting power system in residuals zones, 4. Automatic transfer switch
grid power charging backup power system is most useful
than other systems because this system is economic and
without manual operation. As the result of this project,
cadets can use lightning power at a limit time that is 24
hours without grid power. (a) (b)

Fig. 3 (a) 25 W bulb

(b) 40 W lamp
II.AUXILIARY POWER SYSTEM (OR) BACKUP POWER
SYSTEM

In this paper, auxiliary power system is used for


lighting in cadet hostel. The cadet hostel (Myin Saing) is
located in Bayint Naung Batallium and have five-storey.
III. TOTAL POWER DEMAND Power demand for R-phase = 3090 W
Fig. 4 Power distribution in cadet hostel Power demand for Y-phase = 3130 W

Power demand for B-phase = 3055 W

Fig. 6Equivalent power for each phase

IV. CABLE SIZING AND SELECTION


The power of bulb used in cadet hostel = 25 W
To meet various electrical and environmental
The power of lump used in cadet hostel = 40 W operating conditions, multitude types of cable which are
available for incorporation in the low voltage system are
required. Environmental conditions may require cables
which are capable of operation in the presence of water
or moisture, or when subjected to fire risk, or in
extremes of temperature. If the environment is such that
the cable is subjected to such hazards, cables should be
selected with appropriate insulation and sheathing
materials. The commonly used low-voltage cables are as
follows :

(1)Non-armoured pvc-insulated cables installed in


conduits and trunking systems for internal wiring.

(2)Non-armoured pvc-insulated and pvc-sheathed cables


Fig. 5 Power distribution for each feeder for generalindoor use, particularly in domestic and
commercial installations.

Total power demand for first-floor = 1875 W (3)Armoured pvc-insulated cables for mains and sub-
mains applications(i.e. utility’s low-voltage circuits
Total power demand for second-floor = 1845 W buried underground).
Total power demand for third-floor = 1845 W (4) Fire resistant cables or mineral insulated metal
sheathed cables used in areas of extreme temperatures
or for circuits supplied to firefighting equipment.
Total power demand for fourth-floor = 1845 W
(5)Heat, oil and flame retardant cables are intended for
Total power demand for fifth-floor = 1845 W use in severe conditions : examples of these are csp
Total power demand for the hole hostel = 9275 W (chlorosulphinatedpolyethylene) and
pcp(polycholoroprene) sheathed cables.

In this paper, type (1) cable is used that it is


This magnitude is large for single phase in non-armoured pvc-insulated cables installed in conduits
hostel installation. So, these power is equally divided and trunking systems for internal wiring. For choosing
into three phase according to each feeder. suitable cable size, the following equations are used.

P=VIcosθ (1)

Where,

P = power (W)

V = voltage (V)

I = current (A)
cos ɵ = power factor I n= 2 A (MCB selection)
In I t=5.319 A
I t= (2)
C a × C g × Ci ×C d
1 mm2 cable is used.
Where,
For ladder lighting feeder in first floor (175 W),
It = totalcurrent
I b=0.895 A
In = nominalcurrent(from circuit breaker selection)
I n= 1 A (MCB selection)
Ca = correction factor ambient temperature

Cg = correction factor for group I t=2.659 A

Ci = correction factor for thermal insulation 1 mm2 cable is used.

Cd = correction factor depend on protective Cable size for R-phase,

For corridor lighting feeder (150 W), P = 3090 W

P=VIcosθ I b=15.81 A

V = 230 V, I n= 20 A (MCCB selection)


power factor = 0.85 I t=53.19 A
P
I b= 16 mm2 cable is used.
V cosθ
Cable size for Y-phase,
I b=0.767 A
P = 3130 W
I n= 1 A (MCB selection)
I b=16.01 A
In
I t= I n= 20 A (MCCB selection)
C a × C g × Ci ×C d
I t=53.19 A
C a=0.94
16 mm2 cable is used.
C g= 0.8
Cable size for B-phase,
C i=0.5
P = 3055 W
C d=1 I b=15.62 A
I t=2.659 A I n= 20 A (MCCB selection)
1 mm2 cable is used.
I t=53.19 A
For ladder lighting feeder (125 W),
16 mm2 cable is used.
I b=0.639 A TABLE .1

I n= 1 A (MCB selection) CABLE SIZING AND SELECTION TABLE

I t=2.659 A
1 mm2 cable is used.

For room lighting feeder (280 W),

I b=1.432 A
Fig. 8 Molded case circuit breaker ( MCCB)

From this table,

(1/.044) cable size is used for each feeder.

(7/.064) cable size is used for each phase.

V. CIRCUIT BREAKER SELECTION

Miniature circuit breaker(MCB) or Molded case


circuit breaker(MCCB) are widely used in electrical
distribution and installation system for ON/OFF
Fig. 9 Installation of MCB and MCCB for loads
electrical supply and it also give over current and short
circuit protection. Some parameters are important for the VI. AUXILIARY POWER SUPPLY SYSTEMS
selection of circuit breaker. The function of auxiliary power supply system
is to store energy when it is not necessary the backup
Following specification are required to select power by the load. If there is necessary to use backup
appropriate MCB /MCCB. power, it produce the power again from it. Usually, the
auxiliary power system has two main components:
1. Current Related
A. Battery
2. Voltage Related B. Inverter/charger
3. Application Types
4. Accessories
5. Protection Types
6. Other

For lighting load , MCB (2 A)and MCB (1A) is used for


each feeder.

Fig. 10 Components of auxiliary power system

A . Battery

One of the most popular methods of energy storage is


the implementation of batteries, which make use of the
electrochemical process, whereby an electrochemical
Fig. 7 Miniature circuit breaker(MCB) cell, containing a cathode and an anode, storeselectrical
energy and then releases it as and when required by the
For R,Y,B phases, MCCB (32 A) is used for each phase. consumer.

There are many key specifications of batteries


that determine the quality of storage. Some of the most
important of which are:

1. capacity
2. round-trip efficiency
3. self- discharge
4. lifetime and number of cycles
5. depth of discharge
6. charge rate typical inverter system will be used, based on products
7. discharge rate and available on the market.
8. cost.

Total Ampere hour (Ah) calculation,

Total lighting power used in cadet hostel=9275 W

For using 2 days (6 hours/1 day) =9275×2×6

= 111300 W

Battery(assuming20% maximum discharge)= 111300×


1
0.2
= 556500 W

1
For inverter efficiency (85%) =556500×
0.85
= 654705.88 W

The 24 V battery bank is used. Fig. 12 Batteries in series /parallel connection

654705.88 For Y-phase, total power = 3130W


The required Ah is =
24
Apparent power = 3130/0.85
= 27279.4 Ah / 24 Vbattery bank
= 3682.35VA
It is nearly 28000 Ah.
For B-phase, total power = 3055 W
In this paper, (12 V,200 Ah) lead acid battery is used.
Apparent power = 3055/0.85

= 3594.12VA

Therefore, (24 V, 4000 VA) inverter is used.


Fig. 13 (24 V, 4000 VA) inverter

Fig(11)-12 V, 200 Ah Lead acid battery

For 28000 Ah , (12 V,200 Ah) lead acid batteries are


connected in series/parallel.

28000 Ah
Number of batteries =
100 Ah
= 280

Fig. 14 Inverter connection for each phase


B .Inverter/Charger

When using a battery in a residential renewable


energy system, it is necessary to have an AC/DC
inverter, as household appliances and other loads run on VII. AUTOMATIC TRANSFER SWITCH (ATS)
alternating current and battery systems require direct
current. For the simulations carried out for this thesis, a Used for switching power between the primary
(utility) and secondary (backup or supplemental) power
sources, Cummins automatic transfer switches feature
Power Command control technology for easy operation, upgraded to recharge with renewable energy such as
and a robust, high-contact-force design to withstand solar and wind energy. For the feature work, laptops and
thousands of switching cycles. A full line of standard phones will be charged by improving the components in
switches is available from 40 to 4,000 amps for the this system for all cadets.
entire range of power systems with common bus
communication language.
ACKNOWLEDGMENT
1. Open-transition transfer
2. Programmed-transition transfer The author would like to express thankful to
3. Closed-transition transfer Lieuternant Colonel Min Zaw Thein, Head of
Department of Electrical Power Engineering, Defence
In this paper, open –transition transfer switch is used.
Services Technological Academy for giving the
A. Open-transition transfer, permission to submit this paper. The author would like
to express grateful thank to his supervisor Captain Htike
Break-before-makes witching action: The most Linn Aung, Assistant Lecturer, Department of Electrical
basic type of transfer; the connection to one source is Power Engineering, Defence Services Technological
opened before the connection to the second source is Academy for his accomplished guidance and helpful
closed. The sync-check feature included in the open- suggestion. The author wishes to express his gratitude to
transition transfer control monitors both sources and all persons who helped directly and indirectly towards
initiates the transfer—avoiding out-of-phase closing. the successful completion of this paper.

REFERENCES
[1] General Cable , “Conductor Size: Imprerial/Metric Comparison ”
, www.generalcable
[2] Teo Cheng Yu , “Principles and Design of LOW VOLTAGE
SYSTEM” , 2nd Edition , 252Ps
[3] Tervor Linsney, “Advanced Electrical Installation Work”, 5th
Education , 411 P
[4] Tervor Linsney, “Basic Electrical InstallationWork”, 4th
Education , 297 P

(120 V/60 Hz) Lithium-Ion battery

Fig. 15 Automatic transfer switch

Fig. 16Wiring diagram of ATS

VIII. CONCLUSION

The auxiliary power system is very useful


during rainy and stormy weather for cadet hostel,
especially in Cadet’s exam period. This system can be

You might also like