INSTRUCTION MANUAL

WATT TRANSDUCER MODEL LTWT


■■ENVIRONMENT
BEFORE USE .... • Indoor use.
Thank you for choosing M-System. Before use, please check • When heavy dust or metal particles are present in the
contents of the package you received as outlined below. air, install the unit inside proper housing with sufficient
If you have any problems or questions with the product, ventilation.
please contact M-System’s Sales Office or representatives. • Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
■■PACKAGE INCLUDES: • Environmental temperature must be within -10 to +55°C
(14 to 131°F) with relative humidity within 30 to 85% RH
Watt transducer...................................................................(1)
in order to ensure adequate life span and operation.
■■MODEL NO.
■■WIRING
Confirm Model No. marking on the product to be exactly
• Do not install cables close to noise sources (relay drive
what you ordered.
cable, high frequency line, etc.).
• Do not bind these cables together with those in which
■■INSTRUCTION MANUAL
noises are present. Do not install them in the same duct.
This manual describes necessary points of caution when
you use this product, including installation, connection and
■■AND ....
basic maintenance procedures.
• The unit is designed to function as soon as power is sup-
plied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data
POINTS OF CAUTION sheet.
■■CONFORMITY WITH EU DIRECTIVES
• This equipment is suitable for Pollution Degree 2, Meas-
urement Category II (input, transient voltage 4000V) COMPONENT IDENTIFICATION
and Installation Category II (auxiliary power, transient
Connection
voltage 2500V). Reinforced insulation (signal input to Body Diagram
output or auxiliary power input: 550V, output to auxiliary
power input 300V) are maintained. Prior to installation, Specifications

check that the insulation class of this unit satisfies the


system requirements.
• Altitude up to 2000 meters.
• The equipment must be mounted inside a panel.
• The equipment must be installed such that appropriate
clearance and creepage distances are maintained to con-
form to CE requirements. Failure to observe these re- Zero Adjustment
quirements may invalidate the CE conformance.
Span Adjustment
• The actual installation environments such as panel con-
figurations, connected devices, connected wires, may af-
fect the protection level of this unit when it is integrated
in a panel system. The user may have to review the CE INSTALLATION
requirements in regard to the whole system and employ ■■DIN RAIL MOUNTING
additional protective measures to ensure the CE conform- Set the unit so that its DIN rail adaptor is at the bottom.
ity. Position the upper hook at the rear side of the unit on the
• Install lightning surge protectors for those wires connect- DIN rail and push in the lower. When removing the unit,
ed to remote locations. push down the DIN rail adaptor utilizing a minus screw-
driver and pull.
■■AUXILIARY POWER SUPPLY RATING & OPERATIONAL RANGE
• Locate the auxiliary power supply rating marked on the
product and confirm its operational range as indicated
below:
100 – 120V AC rating: 85 – 132V, 47 – 66 Hz, approx. 2VA DIN Rail
200 – 240V AC rating: 170 – 264V, 47 – 66 Hz, approx. 2VA 35mm wide
24V, 48V DC rating: Rating ±10%, approx. 2W
110V DC rating: 85 – 150V, approx. 2W

Spring Loaded
■■GENERAL PRECAUTIONS DIN Rail Adaptor
• Before you remove or mount the unit, turn off the power
supply and input signal for safety.
■■WALL MOUNTING
Refer to “EXTERNAL DIMENSIONS.”
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN EM-3355  Rev.5  P. 1 / 4
Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: info@m-system.co.jp
LTWT

TERMINAL CONNECTIONS
Connect the unit as in the diagram below or refer to the connection diagram on the side of the unit.

■■EXTERNAL DIMENSIONS unit: mm (inch)

10 (.39) 16–M4 SCREW


2–M4 MTG HOLE

TERMINAL COVER (option /T)

DIN RAIL
1 2 3 4 5 6
35mm wide
111 (4.37)
98 (3.86)
80 (3.15)

7 8 9 10

11 12 13 14 15 16

54 (2.13) 8 (.31)
3
72 (2.83) (.12) 143 (5.63) [4 (.16)]

• When mounting, no extra space is needed between units.

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN EM-3355  Rev.5  P. 2 / 4


Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: info@m-system.co.jp
LTWT
■■CONNECTION DIAGRAM

■ 3-PHASE/3-WIRE ■ SINGLE-PHASE/2-WIRE
SOURCE SOURCE
1 2 3 1 2
FUSE U VT u FUSE VT
P1 U u P1
7 13 + 7 13 +
PULSE OUTPUT PULSE OUTPUT
V v P2 V v P2
8 14 – 8 14 –
V v
P3
9 11 + 11 +
U u
DC OUTPUT DC OUTPUT
K K K
12 – 12 –
k 1S k 1S
1 1
k CT
1L 1L
CT 2 2
15 U(+) l 15 U(+)
3S L
l l 5 AUXILIARY * AUXILIARY *
L L POWER POWER
3L
6 16 V(–) 16 V(–)

LOAD LOAD

■ SINGLE-PHASE/3-WIRE ■ 3-PHASE/4-WIRE
SOURCE SOURCE
1 N 2 N 1 2 3
FUSE U VT u FUSE VT
P1 U u P1
7 13 + 7 13 +
PULSE OUTPUT V v PULSE OUTPUT
V v P0 P2
8 14 – 8 14 –
V v U u
P2 V v P3
9 11 + 9 11 +
U u U u
DC OUTPUT V v DC OUTPUT
K K P0
12 – 10 12 –
K K K
k 1S
1
k k 1S
1L 1
CT 2
15 U(+) k 1L
2S k CT 2
l l 5 AUXILIARY *
L L POWER 2S
2L l l l 3
6 16 V(–) L L L
2L
4
LOAD 15 U(+)
3S
5 AUXILIARY *
POWER
3L
Pulse Output Connection Example 6 16 V(–)
LOAD
■ Open Collector

13 + * The transducer can be powered from the input voltage


when the voltage is sufficiently stable and meets within
14 – the range of auxiliary power supply of the unit specified
in the data sheet/instruction manual.

5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN EM-3355  Rev.5  P. 3 / 4


Phone: +81(6)6659-8201  Fax: +81(6)6659-8510  E-mail: info@m-system.co.jp
LTWT

WIRING INSTRUCTIONS MAINTENANCE


■■SCREW TERMINAL Regular calibration procedure is explained below:
Torque: 1.2 N·m
■■CALIBRATION
Warm up the unit for at least 10 minutes. Apply 0%, 25%,
CHECKING 50%, 75% and 100% input signal. Check that the output
signal for the respective input signal remains within accu-
1) Terminal wiring: Check that all cables are correctly con-
racy described in the data sheet. When the output is out of
nected according to the connection diagram.
tolerance, recalibrate the unit according to the “ADJUST-
2) Auxiliary power input voltage: Check voltage across the
MENT PROCEDURE” explained earlier.
terminal 15 – 16 with a multimeter.
3) Input: Calculate the calibration range and check that the
result is within the usable range.
LIGHTNING SURGE PROTECTION
Measuring Wattage
Calibration Range [W] = M-System offers a series of lightning surge protector for
(VT Ratio) × (CT Ratio) protection against induced lightning surges. Please contact
4) DC Output: Check that the load resistance meets the M-System to choose appropriate models.
described specifications.
5) Totalizing pulse output: Check that the load connected to
the open collector output is within 35V DC @100mA.

ADJUSTMENT PROCEDURE
This unit is calibrated at the factory to meet the ordered
specifications, therefore you usually do not need any cali-
bration.
For matching the signal to a receiving instrument or in case
of regular calibration, adjust the output as explained in the
following.

■■HOW TO CALIBRATE THE OUTPUT SIGNAL


Use a signal source and measuring instruments of suffi-
cient accuracy level. Turn the auxiliary power supply on
and warm up for more than 10 minutes.
1) ZERO: Apply 0% input and adjust output to 0%.
2) SPAN: Apply 100% input and adjust output to 100%.
3) Check ZERO adjustment again with 0% input.
4) When ZERO value is changed, repeat the above proce-
dure 1) – 3).