Professional Documents
Culture Documents
BOP Training Report
BOP Training Report
BALANCE OF
PLANT
TRAINING REPORT
TABLE OF CONTENTS
Chapter 01:
Chapter 02:
WATER DEMINERALIZATION…………………………………………19
Chapter 03:
COOLING TOWERS………………………………………………………39
Chapter 04:
APPENDIX………………………………………………………………..62
2
BOP Training Report
CHAPTER # 01
PRE TREATMENT OF
INTAKE WATER
3
BOP Training Report
At AES Lalpir Thermal Power Plant raw water is taken from Canal. Canal
Water from suction pit passes through bar screen whose primary purpose is to
remove the prominent or large debris, which can cause damage. Then canal
water passes through traveling bar screen, having 22 baskets which continuousl y
revolve in such way that water has to pass through their centre, band screen has
the sieve size of 1 mm with the same purpose as of bar screen but is for smaller
debris. The waste collected in these screens is sprayed away to waste collecting
pit and is pumped back to the canal. The raw water is then pumped to the power
plant with the help of canal water pump having 1200m 3 /hr discharge rate, each
pump is supplied with pneumaticall y controlled valve which when open,
recirculates the water back to the bar screen. There are total 4 Canal Water
pumps, two pumps for each unit, when one pump is in service, the other is
standb y.
Canal intake
Canal water pumps
Well water pumps
Settling basins
Clarifier suppl y pumps
Clarifier
Clear well
Dual media filters (DMF)
4
BOP Training Report
Suction
Pit LALPIR
CANAL PUMPS
Suction
Pit
BAR TRAVELLING
SCREEN BAND
SCREEN
WELL
PUMPS
CANAL PAKGEN
PUMPS
Suction
Pit
BAR TRAVELLING
SCREEN BAND
SCREEN
WELL
PUMPS
5
BOP Training Report
SETTLING BASINS
There are three types of objects which can be found in water. In order from smallest to largest,
these objects are chemicals in solution, colloidal solids, and suspended solids. The settling basins
are designed to provide ample retention time for settling of heavy suspended particles, debris and
uncharged particles. Coagulation/flocculation will remove colloidal and suspended solids from
water.
All sedimentation basins have four zones - the inlet zone, the settling zone, the sludge zone, and
the outlet zone. Each zone should provide a smooth transition between the zone before and the
zone after. In addition, each zone has its own unique purpose. Zones can be seen most easily in a
rectangular sedimentation basin, such as the one shown below:
CLARIFICATION
COAGULATION AND FLOCCULATION
In a clarifier, water typically enters the basin from the center rather than from one end and flows
out to outlets located around the edges of the basin. But the four zones can still be found within
the clarifier:
6
BOP Training Report
All waters, especially surface waters, contain both dissolved and suspended particles.
Coagulation and flocculation processes are used to separate the suspended solids portion from
the water.
The suspended particles vary considerably in source, composition charge, particle size, shape,
and density. Correct application of coagulation and flocculation processes and selection of the
coagulants depend upon understanding the interaction between these factors. The small particles
are stabilized (kept in suspension) by the action of physical forces on the particles themselves.
One of the forces playing a dominant role in stabilization results from the surface charge present
on the particles. Most solids suspended in water possess a negative charge and, since they have
the same type of surface charge, repel each other when they come close together. Therefore, they
will remain in suspension rather than clump together and settle out of the water.
PURPOSE
The primary purpose of the coagulation/flocculation process is the removal of turbidity from the
water. Turbidity is a cloudy appearance of water caused by small particles suspended therein.
Water with little or no turbidity will be clear.
7
BOP Training Report
Turbidity is not only an aesthetic problem in water. Water with a high turbidity can be very
difficult or impossible to properly disinfect. As a result, the maximum allowable level of
turbidity in water is 0.5 NTU, while the recommended level is about 0.1 NTU. (NTU, or TU,
stands for nephelometric turbidity units, a measurement of the turbidity of water.)
In addition to removing turbidity from the water, coagulation and flocculation is beneficial in
other ways. The process removes many bacteria which are suspended in the water and can be
used to remove color from the water.
Turbidity and color are much more common in surface water than in groundwater. As surface
water flows over the ground to streams, through streams, and then through rivers, the water picks
up a large quantity of particles. As a result, while aeration is more commonly required for
groundwater, treatment involving coagulation and flocculation is typical of surface water.
In theory and at the chemical level, coagulation and flocculation is a three step process,
consisting of flash mixing, coagulation, and flocculation. However, in practice in the treatment
plant, there are only two steps in the coagulation/flocculation process - the water first flows into
the flash mix chamber, and then enters the flocculation basin.
STEPS OF CLARIFICATION
8
BOP Training Report
PHENOMENON
The chemistry of coagulation and flocculation is primarily based on electricity. Electricity is the
behavior of negative and positively charged particles due to their attraction and repulsion. Like
charges (two negatively charged particles or two positively charged particles) repel each other
while opposite charges (a positively charged particle and a negatively charged particle) attract.
Most particles dissolved in water have a negative charge, so they tend to repel each other. As a
result, they stay dispersed and dissolved or colloidal in the water, as shown above.
The purpose of most coagulant chemicals is to neutralize the negative charges on the turbidity
particles to prevent those particles from repelling each other. The amount of coagulant which
should be added to the water will depend on the zeta potential, a measurement of the magnitude
of electrical charge surrounding the colloidal particles. You can think of the zeta potential as the
amount of repulsive force which keeps the particles in the water. If the zeta potential is large,
then more coagulants will be needed.
9
BOP Training Report
Coagulants tend to be positively charged. Due to their positive charge, they are attracted to the
negative particles in the water, as shown below.
The combination of positive and negative charge results in a neutral, or lack, of charge. As a
result, the particles no longer repel each other.
The next force which will affect the particles is known as Van der Waal's forces. Van der
Waal's forces refer to the tendency of particles in nature to attract each other weakly if they
have no charge.
Once the particles in water are not repelling each other, van der Waal's forces make the particles
drift toward each other and join together into a group. When enough particles have joined
together, they become floc and will settle out of the water.
10
BOP Training Report
COAGULANT SELECTION
The choice of coagulant chemical depends upon the nature of the suspended solid to be removed,
the raw water conditions, the facility design, and the cost of the amount of chemical necessary to
produce the desired result.
Final selection of the coagulant (or coagulants) should be made following thorough jar testing
and plant scale evaluation. Considerations must be given to required effluent quality, effect upon
down stream treatment process performance, cost, method and cost of sludge handling and
disposal, and net overall cost at the dose required for effective treatment.
INORGANIC COAGULANTS
Inorganic coagulants such as aluminum and iron salts are the most commonly used. When added
to the water, they furnish highly charged ions to neutralize the suspended particles. The inorganic
hydroxides formed produce short polymer chains which enhance microfloc formation.
Inorganic coagulants usually offer the lowest price per pound, are widely available, and, when
properly applied, are quite effective in removing most suspended solids. They are also capable of
removing a portion of the organic precursors which may combine with chlorine to form
disinfection by-products. They produce large volumes of floc which can entrap bacteria as they
settle. However, they may alter the pH of the water since they consume alkalinity. When applied
in a lime soda ash softening process, alum and iron salts generate demand for lime and soda ash.
They require corrosion-resistant storage and feed equipment. The large volumes of settled floc
must be disposed of in an environmentally acceptable manner.
11
BOP Training Report
Common coagulant chemicals used are alum, ferric sulfate, ferric chloride, ferrous sulfate, and
sodium aluminate. The first four will lower the alkalinity and pH of the solution while the
sodium aluminate will add alkalinity and raise the pH. The reactions of each follow:
ALUM
A12(SO4)3 + 3 Ca(HCO3)2 -------> 2 Al(OH)3 + 3CaSO4 + 6 CO2
Aluminum + Calcium Aluminum + Calcium + Carbon
Sulfate Bicarbonate Hydroxide Sulfate Dioxide
FERRIC SULFATE
Fe2(SO4)3 + 3 Ca(HCO3)2 --------> 2 Fe(OH)3 + 3CaSO4 + 6 CO2
Ferric + Calcium Ferric + Calcium + Carbon
Sulfate Bicarbonate Hydroxide Sulfate Dioxide
FERRIC CHLORIDE
2 Fe Cl3 + 3 Ca(HCO3)2 ----------> 2 Fe(OH)3 + 3CaCl2 + 6CO2
Ferric + Calcium Ferric + Calcium + Carbon
Chloride Bicarbonate Hydroxide Chloride Dioxide
FERROUS SULFATE
FeS04 + Ca(HCO3)2 ----------> Fe(OH)2 + CaS04 + 2CO2
Ferrous + Calcium Ferrous + Calcium + Carbon
Sulfate Bicarbonate Hydroxide Sulfate Dioxide
SODIUM ALUMINATE
2 Na2A12O4 + Ca(HCO3)2 ---------> 8 Al(OH)3 + 3 Na2CO3 + 6 H20
Sodium + Calcium Aluminum + Sodium + Water
Aluminate Carbonate Hydroxide Carbonate
POLYMERS
Polymers--long-chained, high-molecular-weight, organic chemicals--are becoming more widely
used, especially as coagulant aids together with the regular inorganic coagulants. Anionic
(negatively charged) polymers are often used with metal coagulants. Low-to-medium weight
12
BOP Training Report
positively charged (cationic) polymers may be used alone or in combination with the aluminum
and iron type coagulants to attract the suspended solids and neutralize their surface charge. The
manufacturer can produce a wide range of products that meet a variety of source-water
conditions by controlling the amount and type of charge and relative molecular weight of the
polymer.
Polymers are effective over a wider pH range than inorganic coagulants. They can be applied at
lower doses, and they do not consume alkalinity. They produce smaller volumes of more
concentrated, rapidly settling floc. The floc formed from use of a properly selected polymer will
be more resistant to shear, resulting in less carryover and a cleaner effluent.
Polymers are generally several times more expensive in their price per pound than inorganic
coagulants. Selection of the proper polymer for the application requires considerable jar testing
under simulated plant conditions, followed by pilot or plant-scale trials.
FLOCK
The end product of a well-regulated coagulation/flocculation process is water in which the
majority of the turbidity has been collected into flock, clumps of bacteria and particulate
impurities that have come together and formed a cluster. The flock will then settle out in the
sedimentation basin, with remaining flock being removed in the filter.
In a well-run water treatment plant, adjustments are often necessary in order to maximize the
coagulation/flocculation process. These adjustments are a reaction to changes in the raw water
entering the plant. Coagulation will be affected by changes in the water's pH, alkalinity,
temperature, time, velocity and zeta potential.
13
BOP Training Report
14
BOP Training Report
OPERATING PROCEDURES
There are total 4 Canal Water pumps, two pumps for each unit, when one pump
is in service, the other is standb y. Each pump is supplied with pneumaticall y
controlled valve which when open, re-circulate the water back to the suction
pit. All four pumps lubricating oil and rubber bearings at shaft are cooled b y
cooling water.
After checking all these, ask to CCR start the canal water pump and finall y
Verify that pump discharge pressure is about 2.4 kg/cm 2
15
BOP Training Report
When its suction strainer differential pressure becomes higher than 0.5kg/cm 2 g,
strainer should be cleaned after stopping the Pump.
The sand used in rapid sand filters is coarser (larger) than the sand used in slow sand filters. This
larger sand has larger pores which do not fill as quickly with particles out of the water. Coarse
sand also costs less and is more readily available than the finer sand used in slow sand filtration.
16
BOP Training Report
In many cases, multiple types of media are layered within the filter. Typically, the layers
(starting at the bottom of the filter and advancing upward) are sand and anthracite coal, or garnet,
sand, and anthracite coal. The picture below shows a cross-section through a dual media filter.
The media in a dual or multi-media filter are arranged so that the water moves through media
with progressively smaller pores. The largest particles are strained out by the anthracite. Then
the sand and garnet trap the rest of the particulate matter though a combination of adhesion and
straining. Since the particles in the water are filtered out at various depths in a dual or multi-
media filter, the filter does not clog as quickly as if all of the particles were all caught by the top
layer.
DMF CLEANING/BACKWASHING
After 2 hours of running DMF Filters are cleaned/backwashed to remove the carryover
suspended particles. Clear well Level should be above 70%.
FILL(5 min)
17
BOP Training Report
In this step service inlet of water and air outlet valve opens in this step
DMF fills itself with water. Flow rate is 225 m 3 /hr
BACKWASH(5 min)
Here back wash inlet and outlet valves opens and the water goes to
Settling Basin. Flow rate is 680 m 3 /hr
RINSE(5 min)
Service inlet and rinse outlet valves open and the waste water goes to
distribution chamber. Flow rate is 170 m 3 /hr.
After these steps DMF is ready for service
DMF Backwash and cl ear well overflow goes to settling basin A&B.
18
BOP Training Report
CHAPTER # 02
WATER DEMINERALIZATION
19
BOP Training Report
MULTIMEDIA FILTERS
The media in a dual or multi-media filter must have varying density as well as varying pore size
so that they will sort back into the correct layering arrangement after backwashing. Anthracite
coal is a very light (low density) coal which will settle slowly, ending up as the top layer of the
filter. Garnet is very dense sand which will settle quickly to the bottom of the filter.
Pre-treated water from the filtered water basin is directed to two (2) Multi-Media Filters which
remove residual turbidity and suspended solids from the water. Following multi-media filtration,
the water is injected with sodium bisulphate to remove trace quantities of free chlorine. Multi-
Media filter backwash and rinse water is directed to the inlet distribution box. A portion of the
multi-media filtered water is directed to the potable water tank and chlorinator. If the raw water
source is canal water, the multi-media filtered water effluent is directed to the permeate tank .If
the raw water source is well water, the multi-media filtered water is directed to the reverse
osmosis system. Each multi-media filter is designed to treat 97m3/hr of pre-treated water.
The largest particles are removed by the coal, the medium particles by the sand,
and the smallest particles by the garnet.
20
BOP Training Report
Like DMF gravel layer is also used here for supporting the media. The arrangement of media
from top to bottom is as follows:
21
BOP Training Report
Pi
Filter Water
Basin B
Pi
Filter Water
Basin A
From Filter Water
MMF MMF
A B
Back
Wash
RINSE LINE
BAG
FILTERS
TO RO SYSTEM
22
BOP Training Report
Osmotic flow from the pure water side across the membrane to the salt solution side will occur
until the equilibrium of chemical potential is restored. In scientific terms, the two sides of the
tank have a difference in their “chemical potentials,” and the solution equalizes, by osmosis, its
chemical potential throughout the system. Equilibrium occurs when the hydrostatic pressure
differential resulting from the volume changes on both sides is equal to the osmotic pressure. The
osmotic pressure is a solution property proportional to the salt concentration and independent of
the membrane.
REVERSE OSMOSIS
Application of an external pressure to the salt solution side equal to the osmotic pressure will
also cause equilibrium. Additional pressure will raise the chemical potential of the water in the
salt solution and cause a solvent flow to the pure water side, because it now has a lower chemical
potential. This phenomenon is called reverse osmosis.
23
BOP Training Report
OPERATING PROCEDURES
START-UP
Put RO bank A or B on Auto mode from PLC.
Flush the RO bank until the permeate conductivity falls below 90 micromhos/cm.
RO 4% acid pump should be in service.
RO antiscalant pump should be in service.
Adjust the reject valve flow.
SHUT DOWN
Put RO bank on Manual from PLC and observe the following;
24
BOP Training Report
RO PRESERVATION
RO preservation is for periods where an RO plant must remain out of operation for more than
thirty days with the RO elements in place. Prepare each RO train as follows.
25
BOP Training Report
DEMINERALIZATION
WATER DEIONIZATION PROCESS
The process used for removal of all dissolved salts from water is referred to as
demineralization/deionization. Deionization requires the flow of water through two ion exchange
materials in order to effect the removal of all salt content.
The passage of water through the first exchange material removes the calcium and magnesium
ions just as in the normal softening process. Unlike home equipment, deionization units also
remove all other positive metallic ions in the process and replace them with hydrogen ions
instead of sodium ions.
As the metallic ions in the water affix themselves to the exchange material, the latter releases its
hydrogen ions on a chemically equivalent basis. A sodium ion (Na+) displaces one hydrogen ion
(H+) from the exchanger; a calcium ion (Ca++) displaces two hydrogen ions; a ferric ion
(Fe+++) displaces three hydrogen ions, etc. (Recall that home softeners also release two sodium
ions for every calcium or magnesium ion they attract.)
This exchange of the hydrogen ions for metallic ions on an equivalent basis is chemical necessity
that permits the exchange material to maintain a balance of electrical charges.
Now because of the relatively high concentration of hydrogen ions, the solution is very acid.
At this point the deionization process is just half complete. While the positive metallic ions have
been removed, the water now contains positive hydrogen ions, and the anions originally in the
raw water.
The partially treated water now flows through a second unit, this time an anion exchange
material normally consists of replaceable hydroxyl anions and fixed irreplaceable cations.
Now the negative ions in solution (the anions) are absorbed into the anion exchange
material. Released in their place are hydroxyl anions.
26
BOP Training Report
All that emerges from such a two unit system is ion-free water. It still contains the positive
hydrogen ions released in the initial exchange plus the negative hydroxyl ions released in the
second exchange.
What has become of these two ions? Through the magic of chemistry they have combined
(positive to negative) to produce water molecules which are in no way different from the water in
which they were produced.
The result of this two-stage ion exchange process is water that is mineral-free.
Equipment for use in the deionization process may be of several types. Available are both
multiple bed and single bed units. Multiple bed units have pairs of tanks, one for the cation
exchanger, the other for the anion exchanger. Single bed units incorporate both the cation and
anion exchangers, mixed in a single tank.
Deionized water has a wide range of uses in industry. Chemical production, pharmaceuticals,
electroplating, television tube production and leather goods processing are among the many
diversified applications for deionized water
27
BOP Training Report
OPERATING PROCEDURE
PRE-START CHECKS
Check the level of RO permeate. RO permeate level should be above low level.
Both Demin trains and mixed beds must be in standby mode.
Check demineralizer feed pump. Pump A or B should be on Auto mode.
Decarbonator water forwarding pump and blower A or B should be on Auto mode.
Check the valve line-up of train A or B.
Demineralizer pump suction and discharge manual isolation valve should be open.
Cation inlet and outlet manual isolation valve should be open.
Decarbonator water forwarding pump inlet and outlet manual isolation valve should
be open.
Anion inlet and outlet manual isolation valve should be open.
Mixed bed inlet and outlet manual isolation valve should be open.
Demin water storage tank A or B filling line manual isolation valve should be open.
Demin water storage tank A or B level should be below 80%
START-UP
Start Demin train by pressing ‘Train service’ from PLC.
Wait for pre-service rinse the train will come in service after pre-rinsing.
When the level of Decarbonator is above low level, Decarbonator water forwarding
pump will cut in automatically
Start mixed bed by pressing ‘mixed bed service’ from PLC.
Wait for pre-service rinse the train will come in service after pre-rinsing.
After some time of train operation check the silica of Anion and mixed bed from
laboratory OR from online analyzer.
SHUTDOWN
Demin train will go on standby after reaching the maximum level in the Demin storage tanks,
OR carry out as mentioned below
28
BOP Training Report
The Cation and anion units are regenerated in a split flow counter current manner and therefore
will not be given a full backwash every regeneration. When these units are backwashed
(approximately every 20 regenerations), a double chemical injection will be automatically
provided to recondition the resin at the bottom of the bed.
Regeneration controls are programmed for each Cation and anion unit to totalize the number of
regenerations without a full backwash. When the preset value is reached, the unit will be given a
backwash and double chemical injection during its next regeneration cycle and the appropriate
regeneration tantalizers will be reset to zero after this upset regeneration.
Provisions have been made to override the regeneration if necessary; however, under normal
operating conditions the regeneration cycles should be allowed to time out and sequence through
to completion. Dilution water for the acid and caustic regenerate solutions is demineralized water
delivered by the diluents water pumps. Interlocks are provided to ensure that the acid and caustic
regenerate solutions are delivered at the correct flow rates and chemical strength. A heat
29
BOP Training Report
exchanger is provided to heat the dilution water during preheat caustic injection and
displacement steps of the anion and mixed bed regeneration procedure. Interlocks are provided to
ensure that the minimum anion dilution water temperature is at 35 oC and the mixed bed dilution
water is at 49oC. Dilution water flow is controlled by rate set valves provided for Cation acid
dilution, mixed bed acid dilution, anion caustic dilution and mixed bed caustic dilution.
Time 10 minutes
Time 10 minutes
Time 50 minutes
Displacement
Time 15 minutes
30
BOP Training Report
Fast Rinse
Rate 65 m3/hr
Time 20 minutes
NOTE:
If a full backwash cycle is selected, the 2% H2SO4 injection time is extended to 75 minutes
Times and flow rates may be adjusted to suit operational experience to achieve maximum
efficiency
Time 10 minutes
Time 10 minutes
Preheat@35C
Time 20 minutes
31
BOP Training Report
Time 45 minutes
Displacement
Time 45 minutes
Fast Rinse
Rate 65 m3./hr
Time 20 minutes
Note:
Backwash
Rate 13.6 cu.m./hr
Time 15 minutes
Settle
Rate NIL
Time 5 minutes
Time = 15 minutes
32
BOP Training Report
Time 35 minutes
Time 30 minutes
Time 20 minutes
Drain down
Rate 9. I m3 ./hr
Time 15 minutes
Air Mix
Rate 340 m3 ./hr ( 0.5 kg/ cm2.)
Time 20 minutes
Time I Minute
Fast Fill
Rate 65 m3 ./hr
33
BOP Training Report
Time 2 minutes
Final Rinse
Rate 65 m3 ./hr
Time 10 minutes
34
BOP Training Report
IDENTIFICATION
ANALYSIS
CONSTITUENT in MG/L AS A B C D E F G
A Calcium 111 35 1 0 0 0 0
T Magnesium 289 65 2 0 0 0 0
N Potassium 90 90 4 0 0 0
0
35
BOP Training Report
N Carbonate 0 0 0 0 0 0 0
I Hydroxide 0 0 0 0 0 0.4 0
Turbidity NTU 1 0 0 0 0 0 0
IDENTIFICATION
36
BOP Training Report
ANALYSIS
CONSTITUENT in MG/L AS A B C D E F
A Calcium 83 35 1 0 0 0
T Magnesium 36 33 0 0 0 0
I Sodium 40 50 .5 .5 .5 .04
N Potassium 6 6 0 0 0 0
A Bicarbonate 96 45 0 0 0 0
N Carbonate 0 0 0 0 0 0
I Hydroxide 0 0 0 0 0.4 0
O Sulphate 43 65 55 55 0 0
N Chloride 14 14 14 14 .1 .04
37
BOP Training Report
Conductivity 5 .1
38
BOP Training Report
CHAPTER # 03
COOLING TOWERS
39
BOP Training Report
COOLING TOWERS
Cooling towers are a very important part of many chemical plants. The primary task of a cooling
tower is to reject heat into the atmosphere. They represent a relatively inexpensive and
dependable means of removing low-grade heat from cooling water. The make-up water source is
used to replenish water lost to evaporation. Hot water from heat exchangers is sent to the cooling
tower. The water exits the cooling tower and is sent back to the exchangers or to other units for
further cooling
Cooling towers fall into two main categories: Natural draft and Mechanical draft.
NATURAL DRAFT
Natural draft towers use very large concrete chimneys to introduce air through the media. Due to
3
the large size of these towers, they are generally used for water flow rates above 45,000 m /hr.
These types of towers are used only by utility power stations.
40
BOP Training Report
MECHANICAL DRAFT
Mechanical draft towers utilize large fans to force or suck air through circulated water. The water
falls downward over fill surfaces, which help increase the contact time between the water and the
air - this helps maximize heat transfer between the two. Cooling rates of Mechanical draft towers
depend upon their fan diameter and speed of operation. Since, the mechanical draft cooling
towers are much more widely used
In the counter flow induced draft design, hot water enters at the top, while the air is introduced at
the bottom and exits at the top. Both forced and induced draft fans are used.
In cross flow induced draft towers, the water enters at the top and passes over the fill. The air,
however, is introduced at the side either on one side (single-flow tower) or opposite sides
(double-flow tower). An induced draft fan draws the air across the wetted fill and expels it
through the top of the structure.
The Figure 7.2 illustrates various cooling tower types. Mechanical draft towers are available in a
3
large range of capacities. Normal capacities range from approximately 10 tons, 2.5 m /hr flows
3
to several thousand tons and m /hr. Towers can be factory built or field erected – for example
concrete towers are only field erected. Many towers are constructed so that they can be grouped
together to achieve the desired capacity. Thus, many cooling towers are assemblies of two or
more individual cooling towers or “cells.” The number of cells they have, e.g., a eight-cell tower,
often refers to such towers. Multiple-cell towers can be lineal, square, or round depending upon
the shape of the individual cells and whether the air inlets are located on the sides or bottoms of
the cells.
41
BOP Training Report
42
BOP Training Report
FILL:
Most towers employ fills (made of plastic or wood) to facilitate heat transfer by maximizing
water and air contact. Fill can either be splash or film type.
With splash fill, water falls over successive layers of horizontal splash bars, continuously
breaking into smaller droplets, while also wetting the fill surface. Plastic splash fill promotes
better heat transfer than the wood splash fill.
Film fill consists of thin, closely spaced plastic surfaces over which the water spreads, forming a
thin film in contact with the air. These surfaces may be flat, corrugated, honeycombed, or other
patterns. The film type of fill is the more efficient and provides same heat transfer in a smaller
volume than the splash fill.
The cold water basin, located at or near the bottom of the tower, receives the cooled water that
flows down through the tower and fill. The basin usually has a sump or low point for the cold
water discharge connection. In many tower designs, the cold water basin is beneath the entire fill.
Some forced draft counter flow design, however, the water at the bottom of the fill is In
channeled to a perimeter trough that functions as the cold water basin. Propeller fans are
mounted beneath the fill to blow the air up through the tower. With this design, the tower is
mounted on legs, providing easy access to the fans and their motors.
DRIFT ELIMINATORS:
These capture water droplets entrapped in the air stream that otherwise would be lost to the
atmosphere.
43
BOP Training Report
AIR INLET:
This is the point of entry for the air entering a tower. The inlet may take up an entire side of a
tower—cross flow design— or be located low on the side or the bottom of counter flow designs.
LOUVERS:
Generally, cross-flow towers have inlet louvers. The purpose of louvers is to equalize air flow
into the fill and retain the water within the tower. Many counter flow tower designs do not
require louvers.
NOZZLES:
These provide the water sprays to wet the fill. Uniform water distribution at the top of the fill is
essential to achieve proper wetting of the entire fill surface. Nozzles can either be fixed in place
and have either round or square spray patterns or can be part of a rotating assembly as found in
some circular cross-section towers.
FANS:
Both axial (propeller type) and centrifugal fans are used in towers. Generally, propeller fans are
used in induced draft towers and both propeller and centrifugal fans are found in forced draft
towers. Depending upon their size, propeller fans can either be fixed or variable pitch. A fan
having non-automatic adjustable pitch blades permits the same fan to be used over a wide range
of kW with the fan adjusted to deliver the desired air flow at the lowest power consumption.
Automatic variable pitch blades can vary air flow in response to changing load conditions.
i) “Range” is the difference between the cooling tower water inlet and outlet temperature.
ii) “Approach” is the difference between the cooling tower outlet cold water temperature and
ambient wet bulb temperature. Although, both range and approach should be monitored, the
`Approach’ is a better indicator of cooling tower performance.
iii) Cooling tower effectiveness (in percentage) is the ratio of range, to the ideal range, i.e.,
difference between cooling water inlet temperature and ambient wet bulb temperature, or in other
words it is = Range / (Range + Approach).
44
BOP Training Report
iv) Cooling capacity is the heat rejected in kCal/hr or TR, given as product of mass flow
rate of water, specific heat and temperature difference.
v) Evaporation loss is the water quantity evaporated for cooling duty and, theoretically, for
3
every 10, 00,000 kCal heat rejected, evaporation quantity works out to 1.8 m . An empirical
relation used often is:
3 3
Evaporation Loss (m /hr) = 0.00085 x 1.8 x circulation rate (m /hr) x (T -T )
1 2
vi) Cycles of concentration (C.O.C) is the ratio of dissolved solids in circulating water to
the dissolved solids in make up water.
vii) Blow down losses depend upon cycles of concentration and the evaporation losses and is
given by relation:
viii) Liquid/Gas (L/G) ratio, of a cooling tower is the ratio between the water and the air
mass flow rates. Against design values, seasonal variations require adjustment and tuning of
water and air flow rates to get the best cooling tower effectiveness through measures like water
box loading changes, blade angle adjustments.
Thermodynamics also dictate that the heat removed from the water must be equal to the heat
absorbed by the surrounding air:
CAPACITY
3
Heat dissipation (in kCal/hour) and circulated flow rate (m /hr) are not sufficient to understand
cooling tower performance. Other factors, which we will see, must be stated along with flow rate
3 3 o
m /hr. For example, a cooling tower sized to cool 4540 m /hr through a 13.9 C range might be
3 o
larger than a cooling tower to cool 4540 m /hr through 19.5 C range.
45
BOP Training Report
RANGE
Range is determined not by the cooling tower, but by the process it is serving. The range at the
exchanger is determined entirely by the heat load and the water circulation rate through the
exchanger and on to the cooling water.
o
Range C = Heat Load in kcals/hour / Water Circulation Rate in LPH
Thus, Range is a function of the heat load and the flow circulated through the system.
Initial selection of towers with respect to design wet bulb temperature must be made on the basis
of conditions existing at the tower site. The temperature selected is generally close to the average
maximum wet bulb for the summer months. An important aspect of wet bulb selection is,
whether it is specified as ambient or inlet. The ambient wet bulb is the temperature, which exists
generally in the cooling tower area, whereas inlet wet bulb is the wet bulb temperature of the air
entering the tower. The later can be, and often is, affected by discharge vapours being
recirculated into the tower. Recirculation raises the effective wet bulb temperature of the air
entering the tower with corresponding increase in the cold water temperature. Since there is no
initial knowledge or control over the recirculation factor, the ambient wet bulb should be
specified. The cooling tower supplier is required to furnish a tower of sufficient capability to
absorb the effects of the increased wet bulb temperature peculiar to his own equipment.
Range is a direct function of the quantity of water circulated and the heat load. Increasing the
range as a result of added heat load does require an increase in the tower size. If the cold water
temperature is not changed and the range is increased with higher hot water temperature, the
driving force between the wet bulb temperature of the air entering the tower and the hot water
temperature is increased, the higher level heat is economical to dissipate.
46
BOP Training Report
If the hot water temperature is left constant and the range is increased by specifying a lower cold
water temperature, the tower size would have to be increased considerably.
CHEMICAL TREATMENT OF
COOLING WATER
Chemicals are injected in CW system to stop microbiological growth and corrosion formation.
NALCO 23212
Nalco 23212 is used as a scale inhibitor in the Cooling Tower. It is commonly known as
phosphate treatment. As the ph of the circulating water is kept low so there are less chances of
corrosion formation in the system. The value of phosphate in circulating water is maintained at
1.5-2.2 ppm
SULPHURIC ACID
Sulphuric acid is added to reduce the ph of the circulating water & to reduce M.Alkalinity. The
ph of the Cooling Tower is maintained at about 8.2.
DISPERSANT
The scale formed tends to stay suspended long enough to be removed by either the blow down or
a filtration system. Dispersant is added to remove the scale from the Cooling Tower Basin. It
does not allow the scale to settle down to the bottom of the cooling Tower.
I. Increase blow down to remove solids and prevent their concentrations from going too
high. Unfortunately this approach also increases the quantities of water and treatment
products used and tends not to be cost effective.
II. Utilize heavier dosages of treatment products to prevent deposition possibly with the
Incorporation of an acid-feed system to keep the carbonate equilibrium system in the
more Soluble bicarbonate form. This approach can be very costly and is counter to
good environmental practice.
47
BOP Training Report
CHLORINE
The tendency for biological activity and fouling can be effectively controlled. Chlorine is usually
added as a shock dose, usually at night. It can be added as Cl2 or as hypochlorite depending upon
the size of the system. The hypochlorite should be sodium as opposed to calcium (HTH) as the
calcium would add to the system's scaling potential. Bromination, is also becoming an accepted
procedure when the pH run >8. Alternatively a number of proprietary biocides can be used.
These include iso-thiazalones, carbonates and quaternary products. Unlike chlorine, which
oxidizes cell walls, the use of the proprietary products can lead to the development of an
organism that adapts to the biocide. It is common to alternate biocides to kill off any bacteria that
may have adapted.
Chlorine was dozed as a Biocide in Cooling Tower. At Lalpir Chlorine Dozing has been replaced
by Sodium Hypo Chloride due to safety priority. At PakGen Chlorine is still being used & is to
be replaced till December 2009.
Chlorine is maintained in the Circulating water system on residual basis. The amount of chlorine
present in Circulating water is maintained at maximum of 0.5 ppm.
OPERATING PROCEDURES
48
BOP Training Report
49
BOP Training Report
CHAPTER # 04
HYDROGEN GENERATION SYSTEM
&
WASTE WATER DISPOSAL
50
BOP Training Report
Number of Phases 3
Percent Ripple 5 %
Percent Regulation 1 %
Ambient Temperature 50 0 C
AC power at 380 volts, 3 phase, 50 hertz is supplied from the power feeder
panel through circuit breaker to rectifier and transformer. Circuit breaker is
provided for short circuit protection. In rectifier, voltage is reduced by a
rectifier transformer and converted to a Direct Current at Voltage up to 14 volts.
DC power from Rectifier is supplied to electrol ytic cells through copper bus bar
ELECTROLYTIC CELLS:-
The Stuart electrol ytic cells are of the uni polar tank t ype. The cell is known as
a 3-plate cell, having one nickel-plated iron anode plates and two iron cathode
plate. The anodes are surrounded by cloth diaphragms which prevent mixing of
51
BOP Training Report
the h ydrogen and ox ygen gases formed in the cell. The electrol yte is a 25%
solution of potassium h ydroxide. (Also referred to as ‘caustic potash” or
“KOH”) in water.)
ELECTROLYTE:-
The optimum concentration is 25% by weight KON (Specific Gravit y of 1.24
when measured at 15.5° C).
DC current from the positive terminal of the rectifier enters the first cell in the
bank at the terminals of the anodes. The current flows down the anodes into the
cell, through the electrol yte to the cathodes, up the cathodes to the cathode
terminals (two per cathode), and then on to the anode terminals of the next cell
in the bank. From the last cell in the bank the current flows back to the negative
terminal of the rectifier.
Passage of direct current through the cell causes the water in the cell to be
converted into h ydrogen and ox ygen gases. Hydrogen forms on the cathode
plates:
Ox ygen forms on the anode plates. This process is known as “electrol ysis” and
the cell is called an “electrol ytic cell”. The diaphragms surrounding the anodes
are very effective at keeping bubbles of ox ygen separated from bubbles of
h ydrogen. However, they are less efficient at keeping the actual gases separated.
52
BOP Training Report
For this reason the cell is normall y operated so that the diaphragms are
submerged in the electrol yte.
If for some reason the electrol yte level should drop to the point where the
diaphragms were no longer submerged, hydrogen could pass through the
diaphragms into the ox ygen, and vice-versa. Before this could happen however,
the end of the vent pipe would be exposed, allowing the gases to escape into the
cell room.
This reduces the risk of compressing impure gases. The amount of hydrogen
vented into the room is not a hazard provided the room is adequatel y ventilated.
The amounts of h ydrogen and oxygen formed are directl y proportional to the
amount of DC current flow through the cell. At 2000 amperes (maximum cell
current each cell will produce 0.7 cubic meters of hydrogen and 0.35 cubic
meters of oxygen per hour. (When measured dry, at 0°C, 760 mm of mercury).
The ox ygen gas formed on the anodes bubbles up through the electrol yte, inside
the diaphragms which surrounds the anodes, and flows into the ox ygen
compartment above the electrol yte level.
Similarl y, the h ydrogen formed on the cathodes bubbles up through the
electrol yte, outside the diaphragms, and flows into the hydrogen compartment
above the electrol yte level.
CELL TEMPERATURE
- Voltage tends to decrease as temperature increases.
The recommended cell temperature between 65° C and 700 C. Above this
Temperature the rate of corrosion of cell components increases significantl y.
ELECTROLYTE STRENGTH
- The recommended electrol yte concentration is 25% by weight. Concentrations
above or below this tend to increase cell voltage.
Concentrations above 25% also tend to increase the rate of cell corrosion. As
current flows through the cell to produce hydrogen and ox ygen, some heat is
also evolved.
The gases leaving the cell are cooled in water-cooled gas coolers. Cooling water
enters from the water header flows through the hydrogen and ox ygen gas coolers
for each cell in series and then flows to waste.
53
BOP Training Report
54
BOP Training Report
The h ydrogen then flows to the hydrogen dryer, where it is dried to a dew point
of –50 0 C. The h ydrogen dryer is a molecular sieve, dual column, heatless,
pressure swing t ype.
The h ydrogen then flows through the dust filter where an y dist particles carried
over from the dryer are filtered out.
From the dust filter the hydrogen flows through back pressure maintaining
valve, this valve serves to impose a minimum back pressure on the hydrogen
dryer of approximately 175 kg/cm 2 regardless of the pressure in the downstream
cylinder storage, thereby ensuring that the dryer operates at its maximum
efficiency.
CATALYTIC PURIFIER
The catal ytic purifier is used to remove oxygen impurit y from the hydrogen gas
b y causing the oxygen to catal yticall y combine with hydrogen to form water
vapor. When operating properl y the purifier should remove oxygen to a residual
impurit y of less than ten parts per million
A special “wettable” t ype catal yst is used, which does not require the use of
preheaters, temperature controllers, etc.
When ox ygen is catalyticall y combined with hydrogen, heat is given off and the
temperature of the gas increases. A temperature rise of 16 o C can be expected fro
each tenth of one percent ox ygen reacted. If too much ox ygen is present (more
than 4 %) the gas mixture could explode. For this reason extreme caution must
be taken to exclude excessive ox ygen from the Hydrogen in the catal ytic
purifier.
AFTER COOLER
The after cooler is supplied to cool the hot hydrogen leaving the catal ytic
purifier, before it enters the desiccant dryer. If the hydrogen is not sufficientl y
cooled the desiccant dryer could be overloaded, with harmful effects on the exit
dew point.
The After cooler is a shell and tube t ype heat exchanger, with hydrogen flowing
on the tube side and cooling water flowing on the shell side. Temperature Gauge
at the After cooler outlet indicates hydrogen temperature.
From after cooler the hydrogen gas goes to Hydrogen storage bottles through
coalescing filters.
55
BOP Training Report
56
BOP Training Report
OPERATION OF RECTIFIER
Press the ‘RECTIFIE R START’ pushbutton. The rectifier is now
ON. The RECTIFIER ON indicating light LR should now light up.
Turn the Ampere level control slowl y clockwise in 300 ampere
increments.
After five minutes of operation, check the hydrogen gas purity. When
its purit y reaches above 99.5%, turn hydrogen gas into the gas holder.
Operate at 600 amperes for one and half hour. During this time,
measure cell voltage balance.
Check A-T (anode to tank) voltage. (0.5 to 1.4 volts)
Check C-T (cathode to tank) voltage (1.4 to 0.5 volts)
Operate at 1200 amperes for twent y four hours and then proceed to
2000 amperes in 300 amperes increment every half hour.
Open the gas holder valve slightl y and then close the hydrogen vent
valve completel y.
Adjust the water seal overflow pipe to maintain 25mm (differential)
of water column pressure as observed in manometer on front panel.
57
BOP Training Report
Calcium is used as a parameter to control blow down of Cooling Tower. Condenser pipes are
of Copper metal & Circ Water lines are of CS. The main cause of deterioration in this system is
bicarbonates & carbonates precipitation which is thus calculated by Calcium present in the
system.
EFFLUENT
pH 6~9 6~9
58
BOP Training Report
NORMAL CONDITIONS
After testing all parameters of blow down basin sample in lab, if found with in the limit
start dumping.
If the results are not with in the limit please act as mentioned in the above chart.
During outages after Air Heater Basket washing extreme abnormal conditions are observed,
following procedure deals with such conditions;
59
BOP Training Report
down
CHEMICAL DOSING:
Before starting chemical dosing maintain the pH of the blow down basin
approximately 10.00 by using caustic soda (NaOH).
Then add lime (50ppm), wait for 30 minute.
Put polymer (10ppm) in it, wait for 30 minute.
After 30 minutes stop the recirculation pump and close air scoring valve.
Wait for 2 hours to allow all impurities and suspended solids to settle down.
Now take the sample without putting the pump on recirculation.
60
BOP Training Report
Perform the sample testing with digestion method of the blow down basin. If its results meet
the environmental standards, you can put it on dumping.
Note:
In the process of chemical dosing you have to maintain the pH of the blow down basin up to
10. The basic reason of this is to achieve the proper results of chemical dosing and their
actions. The pH can maintained up to 10 by using Caustic NaOH.
Before dumping if pH is above 8 then bring it to 8 by adding Sulfuric acid again put on
recirculation and again allow it to settle down for 1/2 hrs.
61
BOP Training Report
APPENDIX
62
BOP Training Report
Clarifier 2400 m 3
Coagulant Tank 15 m 3
63
BOP Training Report
MULTIMEDIA FILTERS
Technical Data
Type Vertical
Diameter 2438 mm
Freeboard 590 mm
MULTIMEDIA CLEANING
Time 10 minutes
Time 5 minutes
64
BOP Training Report
5 micron Filters
Quantity/unit 2
Diameter 406 mm
Height 2108 mm
CATION UNIT
Quantity 2
Diameter 1829 mm
Resin/Unit 5.375 m3
65
BOP Training Report
ANION UNIT
Quantity 2
Diameter 1829 mm
Resin/Unit 3.68 m3
Quantity 2
Diameter 1524 mm
66
BOP Training Report
COOLING TOWER
67
BOP Training Report
Diameter 9.76m
68