Professional Documents
Culture Documents
Grey and Yellow Buildings Social Media Report
Grey and Yellow Buildings Social Media Report
INTERNATIONAL
COMMERCE
CENTRE
TALL BUILDINGS WORKSHOP
VAISHNAVI.K
1701086
SEMESTER 8
SECTION B
PAGE 2
ABOUT
INTERNATIONAL
COMMERCE CENTRE
The International Commerce Centre represents a shift in the tall
China via a network of high speed rail, subway, buses, and ferry
terminals.
PAGE 3
LOCATION
CLIENT
TEAM
Hotel)
TYPE
Supertall
SIZE
HEIGHT
484 m / 1,587 ft
UNITS
300 Rooms
PAGE 4
ROWAN MOORE,
ARCHITECTURAL REVIEW'S
If Miami is a city of
surfaces, of pink
plaster and deco
doodahs, this building
is skeletal, naked
PAGE 5
STRUCTURAL SYSTEM
CONSTRUCTION DETAILS
September 2001. The old design had a 100m pyramidal top that
2010.
The new design is a square 484m tower with 118 floors and
ENGINEERING
The façade for the building comprises triple-glazed, glass
concrete overlay.
PAGE 7
VERTICAL CIRCULATION
With a projected daily occupancy of 30,000 workers and visitors,
local elevators and high-speed shuttles to sky lobbies for the upper
office anchor tenants and the Ritz-Carlton Hotel are sited on the
VERTICAL PHASING
The tower's vertical organization facilitated the construction
zones enclosed for fit-out, and the upper floors still under
Hung Kai Properties. When the first tenants moved in, the
onto the future tenant drop-off directly from flat bed trucks
mall.
PAGE 9
FIRE SAFETY
CONCERNS
Fire safety requirements for supertall
prescriptive approach or a
performance-based approach.
activated, only alarms on the fire floor, not always guarantee effective evacuation.
the fire floor will be actuated. Alert The concept of refuge floors was introduced to
affected floors in the same zone and industrial buildings higher than 25 stories, industrial
Fire alarms in other zones will not be intermediate refuge floor within a certain numberof
required (see Figure 3). Despite the international firecodes stipulate the requirement of
the occupancy factorof the refuge floors wouldbe In addition, it is suggested that evacuating some floors
0.22 m2/person. If a greater occupancy factor, above andbelow the firefloor by means of a zoned
such as 1 m2/person in restaurants and 0.5 detection and alarm system may alleviate congestion in
m2/person in a banking hall as stated in the code the MoE (Bukowski 2010). This approach has been
adopted in some supertall buildings such as theSupertall
is considered, there would be too manyevacuees
Building B in HongKong (see Figure4).
on the refuge floor. Therefore, the prescriptive
refuge area calculation in supertall building should As the reliability of fire detection and alarm systemsis
be further studied. crucial to the effectiveness of such an approach, the
HongKong Fire Services Department (FSD) has issueda
Counter flow problem circular letter specifying measures to be carriedout in
Clashing between emergency responders and case of shutdown or repairof detection andalarm
evacuees may increase the time for rescue and systems, such as the provision of standalone smoke
detectors in buildings adopting performance-based
evacuation (SFPE 2012). For this reason, a
design. Additional firefighting staff and equipment are
“hydraulic flow” approach (Chow 2006) may not be also deployed and more frequent patrolling intervals
applicable in estimating the evacuation time of areimposed.
occupants with different physical strengths (Kady
Effective evacuation relies on unobstructed means For this reason, the Hong KongFSD imposed
specificmeasures to maintainthe suppression strength in
of escape (MoE)with adequate width and an
supertall buildings. First, fast response sprinkler heads
ordered evacuation. Although the width of MoE in
are installed in special hazard areas.Also, owners of fire
supertall buildings is regulated by the HongKong service installations (FSIs) are obligedto employ a
Fire Safety Code, the authority, owners, anall MoE registered FSI contractor to inspect the FSIs of their
in supertall buildings are free from obstruction buildings at least onceevery 12 months. Moreover,
and combustibles. In addition, change in use and periodicmaintenance and functional tests during
structural alterations of buildings have to be jointexercise/drills are conducted between the building
approved by the building authority in advance management and FSD personnel.
firefighters
PAGE 11
must be investigated.
Supertall buildings have extremely high loading,and fire whirl) in a single fire model to
façades which are out of reach of aerial generate a converged result could be a
fromthe distance, the width of EVA for new smoke movement. For example, pressuriza- tion of
metersand 7.3 metersas required by the should be pressurized to 50 Pa. However, the pressure
Fireman liftsare required in tall and supertall Code of Practiceon Wind Effects in Hong Kong 2004
and equipment to the firefloor. The Hong façade. Nevertheless, the effect of natural wind to
Kong Fire Safety Code stipulates the
smoke and flame spread is not discussed, not to
dimension, rated load, and speed of a
mention the effect of natural wind on a refuge floor.
fireman’s lift. Nevertheless, there is no
As high windspeed may accelerate fire growth in
additional requirement for fireman’slift in
supertall buildings, empirical study on natural wind
supertall buildings despite more manpower
effect to ventilation-controlled fire growth and smoke
and equipment.
spread is necessary.
PAGE 12
SERVICES-HVAC
PAGE 13
The Hong Kong International Commerce Centre (ICC) is the tallest building
in Hong Kong and the seventh tallest building in the world, as ranked by
the Council on Tall Buildings and Urban Habitat. Rising 484 meters (1,588
feet) above Kowloon Station, the ICC offers more than 270,000 square
meters (2.9 million square feet) of office, exhibition, conference, and hotel
space.
The highest hotel in the world, the Ritz-Carlton Hong Kong, occupies the
top sixteen floors of the ICC. The uppermost story—the 118th—is home
to the world’s highest bar and swimming pool. A critical piece of the
engineering puzzle, therefore, was to ensure that hotel guests remain
comfortable during high wind events.
Hong Kong’s wind climate is one of the world’s most unique. Tall buildings
share space with impressive topography and a wide harbor, and typhoons
occur regularly. The world-renowned engineering consultants at Arup
hired CPP to find out how wind would affect ICC occupants and to answer
key questions about the tower’s response to typhoon-force winds.
To understand the wind climate, CPP’s engineers and atmospheric
scientists first measured wind speeds on a 1:4,000 scale topographical
model of the Hong Kong area. Measuring wind speeds and turbulence
levels right at the ICC construction site gave us the information we needed
to correctly model the approach winds that would influence the building’s
design.
CPP’s structural experts then designed and built a 1:500 scale model of
the ICC and all buildings and structures within a 710 meter (2,300 foot)
radius. We measured wind loads and characterized the ICC’s structural
behavior using our boundary layer wind tunnel in Fort Collins, Colorado.
Our engineers examined data for several candidate building designs,
including the one that the design team ultimately chose to build.
Our engineers demonstrated that the ICC’s occupants would not
experience enough wind-induced building movement to cause
discomfort, and we delivered critical information about the typhoon-
induced wind loads that the ICC’s internal frame would need to withstand.
Construction on the ICC began in 2002 and was completed in 2010. CPP is
proud to have played a critical role in the development of this historic
structure.