SANS 10198 - Earthing Systems Under 33kV - General Provisions - 2004

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 14

Collection of standards in electronic format (PDF)

1. Copyright

This standard is available to staff members of companies that have subscribed to the complete
collection of SANS standards in accordance with a formal copyright agreement. The document
may reside on a CENTRAL FILESERVER or INTRANET SYSTEM only. Unless specific
permission has been granted, this document MAY NOT be sent or given to staff members from
other companies. Doing so would constitute a VIOLATION of SABS copyright rules.

2. Indemnity

Standards South Africa accepts no liability for any damage whatsoever that may result from the
use of this material or the information contained therein, irrespective of the cause and quantum
thererof.

Click on one of the two boxes

I agree with the above I do not agree


This standard may only be used and printed by approved subscription and freemailing clients of the SABS.

ICS 29.240.20
SANS 10198-3:2004
ISBN 0-626-15488-X Edition 2

SOUTH AFRICAN NATIONAL STANDARD

The selection, handling and installation of


electric power cables of rating not exceeding 33
kV

Part 3: Earthing systems — General


provisions

Published by Standards South Africa


1 dr lategan road groenkloof private bag x191 pretoria 0001
tel: 012 428 7911 fax: 012 344 1568 international code + 27 12
www.stansa.co.za
© Standards South Africa 2004
This standard may only be used and printed by approved subscription and freemailing clients of the SABS.

SANS 10198-3:2004
Edition 2

Table of changes
Change No. Date Scope

Abstract
Covers general provisions for the earthing of electric power cables and the apparatus in which the
cables are terminated.

Keywords
earth conductors, earthing, electric cables, electric connectors, electrical protection equipment,
installation, power cables.

Acknowledgement
Standards South Africa wishes to acknowledge the valuable assistance received from the
Association of Electric Cable Manufacturers of South Africa.
This standard may only be used and printed by approved subscription and freemailing clients of the SABS.

SANS 10198-3:2004
Edition 2

Foreword
This South African standard was approved by National Committee StanSA TC 66, Electric cables, in
accordance with procedures of Standards South Africa, in compliance with annex 3 of the
WTO/TBT agreement.

This edition cancels and replaces the first edition (SABS 0198-3:1988).

SANS 10198 consists of the following parts, under the general title The selection, handling and
installation of electric power cables of rating not exceeding 33 kV:

Part 1: Definitions and statutory requirements.

Part 2: Selection of cable type and methods of installation.

Part 3: Earthing systems - General provisions.

Part 4: Current ratings.

Part 5: Determination of thermal and electrical resistivity of soil.

Part 6: Transportation and storage.

Part 7: Safety precautions.

Part 8: Cable laying and installation.

Part 9: Jointing and termination of extruded solid dielectric-insulated cables up to 3,3 kV.

Part 10: Jointing and termination of paper-insulated cables.

Part 11: Jointing and termination of screened polymeric-insulated cables.

Part 12: Installation of earthing system.

Part 13: Testing, commissioning and fault location.

Part 14: Installation of aerial bundled conductor (ABC) cables.

NOTE The first five parts deal with factors to be taken into account when an electrical distribution system is
being designed. The last nine parts deal with the practical aspects of handling and installing cables.

Annex A is for information only.

1
This standard may only be used and printed by approved subscription and freemailing clients of the SABS.

SANS 10198-3:2004
Edition 2

Contents
Page

Abstract

Keywords

Acknowledgement

Foreword .......................................................................................................................................... 1

1 Scope ... ...................................................................................................................................... 3

2 Normative references ................................................................................................................. 3

3 Definitions ... ................................................................................................................................ 3

4 Earthing of transformer and switchgear cables ... ........................................................................ 3

4.1 Distribution transformer cables ... ....................................................................................... 3


4.2 Earth fault paths ... ............................................................................................................. 4
4.3 Earthing of 11/3,3 kV transformer cables... ........................................................................ 4
4.4 Earthing of 11/0,4 kV transformer cables... ........................................................................ 4
4.5 Earth connections ... ........................................................................................................... 4
4.6 Resistance of cable glands, earthing leads, etc. .. ............................................................. 5

Annex A (informative) Additional information on earth connections ... ............................................. 9

Bibliography ... .............................................................................................................................. 11

2
This standard may only be used and printed by approved subscription and freemailing clients of the SABS.

SANS 10198-3:2004
Edition 2

The selection, handling and installation of electric power cables of


rating not exceeding 33 kV
Part 3:
Earthing systems — General provisions

1 Scope
This part of SANS 10198 covers general provisions for the earthing of electric power cables and the
apparatus in which the cables are terminated.

2 Normative references
The following standards contain provisions which, through reference in this text, constitute
provisions of this part of SANS 10198. All standards are subject to revision and, since any reference to
a standard is deemed to be a reference to the latest edition of that standard, parties to
agreements based on this part of SANS 10198 are encouraged to take steps to ensure the use of the
most recent editions of the standards indicated below. Information on currently valid national and
international standards can be obtained from Standards South Africa.

SANS 10198-1, The selection, handling and installation of electric power cables of rating not
exceeding 33 kV - Part 1: Definitions and statutory requirements.

SANS 10200 (SABS 0200), Neutral earthing in medium voltage industrial power systems. 3
Definitions
For the purposes of this part of SANS 10198 the definitions given in SANS 10198-1 apply.

4 Earthing of transformer and switchgear cables

4.1 Distribution transformer cables


A distribution transformer is normally connected in delta-star with the star winding supplying the
load. The neutral point of the star winding is then earthed either directly or through a low
impedance, as given in SANS 10200.

Where a distribution transformer is so connected that no neutral is available (normally a transformer


connected in star-delta with the delta winding supplying the load), an artificial neutral point is
created as given in SANS 10200.

3
This standard may only be used and printed by approved subscription and freemailing clients of the SABS.

SANS 10198-3:2004
Edition 2

An earthing terminal is provided on the transformer tank. Separate earth electrodes are not normally
required for switchboards, distribution boards or motor control centres, provided that an efficient
earth connection can be achieved via the sheath or armour (or both) of the supply cable or via an
earth continuity conductor. If the armour of a cable is used to provide earth continuity, ensure that
effective contact is maintained between the armour and the earthing points.

4.2 Earth fault paths


Ensure that the cable provides a path for earth fault currents to return to the neutral point of the
supply transformer. Consider a typical industrial distribution system as shown schematically in
figure 1. An earth fault, for example at switchboard "B", on the 11 kV winding of transformer "C" or
transformer "G", or on any of the cables connecting "A" to "B", "B" to "C" or "B" to "G", shall return to
the neutral point of transformer "A". An earth fault on the low voltage side of transformer "C" or
transformer "G" will appear as an overcurrent on the high voltage side of the transformer. Parallel
paths exist for the earth fault currents, one via the sheath wires or armour wires, or both, of the
supply cables, the other through the main mass of earth. The earth fault currents often follow a
combination of the two paths.

An earth fault on the cable connecting switchboard "B" to transformer "G" will return to the neutral
point of transformer "A" via

a) the sheath/armour of cable "BG" to switchboard "B", the main earth bar of "B", and the
sheath/armour of cable "AB",

b) the sheath/armour of cable "BG" to transformer "G", the earth connection of "G", and through the
main mass of earth to the earth connection of "A", and

c) the earth or structural steelwork at the fault and the main mass of earth to the earth connection
of "A".

4.3 Earthing of 11/3,3 kV transformer cables


In the case of a transformer such as "C" in figure 1, which supplies only high voltage motors, neutral
is frequently earthed via a low value impedance, usually a resistor. This limits the earth fault current
and the voltage rise above earth at the fault position. Intermediate switchboards and motor control
centres are earthed via the sheath/armour wires of the supply cables or via a separate earth
continuity conductor, or both. It is good practice to provide an additional connection to structural
steelwork at each high voltage motor by means of either a copper strip or an insulated lead.

4.4 Earthing of 11/0,4 kV transformer cables


Ensure that a transformer such as "G" in the example, which supplies both a low voltage motor and a
single-phase and a three-phase distribution system requiring a neutral connection, has its neutral
solidly earthed as close as possible to the transformer terminals.

NOTE Where an LV cable box is provided on a transformer, a separate neutral/earth cable gland is usually
included.

Subdistribution boards, motor control centres and LV motors usually rely on the sheath or armour (or
both) of supply cables or separate earth continuity conductors for their earth connections.

4.5 Earth connections


4.5.1 General

In a situation as shown in figure 2, make the following earth connections described in 4.5.2 to 4.5.6
inclusive. These are normally the responsibility of the team installing, jointing and terminating the
main cables.

4
This standard may only be used and printed by approved subscription and freemailing clients of the SABS.

SANS 10198-3:2004
Edition 2

Make earth connections to structures and equipment at points specifically provided for this purpose.
Do not make earth connections to bolts or clamps designed for mechanical support because these
might be removed temporarily or permanently (for example during maintenance work or alterations to
the structure).

4.5.2 Cable glands to substation earth bar

To avoid having to break connections should equipment be changed at a later date, make the earth
connections directly to the substation earth bar and not to equipment such as transformers. Ensure
that the connections are as straight as possible in order to keep the inductance of the earth path to
a minimum.

4.5.3 Transformer tank earthing terminal to substation earth bar

Make the earth connection to the screwed boss provided on the transformer tank.

4.5.4 Switchboard earth bar to substation earth bar

Make the earth connection to the switchboard earth bar which is normally a copper bar running the
full length of the board near the base.

4.5.5 Structural steelwork to substation earth bar

The earthing of the structural steelwork does not imply that the steelwork may be used as a
conducting path for the earthing of apparatus.

4.5.6 Substation earth bar to substation earthing system

Make the earth connections by means of either rectangular copper bar or stranded copper
conductor, according to local practice.

NOTE Recommended minimum conductor sizes are given in annex A.

4.6 Resistance of cable glands, earthing leads, etc.


Ensure that the resistance of the earth fault path is as low as is practicable in order to keep the
voltage to earth at the fault position to a minimum. In any system, a loose or corroded earthing strap
might considerably increase the voltage to earth of the cable sheath or armour at the fault position.

The earth fault current is limited by

a) the system fault reactance,

b) the resistance of the cable conductor up to the fault, and

c) the resistance of the earth fault path.

The reactance of an 11 kV 250 MVA system is 0,484 Ω and so, for practical purposes, the
resistance of the cable conductor may be ignored. However, the reactance of, for example, a 400 V
31 MVA system is only 0,0052 Ω and the conductor resistance plays an important part in limiting
fault current.

Figure 3 shows how the voltage to earth of cable sheath or armour (or both) at the fault position
varies with the resistance of the earth fault path for an 11 kV system of 250 MVA fault level.

5
This standard may only be used and printed by approved subscription and freemailing clients of the SABS.

SANS 10198-3:2004
Edition 2

Figure 1 — Typical industrial distribution system

6
This standard may only be used and printed by approved subscription and freemailing clients of the SABS.

SANS 10198-3:2004
Edition 2

Figure 2 — Typical layout of substation showing required earthing connections

7
This standard may only be used and printed by approved subscription and freemailing clients of the SABS.

SANS 10198-3:2004
Edition 2

NOTE 1 System voltage 6,35 kV.

NOTE 2 System fault level 250 MVA.

Figure 3 — Graph showing increase in voltage at fault position


with increase in resistance of earth fault path

8
This standard may only be used and printed by approved subscription and freemailing clients of the SABS.

SANS 10198-3:2004
Edition 2

Annex A
(informative)

Additional information on earth connections

A.1 Recommended minimum sizes of copper conductor to be used for


earth connections
The minimum size of bare copper bar or stranded copper conductor, either bare or insulated, to be
used for the earth connections detailed in 4.5, is governed by the maximum allowable temperature of
the copper and the electromagnetic forces resulting from the short-circuit current.

For an allowable final temperature T2 of the earthing conductor, the current density is calculated
from the expression

I = k'
A t

where

I is the short-circuit current, in amperes;

A is the cross-sectional area, in millimetres squared;

k' is a factor determined as follows:

1/2
234,5 + T2
k' = 226 log
e
234,5 + T1
where

T1 and T2 are the initial and final temperatures, in degrees Celsius;

t is the clearance time, in seconds.

NOTE This expression assumes that all the heat energy is stored in the conductor. Theoretically, a current
density of 130 A/mm² will, within a clearance time of 3 s, cause a temperature rise of 450 °C above an ambient
temperature of 30 °C. However, measurements made by the SABS have shown that, because of heat losses, a
temperature rise of approximately 320 °C occurs.

Where bare copper bar is to be used, the recommended minimum sizes based on a current density
of 130 A/mm² for a clearance time of 3 s are given in table A.1. Although a higher current density
would be thermally permissible for shorter clearance times, tests have shown that the resultant
electromagnetic forces, which are proportional to the square of the current, are difficult to contain.

Where stranded copper conductor is to be used, the recommended minimum sizes are given in
table A.2. If the stranded copper conductor is PVC-insulated, a final temperature of 150 °C should not
be exceeded and therefore a lower current density of 80 A/mm² has been employed in the
calculation of the maximum current rating.

Soldered lugs may be used on PVC-insulated earthing leads, provided that they have the
appropriate maximum current rating (3 s). If crimped lugs are used on bare stranded copper
conductor, a higher current density of 110 A/mm² can safely be used in calculations. Lugs intended to
be crimped by means of a compression tool should be used.

9
This standard may only be used and printed by approved subscription and freemailing clients of the SABS.

SANS 10198-3:2004
Edition 2

A.2 Joints in copper earthing bar

The results of tests carried out by the SABS show that joints in copper bar should be made by
welding or brazing. Where this is not possible, a satisfactory joint can be made by tinning the ends
of the bars to be jointed over a distance equal to twice the width of the bar and making a bolted
overlap joint. Two bolts should be used on bars of width 25 mm and 31,5 mm, and four bolts on
bars of width 40 mm and 50 mm. The bolts should be of brass to avoid galvanic corrosion, and
should have an M6 thread and be of sufficient length to accept a brass nut and washer.

Table A.1 — Short-time current ratings of bare rectangular


copper bar for use as earth connections on systems with solidly earthed neutral

1 2 3 4
Dimensions of copper bar, min. Cross-sectional area Maximum current
mm rating (3 s) a

Thickness Width mm² kA


3,15 25,0 78,8 10,2
3,15 31,5 99,2 12,9
4,0 31,5 126 16,4
4,0 40,0 160 20,8
6,3 31,5 198 25,7
6,3 40,0 252 32,8
6,3 50,0 315 40,9
a Although higher current ratings for periods of less than 3 s are thermally permissible, it is recommended that
the ratings given above not be exceeded. Tests have shown that the electromagnetic forces resulting from
such currents are difficult to contain.

Table A.2 — Short-time current ratings of PVC-insulated stranded copper


conductor and bare stranded copper conductor

1 2 3
Nominal cross-sectional area Maximum current rating (3 s) a
of conductor, min. kA
PVC-insulated stranded copper Bare stranded copper
mm 2 conductor b conductor c
70 5,6 7,7
95 7,6 10,4
120 9,6 13,2
150 12,0 16,5
185 14,8 20,4
240 19,2 26,4
300 24,0 33,0
a Soldered lugs may be used with PVC-insulated conductors, but crimped lugs shall be used on bare conductors
when the ratings given in column 3 are adopted. See also footnote a to table A.1.
b
Current density of 80 A/mm² giving a temperature rise of 120 °C above an ambient air temperature of 30 °C.
c Current density of 110 A/mm² giving a temperature rise of 270 °C above an ambient air temperature of 30 °C.

10
This standard may only be used and printed by approved subscription and freemailing clients of the SABS.

SANS 10198-3:2004
Edition 2

Bibliography

SANS 10198-12 (SABS 0198-12), The selection, handling and installation of electric power cables of
rating not exceeding 33 kV - Part 12: Installation of earthing system.

SANS 10199 (SABS 0199), The design and installation of an earth electrode.

© Standards South Africa

11

You might also like