Chloride CP-70Z 31: AC UPS System

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 2

Chloride CP-70Z 31 AC UPS System Industrial Power for

Business-Critical Continuity™
5 to 250kVA - 1ph output

The Chloride CP-70Z industrial The Chloride CP range is designed to meet the harshest electrical and
Uninterruptible Power Supply system mechanical requirements in industrial environments.
(UPS) is the flagship product of Each Chloride CP product is based on interchangeable sub-assemblies to allow
Chloride Industrial Power. It combines
full customization, in compliance with client’s technical specification and with
conservative design topology with
project documentation requirements.
proven digital control technology to
offer the best performances in any
electrical and environmental condition. Associated with an industrial stand-by battery, the Chloride CP-70Z 31 range
is dedicated to protect critical industrial single phase AC equipments and
The Chloride CP range is designed to meet
the stringent electrical and mechanical requi- processes from the damaging effects of power interruption and losses.
rements in industrial environments.
Each Chloride CP product is based on
interchangeable sub-assemblies to allow full
customization, in compliance with client’s
technical specification and with project docu-
mentation requirements.

Benefits
n Tailor made systems to comply with all
customer’s specifications.
n Ruggedized solutions for demanding
environments: extended temperatures,
vibrations, dust, elevation, dripping water
and moisture.
n Efficient maintenance thanks to easy front-
access to all vital modules of the system.
Key Features
n Reliability - Unique design which allows
the UPS to continuously operate for at least
20 years at full load at a permanent 40°C
ambient temperature.
n On-line double conversion - UPS classified
VFI SS 111 as per IEC62040-3
n Robust mechanical design - the system
withstands vertical and horizontal
acceleration stress tests up to 0.5g as
standard
n Galvanic isolation –input and output
transformers as standard
n Multilingual digital graphic display with
embedded event log
n Remote monitoring capabilities: Modbus,
Profibus, DF1, ethernet, volt-free contact,
monitoring software
n Fully customized electrical and mechanical
solutions – On demand design to comply
with every standards (e.g. UL, ANSI, NEMA,
IEC, CSA, ABS, DNV)
n Full compatibility with lead-acid and nickel-
cadmium batteries sealed or vented
Applications
The Chloride CP-70Z AC UPS System range suits all
applications such as:
n Oil and Gas offshore and onshore
n Refining and petrochemical plants
n Power generation plants
n Transportation (rail, metro, tramway)
Chloride CP-70Z 31 UPS System Industrial Power for
5 to 250 kVA - 1ph output Business-Critical Continuity™

Ratings - Output power (kVA) vs DC intermediate voltage (Vdc) Technical Data

While every precaution has been taken to ensure the accuracy and completeness of this literature, Emerson Network power assumes no responsability and disclaims all liability for damages resulting from use of this information or for any errors or
110–120Vdc 220-240Vdc 400Vdc Input
2.5 AC voltage 3 x 400V (380, 415)*
5 Voltage tolerance +/- 10%
7.5 Frequency 50Hz (60Hz)
10 10 Frequency tolerance +/- 5%
15 15 Intermediate DC Circuit
20 20 Nominal DC voltage 110 / 120 / 220 / 240 / 400 V
25 25 Voltage stability +/- 1% in float mode, input within tolerance
+/-1.5% for parallel rectifiers
30 30
Voltage ripple 1% RMS, in float, battery connected
40 40 40
50 50 50 Current limitation I nominal
60 60 60 Charging characteristic UI according to DIN 41773
80 80 Ouput
100 100 Available ratings see table above (at PF 0.8 lagging)
120 120 AC Voltage 1 x 230V (220, 240) ; 1 x 110V (115, 120)*
Up to 250 kVA on request Frequency 50Hz (60Hz)
Frequency stability
Options
• with internal oscillator +/- 0.5%
Rectifier 12-pulse rectifier
Harmonic filter • with reserve synchronism +/-3% (from 0.2 to 6% adjustable)
Ripple filters Frequency response <1Hz/s (0.1Hz/s for parallel systems)
Blocking diode
Voltage stability (for 0-100% load variation)
Other input voltage (3x190 to 3x690VAC)
Inrush current limitation to 8In • static +/-1% (+/-2% for parallel systems)
Surge and Lightning protections • dynamic +/-2% (+/-3% for parallel systems)
Battery Battery circuit protection box Overload inverter
Battery cabinet • 1 minute 150% of nominal power
Low-voltage disconnect contactor
Battery Management System • 10 minutes 125% of nominal power
Battery room temperature sensor Short circuit clearance
System Dual configurations • 100 ms 250% of nominal current
Hot stand-by configuration
Input / intermediate /output isolators • 5s 175% of nominal current
DC/DC serial regulator Distortion
isolated DC/DC converter • With 100% linear load 3%
AC distribution • With 100% non-linear load Complies with IEC 62040-1-2
Earth fault monitoring
Allowable power factor 0.5 lagging to 0.5 leading
Backfeed protection
Internal lighting Allowable crest factor 3
Anti-condensation heater Battery
Temperature monitor Type Lead Acid or Nickel Cadmium vented or
Special cabinet identification recombination
Reserve transformer
Reserve stabilizer Autonomy From few minutes to several hours, as per
customer’s requirement
Mechanical Up to IP42 external
Top cable entry Battery current limitation 0.1C (Lead Acid battery)
Other frame colour (typical, float & charge modes) 0.2C (Nickel Cadmium battery)
Anti-seismic design Battery current limitation 0.05C (Lead acid battery)
Communication Front-panel analog meters (72x72 class 1.5) (typical, boost mode) 0.1C (Nickel Cadmium battery)
Transducers General Data
Additional Volt-free contacts Operating temperature 0 to 40°C*
Remote monitoring via Modbus
Remote monitoring via other bus Storage temperature (°C) -20 to +70°C
PPVis monitoring software Relative humidity (%) <90% non condensing
Passive or active mimic panel
Non-exhaustive list of options. Consult us for any other requirements.
Operating altitude (m) 1000 m max without derating
Cooling Forced ventilation
Standards
Efficiency Up to 90% according to rating
Compliance IEC 62040 (-1, -2, -3) / 60146 (-1-1, -1-3, -2) / IEC 60950
IEC 61000-6-2 - IEC 61000-6-4 External protection IP 20* according to IEC 60529
IEC 60529 / IEC 60439 / IEC 60076
Noise (dB) 60 – 75 dB according to rating
Conformity Low voltage directive: 2006/95/EC
omissions.

Frame colour Grey RAL 7032


EMC directive: 2004/108/EC
CE Mark Dimensions Varying according to ratings & options

* other available on request

n AC Power n Embedded Power n Power Switching & Controls


Emerson Network Power.
n Connectivity n Industrial Power n Precision Cooling
The global leader in enabling
Business-Critical Continuity™.
n DC Power n Infrastructure Management & Monitoring n Racks & Integrated Cabinets
n Embedded Computing n Outside Plant n Services
Emerson Network Power IS S.A.S Emerson, Business-Critical Continuity and
30 Avenue Montgolfier - BP90 - 69684 Chassieu Cedex France Emerson Network Power are trademarks of
T: +33 (0)4 78 40 13 56 F: +33 (0)4 78 90 58 90 Emerson Electric Co. or one of its affiliated companies.
Industrial.Sales.Chloride@Emerson.com ©2013 Emerson Electric Co.
EmersonNetworkPower.com CP70Z 31 AC UPS System-DSUK-Rev2-02/2013

You might also like