Data Centre

You might also like

Download as pdf or txt
Download as pdf or txt
You are on page 1of 18

Datacenter Tier Classification:

Mega Business
Redundant Components: 2(N+N) Tier 4
Availability 99.995% Fault
Annual Down time: 0.4hrs Tolerant

Large Business No. of Delivery Paths: 2


Redundant Components: (N+1) Tier 3
(T2 + Independent Distribution Path)
Availability 99.982% Concurrently
Annual Down time: 1.6hrs Maintainable

Medium Business
Tier 2 No. of Delivery Paths: 1
Redundant Components: N+1 Availability
Redundant Components (T1 + Redundant Capacity
99.749%
Component )
Annual Down time: 22.0hrs

Small Business
Redundant Components: N Tier 1 No. of Delivery Paths:
Availability 99.671% Basic 1
Annual Down time: 28.8hrs
Cooling: Racks:
PAC Server Rack
Containment Solution Network Rack
INRow Cooling Integrated Cooling Rack
RDHx Solution IPDU with Temp/Hum
Chip Level Cooling

Solutions
MODULAR & SCALABLE
 Taylor Made Solutions
UPS: Offered
Standalone
Modular DCIM:
Rack Level Monitoring
Batteries: Room Level Monitoring
SMF Periodic Health Check
Lithium ion Real Time Alert
Data Centre Infrastructure :

13% 4%1%
13%

13%
9% Savings on
Space / Power /
Cooling

17% 17%

9% 4%
Changing Trends : Space, Power & Cooling
Changing trends in IT hardware in terms of servers, storages & switches is always a challenge for the
organization. An healthy organization or a growing organization is one, which has a balanced growth on both IT
& Facility.

55kW

3kW

IT Rack Density/Rack

How about your facility???


Desktop Server: <1kW

IT HAS CHANGED
SINCE 1980’S TO 2020

 How about your Infrastructure?

Blade Chassis: 3-5kW We address all your bottlenecks


from ‘Space to Power to Cooling’

Pizza Box Server: 1-2kW

HPC Server: 5-10kW


Cooling Comparison: CRAC Vs INRow Vs RDHx
S.NO Description CRAC INROW Cooling RDHx Cooling
1 Capacity Per Rack Upto 8kW 10-15kW 3-106kW
2 Scalability Limited to product Limited to product specification Highly scalable by increasing the
specification flow rate without changing the
existing infrastructure.
3 Efficiency Very Low, more than 50% of Flow of air is not channelized to Very High, heat from the source
the air flow gets blocked at support the IT Load, 100% Hot is suppressed at the rack level,
the False floor and Door Aisle Containment is must for good entire room is Cold Zone.
Perforation performance.
4 Flexibility Very Difficult Highly Critical Easy to move the door between
the required area.
5 Footprint High Occupies rack space 300mm at the rear of the cabinet

6 Control Must, Hot/Cold Aisle Must, Hot Aisle Containment Each door has inbuilt water flow
Containment and Due Point control
7 False Floor Must Depends on situation Depends on situation
8 PUE (Power Usage 2 to 2.5 1.4 to 2.0 1.2 to 1.6
Effectiveness)
9 Carbon Footprint High Medium Lowest
10 ROI 16 to 28 months 12 to 20 months 6 to 10 months
Design Capacity: PAC Systems
Advantage: Dis-Advantage:
• Supports Upto 8kVA Per Rack. • PAC Design supports upto 197 Racks only

• Cold Aisle Containment avoids Hot & Cold Air Mixing, • Racks in the middle of the row, face very low air-flow.

resulting better efficiency. • Bottleneck found on the False floor, which has very low

• Active tiles can be used for higher KVA design. CFM output and Rack Door Perforation (80%) (Air Flow).

• Proven technology for more than 3 decades. • Support on HPC Servers, Blade Chassis and next

• Maintenance and work flow is very simple . generation servers are highly challenging.

• Suitable for small and medium server room. • Active tiles booster disturbs the air flow on other racks.
• Very Low efficiency.
• Higher PUE – 2.2 to 2.3.
• Consumes very high white space, results in lesser racks.
• Chilled Water supply @ 7oC/12oC which consumes higher
energy.
Cooling Comparison: INRow Systems
Advantage: Dis-Advantage:
• Supports Upto 20kVAPer Rack. • Scalability: Defined capacity, rackload cannot be increased

• 266 Racks compared to 197 Racks of PACdesign. in future when the demand increases.

• Lesserwhitespace compared to PACsolution. • Comfort: Person working in the Hot Aisle will be highly

• Efficiency of the equipment increases, since coolingis uncomfortable, as the temperature may go as high as 50oC.

provided very next to the cabinet. • Whitespace: Occupies Rack space, results in lesser racks.
• Hot Aisle Containment avoids, Hot & Cold Air Mixing, • Fansconsume high power and noice.
resulting better efficiency. • Average PUE– 1.9 to 2.0
• Modular Hot SwappableActive Fanshelps in achieving • Maintenance and work flow needs proper care.
higher heat load rejection. • Addition, Movement or change in cooling unit is very

• Proven technology for more than 2 decades. difficult.

• Chilled Water supply @ 14oC/20oC which consumesless


energy.
Cooling Comparison: RDHx Rack Positioning

Tota Total IT
Row 15kW 6kW l Load
Rac
k
(70%) (30%)
A 32 14 46 564
B 32 14 46 564
C 32 14 46 564
D 24 11 35 426
E 28 12 40 492
F 28 12 40 492
G 28 12 40 492

Total No. of Racks 293


Total IT Load 3594
Total Cooling
Required Ton 1022
Cooling Comparison: RDHx Systems
Advantage:
• Scalable: 15kW Door Supports 20kW or more by flow increase or • Entire Room is Cold Zone, there is no hot spot or loss.

temperature decrease but without impacting the design. • Door Can be mounted to any existing rack (subject to rack load

• Modular: Rackdoor can be moved, mounted/changed asper rating).

demand. • Door is 100% Passive, hence no moving parts or electrical

• 293 Racks compared to 266 Racks of INROW design. consumption.

• Lowestwhitespace compared to INROW & PACsolution. • In caseof server activity, maintenance or shutdown of 1 or few
• Efficiency of the equipment increases, since removal of heat is on the racks, the heat load of these racksare absorbed by the racksnext
cabinet. to the cabinet and maintains the Roomlevel temperature.

• Proven technology for more than 2 decades. • Datacenter isdivided into 2 Zones for easymaintenance and
• Chilled Water supply @ 14oC/20oC which consumes less energy. energy savings.
• LowestPUE– 1.5 to1.6 • RDHxhasinbuilt intelligence to control the water flow and
• Lower Capex– Increased Density, No Containment, Reduced Chiller maintain temperature above due point to avoid condensation.
capacity, RealEstate Cost and lowest OPEX. • Additional precaution is taken by providing PAHUunits with
• Lower TCO& ROI: Significantly faster than other energy efficient Humidifier and De-Humidifier.
cooling solutions.
Dis-Advantage:
• Supports TIERIII Design
• RDHx Door has singlepath.
Scalability: IT & CoolingLoad

Server Rack 5000


350 4500
293 1022
300 266 4000 930
250 3500
197
200 3000 692
150 2500
100 2000 3270 3603
50 1500 2433
0 1000
CRAC INROW RDHx
500
Rack 0
CRAC INROW RDHx
IT Load2 CoolingTon
Conclusion:
1. RDHx canaccommodate96 Racksmore than PACsolution & 27 Racksmore on INROW CoolingSolution.
2. RDHx has the potential to vertically increase the load density at very lowcooling cost.
3. RDHx is highly modular and canbe moved with ease.
Rack Arrangement:

Rack Front to Back: Rack Front to Front:

Advantage: Advantage:
• Easy Access: Clients can easily mount or manage their
• Each Row will have dedicated Power distribution path,
equipment's at ease on both the rows.
water line Piping, etc…
• Dual Path: Each row will have dual distribution path of Chilled
water piping and electrical busduct. Dis-Advantage:
• Maintenance: Incase of maintenance work on Power or cooling, • In-case of server activity at the rear side of the cabinet,
this design is easy to manage. Hot air from the cabinet can affect the rack which is
• Cooling: In-case of server activity at the rear side of the cabinet, exactly below this rack.
Hot air (Heat Load) from the cabinet is evenly distributed and • Accessing the second row is very difficult, he may have to
shared among the cabinets around the rack. travel a lot.
Redundancy, Distribution and Concurrent Maintenance:

• Redundancy (N+1) is maintained at all critical levels, which includes,

• Electrical: Transformer, Diesel Generator, Electrical Panels, UPS, Batteries, Floor PDU, Busduct

System, Electrical distribution.

• Cooling: Chiller, Pumps, AHU, Make-up-tank, Water Line distribution (Dual Path).

• Rack Arrangement: Racks are arranged in front to back Concept.

• IPDU: Each is provided with dual Power Distribution Unit with Temperature & Humidity Sensor

to monitor the real time health of the equipment's.


Server Rack
Key Features…

 Height 42U
 Width 600mm
 Depth 1200mm
 Fully adjustable 19-inch rails
 80% Perforated Steel Doors
 1500kgs Load Capacity
 Split hinged side panels
 NEMA/IP20 Rating
 Confirms to DIN 41494 and
EIA 310 and ROHs and
REACH Standards
IPDU – 3Phase (32A, 22kW)

IPDU Supports…
• Temperature/Humidity Sensor
• Smoke Sensor
• Water Leak Sensor
• Air Flow Sensor
• Beacon Sensor
• Door Contact etc…
• Works at 60°C Temperature
Over Head Networking
• Neat, Clean & easily accessible
• Troubleshooting made very simple
• Addressable & Aesthetic
RDHx – High Density Cooling Solution Upto 106kw/Rack

• Removal of Heat at the source


• Highly Efficient Solution
• PUE from 1.1 to 1.6
• ROI @ <6 Months
• More than 100 Installations across the world