Definition





The first safety
switch or circuit
breaker after the
electric meter shall
constitute as the
service protective
device
WIRE GUTTER

METER
PROTECTIVE
DEVICE

GROUND ROD

2.25.2.4 Maximum Number of Disconnects


(a) General. The disconnecting means for each supply permitted by 2.25.2.1 shall consist of
TO INDIVIDUAL UNIT/ OCCUPANT not more than six circuit breakers mounted in a single enclosure, in a group of separate
enclosures, or in or on a switchboard. There shall be no more than six disconnects per
supply grouped in any one location.



• •









è Minimum Clearance from Buildings

Minimum
Clearance
mm (ft-in)
1500
a) Horizontal
(4’11”)

b) Vertical
• Over or under
roofs or
1070
projections not
(3’6”)
readily accessible
to pedestrians
• Over or under
balconies or roofs 3400
accessible to (11’2”)
pedestrians
• Over roofs
accessible to 3400
vehicles but not (11’2”)
trucks