Professional Documents
Culture Documents
Prak - ASTL Ganjil 2021/2022 Lab. Sistem Tenaga Listrik 1 26-11-2021 4359168
Prak - ASTL Ganjil 2021/2022 Lab. Sistem Tenaga Listrik 1 26-11-2021 4359168
Short-Circuit Analysis
Number of Buses: 1 0 44 45
Number of Branches: 19 0 0 24 0 2 45
Number of Machines: 5 1 1 2 13 22
Adjustments
Apply Individual
Tolerance Adjustments /Global Percent
Cable Length: No
Apply Individual
Temperature Correction Adjustments /Global Degree C
45 Buses Total
ohms or siemens per 1000 m per Conductor (Cable) or per Phase (Line)
Line/Cable Length
SKUTM 25% 20NCUS3 400 2400.0 0.0 1 75 0.0610416 0.0898000 0.0970562 0.2280900
SKUTM 50% 20NCUS3 400 2500.0 0.0 1 75 0.0610416 0.0898000 0.0970562 0.2280900
SKUTM 75% 20NCUS3 400 2500.0 0.0 1 75 0.0610416 0.0898000 0.0970562 0.2280900
SKUTM 100% 20NCUS3 400 2500.0 0.0 1 75 0.0610416 0.0898000 0.0970562 0.2280900
SKUTM III 20NCUS3 400 12000.0 0.0 1 75 0.0610416 0.0898000 0.0970562 0.2280900
SKUTM VII 20NCUS3 400 14000.0 0.0 1 75 0.0610416 0.0898000 0.0970562 0.2280900
SUTR V 1,0MCUN3 400 250.0 0.0 1 75 0.0610416 0.0710000 0.0001687 0.1922810 0.1746600
SUTR VI 1,0MCUN3 400 70.0 0.0 1 75 0.0610416 0.0710000 0.0001687 0.1922810 0.1746600
SUTR VII 1,0MCUN3 400 35.0 0.0 1 75 0.0610416 0.0710000 0.0001687 0.1922810 0.1746600
Line1 158 35000.0 0.0 1 75 0.1500000 0.4566700 0.0000000 0.1200000 1.3616500 0.0000001
Line5 158 45000.0 0.0 1 75 0.1500000 0.4566700 0.0000000 0.1200000 1.3616500 0.0000001
Line8 158 30000.0 0.0 1 75 0.1500000 0.4566700 0.0000000 0.1200000 1.3616500 0.0000001
Line9 158 30000.0 0.0 1 75 0.1500000 0.4566700 0.0000000 0.1200000 1.3616500 0.0000001
SUTET I 158 90000.0 0.0 1 75 0.1500000 0.4566700 0.0000000 0.1200000 1.3616500 0.0000001
SUTET II 158 80000.0 0.0 1 75 0.1500000 0.4566700 0.0000000 0.1200000 1.3616500 0.0000001
SUTT I 158 50000.0 0.0 1 75 0.1500000 0.4566700 0.0000000 0.1200000 1.3616500 0.0000001
sutt iii 158 35000.0 0.0 1 75 0.1500000 0.4566700 0.0000000 0.1200000 1.3616500 0.0000001
Trafo Dist III 20/0,4 0.125 20.000 0.400 4.00 1.50 0 0 0 0 0 4.00 Dyn 30.00
Trafo Dist IV 20/0,4 0.500 20.000 0.400 4.00 1.50 0 0 0 -5.000 0 4.00 Dyn 30.00
Trafo Dist. II 20/0,4 kV 0.563 20.000 0.400 4.00 1.50 0 0 0 0 0 4.00 Dyn 30.00
Trafo Distribusi I 20/0,4 0.625 20.000 0.400 4.00 1.50 0 0 0 0 0 4.00 Dyn 30.00
Trafo Interbus 500/150 6.250 500.000 150.000 7.15 8.50 0 0 0 0 0 7.15 YNyn 0.00
Trafo tng I 13,8/150 5.000 13.800 150.000 7.15 8.50 0 0 0 0 0 7.15 YNyn 0.00
Trafo Tng I 13,8/500 kV 11.250 13.800 500.000 8.35 13.00 0 0 0 0 0 8.35 YNyn 0.00
Trafo Tng I 150/20 1.250 150.000 20.000 5.00 3.50 0 0 0 0 0 5.00 YNd 30.00
Trafo tng II 13,8/500 kV 3.100 13.800 500.000 6.25 6.00 0 0 0 0 0 6.25 YNyn 0.00
Trafo tng II 150/20 3.125 150.000 20.000 6.25 6.00 0 0 0 0 0 6.25 YNd 30.00
Trafo tng III 13,8/500 7.500 13.800 500.000 8.35 13.00 0 0 0 0 0 8.35 YNyn 0.00
Trafo tng III 150/20 0.438 150.000 20.000 4.00 1.50 0 0 0 0 0 4.00 YNd 30.00
Trafo tng IV 150/20 1.875 150.000 20.000 6.25 6.00 0 0 0 0 0 6.25 YNd 30.00
Grounding
Transformer Rating Conn. Primary Secondary
ID MVA Prim. kV Sec. kV Type Type kV Amp ohm Type kV Amp ohm
Trafo Dist III 20/0,4 0.125 20.000 0.400 D/Y Resistor 5.8 40.00000
Trafo Dist IV 20/0,4 0.500 20.000 0.400 D/Y Resistor 5.8 40.00000
Trafo Dist. II 20/0,4 kV 0.563 20.000 0.400 D/Y Resistor 5.8 40.00000
Trafo Distribusi I 20/0,4 0.625 20.000 0.400 D/Y Resistor 5.8 40.00000
Project: Prak.ASTL Ganjil 2021/2022 ETAP Page: 7
Grounding
Transformer Rating Conn. Primary Secondary
ID MVA Prim. kV Sec. kV Type Type kV Amp ohm Type kV Amp ohm
Trafo Interbus 500/150 6.250 500.000 150.000 Y/Y Resistor 7216.9 40.00000 Resistor 2165.1 40.00000
Trafo tng I 13,8/150 5.000 13.800 150.000 Y/Y Resistor 199.2 40.00000 Resistor 2165.1 40.00000
Trafo Tng I 13,8/500 kV 11.250 13.800 500.000 Y/Y Resistor 199.2 40.00000 Resistor 7216.9 40.00000
Trafo Tng I 150/20 1.250 150.000 20.000 Y/D Resistor 2165.1 40.00000
Trafo tng II 13,8/500 kV 3.100 13.800 500.000 Y/Y Resistor 199.2 40.00000 Resistor 7216.9 40.00000
Trafo tng II 150/20 3.125 150.000 20.000 Y/D Resistor 2165.1 40.00000
Trafo tng III 13,8/500 7.500 13.800 500.000 Y/Y Resistor 199.2 40.00000 Resistor 7216.9 40.00000
Trafo tng III 150/20 0.438 150.000 20.000 Y/D Resistor 2165.1 40.00000
Trafo tng IV 150/20 1.875 150.000 20.000 Y/D Resistor 2165.1 40.00000
Project: Prak.ASTL Ganjil 2021/2022 ETAP Page: 8
Branch Connections
Trafo Dist III 20/0,4 2W XFMR GD III GD IIIA 1735.94 2603.91 3129.51
Trafo tng I 13,8/150 2W XFMR GI KIT IIIA GI KIT III 16.75 142.35 143.33
Trafo tng III 13,8/500 2W XFMR GI KIT IIA GI KIT II 8.50 110.48 110.81
Trafo tng III 150/20 2W XFMR GI III GI IIIA 519.60 779.40 936.72
SKUTM 25% Cable Bus Keluaran 1% Bus SALURAN 25% 3.66 5.39 6.51
SKUTM 50% Cable Bus SALURAN 25% Bus Saluran 50% 3.82 5.61 6.79
SKUTM 75% Cable Bus Saluran 50% Bus Saluran 75% 3.82 5.61 6.79
SKUTM 100% Cable Bus Saluran 75% Bus saluran 100% 3.82 5.61 6.79
SUTR VII Cable GD IIA Bus Beban XI 133.53 155.31 204.82 0.0000009
% Impedance
Rating 100 MVA Base
Grounding
Power Grid ID Connected Bus ID MVASC kV R X" R/X" Type
Jaringan Transmisi TET GITET 5.000 500.000 99.87523 1997.50500 0.05 Wye - Solid
PLTA Unit1 Steam Turbo 3.529 13.800 1500 85.00 1.000 19.00 0.0 0.05 155.00 Wye Solid 0.00 Turbine 130%
PLTG Unit 1 Steam Turbo 4.706 13.800 1500 85.00 1.000 19.00 0.0 0.05 155.00 Wye Solid 0.00 Turbine 130%
PLTU Unit 1 Steam Turbo 2.353 13.800 3000 85.00 1.000 19.00 0.0 0.05 155.00 Wye Solid 0.00 Turbine 130%
PLTU Unit 2 Steam Turbo 2.353 13.800 3000 85.00 1.000 19.00 0.0 0.05 155.00 Wye Solid 0.00 Turbine 130%
PLTU Unit 3 Steam Turbo 3.529 13.800 3000 85.00 1.000 19.00 0.0 0.05 155.00 Wye Solid 0.00 Turbine 130%
Syn1 Motor 1 1.249 15.38 0.0 0.08 Wye Open Turbine 130%
ID Type Qty ID HP/kW kVA kV Amp PF %R % X" R/X" Conn. Type Amp MW/PP
Mtr1 Motor 1 Bus Beban VIII 250.00 267.68 20.000 7.73 75.00 3.52 14.98 0.24 Wye Open 0.09
Mtr 2 Motor 1 Cmtr1 250.00 236.19 20.000 6.82 85.00 3.52 14.98 0.24 Wye Open 0.09
Motor Loads
Lumped Load % Impedance
Rating % Load Loading (Machine Base) Grounding mFact.
Lumped Load ID kVA kV Amp % PF MTR STAT kW kvar R X" R/X" Conn. Type Amp MW/PP
Lump1 230.0 0.400 331.98 85.00 80 20 156.40 96.93 6.46 15.37 0.42 Delta 0.16
Lump 2 200.0 0.400 288.68 85.00 80 20 136.00 84.29 6.46 15.37 0.42 Delta 0.14
Lump 3 200.0 20.000 5.77 85.00 80 20 136.00 84.29 2.47 16.48 0.15 Delta 0.14
Lump 4 200.0 20.000 5.77 85.00 80 20 136.00 84.29 2.47 16.48 0.15 Delta 0.14
Lump 5 200.0 20.000 5.77 85.00 80 20 136.00 84.29 2.47 16.48 0.15 Delta 0.14
Lump 6 170.0 20.000 4.91 85.00 80 20 115.60 71.64 2.47 16.48 0.15 Delta 0.12
Lump 7 180.0 20.000 5.20 85.00 80 20 122.40 75.86 2.47 16.48 0.15 Delta 0.12
Lump 8 350.0 0.400 505.18 85.00 80 20 238.00 147.50 6.46 15.37 0.42 Delta 0.24
Lump9 200.0 0.400 288.68 85.00 80 20 136.00 84.29 6.46 15.37 0.42 Delta 0.14
Lump 10 200.0 0.400 288.68 85.00 80 20 136.00 84.29 6.46 15.37 0.42 Delta 0.14
Lump 11 200.0 0.400 288.68 85.00 80 20 136.00 84.29 6.46 15.37 0.42 Delta 0.14
Lump 12 200.0 0.400 288.68 85.00 80 20 136.00 84.29 6.46 15.37 0.42 Delta 0.14
Lump 13 200.0 0.400 288.68 85.00 80 20 136.00 84.29 6.46 15.37 0.42 Delta 0.14
From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0
Bus Beban I Total 0.00 8.159 0.00 173.14 173.20 0.006 0.006 9.47E+002 1.60E+003 7.50E+006 2.72E+003
GD IA Bus Beban I 49.59 6.506 0.06 173.12 173.21 0.005 0.006 1.26E+003 1.96E+003 7.50E+006 2.72E+003
Lump1 Bus Beban I 100.00 1.673 100.00 100.00 100.00 0.001 0.000 3.51E+003 8.35E+003
GD I GD IA 76.31 6.506 99.99 100.00 100.00 0.005 0.006 * 4.95E+002 1.09E+003 7.50E+006 5.21E+002
Fault at bus: GI II
Nominal kV = 150.000
Voltage c Factor = 1.10 (User-Defined)
Positive & Zero Sequence Impedances
Contribution 3-Phase Fault Line-To-Ground Fault Looking into "From Bus"
From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0
GI II Total 0.00 0.265 0.00 85.70 98.66 0.314 0.314 2.17E+001 1.58E+002 3.71E+001 8.18E+001
Bus2 GI II 0.33 0.019 0.26 85.77 98.68 0.015 0.000 8.33E+002 2.11E+003
GI I GI II 1.87 0.124 2.31 85.43 98.86 0.118 0.059 3.43E+001 3.40E+002 2.21E+002 4.24E+002
GI III GI II 0.32 0.021 1.71 85.10 98.34 0.050 0.102 5.18E+002 1.94E+003 1.02E+002 2.57E+002
GI KIT III GI II 1.43 0.081 1.50 85.60 98.88 0.072 0.023 4.56E+001 5.22E+002 6.49E+002 1.01E+003
GI IIA GI II 10.16 0.021 59.06 53.03 99.76 0.060 0.130 * 3.86E+002 1.95E+003 8.65E+001 1.99E+002
Bus11 Bus2 5.21 0.019 4.09 87.09 98.66 0.015 0.000 8.31E+002 2.10E+003
GI KIT III GI I 1.43 0.020 1.50 85.60 98.88 0.022 0.021 2.92E+002 2.09E+003 5.23E+002 1.17E+003
GITET II GI I 5.40 0.140 5.44 85.47 99.54 0.116 0.017 2.77E+001 2.96E+002 1.12E+003 1.15E+003
GI IA GI I 5.34 0.004 57.91 51.31 99.56 0.024 0.064 * 4.75E+003 1.02E+004 1.65E+002 3.91E+002
GI IIIA GI III 14.63 0.006 63.44 51.36 99.66 0.014 0.027 * 1.37E+003 6.37E+003 5.73E+002 7.79E+002
GI IIIB GI III 11.89 0.015 58.90 54.18 99.92 0.036 0.076 * 8.05E+002 2.78E+003 1.09E+002 3.31E+002
GI KIT IIIA GI KIT III 22.13 0.061 39.38 87.01 89.63 0.050 0.004 4.51E+001 6.81E+002 6.40E+003 3.41E+002
GD II GI IIA 10.65 0.063 59.32 53.10 99.77 0.043 0.000 1.65E+003 4.32E+003
Bus Beban II GI IIA 11.07 0.097 59.55 53.15 99.80 0.065 0.000 1.13E+003 2.75E+003
From Bus To Bus %V kA % Voltage at From Bus kA Symm. rms % Impedance on 100 MVA base
ID ID From Bus Symm. rms Va Vb Vc Ia 3I0 R1 X1 R0 X0
GI KIT IA Total 0.00 3.018 0.00 97.76 100.68 3.068 3.068 1.21E+001 1.52E+002 2.45E+001 1.48E+002
GI KIT I GI KIT IA 30.17 1.880 52.89 91.18 89.13 1.271 0.071 2.35E+001 2.44E+002 6.42E+003 2.83E+002
PLTU Unit 1 GI KIT IA 100.00 0.569 100.00 100.00 100.00 0.899 1.527 4.25E+001 8.07E+002 4.25E+001 2.97E+002
PLTU Unit 2 GI KIT IA 100.00 0.569 100.00 100.00 100.00 0.899 1.527 4.25E+001 8.07E+002 4.25E+001 2.97E+002
GITET GI KIT I 30.70 0.040 53.26 91.18 89.24 0.027 0.002 2.45E+001 2.21E+002 9.83E+001 2.16E+002
GI KIT IB GI KIT I 49.25 0.012 66.49 91.91 92.28 0.008 0.000 6.17E+001 7.39E+002
Bus Beban I 0.400 8.159 13.773 6.414 0.006 0.010 0.006 0.006 7.066 11.929 7.066 7.066 7.068 11.931 7.068 7.068
GI II 150.000 0.265 0.637 0.207 0.314 0.754 0.314 0.314 0.231 0.555 0.231 0.231 0.318 0.763 0.318 0.318
GI KIT IA 13.800 3.018 7.690 2.828 3.068 7.819 3.068 3.068 2.651 6.757 2.651 2.651 3.087 7.868 3.087 3.087
All fault currents are in rms kA. Current ip is calculated using Method C.
* LLG fault current is the larger of the two faulted line currents.
Project: Prak.ASTL Ganjil 2021/2022 ETAP Page: 17
Bus Positive Seq. Imp. (ohm) Negative Seq. Imp. (ohm) Zero Seq. Imp. (ohm) Fault Zf (ohm)
ID kV Resistance Reactance Impedance Resistance Reactance Impedance Resistance Reactance Impedance Resistance Reactance Impedance
Bus Beban I 0.400 0.01516 0.02557 0.02972 0.01519 0.02554 0.02972 120.02500 0.04359 120.02500 0.00000 0.00000 0.00000
GI II 150.000 48.76826 356.48630 359.80660 55.43505 350.87470 355.22680 83.38947 183.94420 201.96360 0.00000 0.00000 0.00000
GI KIT IA 13.800 0.23092 2.89525 2.90444 0.32047 2.80350 2.82176 0.46724 2.80967 2.84825 0.00000 0.00000 0.00000