Download as pdf or txt
Download as pdf or txt
You are on page 1of 7

Date Rev.

Prepared by Suresh Babu

SIEMENS 11.11.2011 A
Checked by Vivek Garg
Client Rapid MetroRail Gurgoan Ltd.

Project Rapid MetroRail Gurgoan


Approved by Dinesh Sharma
SIKANDERPUR(+1ST01)-750V DC PANELS +TSS01 Doc. No. TTD0200000560

INTERCONNECTION DETAILS
CABLE NO. EQUIPMENT DESIGNATION
From To LENGTH APPLICATION REF. DRG. NO. Remarks
Station Type No's CABLE SIZE FROM TO
code code FROM TO MTRS CORE
code code code code TERMINAL FERRULE TERMINAL FERRULE
+1ST01 5 MC ND 24 +1ST01 +MC42 DCDB 5CX2.5 CU. 18.0 1 X1-2 Main 110V DC CONTROL
LOAD BREAK SWITCH PANEL 2 X1-4
3 X1-6 Main 110V DC MOTOR DRIVES
4 X1-8
5 * * * *
+1ST01 5 MC ND 25 +1ST01 +MC42 DCDB 5CX2.5 CU. 18.0 1 X1-13 Main 110V DC for BLS Network
LOAD BREAK SWITCH PANEL 2 X1-15
3 * * * *
4 * * * *
5 * * * *
+1ST01 5 MC BL 26 +1ST01 +MC42 BLS no 1 5CX2.5 CU. 75.0 1 X2-14 X2-14 to BLS1 X3-1 X3-1 X3-1 to +MC42 X2-14 BLS 110V DC AUX.
LOAD BREAK SWITCH PANEL 2 X2-16 X2-16 to BLS1 X3-3 X3-3 X3-3 to +MC42 X2-16
3 * * * *
4 * * * *
5 * * * *
+1ST01 6 MC NA 27 +1ST01 +MC42 ACDB 5CX2.5 CU. 18.0 1 X2-2 Main 230V AC Supply
LOAD BREAK SWITCH PANEL 2 X2-4
3 * * * *
4 * * * *
5 * * * *
+1ST01 9 MC BL 28 +1ST01 +MC21 BLS no 3 5CX2.5 CU. 40.0 1 X3-1 X3-1 to BLS3 X3-21 X3-21 X3-21 to +MC21 X3-1 BLS Trip / Interlockings
SECTION FEEDER PANEL1 2 X3-3 X3-3 to BLS3 X3-23 X3-23 X3-23 to +MC21 X3-3
3 * * * *
4 * * * *
5 * * * *
+1ST01 5 MC MD 29 +1ST01 +MC11 +MD51 5CX2.5 CU. 8.0 1 X1-164 X1-164 to +MD51 X1-168 X1-168 X1-168 to +MC11 X1-164 Release Interlocking
INCOMER PANEL1 RETURN LINE PANEL 2 X1-165 X1-165 to +MD51 X1-175 X1-175 X1-175 to +MC11 X1-165
3 X1-175 X1-175 to +MD51 X1-165 X1-165 X1-165 to +MC11 X1-175 Release Interlocking
4 X1-170 X1-170 to +MD51 X1-164 X1-164 X1-164 to +MC11 X1-170
5 X1-168 X1-168 to +MD51 X1-166 X1-166 X1-166 to +MC11 X1-168
+1ST01 5 MC MD 30 +1ST01 +MC12 +MD51 5CX2.5 CU. 9.0 1 X1-164 X1-164 to +MD51 X1-169 X1-169 X1-168 to +MC11 X1-169 Release Interlocking
INCOMER PANEL2 RETURN LINE PANEL 2 X1-165 X1-165 to +MD51 X1-176 X1-176 X1-175 to +MC11 X1-176
3 X1-175 X1-175 to +MD51 X1-178 X1-178 X1-165 to +MC11 X1-178 Release Interlocking
4 X1-170 X1-170 to +MD51 X1-177 X1-177 X1-164 to +MC11 X1-177
5 X1-168 X1-168 to +MD51 X1-179 X1-179 X1-166 to +MC11 X1-179
+1ST01 9 MC BL 31 +1ST01 +MC22 +1ST02 BLS no 8 12CX2.5 CU. 880.0 1 * * BLS Trip / Interlockings
SECTION FEEDER PANEL2 DLF PHASE 2 ST., 2 * *
3 X3-2 X3-2 to BLS8 X3-21 X3-21 X3-21 to +MC22 X3-2
4 X3-4 X3-4 to BLS8 X3-23 X3-23 X3-23 to +MC22 X3-4
5 X1-201 X1-201 to BLS8 X3-61 X3-61 X1-61 to +MC22 X3-201
6 X1-202 X1-202 to BLS8 X3-63 X3-63 X1-63 to +MC22 X3-202
7 X1-203 X1-203 to BLS8 X3-65 X3-65 X1-65 to +MC22 X3-203
8 X1-204 X1-204 to BLS8 X3-67 X3-67 X1-67 to +MC22 X3-204
9 X3-16 X3-16 to BLS8 X3-92 X3-92 X3-92 to +MC22 X3-16
10 X3-17 X3-17 to BLS8 X3-94 X3-94 X3-94 to +MC22 X3-17
11 X3-1 X3-1 to BLS8 X3-96 X3-96 X3-96 to +MC22 X3-1
12 X3-5 X3-5 to BLS8 X3-98 X3-98 X3-98 to +MC22 X3-5
+1ST01 5 MC MD 32 +1ST01 +MC23 +MD51 12CX2.5 CU. 8.0 1 X1-41 X1-41 to +MD51 X1-45 X1-45 X1-45 to +MC23 X1-41 Frame Fault Protection(64DC)
SECTION FEEDER PANEL3 RETURN LINE PANEL 2 X1-43 X1-43 to +MD51 X1-46 X1-46 X1-46 to +MC23 X1-43 +MC-21,22&23(64DC)
3 X1-45 X1-45 to +MD51 X1-42 X1-42 X1-42 to +MC23 X1-45 +MC-11(64DC) Protection
4 X1-47 X1-47 to +MD51 X1-48 X1-48 X1-48 to +MC23 X1-47
5 X1-49 X1-49 to +MD51 X1-44 X1-44 X1-44 to +MC23 X1-49 +MC-12(64DC) Protection

1of7
Date Rev. Prepared by Suresh Babu

SIEMENS 11.11.2011 A
Checked by Vivek Garg
Client Rapid MetroRail Gurgoan Ltd.

Project Rapid MetroRail Gurgoan


Approved by Dinesh Sharma
SIKANDERPUR(+1ST01)-750V DC PANELS +TSS01 Doc. No. TTD0200000560

INTERCONNECTION DETAILS
CABLE NO. EQUIPMENT DESIGNATION
From To LENGTH APPLICATION REF. DRG. NO. Remarks
Station Type No's CABLE SIZE FROM TO
code code FROM TO MTRS CORE
code code code code TERMINAL FERRULE TERMINAL FERRULE
6 X1-51 X1-51 to +MD51 X1-50 X1-50 X1-50 to +MC23 X1-51
7 * * * *
8 * * * *
9 * * * *
10 * * * *
11 * * * *
12 * * * *
+1ST01 5 MC BL 33 +1ST01 +MC23 BLS No 1 12CX2.5 CU. 75.0 1 X3-2 X3-2 to BLS1 X3-21 X3-21 X3-21 to +MC23 X3-2 BLS Trip / Interlockings
SECTION FEEDER PANEL3 2 X3-4 X3-4 to BLS1 X3-23 X3-23 X3-23 to +MC23 X3-4
3 * * *
4 * * *
5 X1-204 X1-204 to BLS8 X3-62 X3-62 X3-62 to +MC23 X1-204
6 X1-203 X1-203 to BLS8 X3-64 X3-64 X3-64 to +MC23 X1-203
7 X1-202 X1-202 to BLS8 X3-66 X3-66 X3-66 to +MC23 X1-202
8 X1-201 X1-201 to BLS8 X3-68 X3-68 X3-68 to +MC23 X1-201
9 X3-1 X3-1 to BLS1 X3-81 X3-81 X3-81 to +MC23 X3-1
10 X3-5 X3-5 to BLS1 X3-83 X3-83 X3-83 to +MC23 X3-5
11 X3-12 X3-12 to BLS1 X3-85 X3-85 X3-85 to +MC23 X3-12
12 X3-13 X3-13 to BLS1 X3-87 X3-87 X3-87 to +MC23 X3-13
+1ST01 6 MC MG 34 +1ST01 +MC41 +MG01 5CX2.5 CU. 9.0 1 X2-2 X2-2 to +MG01 X2-2 X2-2 X2-2 to +MC41 X2-2 AC 230 V SUPPLY
COUPLING PANEL RECTIFIER 2 X2-4 X2-4 to +MG01 X2-4 X2-4 X2-4 to +MC41 X2-4
3 * * * *
4 * * * *
5 * * * *
+1ST01 5 MC MG 35 +1ST01 +MC41 +MD51 5CX2.5 CU. 5.0 1 X1-5 X1-5 to +MD51 X1-1 X1-1 X1-1 to +MC41 X1-5 Main DC 110V CONTROL
COUPLING PANEL RETURN LINE PANEL 2 X1-10 X1-10 to +MD51 X1-3 X1-3 X1-3 to +MC41 X1-10
3 X1-12 X1-12 to +MD51 X1-5 X1-5 X1-5 to +MC41 X1-12 Main DC 110V MOTOR DRIVES
4 X1-14 X1-14 to +MD51 X1-7 X1-7 X1-7 to +MC41 X1-14
5 * * * *
+1ST01 5 MC RT 36 +1ST01 +MC41 RTU / SCADA 12CX2.5 CU. 8.0 1 X1-201 X1-201 to RTU 1 * SIGNALS
COUPLING PANEL 2 X1-202 X1-202 to RTU 2 *
3 X1-203 X1-203 to RTU 3 *
4 X1-204 X1-204 to RTU 4 *
5 X1-205 X1-205 to RTU 5 *
6 X1-206 X1-206 to RTU 6 *
7 X1-207 X1-207 to RTU 7 *
8 X1-208 X1-208 to RTU 8 *
9 X1-209 X1-209 to RTU 9 *
10 X1-210 X1-210 to RTU 10 *
11 X1-211 X1-211 to RTU 11 *
12 X1-212 X1-212 to RTU 12 *
+1ST01 5 MC RT 37 +1ST01 +MC41 RTU / SCADA 12CX2.5 CU. 8.0 1 X1-213 X1-213 to RTU 20 * SIGNALS
COUPLING PANEL 2 X1-214 X1-214 to RTU 21 *
3 X1-215 X1-215 to RTU 22 *
4 X1-216 X1-216 to RTU 23 *
5 X1-217 X1-217 to RTU 24 *
6 X1-218 X1-218 to RTU 25 *
7 X1-219 X1-219 to RTU 27 *
8 X1-220 X1-220 to RTU 28 *
9 X1-221 X1-221 to RTU 29 *
10 X1-222 X1-222 to RTU 30 *
11 * * * *
12 * * * *
+1ST01 5 MC RT 38 +1ST01 +MC41 RTU / SCADA 12CX2.5 CU. 8.0 1 X1-223 X1-223 to RTU 31 * SIGNALS
COUPLING PANEL 2 X1-224 X1-224 to RTU 32 *

2of7
Date Rev. Prepared by Suresh Babu

SIEMENS 11.11.2011 A
Checked by Vivek Garg
Client Rapid MetroRail Gurgoan Ltd.

Project Rapid MetroRail Gurgoan


Approved by Dinesh Sharma
SIKANDERPUR(+1ST01)-750V DC PANELS +TSS01 Doc. No. TTD0200000560

INTERCONNECTION DETAILS
CABLE NO. EQUIPMENT DESIGNATION
From To LENGTH APPLICATION REF. DRG. NO. Remarks
Station Type No's CABLE SIZE FROM TO
code code FROM TO MTRS CORE
code code code code TERMINAL FERRULE TERMINAL FERRULE
3 X1-225 X1-225 to RTU 33 *

3of7
Date Rev. Prepared by Suresh Babu

SIEMENS 11.11.2011 A
Checked by Vivek Garg
Client Rapid MetroRail Gurgoan Ltd.

Project Rapid MetroRail Gurgoan


Approved by Dinesh Sharma
SIKANDERPUR(+1ST01)-750V DC PANELS +TSS01 Doc. No. TTD0200000560

INTERCONNECTION DETAILS
CABLE NO. EQUIPMENT DESIGNATION
From To LENGTH APPLICATION REF. DRG. NO. Remarks
Station Type No's CABLE SIZE FROM TO
code code FROM TO MTRS CORE
code code code code TERMINAL FERRULE TERMINAL FERRULE
4 X1-226 X1-226 to RTU 34 *
5 X1-227 X1-227 to RTU 35 *
6 X1-228 X1-228 to RTU 36 *
7 X1-233 X1-233 to RTU 37 *
8 X1-234 X1-234 to RTU 38 *
9 * * * *
10 * * * *
11 * * * *
12 * * * *
+1ST01 5 MC RT 39 +1ST01 +MC41 RTU / SCADA 5CX2.5 CU. 8.0 1 X1-235 X1-235 to RTU 31 * SIGNALS
COUPLING PANEL 2 X1-236 X1-236 to RTU 32 *
3 X1-237 X1-237 to RTU 33 *
4 X1-238 X1-238 to RTU 34 *
5 X1-239 X1-239 to RTU 35 *
+1ST01 5 MD MC 40 +1ST01 +MD51 +1ST01 +MC41 5CX2.5 CU. 5.0 1 X1-9 X1-9 to +MC41 X1-15 X1-15 X1-15 to +MD51 X1-9 Main 24V DC Supply
RETURN LINE PANEL COUPLING PANEL 2 X1-11 X1-11 to +MC41 X1-17 X1-17 X1-17 to +MD51 X1-11
3 * * * *
4 * * * *
5 * * * *
+1ST01 5 MF RT 41 +1ST01 +MF01 RTU / SCADA 12CX2.5 CU. 8.0 1 X1-163 X1-163 to RTU XF36-1 XF36-1 XF36-1 to +MF01 X1-163 SIGNALS
SHORT CIRCUITING DEVICE 2 X1-169 X1-169 to RTU XF36-2 XF36-2 XF36-2 to +MF01 X1-169
3 X1-170 X1-170 to RTU XF36-3 XF36-3 XF36-3 to +MF01 X1-170
4 X1-166 X1-166 to RTU XF36-4 XF36-4 XF36-4 to +MF01 X1-166
5 X1-167 X1-167 to RTU XF36-5 XF36-5 XF36-5 to +MF01 X1-167
6 X1-168 X1-168 to RTU XF36-6 XF36-6 XF36-6 to +MF01 X1-168
7 * * * *
8 * * * *
9 * * * *
10 * * * *
11 * * * *
12 * * * *
+1ST01 5 MF NA 42 +1ST01 +MF01 ACDB 5CX2.5 CU. 14.0 1 X2-1 X2-1 to ACDB MAIN AC 230V
SHORT CIRCUITING DEVICE 2 X2-3 X2-3 to ACDB
3 * * * *
4 * * * *
5 * * * *
+1ST01 9 RT BL 43 RTU / SCADA BLS no 1 12CX2.5 CU. 80.0 1 X3-5
2 D1 X3-7
3 D2 X3-9
4 D3 X3-11
5 D4 X3-13
6 D5 X3-15
7
8
9
10
11
12
+1ST01 9 BL BL 44 BLS no 1 BLS no 3 12CX2.5 CU. 40.0 1 X3-6 X3-6 to BLS3 X3-5 X3-5 X3-5 to BLS1 X3-6 BLS Trip / Interlockings
2
3 X3-10 X3-10 to BLS3 X3-9 X3-9 X3-9 to BLS1 X3-10
4 X3-12 X3-12 to BLS3 X3-11 X3-11 X3-11 to BLS1 X3-12
5 X3-14 X3-14 to BLS3 X3-13 X3-13 X3-13 to BLS1 X3-14
6 X3-16 X3-16 to BLS3 X3-15 X3-15 X3-15 to BLS1 X3-16
7 X3-2 X3-2 to BLS3 X3-1 X3-1 X3-1 to BLS1 X3-2

4of7
Date Rev. Prepared by Suresh Babu

SIEMENS 11.11.2011 A
Checked by Vivek Garg
Client Rapid MetroRail Gurgoan Ltd.

Project Rapid MetroRail Gurgoan


Approved by Dinesh Sharma
SIKANDERPUR(+1ST01)-750V DC PANELS +TSS01 Doc. No. TTD0200000560

INTERCONNECTION DETAILS
CABLE NO. EQUIPMENT DESIGNATION
From To LENGTH APPLICATION REF. DRG. NO. Remarks
Station Type No's CABLE SIZE FROM TO
code code FROM TO MTRS CORE
code code code code TERMINAL FERRULE TERMINAL FERRULE
8 X3-4 X3-4 to BLS3 X3-3 X3-3 X3-3 to BLS1 X3-4

5of7
Date Rev. Prepared by Suresh Babu

SIEMENS 11.11.2011 A
Checked by Vivek Garg
Client Rapid MetroRail Gurgoan Ltd.

Project Rapid MetroRail Gurgoan


Approved by Dinesh Sharma
SIKANDERPUR(+1ST01)-750V DC PANELS +TSS01 Doc. No. TTD0200000560

INTERCONNECTION DETAILS
CABLE NO. EQUIPMENT DESIGNATION
From To LENGTH APPLICATION REF. DRG. NO. Remarks
Station Type No's CABLE SIZE FROM TO
code code FROM TO MTRS CORE
code code code code TERMINAL FERRULE TERMINAL FERRULE
9
10
11
12
+1ST01 9 BL BL 45 BLS no 1 BLS no 3 5CX2.5 CU. 40.0 1 X3-22 X3-22 to BLS3 X3-31 X3-31 X3-31 to BLS1 X3-22 BLS Trip / Interlockings
2 X3-24 X3-24 to BLS3 X3-33 X3-33 X3-33 to BLS1 X3-24
3 X3-31 X3-31 to BLS3 X3-42 X3-42 X3-42 to BLS1 X3-31
4 X3-33 X3-33 to BLS3 X3-44 X3-44 X3-44 to BLS1 X3-33
5 X3-61 X3-61 to BLS3 X3-62 X3-62 X3-62 to BLS1 X3-61
6 X3-63 X3-63 to BLS3 X3-64 X3-64 X3-64 to BLS1 X3-63
7 X3-65 X3-65 to BLS3 X3-66 X3-66 X3-66 to BLS1 X3-65
8 X3-67 X3-67 to BLS3 X3-68 X3-68 X3-68 to BLS1 X3-67
9 X3-82 X3-82 to BLS3 X3-81 X3-81 X3-81 to BLS1 X3-82
10 X3-84 X3-84 to BLS3 X3-83 X3-83 X3-83 to BLS1 X3-84
11 X3-86 X3-86 to BLS3 X3-85 X3-85 X3-85 to BLS1 X3-86
12 X3-88 X3-88 to BLS3 X3-87 X3-87 X3-87 to BLS1 X3-88
+1ST01 9 BL BL 46 BLS no 3 BLS no 2 12CX2.5 CU. 40.0 1 X3-6 X3-6 to BLS2 X3-5 X3-5 X3-5 to BLS3 X3-6 BLS Trip / Interlockings
2
3
4 X3-12 X3-12 to BLS2 X3-11 X3-11 X3-11 to BLS3 X3-12
5 X3-14 X3-14 to BLS2 X3-13 X3-13 X3-13 to BLS3 X3-14
6 X3-16 X3-16 to BLS2 X3-15 X3-15 X3-15 to BLS3 X3-16
7 X3-2 X3-2 to BLS2 X3-1 X3-1 X3-1 to BLS3 X3-2
8 X3-4 X3-4 to BLS2 X3-3 X3-3 X3-3 to BLS3 X3-4
9
10
11
12
+1ST01 9 BL BL 47 BLS no 3 BLS no 2 12CX2.5 CU. 40.0 1 X3-32 X3-32 to BLS2 X3-21 X3-21 X3-21 to BLS3 X3-32 BLS Trip / Interlockings
2 X3-34 X3-34 to BLS2 X3-23 X3-23 X3-23 to BLS3 X3-34
3 X3-41 X3-41 to BLS2 X3-32 X3-32 X3-21 to BLS3 X3-32
4 X3-43 X3-43 to BLS2 X3-34 X3-34 X3-23 to BLS3 X3-34
5 X3-61 X3-61 to BLS2 X3-62 X3-62 X3-23 to BLS3 X3-34
6 X3-63 X3-63 to BLS2 X3-64 X3-64 X3-15 to BLS3 X3-16
7 X3-65 X3-65 to BLS2 X3-66 X3-66 X3-1 to BLS3 X3-2
8 X3-67 X3-67 to BLS2 X368 X3-68 X3-3 to BLS3 X3-4
9 X3-82 X3-82 to BLS2 X3-81 X3-81 X3-81 to BLS3 X3-82
10 X3-84 X3-84 to BLS2 X3-83 X3-83 X3-83 to BLS3 X3-84
11 X3-86 X3-86 to BLS2 X3-85 X3-85 X3-85 to BLS3 X3-86
12 X3-88 X3-88 to BLS2 X3-87 X3-87 X3-87 to BLS3 X3-88
+1ST01 9 BL BL 48 BLS no 2 BLS no 5 12CX2.5 CU. 22.0 1 X3-6 X3-6 to BLS5 X3-5 X3-5 X3-5 to BLS2 X3-6 BLS Trip / Interlockings

6of7
Date Rev. Prepared by Suresh Babu

SIEMENS 11.11.2011 A
Checked by Vivek Garg
Client Rapid MetroRail Gurgoan Ltd.

Project Rapid MetroRail Gurgoan


Approved by Dinesh Sharma
SIKANDERPUR(+1ST01)-750V DC PANELS +TSS01 Doc. No. TTD0200000560

INTERCONNECTION DETAILS
CABLE NO. EQUIPMENT DESIGNATION
From To LENGTH APPLICATION REF. DRG. NO. Remarks
Station Type No's CABLE SIZE FROM TO
code code FROM TO MTRS CORE
code code code code TERMINAL FERRULE TERMINAL FERRULE
2 * *
3 * *
4 * *
5 X3-14 X3-14 to BLS5 X3-13 X3-13 X3-13 to BLS2 X3-14
6 X3-16 X3-16 to BLS5 X3-15 X3-15 X3-15 to BLS2 X3-16
7 X3-2 X3-2 to BLS5 X3-1 X3-1 X3-1 to BLS2 X3-2
8 X3-4 X3-4 to BLS5 X3-3 X3-3 X3-3 to BLS2 X3-4
9 * *
10 * *
11 * *
12 * *
+1ST01 9 BL BL 49 BLS no 5 BLS no 4 12CX2.5 CU. 80.0 1 X3-6 X3-6 to BLS4 X3-5 X3-5 X3-5 to BLS5 X3-6 BLS Trip / Interlockings
2 * *
3 * *
4 * *
5 * *
6 X3-16 X3-16 to BLS4 X3-15 X3-15 X3-15 to BLS5 X3-16
7 X3-2 X3-2 to BLS4 X3-1 X3-1 X3-1 to BLS5 X3-2
8 X3-4 X3-4 to BLS4 X3-3 X3-3 X3-3 to BLS5 X3-4
9 * *
10 * *
11 * *
12 * *
+1ST01 9 BL BL 50 BLS no 3 BLS no 4 5CX2.5 CU. 60.0 1 X3-22 X3-22 to BLS4 X3-21 X3-21 X3-21 to BLS3 X3-22 BLS Trip / Interlockings
2 X3-24 X3-24 to BLS4 X3-21 X3-23 X3-23 to BLS3 X3-24
3 * *
4 * *
5 * *
+1ST01 9 BL BL 51 BLS no 4 BLS no 5 5CX2.5 CU. 80.0 1 X3-22 X3-22 to BLS5 X3-21 X3-21 X3-21 to BLS4 X3-22 BLS Trip / Interlockings
2 X3-24 X3-24 to BLS5 X3-23 X3-23 X3-23 to BLS4 X3-24
3 * *
4 * *
5 * *

7of7

You might also like