Professional Documents
Culture Documents
Giacomini UFH Brochure June 10
Giacomini UFH Brochure June 10
H E AT I N G
PRODUCTS
A World Leader in Underfloor Heating Systems
PAGE PAGE
9 — 10 Design of Rooms with High Ceilings 47 Mixing Manifold Underfloor Heating System
Commissioning Procedure
11 — 12 Generic Underfloor Heating Drawing
48 Mixing Manifold Components
13 Controls
49 — 50 Mixing Manifold continued
14 Typical Mixing Manifold PM100W Wiring Layout
51 Underfloor Heating F.A.Q.
15 Typical Distribution Manifold Wiring Layout
52 Mixing and Distribution Manifolds
16 Weather Compensation
53 Modular Manifold Components
17 — 18 Plastic Pipes
54 — 55 Manifold Components
19 — 22 Giacotherm PE-X Pipe
56 — 57 Thermostats and Electrical Components
23 — 26 Pb Pipe
58 Pipe and Accessories
27 — 30 PE-RT Pipe
59 Accessories
E: enquiries@giacomini.co.uk W: www.giacomini.co.uk
How Underfloor Heating Works
A traditional radiator system transfers energy into a room or The energy reaches into every corner of the room or
space largely by convection. This convection results in the space, which means no cold spots, no warm ceiling and no
floor being the coolest part of the room, leaving a mass of cold feet! In buildings with high ceilings, the temperature
warm air at ceiling level. It also picks up fine dust particles actually reduces as the height increases, whilst with other
from the floor and distributes them into the air and over systems, the convection effect increases the temperatures
furnishings. at high level, giving a high heat loss through the roof. In
addition to this, with underfloor heating, the comfort level
An underfloor system, however, heats almost entirely by
is achieved with an air temperature that is 2°C lower than
radiation. This is the most natural and comfortable form of
convection heating systems. These factors mean that when
heating, like the sun. Radiant energy is emitted by the floor,
designing an underfloor heating system, little allowance is
partly reflected by each surface and partly absorbed. Where it
required for buildings with high ceilings such as churches,
is absorbed, that surface becomes a secondary heat emitter.
barns, sports halls and similar buildings.
After a while, all surfaces and furnishings themselves radiate
energy and the room becomes evenly and uniformly warmed.
• It is easy to control
E: enquiries@giacomini.co.uk W: www.giacomini.co.uk 2
Screed Floor System
Solid floor underfloor heating systems include all floor Insulation is then laid, which is necessary to meet current
constructions that have underfloor heating pipework building ‘U’ values to comply with current building
embedded in concrete or screed. regulations, as well as to reduce the heat loss from the
underfloor heating pipework to the floor below.
They include concrete structural floors and concrete screed
floors, as well as block and beam floors with a screed finish. Giacomini PE-X or Pb pipework is then laid, held in place
with one of the anchorage types and the concrete. The
The structure of the concrete floor will depend upon the
makeup and thickness of the concrete will be determined
structural requirements of the floor. A typical concrete floor
by the structural requirements of the floor. Concrete used
section is shown pointing out the different elements of the
for this type of underfloor heating should not include any
floor structure and showing the Giacomini underfloor heating
insulating materials. The heating pipework is positioned
pipework within the structure.
giving a minimum screed depth of 60mm.
The sub-base will usually be made up of two layers, the first
Screed floors will be laid onto a sub-base, which can be a
being a compact or consolidated hard-core, which will have
concrete base or a block and beam sub floor.
a binding layer on top. A damp proof membrane (DPM) is
usually included at this level; this is essential to stop moisture
transfer into the concrete base.
Underfloor heating systems may be successfully installed Sprung floor: With battens loose laid onto blocks supported
within suspended floors providing the floor is constructed to on a solid base, the underfloor heating is fitted in the normal
suit the application. Therefore it is essential that planning manner, but using double sided tape to hold the plates in
begins at an early stage in the project and the building position. The use of tape avoids dislodging the battens when
contractor is informed of the construction required for the fixing the plates.
radiant panel. The underfloor heating plated system can be
Acoustic pads: To reduce sound transmission from the floor,
easily adapted to accommodate a number of special floor
an acoustic pad is included in the floor makeup. This pad
details, including sprung floors, acoustic pads and cross
should be fitted to the top of the joist or batten with the
battens.
diffusion plate being fixed to the pad with double sided tape.
Suspended floor systems include both joisted floors with Fixings must not penetrate the pad as this will lead to acoustic
conventional joists, supported on end walls of sleeper walls, bridging.
as well as solid floors with battens fixed to the floor. The
Cross battens: If joist centres are not suitable for installing
underfloor heating system consists of aluminium diffusion
the diffusion plate, the floor can be cross battened with the
plates between the joists or battens. The diffusion plates are
battens fixed at 400mm centres. The underfloor heating
grooved to accept the heating pipework.
system can be installed on the cross battens. Outputs from
the plated system are limited to 70W/m2 and floor loadings
are unaffected by this type of system, but will depend upon
the construction for installation.
E: enquiries@giacomini.co.uk W: www.giacomini.co.uk 4
Floating Floor System
Floating floors reduce the overall loading within a building, The grooves are made so an aluminium plate can be
reducing the weight of the floor compared to other floor installed that spreads the heat from the pipe to the
systems. underside of the floor. The panels are produced in a range
from 30mm–100mm in thickness. The installation of this
Insulation panels are pre-grooved at 200mm centres with a
system is very simple. Panels are laid with the bell at each
bell shaped groove at one end of the panel to allow the pipe to
end of the room with panels butt jointed and cut to size.
turn at the end of its run.
Once the panels are in place, the aluminium plates are fitted
within the grooves in much the same way as the plated
system, leaving a gap at each end for the pipe turns.
PitchPitch
Pitch
Pitch
Project Parameters
To obtain maximum comfort from an underfloor radiant Another very important aspect to be considered is the
installation, it must be designed with great care. superficial floor cover of the various rooms, both as regards
the type of material used and the thickness of the same, since
First of all it is important to know the physical characteristics
these factors are extremely influential in the design phase of a
of the building in which the system is to be installed, in
radiant system.
particular the ‘U’ valve of the insulation, so as to correctly
estimate potential heat loss through the building itself. In the design phase it is also useful to be aware of the position
where the manifold will be placed within the area to be heated,
The level of comfort required may vary from one room to
in order to achieve best supply and return circuit distribution.
another within the same building, depending on the purpose
For this reason it is advisable to position the manifold in a
and conditions of the environment. In the case of living
fairly central area in relation to the various rooms which will
areas, approx 20°C is considered an adequate, comfortable
be served by the radiant system, and choosing a spot which
ambient temperature. Also consideration should be given to
will also allow easy inspection.
the UNI EN 1264 norm in terms of maximum floor surface
temperature acceptable for the human body, which is reported The layout of the circuits composing the installation can be of
to be equal to 35°C for peripheral zones, 33°C for bathrooms the “spiral” type or of the “coil” type. The spiral distribution
and 29°C for living areas. guarantees a more uniform surface temperature distribution.
On the other hand, the coil distribution causes a gradual drop
in the superficial temperature from the manifold supply point
to the return point, this makes the coil distribution more
suitable in applications, where there are large screed areas,
such as industrial floors.
E: enquiries@giacomini.co.uk W: www.giacomini.co.uk 6
30 Ta = 18°C
Ta = 20°C
Ta = 22°C
25
Logarithmic mean ΔTh
20
15
10
0
25 30 35 40 45 50
Supply temperature [°C]
Installation Dimensioning
Tv - TR
When reaching the actual installation dimensioning phase, it ∆Th =
will therefore be necessary to consider the various aspects In T
v - Ta
evaluated in the preparatory phase: (thermal insulation, floor TR - Ta
cover, manifold position) in addition to the other factors, such
as pressure loss and ∆T. temperature difference. where: T
v = supply temperature [°C]
TR = return temperature [°C]
For the practical calculation of the pipe spacing and thermal
Ta = ambient temperature [°C]
output the following steps must be followed:
ln = natural logarithm
• First of all the maximum installation supply temperature
• Once the choice of floor cover is known, with the ∆Th
and the required ambient comfort temperature must be
value obtained from the diagram, it is possible to find the
established. With this data follow the diagram to obtain the
spacing between the pipes corresponding to the thermal
value of the ∆Th logarithmic mean, analytically defined as:
requirement q expressed in W/m2.
200 T = 10 cm
T = 5 cm
T = 15 cm T = 7,5 cm
150 T = 10 cm
150 T = 20 cm T = 15 cm
Yield q [W/m2]
Yield q [W/m2]
T = 22,5 cm T = 20 cm
T = 22,5 cm
100
T = 30 cm T = 30 cm
100
50
50
0 0 5 10 15 20 25 30
T = 5 cm
T = 7,5 cm
T = 10 cm
T = 15 cm T = 5 cm
100 100 T = 7,5 cm
Yield q [W/m2]
Yield q [W/m2]
T = 20 cm T = 10 cm
T = 22,5 cm T = 15 cm
T = 30 cm T = 20 cm
T = 22,5 cm
T = 30 cm
50 50
0 0
0 5 10 15 20 25 30 0 5 10 15 20 25 30
30 T = 18°C
T = 20°C
25
T = 22°C
ΔTh logarithmic mean
20
Surface finish:
Thermal output as a function of
15
ΔTh logarithmic mean and of T pitch between the tubes
250
10
T = 5 cm
T = 7,5 cm
200 T = 10 cm
5
T = 15 cm
T = 20 cm
Yieldq [W/m2]
150
T = 22,5 cm
0
25 30 35 40 45 50
T = 30 cm
100
0 5 10 15 20 25 30
E: enquiries@giacomini.co.uk W: www.giacomini.co.uk 8
9 T: 01454 311012 F: 01454 316345
Design of Rooms with High Ceilings
such as Industrial Buildings and Churches
Thermal comfort is known to be influenced not only by In an industrial floor, for example, consideration must be given
air temperature, but also by the temperature of surfaces to the fact that the floor installation may function 24hrs a
surrounding the person and by the presence of draughts. day. This allows for more constant thermal output and for
the heat source to operate with a seasonal average output,
An area heated with a low temperature radiant system,
out‑performing that of traditional installation solutions.
especially if the height is significant, has low air movement.
This avoids air stratification, which occurs with traditional
heating systems and a notable upward dispersion of heat, as
well as excessively dry ambient air.
E: enquiries@giacomini.co.uk W: www.giacomini.co.uk 10
Typical Underfloor Heating Pipe Layout
E: enquiries@giacomini.co.uk W: www.giacomini.co.uk 12
Controls
THERMOSTATS
(VOLTAGE FREE)
T1 T2 T3 T4 T5
G. Power switch
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 18 19 20 21 22 25 26
L1 L2 L3 L4 L5 L6 L7 L8 230V AC
PUMP
ACTUATORS
Note:
Pump and boiler will switch on only after a
230V AC
4 minute delay. Neutral for pump. Boiler must BOILER
Diagram shows 4 thermostats controlling 4 single UFH loops and 1 thermostat controlling 4 loops
E: enquiries@giacomini.co.uk W: www.giacomini.co.uk 14
Typical Distribution Manifold Wiring Layout
L
230v
N
Weather compensation is a highly efficient way of controlling Our weather compensator can be added onto the
a heating system, which monitors the outside temperature, mixing manifold for greater fuel economy and optimum
providing water to the manifold at the optimum temperature. comfort levels.
The very low flow temperatures generated by this system are • Night setback
ideal for use with condensing type boilers, allowing them to
• Intelligent optimization
operate at maximum efficiency almost continuously.
• Automatic temperature adjustment that reacts to
outside temperatures
• Fully programmable
2. Low Mass Radiant 80 Please contact our Sales Office on 01454 311012 for
Supply Water Temperature
60
50
45
40
35
21
21 10 -3
E: enquiries@giacomini.co.uk W: www.giacomini.co.uk 16
Plastic Pipes
In radiant floor systems a fundamental role is played by the of iron components of the installation, since the quantity of
tubing, which is laid on the insulation panels. These pipes oxygen permeating from outside becomes totally negligible.
are flexible and therefore easy to install, as well as having
The ISO 10508 norm refers to tubing in plastic material
chemical-physical characteristics, suitable for radiant systems.
for conveyance of hot and cold water and establishes a
Giacomini pipes in PE-X, Pb and PE-RT are equipped with an
subdivision of the various types of pipes in application classes.
anti-oxygen barrier (BAO), which prevents the risk of corrosion
TUBING TYPES
EXCESSIVE TEMPERATURE
OPERATING TIME TIME TIME
APPLICATION Tmax DUE TO
TEMPERATURE T0 Tmax Tm FIELD OF APPLICATION
CLASS [°C] MALFUNCTIONING
T0 [°C] [years] [years] [hours]
Tm [°C]
E: enquiries@giacomini.co.uk W: www.giacomini.co.uk 18
PE-X
Resilience No breaking
E: enquiries@giacomini.co.uk W: www.giacomini.co.uk 20
Thermal Expansion
ΔT
10 20 30 40 50 60 70
10
9 80
7
Tube length [m]
0
0 10 20 30 40 50 60 70 80 90 100
Expansion [mm]
The Giacotherm pipe in PE-X is supplied in coils of various storage and protect the pipe both from sunlight and accidental
sizes and distributed in special carton boxes, which facilitate damage.
ΔP [mm H2O]
x2
x2
17
x2
14
In the design and installation phases of applications with PE-X
16
,5;
x2
x2
50
18
x1
20
16
pipework, the thermal expansion must be taken into account.
3
x2,
25
Thermal expansion is calculated as:
∆l = α · L · ∆T
10
where: ∆
l = expansion [mm] 50 100 500 1000 2000
100
ΔP [mm H2O]
x2
17
x2
50
16
,5;
x2
x2
18
x1
20
16
3
x2,
25
10
Q [l/h]
T = 80°C
300
100
ΔP [mm H2O]
x2
17
16 16x2
x2
,5;
x2
50
18
x1
20
3
x2,
25
10
Q [l/h]
E: enquiries@giacomini.co.uk W: www.giacomini.co.uk 22
Giacomini Plastics Factory, San Maurizio.
The R986 Giacomini polybutylene pipe is used for hot and The manufacturing of the Pb pipe starts from the 1-buthene
cold water distribution in heating and cooling radiant panel monomer and realizing a specific stereo polymerization
systems, in traditional heating systems distribution and in the assisted by the Ziegler Natta catalyzer. This stereo-specificity
distribution of hot and cold water for sanitary use. of the reaction allows the achievement of neat and crystalline
molecular structures with high standard mechanical
characteristics.
R986 Pb PIPE
E: enquiries@giacomini.co.uk W: www.giacomini.co.uk 24
Thermal Expansion
ΔT
5 10 20 30 40 50 60 70
10
80
9
7
Tube length [m]
0
0 10 20 30 40 50 60 70 80 90 100
Expansion [mm]
The R986 polybutylene pipe is supplied in coils of various and protect the pipe both from sunlight and accidental
sizes distributed in special carton boxes to facilitate storage damage.
∆P [mm H2O]
x2
6x2
In the design and installation phases of applications with PE-X
15
20 2
51
x2
x
x2
18
50
22
x1,
pipework, the thermal expansion must be taken into account.
14
Thermal expansion is calculated as:
∆l = α · L · ∆T
10
where: ∆
l = expansion [mm] 50 100 500 1000 2000
100
5x2
∆P [mm H2O]
x2
51
16
20 2
x
x1,
x2
18
x2
14
50
22
10
Q [l/h]
T = 80°C
300
100
∆P [mm H2O]
5x2
x2
51
16
x1,
x2
50
x2
14
18
20
x2
22
10
Q [l/h]
E: enquiries@giacomini.co.uk W: www.giacomini.co.uk 26
Giacomini Plastics Factory, San Maurizio.
The PE-RT R978 polyethylene pipe with enhanced thermal The resistance to combined “pressure/temperature” stresses
resistance differs from the well-known cross bonded performed by PE-RT pipes is such as to indicate this product
polyethylene PE-X, starting from the raw material with which as suitable for the distribution of mixed water in panel
they are respectively produced, since the compound used installations. A series of advantages motivate its use, including
for PE-RT is specifically designed for this production. On a the simplicity and rapidity of installation, with notable labour-
molecular level, it consists of a polyethylene polymer chain, saving; the absence of welding and mechanical joints under
which includes a minimal percentage of 1-ottene molecule. the track, which could in time induce fluid leakage; the high
In fact, this is a co-polymer, providing a far greater thermal durability of this material, which is not subject to encrustation
resistance than the traditional polyethylene. or electro-chemical phenomena.
E: enquiries@giacomini.co.uk W: www.giacomini.co.uk 28
Thermal Expansion
ΔT
10 20 30 40 50
10
9 60
8
70
7
80
Tube length [m]
0
0 10 20 30 40 50 60 70 80 90 100
Expansion [mm]
Min radius of curvature without pipe curving unit 5·Dest (per curve a 90°) 5.5·Dest (per curve a 180°)
R978Y0122 16 x 2 BAO 90 m
∆P [mm H2O]
x2
x2
16
17
In the design and installation phases of applications with PE-X 50
Δl = α · L · ΔT
10
where: Δ
l = expansion [mm] 50 100 500 1000 2000
100
∆P [mm H2O]
x2
x2
16
50
17
10
Q [l/h]
T = 80°C
300
100
∆P [mm H2O]
x2
x2
50
16
17
10
Q [l/h]
E: enquiries@giacomini.co.uk W: www.giacomini.co.uk 30
PE-X/Al/PE-X Multi-layer
The Giacomini R999 multi-layer pipe in PE-X/Al/PE-X can be The presence of the aluminium layer, welded head-to-head
used in the installation of hot and cold distribution systems with laser technology, guarantees a secure barrier against
for sanitary applications; heating and cooling radiant panel oxygen and other gases, as well as conferring excellent
systems; traditional heating systems with cast iron, aluminium crush resistance to the product.
or steel heating elements.
The multi-layer PE-X/Al/PE-X pipe is suitable for conveying
The water distribution with synthetic material pipes provides potable water according to the norms in force.
enormous advantages:
The multi-layer PE-X/Al/PE-X pipe is characterized by an
• The limited internal roughness of the pipe creates limited internal layer in PE-Xb, an intermediate layer in aluminium,
pressure drop, thereby guaranteeing the minimum pressure longitudinally welded with laser technology, and by an
to the appliance’s usability, even when the upriver pressure external layer in PE-Xb. The intermediate layers of adhesive
available in the installations is low. homogenously bind the aluminium and PE-Xb layers.
ADHESIVE
ALUMINIUM
ADHESIVE
PE-Xb
E: enquiries@giacomini.co.uk W: www.giacomini.co.uk 32
Thermal Expansion
ΔT
10 20 30 40 50 60 70 80
10
0
0 10 20
Expansion [mm]
Dimensions
The multi-layer PE-X/Al/PE-X pipe is supplied in 100m and and protect the pipe both from sunlight and accidental
200m coils packed in carton boxes, which facilitate storage damage.
Connections T = 10°C
300
∆P [mm H2O]
the aluminium from the brass fitting, preventing galvanic
x2
x2
x2
16
18
corrosion.
20
50
Thermal Expansion
In the design and installation phases of applications with PE-X
10
pipework, the thermal expansion must be taken into account.
50 100 500 1000 2000
Δl = α · L · ΔT
where: Δ
l = expansion [mm] T = 50°C
300
α = coefficient of linear thermal expansion
(0.024 [mm/mK])
L = pipe length [m]
100
ΔT = temperature variation [K] o [°C]
∆P [mm H2O]
50 x2
x2
x2
16
18
20
10
Q [l/h]
T = 80°C
300
100
∆P [mm H2O]
50
x2
x2
x2
16
18
20
10
Q [l/h]
E: enquiries@giacomini.co.uk W: www.giacomini.co.uk 34
PE-RT/Al/PE-RT Multi-layer
The presence of the aluminium layer, welded head-to-head • Greatly reduced sound transmission when compared with
with laser technology, guarantees a secure barrier against metallic pipework installations particularly during heat up
oxygen and other gases, as well as conferring excellent and expansion.
crush resistance to the product.
• Very low thermal conductivity: approx 700 times lower
Water distribution with synthetic material pipes provides than copper, 100 times lower than iron.
enormous advantages:
The multi-layer PE-RT/Al/PE-RT pipe is characterized by an
• The limited internal roughness of the pipe creates limited internal layer in PE-RT, an intermediate layer in aluminium,
pressure drop, thereby guaranteeing the minimum pressure longitudinally welded with laser technology, and by an
to the appliances usability, even when the upriver pressure external layer in PE-RT. The intermediate layers of adhesive
available in the installations is low. homogenously bind the aluminium and PE-RT layers.
ADHESIVE
ALUMINIUM
ADHESIVE
PE-Xb
PE-RT/Al/PE-RT PIPE
E: enquiries@giacomini.co.uk W: www.giacomini.co.uk 36
Thermal Expansion
ΔT
10 20 30 40 50 60 70
10
80
9
0
0 10 20
Expansion [mm]
Dimensions
R977 16 x 2 16 12 2 0.113 80
R977 18 x 2 18 14 2 0.154 90
The multi-layer PE-RT/Al/PE-RT pipe is supplied in 100m and and protect the pipe both from sunlight and accidental
200m coils packed in carton boxes, which facilitate storage damage.
Connections T = 10°C
300
∆P [mm H2O]
the aluminium from the brass fitting, preventing galvanic
x2
x2
x2
16
18
corrosion.
20
50
Thermal Expansion
In the design and installation phases of applications with
10
PE-RT/Al/PE-RT pipework, the thermal expansion must be
50 100 500 1000 2000
taken into account.
Q [l/h]
Thermal expansion is calculated as:
Δl = α · L · ΔT
T = 50°C
300
where: Δ
l = expansion [mm]
α = coefficient of linear thermal expansion
(0.026 [mm/mK])
100
L = pipe length [m]
∆P [mm H2O]
x2
x2
16
18
20
10
Q [l/h]
T = 80°C
300
100
∆P [mm H2O]
50
x2
x2
x2
16
18
20
10
Q [l/h]
E: enquiries@giacomini.co.uk W: www.giacomini.co.uk 38
Manifold Cabinets
R500
The series R500 cabinets are built-in, stove-enamelled The cabinets can be equipped with R510 wall fixings,
cabinets, designed and manufactured to allow the housing and also stove-enamelled, available in four versions to match
inspection of manifolds. The R500 series features no less than the cabinets (A, B, C, D), which raise it 200mm from the
four types of cabinets (A, B, C, D) in various sizes, which can unfinished floor to allow the correct accommodation of the
be adapted to the different manifold dimensions. pipework connected to the manifold.
R501
The series R501 cabinets are designed for external inspection of the manifolds. The R501 series features no
installations, are inclusive of wall fixings, stove-enamelled, less than four types of cabinets (A, B, C, D) in various sizes,
and are designed and manufactured to allow the housing and which can be adapted to the different manifold dimensions.
R502
The series R502 cabinets are stove-enamelled, built-in The R502 series features no less than four types of
cabinets inclusive of wall fixings, designed and manufactured cabinets (A, B, C, D) in various sizes, which can be adapted
to allow the housing and inspection of the manifolds. to the different manifold dimensions.
M (min:max)
TYPE NET USABLE Dimensions L [mm] P [mm] Lmax [mm]
[mm]
A 400 x 650 : 720 x 110 440 630 : 740 115 475 single door
B 600 x 650 : 720 x 110 640 630 : 740 115 675 single door
C 800 x 650 : 720 x 110 840 630 : 740 115 875 double door
D 1000 x 650 : 720 x 110 1040 630 : 740 115 1075 double door
L P
M
L P
M(min)
M(max)
Lmax
E: enquiries@giacomini.co.uk W: www.giacomini.co.uk 40
R509
In case the use of a proper cabinet is not envisaged and the R509 is available, consisting of a stove-enamelled frame
manifold is to be installed directly in the service area, item and door to close the doorway of the service area.
R557I
The series R557I features three types of cabinets in different
The series R557I cabinets are built-in, stove-enamelled
sizes adaptable to the various manifold dimensions.
cabinets, designed and manufactured to allow the housing
and inspection of the manifolds. This cabinet is included in the pre-assembled R557R unit.
L max M max
TYPE Code NET USABLE Dimensions L [mm] M [mm] N [mm]
[mm] [mm]
R559I
The series R559I features two types of cabinets in different
The series R559I cabinets are built-in, stove-enamelled
sizes, which can be adapted to the various manifold dimensions.
cabinets, designed and manufactured to allow the housing and
inspection of the manifolds. This cabinet is included in the pre-assembled R559 unit.
L max M max
Code NET USABLE Dimensions L [mm] M [mm] N [mm] P [mm]
[mm] [mm]
N
M
L P
M
N
Mmax
Lmax
L L
P P
MmaxM
M
Mmax
Lmax Lmax
E: enquiries@giacomini.co.uk W: www.giacomini.co.uk 42
Distribution Manifolds
• Flow meters
E: enquiries@giacomini.co.uk W: www.giacomini.co.uk 44
Modular Manifolds
overall Dimensions
PORTS 2 3 4 5 6 7 8 9 10 11 12
H [mm] 450 450 450 450 450 450 450 450 450 450 450
L [mm] 300 350 400 450 525 575 625 675 725 775 825
The injector valve (4) and the lockshield valve (7) are the It is this process that maintains the relatively low
connection points to the primary circuit from the heat source. temperatures required by underfloor heating. The addition of
Water from the heat source, at a temperature lower than actuator heads to the return manifold allows the temperature
90°C, flows through the injector valve (4) and is pumped of different rooms, or zones, to be controlled by their own
past the sensor (6) into the upper flow manifold (1), passing individual thermostat or sensor.
through the pipe circuits to the return manifold (2). A large
The differential valve automatically regulates pressure
proportion of this water is then re-circulated via the pump
changes within the manifold, allowing for accurate setting of
(3), past the sensor and back into the flow manifold. If the
flow rates via the flow meters.
water temperature at the sensor is greater than the limit set
by the thermostatic head (5), the injector valve (4) closes so For added safety the thermostat with immersion sensor (part
that the water is re-circulated until it reaches a low enough of the PM100 wiring centre) should be fitted. This operates
temperature to re-open the injector valve, allowing in in the event of the thermostatic head (5) failing, by shutting
more water. down the pump (3), allowing water to pass directly from the
injector to the lockshield valve (7) without passing through
the circuits.
5. Thermostatic head
7. Lockshield valve
4. Injector
valve
3. Pump
2. Return manifold
E: enquiries@giacomini.co.uk W: www.giacomini.co.uk 46
Mixing Manifold Underfloor Heating
System Commissioning Procedure
1. After all the final connections have been made, the 11. Once the pressure test has been completed, a 3 bar
underfloor heating circuits must be filled and pressure Water or 1 bar Air pressure should be maintained in the
tested before the screed or wooden floor is laid. circuit whilst the screed or flooring is being laid.
2. The system must now be fully bled of air. 12. It is important the screed is absolutely dry before heat
is applied. The screed must be left at least 20 days to
3. Make sure the isolation valves (4, 7) and at least one
achieve strength.
pump valve are shut off.
The initial flow temperature should be 20-25°C. This can be
Note: Actuators must not be fitted at this stage.
controlled using the thermostatic head (5) and should be
4. Connect a suitable length of hose securely to each drain maintained for at least 3 days. Subsequently the maximum
point (9). design temperature shall be set and maintained for a
further 4 days. For further guidance see BS EN 1264-4.
5. Place one end of a hose into a half filled bucket of water.
The other hose when connected to a water supply can be Note: Placing heat into a floor, which is not fully dry, can
controlled by the drain valve (9). lead to the screed cracking.
6. Shut off all flow and return valves, except for the circuit to In exceptionally cold weather precautions must be made
be flushed. against frost damage. It is not advisable to screed a floor if
the building cannot be protected against freezing.
7. Open the drain valve (9). This allows water to flow through
the circuit. Monitor the hose pipe in the bucket of water
until all the air bubbles cease and the water is flowing
freely. This will indicate all the air has been removed and
that circuit is full of water.
8. Differential valve
14. Immersion
sensor pocket
3. Pump
9. Drain
cock
5. Thermostatic head
2. Lower
return manifold
13. Regulating
valve
overall Dimensions
PORTS 2 3 4 5 6 7 8 9 10 11 12
H [mm] 450 450 450 450 450 450 450 450 450 450 450
L [mm] 515 565 615 665 740 790 840 890 940 990 1040
E: enquiries@giacomini.co.uk W: www.giacomini.co.uk 48
Mixing Manifold continued
5. Turn off the heat source on the boiler so that the system
runs cold.
15. When the system has been set, all regulating valves
should be opened.
Heat Commissioning
1. Do not carry out heat commissioning for at least 21 days 3. For a screed type floor system the thermostatic head
after the laying of the screed or in accordance with the (5) must be set on the lowest setting. The underfloor
manufacturer’s instructions. For anhydrite screeds at least heating can then be gradually brought up to full working
7 days must be left before commissioning. temperature over a period of days.
2. With all the system balanced and all the actuators open, 4. The system is to be run at approximately 20-25°C for at
the boiler can be fired. least 3 days and then subsequently increase by 5°C every
day thereafter until the design temperature is reached.
(For further information see BS EN 1264-4.4). The
maximum design temperature shall then be set (see table
below for thermostatic head (5) calibration) and maintained
for at least 4 days.
POSITION * 1 2 3 4 5 FULL
T (°C) 20 23 34 45 56 67 70
Final Balancing
1. Now that the system is operational, final checks need to be 6. One by one, turn the room thermostats down so the
carried out. corresponding actuators close. This is a good opportunity
to check that each room stat closes the correct circuit.
2. With the system at the correct flow temperature and all the
circuits open, a final check must be made on the pressure 7. As the actuators close, the pressure differential valve
differential valve. should open allowing water to pass through.
3. Make a note of the setting and then slowly open the valve Note: The finished floor temperatures can now be measured.
until water can be heard or felt passing through the bypass This can be done with the aid of an infrared type temperature
pipe. gauge. Designed floor temperatures indicated on the data
sheet should achieve the heat required. Do not allow the
4. Close the valve gradually until the flow of water is stopped.
finished floor temperatures in habitable areas (i.e. living room)
5. Each individual circuit must now be tested using the room to exceed 29°C, or 33°C in a bathroom.
thermostats.
(For further information see BS EN 1264-2).
E: enquiries@giacomini.co.uk W: www.giacomini.co.uk 50
Underfloor Heating F.A.Q.
1. H
ow do I connect my underfloor heating system to the 9. What type of screed do I use?
boiler?
In most cases normal sharp sand and cement mix can be used for a
The underfloor heating system should be connected to the boiler through standard 75mm screed. If the screed is to be less than 75mm other
the manifold. The manifold controls the heat requirement for the underfloor options should be considered. Advice should be sought from a screed
system by blending hot water from the boiler with cooler returned water manufacturer as additives and fibres can be added for additional
from the floor circuits. Most boilers have a high output temperature strength and flexibility. For very thin screeds a special mix is required,
(80-85°C) to cater for the other heat requirements of the dwelling (e.g. hot however there is a possibility that the floor temperature will not be even,
water cylinder, radiators and towel rails), which means that they should not with warm strips above the pipe centres.
be connected directly to the underfloor system.
10. Do I need to add a plasticizer to the screed mix?
2. Why do I need another pump on the manifold?
No, however it is important when screeding an underfloor heating
The pump circulates the water within the underfloor heating system and will system that the screed envelopes the pipe fully for it to work to its full
continue to operate after the injector valve has closed and hot water is no potential. Screed is normally installed very dry, therefore care must be
longer being mixed with the return water. It is also required where the pump taken to avoid air pockets around the UFH pipe. Adding a plasticizer to
on the boiler would not achieve the required flow rates in the system. the mix can help the screed flow better, thereby avoiding air pockets.
Screed as a wet mix should be avoided because this can cause shrinkage
3. Where should the manifold be positioned? and cracking when drying out. It is advisable to seek expert advice from
a screed manufacturer.
The manifold can be positioned virtually anywhere in the building, as long as
there is enough heat output to supply the demand. However it is preferable 11. What is the edge insulation strip for?
to site the manifold centrally in the building to ensure pipe runs to circuits
are kept to a minimum. Edge insulation strip serves two purposes. Firstly it forms an insulation
barrier around the floor slab and therefore prevents heat loss to
4. Will putting carpet over the underfloor heating have an surrounding walls. Secondly, it acts to fill the expansion gap around the
effect on it? slab, allowing the floor to expand and contract as it warms up and cools
down.
Yes, carpet will slow the heat transmission down because of its thermal
resistance. However this should not significantly affect the overall 12. What is the conduit used for?
performance of the system. It is important that carpeting is specified as a
requirement during the design of the system and that the correct underlay On screeded installations the conduit is installed over the underfloor
is fitted; this preferably should have a tog rating of less than I. heating pipes, where they cross into adjoining rooms (generally at
doorways). This is important because if a room is heated and an adjacent
5. Will underfloor heating work with laminate flooring? room is not, the floors expand in different directions and the pipe
passing through the doorway could be damaged. The conduit pipe can
Yes, however care should be taken when selecting laminate underlay. The also be used to sleeve underfloor heating pipe when it passes through an
manufacturer’s advice should be sought regarding suitability for use with area that is not to be heated, e.g. under kitchen units.
underfloor heating, as some laminate underlays are highly insulating.
13. What pipe spacing should I use?
6. Can underfloor heating be installed on a pressurised
sealed system? Giacomini underfloor heating systems are individually designed. Please
refer to your design data sheet or call our design office.
Yes, it can be installed on any sealed or open vented type system.
14. How is the system controlled?
7. How long does underfloor heating take to work?
Electrical actuator heads are fitted to each underfloor heating pipe
Normally from cold, a typical solid floor system will take 3-5 hours to reach circuit. These actuators are controlled either by a central thermostat or
temperature. However when the system is operational, it will only lose on individual room thermostats, linked together with a time clock through a
average 4°C in an 8 hour period, therefore it will only take a couple of hours wiring centre. A weather compensation circuit may also be incorporated
to reach operating temperature in normal operation. in the system to adjust for outside temperature variations.
8. What type and thickness of floor insulation should be 15. How much water will there be in an underfloor heating
used? system?
Any board type of insulation can be used. However the foiled high-density An 18mm pipe will contain .154 litres per lin metre of pipe. In addition
polyurethane foam is likely to suffer less site damage due to the high there will be an amount of water in the manifold and pump.
compressive strength. Pipe fixing staples also hold very firmly into this
type of insulation. The thickness of insulation required is calculated to 16. Can I put a manifold in the floor and feed up?
achieve a U-value of 0.25, which is the minimum permitted by the Building
Regulations. Insulation thickness will therefore be different for every Yes, however air locks may occur.
building and should be calculated when designing the building.
17. Can corrosion inhibitors be used in the system?
Yes, Giacomini recommend the use of corrosion inhibitors such as
Sentinel 100 or Fernox MB in all systems.
Pipe Connectors
Code: R179 X094 15mm pipe
E: enquiries@giacomini.co.uk W: www.giacomini.co.uk 52
Modular Manifolds
E: enquiries@giacomini.co.uk W: www.giacomini.co.uk 54
Manifold Components
E: enquiries@giacomini.co.uk W: www.giacomini.co.uk 56
Thermostats and Electrical Components
Pipe
Code: PE-X R996
Code: Pb R986
E: enquiries@giacomini.co.uk W: www.giacomini.co.uk 58
Accessories
Clip Gun
Code: R863 Y001
E: enquiries@giacomini.co.uk W: www.giacomini.co.uk 60
Giacomini UK Ltd.,
Unit 2 Goodrich Close,
Westerleigh Business Park,
Yate,
South Gloucestershire,
BS37 5YT.
Email: enquiries@giacomini.co.uk
Web: www.giacomini.co.uk
June 2010