Download as pdf or txt
Download as pdf or txt
You are on page 1of 4

AK 1703 ACP · AK 1703

Automation Component

DI-211x/BISI26 Peripheral Element


Binary Signal Input (8x8, 24-60VDC / 110-220VDC)

System element for acquisition and


processing according to IEC
60870-5-101/104, of
N up to 64 single-point information
units, or
N up to 32 double-point information
units, or
N up to 64 integrated totals via count
pulses, or
N a combination thereof
with following features:
DI-2110 24-60VDC N 64 inputs + 8 auxiliary inputs
(8 groups)
N galvanically insulated by
optocouplers
N each group has a common return
N signal voltage
DI-2110: 24-60VDC
DI-2111: 110/220VDC
N parameter settable polarity and
thresholds for each group
N filter-equipped inputs circuits
N for each group, one additional
input for power monitoring
N indication of function and states of
the inputs via LEDs
N binary information is acquired with
D-2111 110/220VDC a 1ms real-time resolution

(vorläufig / preliminary)
Application and Function

The peripheral elements DI-2110/BISI26 and DI-2111/BISI26 are used in automation units of the
systems AK 1703 ACP and AK 1703. It is deployed in the field of telecontrol and automation. The
peripheral elements are used for the acquisition of binary inputs.
Engineering is done using SAT TOOLBOX II, including OPM II.

The Acquisition Functions in Detail

N single-point information
─ acquisition and processing in 1ms grids
─ information blocking and revision
─ inverting
─ firmware filtering
─ bounce suppression
─ power monitoring

N double-point information
─ acquisition and processing in 1ms grids
─ information blocking and revision
─ inverting
─ firmware filtering
─ bounce suppression
─ monitoring intermediate and faulty positions
─ control location detection
─ reporting switching operations in progress
─ breaker tripping detection
─ automatic reclosure
─ power monitoring

N integrated totals via count pulses


─ acquisition supports count pulse frequencies of up to 20Hz
─ counter blocking and revision
─ power monitoring
─ inverting
─ counter value formation
─ set counter value
─ formation of counts (integrated totals)
− current absolute value
− latched absolute value
− latched relative value
− interval control
─ not power-fail safe

DI-211x/BISI26 MC0-015-1.00 -2- (vorläufig / preliminary) AK 1703 ACP · AK 1703


Technical Specifications

Processor and Memory


Processor 80C251, 16 MHz
Program memory PE-ROM 192 kByte
Main memory RAM 32 kByte
Parameter memory EEPROM 256 Bytes

Binary Inputs
64 binary inputs N 8 groups, 8 inputs and one auxiliary input (power monitoring) each
8 auxiliary inputs N Galvanical insulation
N Each group has a common return of settable polarity
N Power monitoring using the auxiliary input of each group (optional)
Filter time typ. 3.5 ms
DI-2110 DI-2111
Nominal voltages 24 .. 60 VDC 110 .. 220 VDC
Rated current 0.75 .. 3.25 mA (at 18 .. 78 V) 0.3 .. 0.8 mA (at 110 .. 220 V)
Input circuits 18 .. 78 VDC 83 .. 286 VDC
The circuits are operated by means of an external voltage
Operating points @ 25% Nominal voltage = "logic 0"
J 70% Nominal voltage = "logic 1"
Can be set using OPM II. The values above are default.

Power Supply
Operating voltage 4.75 .. 5.25 VDC, typ. 4.8 W
The voltage is picked off at the bus of mounting rack

Mechanics and Connectors


Ax 1703 peripheral bus Transmission rate 16Mbps
Peripheral connector 96 pin according to DIN 41612 type C
Dimensions Double-Euroformat 233.4 x 160mm, 4WU
Weight Approx. 300 g

AK 1703 ACP · AK 1703 (vorläufig / preliminary) -3- MC0-015-1.00 DI-211x/BISI26


Block Diagram

Further Documents

SAT 1703 Common Functions Peripheral Elements according to IEC 60870-5-101/104 DC0-011-1

© 2003 by VA TECH SAT GmbH & Co


All rights reserved. Subject to change without notice.
MC0-015-1.00

DI-211x/BISI26 MC0-015-1.00 -4- (vorläufig / preliminary) AK 1703 ACP · AK 1703

You might also like