Ritz Carlton-Residential Curtain Wall F19 - Calculation Note - Rev 01
Ritz Carlton-Residential Curtain Wall F19 - Calculation Note - Rev 01
Structural Calculation
Residential Curtain Walls at F19
Table of Contents
1. Reply on consultant comments ................................................................................................................................ 4
2. Purpose ..................................................................................................................................................................... 5
Material ............................................................................................................................................................. 5
Glazing ....................................................................................................................................................... 6
For Aluminium Framed Entrance & Store Fronts...................................................................................... 6
5. Section Properties ..................................................................................................................................................... 7
Drawings.................................................................................................................................................. 20
Deflection Verification ............................................................................................................................ 22
Stress Verification ................................................................................................................................... 28
Critical Glass Panel having composition 6T/AS=16/66.2AL ............................................................................ 34
Drawings.................................................................................................................................................. 34
Deflection verification ............................................................................................................................. 36
Stress Verification ................................................................................................................................... 41
8. Curtain Wall Verification ......................................................................................................................................... 46
Description ...................................................................................................................................................... 46
Drawing ........................................................................................................................................................... 47
Bending Stress “My” Verification Under “1.2 Dead Load + 1.0 Wind Load Stress” ................................ 51
Bending Stress “Mz” Verification Under “1.2 Dead Load + 1.0 Wind Load Stress” ................................ 52
Shear Stress Verification ................................................................................................................................. 53
Shear stress “Ty” Verification Under “1.2 Dead Load + 1.0 Wind Load Stress”...................................... 53
Shear stress “Tz” Verification Under “1.2 Dead Load + 1.0 Wind Load Stress” ...................................... 53
Verification of Combined Shear and Bending Stresses ................................................................................... 54
Conclusion ....................................................................................................................................................... 54
Reactions Under “1.2 Dead Load + 1.0 Wind Load Fixation” .......................................................................... 55
Bottom Fixation............................................................................................................................................... 56
Detail ....................................................................................................................................................... 98
Loads applied .......................................................................................................................................... 99
Stress Verification ................................................................................................................................. 100
Connection Bolts SS A2/70 M10 Verification ........................................................................................ 101
3
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
4
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
2. PURPOSE
The objective of this report is to present the structural verification of the curtain walls found at the F19 level in
the Residential Building.
3. DESIGN CRITERIA
According to the approved “Ritz Carlton Hotel & Residences - Design Parameters Rev 01”, Submittal “DT-PK4-014”.
The following is considered:
Material
For Plates
Where:
• E: Young modulus
• G: Shear modulus
• NI: Poisson ratio
• LX: Thermal expansion ratio
• ρ: Density
• Re: Yield Strength
4. LOAD COMBINATIONS
5
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
Deflection limit
Glazing
The maximum lateral deflection should be limited to L/50 in the mid span, where L is the minimum glass dimension
(width or height), or 25mm whichever is less.
For transoms in glazed façade systems, the deflection is limited to the minimum value between L/500 and
3mm, where L is the Length.
• For glazed aluminium curtain walls above a length of 4.1m: The maximum frontal deflection shall not exceed
“L/240 + 6.35mm”, when measured between the points of support or anchorage to the building’s structure.
6
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
5. SECTION PROPERTIES
The aluminum profiles used throughout the curtain walls are listed below:
• Mullions 135005:
• Transoms 135028:
• Steel Insert:
7
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
8
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
6. GENERAL DRAWINGS
Elevations
W10 W11
Mullion 135005
Transom 135028
9
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
W12 W17
v v v v
v v
W13
10
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
W14
W15
11
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
W16
W18 W20
12
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
W19
W21 W3
13
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
The Table below Shows all Curtain walls that are covered in this report
Curtain Walls
CW 10
CW 11
CW 12
CW 13
CW 14
CW 15
CW 16
CW 17
CW 18
CW 19
CW 20
CW 21
CW 3
14
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
7. GLASS VERIFICATION
Elevations
W10 W11
15
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
W12 W17
W13
16
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
W14
W15
17
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
W16
W18 W20
18
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
W19
W21 W3
19
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
Drawings
20
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
Horizontal Section
Vertical Section
21
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
Deflection Verification
22
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
23
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
24
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
25
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
26
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
27
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
Stress Verification
28
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
29
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
30
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
31
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
32
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
33
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
Drawings
Elevation
34
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
Horizontal Section
Vertical Section
35
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
Deflection verification
36
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
37
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
38
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
39
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
40
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
Stress Verification
41
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
42
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
43
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
44
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
45
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
Description
The mullions of the curtain wall have a length of L = 3100 mm, and the span widths are 550 mm & 580 mm &
2500 mm.
The system is bottom supported, indicating that the top support is for wind only (Ux & Uy blocked, Uz free),
whereas the bottom support is for dead and wind loads (Ux, Uy, & Uz blocked).
The transoms are attached from both sides to the corresponding mullions, considered as pin supported.
All the glass panels have the same composition, which is “6T/AS=18/8T”.
The mullions used are 135005.
46
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
Drawing
Elevation view
Mullion 135005
Transom 135028
Vertical Section
47
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
Load Definition
Dead Load
The weight of the mullions and transoms are considered automatically by the software.
48
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
Wind Load
49
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
Deflection Verification
Under Dead Load
50
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
Bending Stress “My” Verification Under “1.2 Dead Load + 1.0 Wind Load Stress”
51
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
Bending Stress “Mz” Verification Under “1.2 Dead Load + 1.0 Wind Load Stress”
Maximum Bending Stress =√(My2+Mz2) =√ 114.042+02=114.04 MPa< Maximum Allowable Bending Stress for
Aluminum Alloy 6060-T6= 0.9 x 160 = 144 MPa.
52
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
Shear stress “Ty” Verification Under “1.2 Dead Load + 1.0 Wind Load Stress”
Shear stress “Tz” Verification Under “1.2 Dead Load + 1.0 Wind Load Stress”
Maximum Shear Stress in the Aluminum vertical profile =√(Ty2+Tz2) =√ (02+10.222) =10.22 MPa< Maximum
Allowable Shear Stress for Aluminum Alloy 6060-T6= 0.9 x 95 =85 MPa.
53
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
Based on BS EN 1999-1-1 2007, if a shear force is less than half shear resistance, its effect on moment
resistance is neglected. Therefore, no need to check the combined shear and bending stresses.
In this case:
Actual shear stress = 10.22 MPa
Resisting shear stress=85MPa
Ratio = 10.22/85=0.12 < 0.5
Conclusion
54
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
Critical Loads
on Side Brackets
Critical Loads on
Middle Brackets
55
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
9. BRACKET VERIFICATION
Bottom Fixation
Details
Vertical Section
Horizontal Section
56
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
Loads Applied
57
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
Stress Verification under “1.2 Dead Load + 1.0 Wind Load Fixation”
Max stress =171.37 MPa < Allowable stress for steel S235 = 0.9x235=210 MPa
An additional moment M is created due to the 110mm eccentricity between the connection bolts and the base
plate of thickness 10mm (distance measured in the vertical direction).
58
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
59
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
60
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
61
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
62
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
63
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
64
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
65
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
Due to the existence of a double shear plane, then the resultant force on each shear plane is R:
10𝑚𝑚
𝐹𝑏,𝑅𝑑 = 2.5 × 240𝑀𝑃𝑎 × 2.4𝑚𝑚 × = 11.52 𝐾𝑁 > 𝑅 = 10.1𝐾𝑁 → 𝑆𝐴𝐹𝐸
1.25
➢ Where:
66
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
67
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
Details
Horizontal Section
Loads Applied
68
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
Stress Verification under “1.2 Dead Load + 1.0 Wind Load Fixation”
Max stress =120.56 MPa < Allowable stress for steel S235 = 0.9x235=210 MPa.
69
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
An additional moment M is created due to the 110mm eccentricity between the connection bolts and the base
plate of thickness 10mm (distance measured in the vertical direction).
70
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
71
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
72
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
73
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
74
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
75
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
76
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
77
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
Top Fixation
Middle Bracket
Details
Vertical Section
Horizontal section
78
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
Loads Applied
79
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
Stress Verification under “1.2 Dead Load + 1.0 Wind Load Fixation”
Max stress =95.88 MPa < Allowable stress for steel S235 = 0.9x235=210 MPa.
An additional moment M is created due to the 50mm eccentricity between the connection bolts and the base
plate of thickness 10mm (distance measured in the vertical direction).
80
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
81
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
82
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
83
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
84
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
85
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
86
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
87
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
88
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
Side Bracket
Details
Horizontal Section
Top and bottom brackets are having the same design, and the critical loads are on the bottom bracket.
An additional moment M is created due to the 50mm eccentricity between the connection bolts and the base
plate of thickness 10mm (distance measured in the vertical direction).
89
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
90
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
91
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
92
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
93
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
94
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
95
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
96
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
97
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
Connection 1
Detail
Vertical Section
98
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
Loads applied
Where:
99
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
Stress Verification
The maximum stress shown in the diagram on the right is 301.53 MPa. This value is neglected since it is due to
finite element analysis (FEM) at the location of the bolts and welding areas.
Max stress =160 MPa < Allowable stress for steel S235 = 0.9x235=210 MPa.
100
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
At the ultimate state, the forces acting on the critical bolt are:
Bearing Verification
10𝑚𝑚
𝐹𝑏,𝑅𝑑 = 2.5 × 240𝑀𝑃𝑎 × 2.4𝑚𝑚 × = 11.52 𝐾𝑁 > 𝑅 = 4.32 𝐾𝑁 → 𝑆𝐴𝐹𝐸
1.25
➢ Where:
101
Ritz Carlton-
Residential Curtain Walls at
Tel: +961 5 43 20 45
www.glasslineindustries.com
F19
07 February 2020
Shear Verification
102