INDOOR

INDOOR
UNITS
UNITS

WALL MOUNTED

CEILING MOUNTED CASSETTE

CEILING MOUNTED ROUND CASSETTE

CEILING CONCEALED DUCT

FRESH AIR INTAKE

CEILING SUSPENDED

CONSOLE

124 / 125
INDOOR UNITS _ WALL MOUNTED INDOOR UNITS _ WALL MOUNTED _ KEY FEATURES

S RT

OUNT D Anytime, anywhere access to the unit with Android & iOS-based smartphones.

INDOOR
UNITS
Search “LG ThinQ” on Google market or the App Store to download the app.
LG ThinQ

Integrated Home Appliances Control Access your air conditioner anytime and from anywhere
Control / Monitor all your LG appliances from one place. With a Wi-Fi equipped device and LG’s exclusive control app, LG ThinQ.

WALL MOUNTED
Easy Registration and Log-in
Follow the easy set-up steps that will activate LG ThinQ’s user-friendly features. Wi-Fi Connectivity
Each user can set and save temperature and fan speed preferences in
the LG ThinQ app. If a household has more than one indoor unit, separate
temperature settings can be set for each.

Multiple Devices

* Wi-Fi modem (Option) is necessary for this function

• 6 Different discharge angles can be programmed via the remote controller. • Retail • Hotel
• Easily detachable full surface cover helps to clean the air conditioner. • Restaurant • Multi-family Residence Simple operation for various functions
• Drain pipe can be easily hidden from sight. • Office ※ Can be controlled by multiple users, but not simultaneously.

Multi-Control
S
Smart Wi-Fi ○
Energy Efficiency Energy Display ○
Fast Cooling & Jet Cool ○ On/Off, Current Temp Mode, Set Temp Vane Control
Heating Auto Swing (Up & Down) ○

Ionizer Straight forward Management
~7.1kW Only
Health Pre Filter ○
Auto Cleaning ○
Sleep Mode ○
Timer (On / Off) ○
Comfort Timer (Weekly) ○
Two Thermistor Control ○
Group Control ○
Reservation Energy Smart Filter
※ ○: Applied, - : Not applied Monitoring Diagnosis Management

126 / 127
INDOOR UNITS _ WALL MOUNTED _ KEY FEATURES

R S IR ST OO IN TIN O ORT
I US Cleans Filter with Regular Airflow S S O
The comprehensive auto cleaning function prevents the formation of bacteria
The powerful Ionizer protects you from bad odors and Cool air extends to the entire room regardless of where You can set the daily temperature, fan speed, the operation
and mold on the heat exchanger.
ilizes Over Escherichia
3 Million coliIons)
and Staphylococcus in the surface with over the unit is situated. mode and automatic On / Off time for two weeks.
3 million ions to sterilize to make a safer, and cleaner
particles by infusing the air passing through the air conditioner with over 3 millions ions. How It Works
※ Specifications may vary for each model. It will keep running on that time until cancelled by the user.
environment. ※ This function is for wired remote controller only.
6-Step Vane,
6-Step Vane Control
Control up
upto
to70°
70° 5-Step Louver, Control upisto 55°

INDOOR
※ Wired remote controller need to be separately purchased.
※ Specifications may vary for each model.

UNITS
※ Depending on the experimental conditions.
H
H H
H
The
Thevertical vane,
vertical which
vane, moves
which up andup
moves down,
andhas 6 different
down, has 6settings including
different full-auto swing.
settings The louver, which sways left and right, has 5 different settings including full auto-swing.
H H
O- including full-auto swing.
H+ Sterilization and Deodorization (Utilizes Over 3 Million Ions) S S
O- Ionizer PLUS reduces E.coli and Staphylococcus in the surface with over Setting temperature : 19°C Setting temperature : 21°C
By dehumidifying, (Some models are by Operation time : 09:00 ~ 12:00 Operation time : 13:00 ~ 18:00
H+ 3 million ions.
O- dehumidifying and ionizing), the auto cleaning
function prevents potentially harmful substances

WALL MOUNTED
1
from forming on the surface of the heat exchanger.
How It Works Up & Down 2
rmful Substances OH Radical Production Chemical Reaction e n te Complete
t e Sterilization 70° 3
harmful particles Ion Cluster OH Surrounding
radicles inactivate OH
harmful 4
Radicalsubstances OH radicles
Chemical Reaction bond with H particles inThe
Sterilization thecomprehensive
air Hauto
2O molecules are produced
cleaning function prevents the formation of bacteria and mold on the heat exchanger, providing a more pleasant and comfortable environment. Heating 5
Generation
Ions are released
Harmful Substances Production
H- and O- bond to How It Works
OH radicles inactivate OH radicles bond H2O molecules are
6
into air
2
harmful particles harmful substances with H particles
H H
produced How It Works ※ Angle can be different from each model and working mode. 9:00 12:00 13:00 18:00
e n te t H eH
H H

Sterilization Performance Evaluations 6-Step Vane, Control up to 70°


The comprehensive auto cleaning function prevents the formation of bacteria and mold on the heat exchanger, providing a more pleasant and comfortable environment. Control
5-Step up toControl
Louver, 110° up to 55°
The vertical vane, which moves up and down, has 6 different settings including full-auto swing.
TheLouver
louver, can
whichbesways left and right, hasto5 extend
differentleft
settings
and including full auto-swing.
Sterilize Bacteria E.coli over 99.9% in 30 min. and staphylococcus over
The indoor environment remains odorless By preventing pollution of the heat 110 degrees.
adjusted manually right swing to
T T
99.6% in 60min. ※ Test Conditions : with the advanced deodorizing function. exchanger caused by various germs and The indoor temperature can be checked using the
Space : 52m3 Chamber (measuring
By eliminating the humidity and bacteriabacteria,
left in the performance and lifespan
The indoor environment of the with
remains odorless air the By preventing the polluting of the heat exchangerBenefit
Survival Rate Virus Bacteria (%)

100
2 H
H H with the specimen in the
Hcenter of test chamber)
air conditioner, the auto cleaning function removes advanced deodorizing function.
conditioner can be increased over 10 years. by various germs and bacteria, the cooling performance thermistors in the remote controller as well as from the
H H all substances that might be harmful to human body. and longevity ofthe air conditioner remains unchanged
80 Temperature & Humidity : Normal even after 10 years of usage.
4 Way Swing indoor unit. There may be a significant difference between
60 Pain Point Bacteria E.coli
Bacteria : E coil colon bacillus,
Staphylococcus Aureus Certificate
Benefit ceiling and floor air temperature. Two thermistors can
4 Way Swing disperses cool air quickly and effectively in multiple directions to each corner of a room.
99.9% Tested by Intertek Auto cleaning
40
2.1 odor strength decrease in 60 minutes Air conditioners with
Sanitization
vanes that only move up and
By eliminating
staphylococcus
down are Removes
the humidity and bacteria left in the
Auto Harmful Particles
Intertek, Verification Certifying Antibacterial
TheCleaning
indoor environment
provides remains odorless
clean withpreventing
air by the By preventing the polluting
bacteria, mold of the
andheat exchanger
odors that Left & Right optimize indoor air temperature for a more comfortable
20 unable to suitably cool all areas of aairroom.
conditioner, the auto cleaning function removes
Auto Cleaning deodorizing
advancedprovides cleanfunction.
air by eliminating bacteria, moldbyand
various
odorsgerms andotherwise
that can bacteria, the cooling performance
accumulate in an indoor unit.
30 min.
99.9%
An odor of strength 2 or less indicates that there is odor but no sense
all substances that might be harmful to human body.
Sanitization
Function of Plasmaster Ionizer+ / Ionizer
can otherwise accumulate in an indoor unit. and longevity ofthe air conditioner remains unchanged
even after 10 years of usage.
110° environment.
Heating /
of displeasure
0 (degree of odor permissible).
Benefit Cooling
d and bacteria growing on 15 30 45 60 Time (min)
※ Angle can be different from each model and working mode.
he heat exchanger is wet. Removes Harmful Particles
2.1
Odor
odor strength decrease
Autoin 60 minutes
Cleaning provides clean air by eliminating bacteria, mold and odors that can otherwise accumulate in an indoor unit. Easy and Simple Control Indoor Unit
1 2 3 4
Strength
An odor of measured as 2 European odor units (ouE/m³) or less Thermistor
Airflow direction can be changed
indicates that the level of odor falls within permissible limits.
by LG ThinQ Wi-Fi app.
Normal Odor Strength 1 2 3 4
reus Offensive
odor Benefit Bacteria Elimination Odor Elimination Mold Elimination
substance
Offensive
sensitivity odor
4 Way Swing
substance
Mountain
smell
Indoor life
smell
Bathroom
smell
Food waste
smell
How It Works
sensitivity Mountain Indoor life Bathroom Food waste 4 Way Swing disperses cool air quickly and effectively in multiple directions to each corner of a room.
smell smell smell smell Up / Down Swing
and down are Odor strength Light Moderate Strong Very Strong e n te t e Remote Controller
level Thermistor
Odor strength level Light Moderate Strong Very Strong The comprehensive auto cleaning function prevents the formation of bacteria and mold on the heat exchanger, providing a more pleasant and comfortable environment.
Bacteria
Bacteria Elimination Odor Odor
Elimination MoldMold
Elimination
1.5 3.6 Prevention Elimination Elimination
LG air conditioners provide optimized high-speed airflow,
Odor strength reduce 3.6 1.5 / The Odor floating in the room as well as curtain and clothes. which can cool rooms faster while delivering cool air evenly
60
me(min)
Odor※strength reduce 3.6
Test conditions : 1.5 / The Odor floating in the room as well as curtain and clothes. in every direction. Group control by new remote controller (PREMTB100 /
Space: 8m3 Chamber
Temperature & Humidify : Normal ※ Specifications may vary for each model.
Tested by Intertek ※ Depending on the experimental conditions. PREMTBB10) has more functions than previous model.
I One Click “Jet Mode”
By eliminating the humidity and bacteria left in the The indoor environment remains odorless with the By preventing
Reduces thetemperature
the polluting of theof
heat exchanger air to 18°C for 30 minutes with
outflowing
Installation Support Clip
air conditioner, the auto cleaning function removes advanced deodorizing function. by various germs and bacteria, the cooling performance
The unit has a self-cleaning function that dries the heat all substances that might be harmful to human body. justlongevity
and one click.
ofthe air conditioner remains unchanged
A support clip creates adequate space between the wall and the unit for even after 10 years of usage.
exchanger before sterilizing the interior. easier installation.
Benefit
Cooling / Heating Dehumidification
Removes Harmful Particles Fan only operating Setting temp.
Pain Point 25°
Auto Cleaning provides clean air by eliminating bacteria, mold and odors that can otherwise accumulate in an indoor unit.
The main cause of odor within air conditioners is mold and bacteria
growing on the heat exchanger. These germs can spread when the heat Standard Operation
exchanger is wet.
ng on
wet. More Powerful Performance In Case of Group Control
By reducing the second vortex, which
decreases airflow within the air outlet,
and enlarging the fan size, the amount of
167mm
air flow is increased to 13 CMM.

Low Magnitude of High


Velocity
Bacteria Elimination Odor Elimination Mold Elimination

128 / 129
INDOOR UNITS _ WALL MOUNTED _ SPECIFICATION

ST ND RD ST ND RD
ARNU05GSJN4 / ARNU07GSJN4 ARNU18GSK*4 / ARNU24GSK*4
ARNU09GSJN4 / ARNU12GSJN4 ARNU30GSVA4 / ARNU36GSVA4
ARNU15GSJN4

INDOOR
UNITS
U RNU SN RNU SN RNU SN RNU SN RNU SN U RNU S RNU S RNU S RNU S

WALL MOUNTED
kW 1.6 2.2 2.8 3.6 4.5 kW 5.6 7.1 8.8 10.4
kW 1.8 2.5 3.2 4.0 5.0 kW 6.3 7.5 9.4 10.8
I I
Nominal W 11 / 10 / 9 12 / 11 / 9 13 / 12 / 9 15 / 13 / 11 23 / 18 / 11 Nominal W 32 / 26 / 16 39 / 26 / 16 54 / 43 / 31 85 / 51 / 36
White White White White White White White White White
R RAL 9016 RAL 9016 RAL 9016 RAL 9016 RAL 9016 R RAL 9016 RAL 9016 RAL 9016 RAL 9016
D Body mm 818 x 316 x 189 818 x 316 x 189 818 x 316 x 189 818 x 316 x 189 818 x 316 x 189 D Body mm 975 x 354 x 209 975 x 354 x 209 1,190 x 346 x 265 1,190 x 346 x 265
D Shipping mm 892 x 381 x 249 892 x 381 x 249 892 x 381 x 249 892 x 381 x 249 892 x 381 x 249 D Shipping mm 1,063 x 420 x 274 1,063 x 420 x 274 1,265 x 432 x 335 1,265 x 432 x 335
Type Cross Flow Fan Cross Flow Fan Cross Flow Fan Cross Flow Fan Cross Flow Fan Type Cross Flow Fan Cross Flow Fan Cross Flow Fan Cross Flow Fan
Motor Output x Number W x No. 30 x 1 30 x 1 30 x 1 30 x 1 30 x 1 Motor Output x Number W x No. 58 x 1 58 x 1 113 x 1 113 x 1
Air Flow Rate (H / M / L) m³/min 6.8 / 6.5 / 5.9 7.2 / 6.8 / 5.9 7.8 / 7.2 / 5.9 8.5 / 7.8 / 6.8 10.5 / 9.5 / 6.8 Air Flow Rate (H / M / L) m³/min 14.0 / 12.0 / 10.5 15.2 / 12.7 / 10.5 23.0 / 20.0 / 17.0 26.0 / 23.0 / 19.0
Motor Type BLDC BLDC BLDC BLDC BLDC Motor Type BLDC BLDC BLDC BLDC
Pre Filter Pre Filter Pre Filter Pre Filter Pre Filter Pre Filter Pre Filter Pre Filter Pre Filter
Liquid Side mm (inch) Ø6.35 (1/4) Ø6.35 (1/4) Ø6.35 (1/4) Ø6.35 (1/4) Ø6.35 (1/4) Liquid Side mm (inch) Ø6.35 (1/4) Ø9.52 (3/8) Ø9.52 (3/8) Ø9.52 (3/8)
Gas Side mm (inch) Ø12.7 (1/2) Ø12.7 (1/2) Ø12.7 (1/2) Ø12.7 (1/2) Ø12.7 (1/2) Gas Side mm (inch) Ø12.7 (1/2) Ø15.88 (5/8) Ø15.88 (5/8) Ø15.88 (5/8)
Drain Pipe (Internal Dia.) mm (inch) Ø16 (5/8) Ø16 (5/8) Ø16 (5/8) Ø16 (5/8) Ø16 (5/8) Drain Pipe (Internal Dia.) mm (inch) Ø16 (5/8) Ø16 (5/8) Ø16 (5/8) Ø16 (5/8)
Body kg 8.4 8.4 8.4 8.4 8.4 Body kg 12.2 12.2 16.6 16.6
S dB(A) 30 / 29 / 28 32 / 30 / 28 34 / 32 / 28 37 / 34 / 30 42 / 39 / 32 S dB(A) 43 / 39 / 34 46 / 41 / 34 49 / 44 / 42 52 / 47 / 43
S dB(A) 54 / 53 / 52 54 / 53 / 52 55 / 54 / 52 55 / 54 / 53 58 / 56 / 54 S dB(A) 63 / 57 / 54 65 / 60 / 54
S Ø, V, Hz 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 S Ø, V, Hz 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50
mm2 x No. 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C mm2 x No. 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C
Note : 1. Performance tested under EN14511 * : N or C can be applied which has little bit different shape of panel.
2. Capacities are based on the following conditions. Note : 1. Performance tested under EN14511
- Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero 2. Capacities are based on the following conditions.
- Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero
3. Due to our policy of innovation, some specifications may be changed without notification. - Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero
3. Due to our policy of innovation, some specifications may be changed without notification.

Accessories Accessories
RNU SN RNU SN RNU SN RNU SN RNU SN RNU S RNU S RNU S RNU S
D - D - -
- - -
R D PRLDNVS0 R D PRLDNVS0 PRLDNVS0
PRGK024A0 PRGK024A0 -
I PRIP0 I PRIP0 PRIP0
R - R - -
○ ○ ○
I ○ I ○ -
O S - O S - -
- - -
IR R - IR R - -
- - -
PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible), PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible),
D D
PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus) PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus)
I ○ I ○ ○
○ ○ PWFMDD200

※ ○ : Applied, - : Not applied ※ ○ : Applied, - : Not applied


Option : Refer to model name in table Option : Refer to model name in table

130 / 131
INDOOR UNITS _ CEILING MOUNTED CASSETTE INDOOR UNITS _ CEILING MOUNTED CASSETTE _ KEY FEATURES

N D SI N
N D D
I IN OUNT D New Excellent Technology (NET) certifies new 4 Way dual vane
design that promotes comfortable and convenient airflow.
Bigger inlet and outlet make faster cooling / heating airflow.

SS TT

INDOOR
UNITS
4 Way
Dual Vane Increased Inlet Area

Normal 4 Way

CEILING MOUNTED CASSETTE


x2

Dual Vane 4 Way

*New types wind


Normal Dual Vane DT
Full 3D Turbo fan decreases air resistance,
so it makes High Efficient and reduces noise level.
Indirect
Wind Turbo fan

Direct
Wind

Full 3D Turbo fan


*6 Airflows mode Power consumption 13W ↓, Noise 3dB(A) ↓

Fast and Quick Fresh and Natural Auto Vane Control


Power Mode Up / Down Swing Smart Mode

Improved outlet flow rate

5m

• New Dual Vane 4 Way cassette allows comfortable air flow. • Retail Indirect cooling & Heating Suitable for High Ceiling Provide high concentration
Indirect Wind Direct Wind Refresh Mode
Ø5 High Density Heat Exchanger increases cooling
• Full 3D Turbo fan decreases air resistance, providing high air flow • School / heating efficiency by 10%.
and low sound levels. • Office
• 5-Step air cleaning process removes invisible, ultra fine dust, odor Normal Ø7 HEX
• Hotel
and germs to ensure a clean and healthy living • Dormitory Color enhancement allows cassette to blend in to most
• Restaurant interior ceiling spaces.

Normal Ivory Dual Vane White


Smart Wi-Fi ○ ○ ○ T 12 Column
Energy Efficiency Human Detect Sensor ○ - - 12 Column
I 21
Drain Pump ○ ○ ○
Sleep Mode ○ ○ ○
High Efficient Ø5 HEX
Timer (On / Off) ○ ○ ○
Comfort
Timer (Weekly) ○ ○ ○
Two Thermistor Control ○ ○ ○
Group Control ○ ○ ○
Air purification ○ - ○

T 18 Column
18 Column I 22

132 / 133
INDOOR UNITS _ CEILING MOUNTED CASSETTE _ KEY FEATURES

S RT S RT INST TION
T S R
With a special sensor that sense both ceiling and floor Air cleaning function provides fresh, filtered air. Wi-Fi functionality for anytime, anywhere indoor unit With a height of 132mm, the LG 1 Way cassette is the ideal
temperature, Dual Vane 4 Way cassette provides comfort air. control and air quality level display. solution for limited-space installations.

IDU Temperature ① Smart indicator (Air quality) ② Remote controller

INDOOR
Real-time indoor air quality level Air quality level displayed

UNITS
displayed on indoor unit on remote controller
132mm

Calculate Room Good Unhealthy


Temperature

CEILING MOUNTED CASSETTE


Moderate Poor

Size Comparison (Unit : mm)


③ Mobile
Floor Temperature
Anytime, anywhere access to check
& control air status via mobile
1 Way
※ Available only for products with floor temperature sensor.. 215 230 132
Cassette

Human detection provides users with direct or indirect air I


flow preferences. 1 Way cassette doesn’t require the inspection access hole,
so that simple installation is possible.
Indirect comfort Direct cooling
D
Grille automatically detaches and re-attaches with 4 touchpoints 1 Way cassette Duct
Provides air flow that blows away
from user for comfort.
Provides air flow that blows directly
onto user for cooling. S for enhanced stability & convenient filter management.
Duct

It captures 99% of microfine dust (PM1.0) Normal 4 Way Smart Dual Vane IDU
Besides, Easy-to-maintain system with washable filters
Inspection hole

No touch Direct airflow


Indirect airflow 4m
2°C
Comfort Cooler

Phase 5 I Ion Emission


I S
① Horizontal Sensor ② Check Close grille ① Detect Obstacle ③ Set Stop Point
② Horizontal Sensor ④ Check Close grille
D O Air
purification Deodorization filter Phase 4 I Deodorizes
kit
T
Indoor unit senses human presence to switch on or off for Anytime anywhere access to indoor units with LG ThinQ

300 or more
Phase 3 I Captures microfine dust
maximum power savings of 54%. PM1.0 Filter mobile app. Ceiling
Ceiling Board
Dust electrification Ceiling Board
Operation On Turning Off Turning On

300 or less
On Off On
Phase 2 I Dust Electrification 500 or

or more
500 or

1,000
more more

4,000 or less
Above 2,500
Pre-filter
PM1.0
Sensor
Phase 1 I Captures fine dust
Unit : mm

Air
In office Absence In office purification
Floor
panel
Learning time for
↑2°C, running
Power saving Max. 54%
25min Power saving
Manageable set time Power saving
(If set time 30min) ① Monitoring Air status ② Mobile Remote Control
30min/60min/90min Smart Easy to check indoor air status Remote control by using mobile phone
indicator • Ultra Fine / Extra Fine / Fine Dust • Control Mode / Temperature
Absence → Turn off after 30min (Set turn off)
• Day / Week /Month / Yearly / Air flow etc.
Learning time for Absence Cycle Management
5min ③ Display Power Consumption
D
※ Smart Dual Vane Indoor Unit ‘20 Line up. Check power consumption of A/C
※ Data Based on actual test of LG, single product 2 hours measurement result. Easy removable pre-filter 6 months / Washable 6 months / Dry in sunlight • Check energy display
(Cooling 26 °C, strong wind) • Set target energy consumption level

134 / 135
INDOOR UNITS _ CEILING MOUNTED CASSETTE _ SPECIFICATION

DU N SS TT (840 X 840) DU N SS TT (840 X 840)

ARNU24GTBB4 / ARNU28GTBB4 ARNU36GTAB4 / ARNU42GTAB4


ARNU30GTBB4 ARNU48GTAB4

INDOOR
UNITS
U RNU T RNU T RNU T U RNU T RNU T RNU T

CEILING MOUNTED CASSETTE


kW 7.1 8.2 9.0 kW 10.6 12.3 14.1
kW 8.0 9.2 10.0 kW 11.9 13.8 15.9
I I
Nominal W 32 / 27 / 20 37 / 30 / 22 48 / 36 / 25 Nominal W 69 / 49 / 37 97 / 69 / 49 110 / 76 / 61

D Body mm 840 x 204 x 840 840 x 204 x 840 840 x 204 x 840 D Body mm 840 x 288 x 840 840 x 288 x 840 840 x 288 x 840
D Shipping mm 922 x 276 x 917 922 x 276 x 917 922 x 276 x 917 D Shipping mm 922 x 360 x 917 922 x 360 x 917 922 x 360 x 917
Type Full 3D Turbo Fan Full 3D Turbo Fan Full 3D Turbo Fan Type Full 3D Turbo Fan Full 3D Turbo Fan Full 3D Turbo Fan
Motor Output x Number W x No. 51 x 1 51 x 1 51 x 1 Motor Output x Number W x No. 135 x 1 135 x 1 135 x 1
Air Flow Rate (H / M / L) m3/min 18 / 17 / 15 19 / 17 / 15 21 / 19 / 16 Air Flow Rate (H / M / L) m3/min 29 / 26 / 22 33 / 29 / 26 34 / 30 / 28
Motor Type BLDC BLDC BLDC Motor Type BLDC BLDC BLDC
Pre Filter Pre Filter Pre Filter Pre Filter Pre Filter Pre Filter
Liquid Side mm (inch) Ø9.52 (3/8) Ø9.52 (3/8) Ø9.52 (3/8) Liquid Side mm (inch) Ø9.52 (3/8) Ø9.52 (3/8) Ø9.52 (3/8)
Gas Side mm (inch) Ø15.88 (5/8) Ø15.88 (5/8) Ø15.88 (5/8) Gas Side mm (inch) Ø15.88 (5/8) Ø15.88 (5/8) Ø15.88 (5/8)
Drain Pipe (Internal Dia.) mm (inch) Ø25 (1) Ø25 (1) Ø25 (1) Drain Pipe (Internal Dia.) mm (inch) Ø25 (1) Ø25 (1) Ø25 (1)
Body kg 21 21 21 Body kg 26 26 26
S dB(A) 36 / 34 / 31 39 / 35 / 34 40 / 36 / 33 S dB(A) 42 / 39 / 36 44 / 41 / 39 46 / 43 / 41
S dB(A) 46 / 44 / 42 50 / 46 / 43 53 / 50 / 45 S dB(A) 54 / 51 / 47 56 / 53 / 49 58 / 54 / 53
S Ø, V, Hz 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 S Ø, V, Hz 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50
mm2 x No. 1.25 x 2C 1.25 x 2C 1.25 x 2C mm2 x No. 1.25 x 2C 1.25 x 2C 1.25 x 2C
PT-AAGW0 PT-AAGW0 PT-AAGW0 PT-AAGW0 PT-AAGW0 PT-AAGW0
Model Name PT-AFGW0 PT-AFGW0 PT-AFGW0 Model Name PT-AFGW0 PT-AFGW0 PT-AFGW0
PT-AEGW0 PT-AEGW0 PT-AEGW0 PT-AEGW0 PT-AEGW0 PT-AEGW0
D Exterior Color White White White D Exterior Color White White White
RAL Code RAL 9003 RAL 9003 RAL 9003 RAL Code RAL 9003 RAL 9003 RAL 9003
Net Dimensions Net Dimensions
mm 950 x 35 x 950 950 x 35 x 950 950 x 35 x 950 mm 950 x 35 x 950 950 x 35 x 950 950 x 35 x 950
(W x H x D) (W x H x D)
Net Weight kg 7.1 / 7.5 / 8.5 7.1 / 7.5 / 8.5 7.1 / 7.5 / 8.5 Net Weight kg 7.1 / 7.5 / 8.5 7.1 / 7.5 / 8.5 7.1 / 7.5 / 8.5

Note : 1. Performance tested under EN14511 Note : 1. Performance tested under EN14511
2. Capacities are based on the following conditions. 2. Capacities are based on the following conditions.
- Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero
- Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero
3. Due to our policy of innovation, some specifications may be changed without notification. 3. Due to our policy of innovation, some specifications may be changed without notification.

Accessories Accessories
RNU T RNU T RNU T RNU T RNU T RNU T
D ○ D ○
PTDCA PTDCA
R D PRLDNVS0 R D PRLDNVS0
- -
I PRIP0 I PRIP0
R - R -
○ ○
I - I -
O S - O S -
- -
IR R - IR R -
- -
PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible), PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible),
D D
PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus) PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus)
I ○ I ○
PWFMDD200 PWFMDD200
PTVSAA0 PTVSAA0
T S PT-AFGW0 :○ T S PT-AFGW0 : ○
PT-AFGW0 : PTAHMP0 PT-AFGW0 : PTAHMP0
PT-AEGW0 :○ PT-AEGW0 : ○

136 / 137
INDOOR UNITS _ CEILING MOUNTED CASSETTE _ SPECIFICATION

DU N SS TT (840 X 840) HIGH SENSIBLE DU N SS TT (840 X 840) HIGH SENSIBLE

ARNU07GTAA4 / ARNU09GTAA4 ARNU24GTAA4 / ARNU28GTAA4


ARNU12GTAA4 / ARNU15GTAA4 ARNU36GTAA4 / ARNU42GTAA4
ARNU18GTAA4 ARNU48GTAA4

INDOOR
UNITS
U RNU T RNU T RNU T RNU T RNU T U RNU T RNU T RNU T RNU T RNU T

CEILING MOUNTED CASSETTE


kW 2.2 2.8 3.6 4.5 5.6 kW 7.1 8.2 10.6 12.3 14.1
kW 2.5 3.2 4.0 5.0 6.3 kW 8.0 9.2 11.9 13.8 15.9
I I
Nominal W 23 / 16 / 11 25 / 18 / 11 26 / 19 / 13 29 / 20 / 15 31 / 23 / 16 Nominal W 35 / 29 / 20 40 / 31 / 25 65 / 43 / 31 86 / 65 / 43 100 / 67 / 53

D Body mm 840 x 288 x 840 840 x 288 x 840 840 x 288 x 840 840 x 288 x 840 840 x 288 x 840 D Body mm 840 x 288 x 840 840 x 288 x 840 840 x 288 x 840 840 x 288 x 840 840 x 288 x 840
D Shipping mm 922 x 360 x 917 922 x 360 x 917 922 x 360 x 917 922 x 360 x 917 922 x 360 x 917 D Shipping mm 922 x 360 x 917 922 x 360 x 917 922 x 360 x 917 922 x 360 x 917 922 x 360 x 917
Type Full 3D Turbo Fan Full 3D Turbo Fan Full 3D Turbo Fan Full 3D Turbo Fan Full 3D Turbo Fan Type Full 3D Turbo Fan Full 3D Turbo Fan Full 3D Turbo Fan Full 3D Turbo Fan Full 3D Turbo Fan
Motor Output x Number W x No. 166 x 1 166 x 1 166 x 1 166 x 1 166 x 1 Motor Output x Number W x No. 166 x 1 166 x 1 166 x 1 166 x 1 166 x 1
Running Current A 0.23 0.25 0.25 0.27 0.28 Running Current A 0.38 0.46 0.60 0.80 0.88
Air Flow Rate (H / M / L) m3/min 19 / 16 / 13 19 / 16 / 13 20 / 17 / 15 20 / 17 / 15 21 / 19 / 16 Air Flow Rate (H / M / L) m3/min 23 / 21 / 19 24 / 22 / 20 28 / 24 / 21 31 / 28 / 24 33 / 28 / 26
Motor Type BLDC BLDC BLDC BLDC BLDC Motor Type BLDC BLDC BLDC BLDC BLDC
Pre Filter Pre Filter Pre Filter Pre Filter Pre Filter Pre Filter Pre Filter Pre Filter Pre Filter Pre Filter
Liquid Side mm (inch) Ø9.52 (3/8) Ø9.52 (3/8) Ø9.52 (3/8) Ø9.52 (3/8) Ø9.52 (3/8) Liquid Side mm (inch) Ø9.52 (3/8) Ø9.52 (3/8) Ø9.52 (3/8) Ø9.52 (3/8) Ø9.52 (3/8)
Gas Side mm (inch) Ø15.88 (5/8) Ø15.88 (5/8) Ø15.88 (5/8) Ø15.88 (5/8) Ø15.88 (5/8) Gas Side mm (inch) Ø15.88 (5/8) Ø15.88 (5/8) Ø15.88 (5/8) Ø15.88 (5/8) Ø15.88 (5/8)
Drain Pipe (Internal Dia.) mm (inch) Ø25 (1) Ø25 (1) Ø25 (1) Ø25 (1) Ø25 (1) Drain Pipe (Internal Dia.) mm (inch) Ø25 (1) Ø25 (1) Ø25 (1) Ø25 (1) Ø25 (1)
Body kg 26 26 26 26 26 Body kg 26 26 26 26 26
S dB(A) 32 / 30 / 26 33 / 30 / 26 34 / 31 / 27 34 / 32 / 29 35 / 32 / 30 S dB(A) 39 / 36 / 33 40 / 37 / 34 42 / 39 / 35 46 / 42 / 39 47 / 43 / 41
S dB(A) 41 / 38 / 34 42 / 39 / 34 42 / 40 / 36 43 / 40 / 37 44 / 41 / 38 S dB(A) 47 / 45 / 42 48 / 46 / 42 51 / 48 / 44 54 / 51 / 48 56 / 52 / 50
S Ø, V, Hz 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 S Ø, V, Hz 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50
mm2 x No. 1.25 x 2C 1.25 x 2C 1.25 x 2C 1.25 x 2C 1.25 x 2C mm2 x No. 1.25 x 2C 1.25 x 2C 1.25 x 2C 1.25 x 2C 1.25 x 2C
Exterior Color White White White White White PT-AAGW0 PT-AAGW0 PT-AAGW0 PT-AAGW0 PT-AAGW0
Model Name PT-AFGW0 PT-AFGW0 PT-AFGW0 PT-AFGW0 PT-AFGW0
D RAL Code RAL 9003 RAL 9003 RAL 9003 RAL 9003 RAL 9003 PT-AEGW0 PT-AEGW0 PT-AEGW0 PT-AEGW0 PT-AEGW0
Net Dimensions D Exterior Color White White White White White
mm 950 x 35 x 950 950 x 35 x 950 950 x 35 x 950 950 x 35 x 950 950 x 35 x 950
(W x H x D)
Net Weight kg 7.1 / 7.5 / 8.5 7.1 / 7.5 / 8.5 7.1 / 7.5 / 8.5 7.1 / 7.5 / 8.5 7.1 / 7.5 / 8.5 RAL Code RAL 9003 RAL 9003 RAL 9003 RAL 9003 RAL 9003
Net Dimensions
mm 950 x 35 x 950 950 x 35 x 950 950 x 35 x 950 950 x 35 x 950 950 x 35 x 950
Note : 1. Performance tested under EN14511 (W x H x D)
2. Capacities are based on the following conditions. Net Weight kg 7.1 / 7.5 / 8.5 7.1 / 7.5 / 8.5 7.1 / 7.5 / 8.5 7.1 / 7.5 / 8.5 7.1 / 7.5 / 8.5
- Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero
- Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero Note : 1. Performance tested under EN14511
3. Due to our policy of innovation, some specifications may be changed without notification. 2. Capacities are based on the following conditions.
- Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero
- Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero
3. Due to our policy of innovation, some specifications may be changed without notification.

Accessories Accessories
RNU T RNU T RNU T RNU T RNU T RNU T RNU T RNU T RNU T RNU T
D ○ D ○
PTDCA PTDCA
R D PRLDNVS0 R D PRLDNVS0
- -
I PRIP0 I PRIP0
R - R -
○ ○
I - I -
O S - O S -
- -
IR R - IR R -
- -
PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible), PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible),
D D
PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus) PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus)
I ○ I ○
PWFMDD200 PWFMDD200
PTVSAA0 PTVSAA0
T S PT-AFGW0 : ○ T S PT-AFGW0 : ○
PT-AFGW0 : PTAHMP0 PT-AFGW0 : PTAHMP0
PT-AEGW0 : ○ PT-AEGW0 : ○

138 / 139
INDOOR UNITS _ CEILING MOUNTED CASSETTE _ SPECIFICATION

SS TT (570 X 570) SS TT (570 X 570)

ARNU05GTRB4 / ARNU07GTRB4 ARNU15GTQB4 / ARNU18GTQB4


ARNU09GTRB4 / ARNU12GTRB4 ARNU21GTQB4

INDOOR
UNITS
U RNU TR RNU TR RNU TR RNU TR U RNU T RNU T RNU T

CEILING MOUNTED CASSETTE


kW 1.6 2.2 2.8 3.6 kW 4.5 5.6 6.0
kW 1.8 2.5 3.2 4.0 kW 5.0 6.3 6.8
I I
Nominal W 13 / 12 / 11 13 / 12 / 11 14 / 13 / 12 17 / 15 / 13 Nominal W 24 / 21 / 18 25 / 22 / 19 28 / 23 / 20

D Body mm 570 x 214 x 570 570 x 214 x 570 570 x 214 x 570 570 x 214 x 570 D Body mm 570 x 256 x 570 570 x 256 x 570 570 x 256 x 570
D Shipping mm 667 x 285 x 646 667 x 285 x 646 667 x 285 x 646 667 x 285 x 646 D Shipping mm 667 x 327 x 646 667 x 327 x 646 667 x 327 x 646
Type Turbo Fan Turbo Fan Turbo Fan Turbo Fan Type Turbo Fan Turbo Fan Turbo Fan
Motor Output x Number W x No. 43 x 1 43 x 1 43 x 1 43 x 1 Motor Output x Number W x No. 43 x 1 43 x 1 43 x 1
Air Flow Rate (H / M / L) m³/min 7.5 / 7.0 / 6.6 7.5 / 7.0 / 6.6 8.0 / 7.5 / 7.1 8.7 / 8.0 / 7.0 Air Flow Rate (H / M / L) m³/min 11.0 / 10.0 / 9.3 11.2 / 11.0 / 10.0 12.0 / 11.1 / 9.4
Motor Type BLDC BLDC BLDC BLDC Motor Type BLDC BLDC BLDC
Pre Filter Pre Filter Pre Filter Pre Filter Pre Filter Pre Filter Pre Filter
Liquid Side mm (inch) Ø6.35 (1/4) Ø6.35 (1/4) Ø6.35 (1/4) Ø6.35 (1/4) Liquid Side mm (inch) Ø6.35 (1/4) Ø6.35 (1/4) Ø9.52 (3/8)
Gas Side mm (inch) Ø12.7 (1/2) Ø12.7 (1/2) Ø12.7 (1/2) Ø12.7 (1/2) Gas Side mm (inch) Ø12.7 (1/2) Ø12.7 (1/2) Ø15.88 (5/8)
Drain Pipe (Internal Dia.) mm (inch) Ø25 (1) Ø25 (1) Ø25 (1) Ø25 (1) Drain Pipe (Internal Dia.) mm (inch) Ø25 (1) Ø25 (1) Ø25 (1)
Body kg 12.6 12.6 13.7 13.7 Body kg 15.0 15.0 15.0
S dB(A) 29 / 27 / 26 29 / 27 / 26 30 / 29 / 27 32 / 30 / 27 S dB(A) 36 / 34 / 32 37 / 35 / 34 40 / 38 / 34
S dB(A) 45 / 43 / 42 45 / 43 / 42 46 / 43 / 42 48 / 46 / 43 S dB(A) 50 / 48 / 46 51 / 50 / 46 53 / 51 / 46
S Ø, V, Hz 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 S Ø, V, Hz 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50
mm2 x No. 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C mm2 x No. 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C
Model Name PT-QCHW0 PT-QCHW0 PT-QCHW0 PT-QCHW0 Model Name PT-QCHW0 PT-QCHW0 PT-QCHW0
Exterior Color Morning Fog Morning Fog Morning Fog Morning Fog Exterior Color Morning Fog Morning Fog Morning Fog
D D
RAL Code RAL 9001 RAL 9001 RAL 9001 RAL 9001 RAL Code RAL 9001 RAL 9001 RAL 9001
Net Dimensions 700 x 22 x700 700 x 22 x700 700 x 22 x700 700 x 22 x700 Net Dimensions 700 x 22 x700 700 x 22 x700 700 x 22 x700
mm mm
(W x H x D) 620 x 20 x 620 620 x 20 x 620 620 x 20 x 620 620 x 20 x 620 (W x H x D) 620 x 20 x 620 620 x 20 x 620 620 x 20 x 620
Net Weight kg 3.0 / 3.0 3.0 / 3.0 3.0 / 3.0 3.0 / 3.0 Net Weight kg 3.0 / 3.0 3.0 / 3.0 3.0 / 3.0

Note : 1. Performance tested under EN14511 Note : 1. Performance tested under EN14511
2. Capacities are based on the following conditions. 2. Capacities are based on the following conditions.
- Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero
- Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero
3. Due to our policy of innovation, some specifications may be changed without notification. 3. Due to our policy of innovation, some specifications may be changed without notification.

Accessories Accessories
RNU TR RNU TR RNU TR RNU TR RNU T RNU T RNU T
D ○ D ○
PTDCQ PTDCQ
R D PRLDNVS0 R D PRLDNVS0
PRGK024A0 (~4.5kW) PRGK024A0 (~4.5kW)
I PRIP0 I PRIP0
R - R -
○ ○
I - I -
O S - O S -
PTVK430 PTVK430
IR R - IR R -
- -
PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible), PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible),
D D
PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus) PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus)
I ○ I ○
PWFMDD200 PWFMDD200
※ ○ : Applied, - : Not applied ※ ○ : Applied, - : Not applied
Option : Refer to model name in table Option : Refer to model name in table

140 / 141
INDOOR UNITS _ CEILING MOUNTED CASSETTE _ SPECIFICATION

SS TT (840 X 840) SS TT (840 X 840)

ARNU24GTPA4 / ARNU28GTPA4 ARNU42GTMA4 / ARNU48GTMA4


ARNU30GTPA4 / ARNU36GTNA4 ARNU54GTMA4

INDOOR
UNITS
U RNU T RNU T RNU T RNU TN U RNU T RNU T RNU T

CEILING MOUNTED CASSETTE


kW 7.1 8.2 9.0 10.6 kW 12.3 14.1 15.8
kW 8.0 9.2 10.0 11.9 kW 13.8 15.9 18.0
I I
Nominal W 18 / 16 / 14 20 / 17 / 15 26 / 24 / 21 70 / 53 / 43 Nominal W 86 / 78 / 69 89 / 84 / 78 98 / 92 / 78

D Body mm 840 x 204 x 840 840 x 204 x 840 840 x 204 x 840 840 x 246 x 840 D Body mm 840 x 288 x 840 840 x 288 x 840 840 x 288 x 840
D Shipping mm 950 x 35 x 950 950 x 35 x 950 950 x 35 x 950 950 x 35 x 950 D Shipping mm 950 x 35 x 950 950 x 35 x 950 950 x 35 x 950
Type Turbo Fan Turbo Fan Turbo Fan Turbo Fan Type Turbo Fan Turbo Fan Turbo Fan
Motor Output x Number W x No. 30 x 1 30 x 1 30 x 1 135 x 1 Motor Output x Number W x No. 135 x 1 135 x 1 135 x 1
Air Flow Rate (H / M / L) m³/min 17.0 / 15.0 / 13.0 19.0 / 16.0 / 14.0 24.3 / 22.8 / 19.5 25 / 21 / 19 Air Flow Rate (H / M / L) m³/min 30 / 27 / 24 31 / 29 / 27 34 / 32 / 27
Motor Type BLDC BLDC BLDC BLDC Motor Type BLDC BLDC BLDC
Pre Filter Pre Filter Pre Filter Pre Filter Pre Filter Pre Filter Pre Filter
Liquid Side mm (inch) Ø9.52 (3/8) Ø9.52 (3/8) Ø9.52 (3/8) Ø9.52 (3/8) Liquid Side mm (inch) Ø9.52 (3/8) Ø9.52 (3/8) Ø9.52 (3/8)
Gas Side mm (inch) Ø15.88 (5/8) Ø15.88 (5/8) Ø15.88 (5/8) Ø15.88 (5/8) Gas Side mm (inch) Ø15.88 (5/8) Ø15.88 (5/8) Ø15.88 (5/8)
Drain Pipe (Internal Dia.) mm (inch) 25 (1) 25 (1) 25 (1) 25 (1) Drain Pipe (Internal Dia.) mm (inch) 25 (1) 25 (1) 25 (1)
Body kg 20.8 (45.8) 20.8 (45.8) 20.8 (45.8) 23.5 (51.8) Body kg 25.6 (56.4) 25.6 (56.4) 26.5 (58.4)
S dB(A) 36 / 34 / 31 39 / 35 / 33 40 / 36 / 33 43 / 40 / 37 S dB(A) 44 / 41 / 38 46 / 43 / 41 50 / 48 / 44
S dB(A) 46 / 44 / 43 52 / 46 / 44 58 / 57 / 54 56 / 53 / 51 S dB(A) 58 / 55 / 50 60 / 56 / 55 60 / 58 / 55
S Ø, V, Hz 1, 220-230-240, 50/60 1, 220-230-240, 50/60 1, 220-230-240, 50/60 1, 220-230-240, 50/60 S Ø, V, Hz 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50
mm2 x No. 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C mm2 x No. 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C
PT-MCGW0 PT-MCGW0 PT-MCGW0 PT-MCGW0 PT-MCGW0 PT-MCGW0 PT-MCGW0
Model Name Model Name
PT-MPGW0 PT-MPGW0 PT-MPGW0 PT-MPGW0 PT-MPGW0 PT-MPGW0 PT-MPGW0
D Exterior Color Morning Fog Morning Fog Morning Fog Morning Fog D Exterior Color Morning Fog Morning Fog Morning Fog
RAL Code RAL 9001 RAL 9001 RAL 9001 RAL 9001 RAL Code RAL 9001 RAL 9001 RAL 9001
Net Dimensions 950 x 25 x 950 950 x 25 x 950 950 x 25 x 950 950 x 25 x 950 Net Dimensions 950 x 25 x 950 950 x 25 x 950 950 x 25 x 950
mm mm
(W x H x D) 950 x 35 x 950 950 x 35 x 950 950 x 35 x 950 950 x 35 x 950 (W x H x D) 950 x 35 x 950 950 x 35 x 950 950 x 35 x 950
Net Weight kg 5.0 / 6.3 5.0 / 6.3 5.0 / 6.3 5.0 / 6.3 Net Weight kg 5.0 / 6.3 5.0 / 6.3 5.0 / 6.3
Note : 1. Performance tested under EN14511 Note : 1. Performance tested under EN14511
2. Capacities are based on the following conditions. 2. Capacities are based on the following conditions.
- Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero
- Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero
3. Due to our policy of innovation, some specifications may be changed without notification. 3. Due to our policy of innovation, some specifications may be changed without notification.

Accessories Accessories
RNU T RNU T RNU T RNU TN RNU T RNU T RNU T
D ○ D ○
PTDCM PTDCM
R D PRLDNVS0 R D PRLDNVS0
- -
I PRIP0 I PRIP0
R - R -
○ ○
I - I -
O S - O S -
PTVK430 PTVK430
IR R - IR R -
- -
PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible), PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible),
D D
PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus) PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus)
I ○ I ○
PWFMDD200 PWFMDD200
PT-MPGW0 : PTAHMP0 PT-MPGW0 : PTAHMP0
PTVSAA0 PTVSAA0
※ ○ : Applied, - : Not applied ※ ○ : Applied, - : Not applied
Option : Refer to model name in table Option : Refer to model name in table

142 / 143
INDOOR UNITS _ CEILING MOUNTED CASSETTE _ SPECIFICATION

SS TT SS TT
ARNU09GTSA4 / ARNU12GTSA4 ARNU18GTSA4 / ARNU24GTSA4

INDOOR
UNITS
U RNU TS RNU TS U RNU TS RNU TS

CEILING MOUNTED CASSETTE


kW 2.8 3.6 kW 5.6 7.1
kW 3.2 4.0 kW 6.3 8.0
I I
Nominal W 16 / 14 / 11 18 / 14 / 11 Nominal W 19 / 16 / 14 31 / 22 / 14

D Body mm 830 x 225 x 600 830 x 225 x 600 D Body mm 830 x 225 x 600 830 x 225 x 600
D Shipping mm 1,055 x 290 x 682 1,055 x 290 x 682 D Shipping mm 1,055 x 290 x 682 1,055 x 290 x 682
Type Turbo Fan Turbo Fan Type Turbo Fan Turbo Fan
Motor Output x Number W x No. 37 x 1 37 x 1 Motor Output x Number W x No. 37 x 1 37 x 1
Air Flow Rate (H / M / L) m³/min 10.8 / 9.8 / 9.1 11.1 / 10.3 / 9.1 Air Flow Rate (H / M / L) m³/min 11.8 / 10.8 / 9.8 14.5 / 12.4 / 10.3
Motor Type BLDC BLDC Motor Type BLDC BLDC
Pre Filter Pre Filter Pre Filter Pre Filter
Liquid Side mm (inch) Ø6.35 (1/4) Ø6.35 (1/4) Liquid Side mm (inch) Ø6.35 (1/4) Ø9.52 (3/8)
Gas Side mm (inch) Ø12.7 (1/2) Ø12.7 (1/2) Gas Side mm (inch) Ø12.7 (1/2) Ø15.88 (5/8)
Drain Pipe (Internal Dia.) mm (inch) 25 (1) 25 (1) Drain Pipe (Internal Dia.) mm (inch) 25 (1) 25 (1)
Body kg 18.1 18.1 Body kg 18.1 18.1
S dB(A) 33 / 31 / 29 34 / 32 / 29 S dB(A) 35 / 33 / 31 40 / 37 / 33
S dB(A) 42 / 40 / 38 43 / 41 / 39 S dB(A) 44 / 42 / 40 48 / 45 / 40
S Ø, V, Hz 1, 220-230-240, 50/60 1, 220-230-240, 50/60 S Ø, V, Hz 1, 220-230-240, 50/60 1, 220-230-240, 50/60
mm2 x No. 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C mm2 x No. 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C
Model Name PT-USC PT-USC Model Name PT-USC PT-USC
Exterior Color Morning Fog Morning Fog Exterior Color Morning Fog Morning Fog
D D
RAL Code RAL 9001 RAL 9001 RAL Code RAL 9001 RAL 9001
Net Dimensions Net Dimensions
mm 1,100 x 28 x 690 1,100 x 28 x 690 mm 1,100 x 28 x 690 1,100 x 28 x 690
(W x H x D) (W x H x D)
Net Weight kg 4.65 4.65 Net Weight kg 4.65 4.65

Note : 1. Performance tested under EN14511 Note : 1. Performance tested under EN14511
2. Capacities are based on the following conditions. 2. Capacities are based on the following conditions.
- Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero
- Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero
3. Due to our policy of innovation, some specifications may be changed without notification. 3. Due to our policy of innovation, some specifications may be changed without notification.

Accessories Accessories
RNU TS RNU TS RNU TS RNU TS
D ○ D ○
- -
R D PRLDNVS0 R D PRLDNVS0
PRGK024A0 (~5.6kW) PRGK024A0 (~5.6kW)
I PRIP0 I PRIP0
R - R -
○ ○
I - I -
O S - O S -
- -
IR R - IR R -
- -
PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible), PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible),
D D
PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus) PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus)
I ○ I ○
PWFMDD200 PWFMDD200

※ ○ : Applied, - : Not applied ※ ○ : Applied, - : Not applied


Option : Refer to model name in table Option : Refer to model name in table

144 / 145
INDOOR UNITS _ CEILING MOUNTED CASSETTE _ SPECIFICATION

SS TT SS TT
ARNU07GTUB4 / ARNU09GTUB4 ARNU18GTTB4 / ARNU24GTTB4
ARNU12GTUB4

INDOOR
UNITS
U RNU TU RNU TU RNU TU U RNU TT RNU TT

CEILING MOUNTED CASSETTE


kW 2.2 2.8 3.6 kW 5.6 7.1
kW 2.5 3.2 4.0 kW 6.3 7.1
I I
Nominal W 20 / 18 / 16 22 / 20 / 18 24 / 22 / 20 Nominal W 38 / 28 / 24 51 / 33 / 26

D Body mm 860 x 132 x 450 860 x 132 x 450 860 x 132 x 450 D Body mm 1,180 x 132 x 450 1,180 x 132 x 450
D Shipping mm 1,129 x 259 x 538 1,129 x 259 x 538 1,129 x 259 x 538 D Shipping mm 1,499 x 259 x 538 1,499 x 259 x 538
Type Cross Flow Fan Cross Flow Fan Cross Flow Fan Type Cross Flow Fan Cross Flow Fan
Motor Output x Number W x No. 30 x 1 30 x 1 30 x 1 Motor Output x Number W x No. 30 x 1 30 x 1
Air Flow Rate (H / M / L) m³/min 8.2 / 7.3 / 6.4 9.2 / 8.6 / 8.2 10.0 / 9.2 / 8.2 Air Flow Rate (H / M / L) m³/min 13.3 / 12.1 / 10.9 14.6 / 13.3 / 11.5
Motor Type BLDC BLDC BLDC Motor Type BLDC BLDC
Pre Filter Pre Filter Pre Filter Pre Filter Pre Filter
Liquid Side mm (inch) Ø6.35 (1/4) Ø6.35 (1/4) Ø6.35 (1/4) Liquid Side mm (inch) Ø6.35 (1/4) Ø9.52 (3/8)
Gas Side mm (inch) Ø12.7 (1/2) Ø12.7 (1/2) Ø12.7 (1/2) Gas Side mm (inch) Ø12.7 (1/2) Ø15.88 (5/8)
Drain Pipe (Internal Dia.) mm (inch) Ø25 (1) Ø25 (1) Ø25 (1) Drain Pipe (Internal Dia.) mm (inch) Ø25 (1) Ø25 (1)
Body kg 13.6 13.6 13.6 Body kg 15.6 15.6
S dB(A) 32 / 29 / 25 35 / 34 / 32 38 / 35 / 32 S dB(A) 40 / 37 / 35 43 / 40 / 36
S dB(A) 47 / 44 / 41 50 / 48 / 47 52 / 50 / 47 S dB(A) 56 / 51 / 48 59 / 53 / 50
S Ø, V, Hz 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 S Ø, V, Hz 1, 220-240, 50 1, 220-240, 50
mm2 x No. 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C mm2 x No. 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C
Model Name PT-UAHW0, PT-UPHG0 PT-UAHW0, PT-UPHG0 PT-UAHW0, PT-UPHG0 Model Name PT-TAHW0, PT-TPHG0 PT-TAHW0, PT-TPHG0
Exterior Color Noble White Noble White Noble White Exterior Color Noble White Noble White
D D
RAL Code RAL 9003 RAL 9003 RAL 9003 RAL Code RAL 9003 RAL 9003
Net Dimensions Net Dimensions
mm 1,160 x 34 x 500 1,160 x 34 x 500 1,160 x 34 x 500 mm 1,480 x 34 x 500 1,480 x 34 x 500
(W x H x D) (W x H x D)
Net Weight kg 3.3 / 4.1 3.3 / 4.1 3.3 / 4.1 Net Weight kg 4.5 / 4.9 4.5 / 4.9

Note : 1. Performance tested under EN14511 Note : 1. Performance tested under EN14511
2. Capacities are based on the following conditions. 2. Capacities are based on the following conditions.
- Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero
- Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero
3. Due to our policy of innovation, some specifications may be changed without notification. 3. Due to our policy of innovation, some specifications may be changed without notification.

Accessories Accessories
RNU TU RNU TU RNU TU RNU TT RNU TT
D ○ D ○
- -
R D PRLDNVS0 R D PRLDNVS0
PRGK024A0 -
I PRIP0 I PRIP0
R - R -
○ ○
I - I -
O S - O S -
- -
IR R - IR R -
- -
PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible), PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible),
D D
PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus) PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus)
I ○ I ○
PWFMDD200 PWFMDD200
PT-UPHG0 : PTAHTP0 PT-UPHG0 : PTAHTP0

※ ○ : Applied, - : Not applied ※ ○ : Applied, - : Not applied


Option : Refer to model name in table Option : Refer to model name in table

146 / 147
INDOOR UNITS _ CEILING MOUNTED ROUND CASSETTE INDOOR UNITS _ CEILING MOUNTED ROUND CASSETTE _ KEY FEATURES

N D SI N
S
I IN OUNT D Reduce the height of the body by 15% save space and
maximize the openness of the interior space.
With crystal vein for 6-step precision control, you can send
cool / heated air wherever you want.

ROUND SS TT Other Brand LG Round Cassette Other Brand LG Round Cassette

INDOOR
UNITS
384mm
330mm

CEILING MOUNTED ROUND CASSETTE


15% less body height makes
room more higher Crystal Vein
※ Product : 48 kBtu
Wind direction Wind direction
control ❶ ❷ ❸ control ❶ ❷ ❸ ❹ ❺ ❻

Pipes are brought together in one place to minimize exposure. 3D fan increases airflow by 5% and noise reduction
Hanger covers hide installations to add a clean look. technology makes a quieter, more comfortable space.

Other Brand LG Round Cassette D D

Talking
❶ Drain Pipe Library 50 dB(A) Office
40 dB(A) 55 dB(A)
LG Vacuum
Round CST Cleaner
39 dB(A) 70 dB(A)
Previous New
(4 Way) (Round) ※ 48 kBtu, Low flow rate

❷ Refrigerant Pipe ❶ Piping in One Direction Only

❸ Exposed Hanger ❷ Hanger Cover Normal communication Library Noise level 40 dB(A)
Noise level 50 dB(A)

• Luxury round design can make a luxurious space with a round design • Retail
considering side view. • Restaurant Perfect round flow without blind spots. Larger airflow rate, cooling rate is faster than 30%.
• Perfect round air flow without blind spots. • Office
Other Brand LG Round Cassette
• Hotel

R
Smart Wi-Fi ○
Energy Efficiency Human Detect Sensor - Other Brand LG Round Cassette
Drain Pump ○
Sleep Mode ○
Timer (On / Off) ○
Comfort
Timer (Weekly) ○
Two Thermistor Control ○
Group Control ○ Set temperature reach time 18 minutes Set temperature reach time 12 minutes
(Height 1.1m) (Height 1.1m)

※ Based on test results from LG chamber, this image is designed to help customers
understand. Experimental environment: height 3.2m, 48 kBtu, cooling mode,
3 Way airflow with blind spot. Perfect circular airflow without blind spots. high flow rate, horizontal air flow direction

148 / 149
INDOOR UNITS _ CEILING MOUNTED ROUND CASSETTE _ SPECIFICATION

ROUND I IN SS TT
ARNU24GTYA4 / ARNU36GTYA4
ARNU48GTYA4

INDOOR
UNITS
U RNU T RNU T RNU T

CEILING MOUNTED ROUND CASSETTE


kW 7.1 10.6 14.1
kW 8.0 11.9 15.9
I
Nominal W 44 / 36 / 29 63 / 47 / 36 98 / 70 / 44

D Body mm 1,050 x 330 x 1,050 1,050 x 330 x 1,050 1,050 x 330 x 1,050
D Shipping mm 1,137 x 395 x 1,132 1,137 x 395 x 1,132 1,137 x 395 x 1,132
Type 3D Turbo Fan 3D Turbo Fan 3D Turbo Fan
Motor Output x Number W x No. 157 x 1 157 x 1 157 x 1
Air Flow Rate (H / M / L) m3/min 22 / 21 / 19 27 / 24 / 21 32 / 28 / 23
Motor Type BLDC BLDC BLDC
Long life Long life Long life
Liquid Side mm (inch) Ø9.52 (3/8) Ø9.52 (3/8) Ø9.52 (3/8)
Gas Side mm (inch) Ø15.88 (5/8) Ø15.88 (5/8) Ø15.88 (5/8)
Drain Pipe (Internal Dia.) mm (inch) Ø25 (1) Ø25 (1) Ø25 (1)
Body kg 30 30 30
S dB(A) 39 / 37 / 34 43 / 39 / 37 47 / 44 / 39
S dB(A) 48 / 46 / 43 52 / 48 / 46 56 / 53 / 48
S Ø, V, Hz 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50
mm2 x No. 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C

Note : 1. Performance tested under EN14511


2. Capacities are based on the following conditions.
- Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero
- Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero
3. Due to our policy of innovation, some specifications may be changed without notification.

Accessories
RNU T RNU T RNU T
D ○
-
R D PRLDNVS0
-
I PRIP0
R -

I -
O S -
-
IR R -
-
PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible),
D
PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus)
I ○
PWFMDD200
-
T S -
-
-

※ ○ : Applied, - : Not applied


Option : Refer to model name in table

150 / 151
INDOOR UNITS _ CEILING CONCEALED DUCT INDOOR UNITS _ CEILING CONCEALED DUCT _ KEY FEATURES

S RT N R I I N
S S
I IN Anytime, anywhere access with LG ThinQ mobile app. User has easy access to air volume selection via remote
controller using the ESP control function.

ON D DU T T
Search “LG ThinQ” on Google market or Appstore then
The BLDC motor can control fan speed and air volume.
No additional accessories are necessary to control air flow.

INDOOR
download the app.

UNITS
LG ThinQ
E.S.P. E.S.P.
Control Control

Comfort Cooling / Comfort Cooling /


Wi-Fi Heating Heating

CEILING CONCEALED DUCT


S S
Depending on the installation environment, LG's ceiling
concealed duct controls the static pressure with 11steps
to provide maximized comfort to any environment.

LG ThinQ N

1 step
Static Pressure
Low Setting
* Wi-Fi modem (Option) is necessary for this function

Easy Registration and Log-in 11 steps

Follow the easy set-up steps that will activate LG ThinQ’s user-friendly features. Static Pressure
Power Setting

Accumulated electric energy of the indoor unit can be


identified with wired remote control, as well as with
the central controller. This function is an advantage for
energy management.

Install Scene Apply for multistory building


• Easy and flexible duct adjusts air volume with External Static Pressure (ESP) • Office 100kWh
control function. • Hotel
Watt PDI
• Minimalist visibility (Hidden within ceiling) to blend seamlessly into any interior • Retail Meter
• Residential building Total Power
Input

Premium Wired Total accumulated


Remote Controller electric energy 20kWh
Simple operation for various functions 595kWh

D 50kWh
Smart Wi-Fi ○ ○ ○
Energy Efficiency E.S.P Control ○ ○ ○ Standard Wired Total accumulated
Drain Pump ○ ○ ○ Remote Controller electric energy 30kWh
Timer (On / Off) ○ ○ ○ 3,977kWh

Comfort Timer (Weekly) ○ ○ ○


On/Off, Current Temp Mode, Set Temp Vane Control ※ Outdoor unit's accumulated electric energy / using rate of individual indoor unit + indoor
Two Thermistor Control ○ ○ ○ unit's accumulated electric energy is displayed in wired remote controller, only when
Group Control ○ ○ ○ central controller, digital integrating electricity meter and PDI are installed and PDI,
outdoor unit and indoor unit are connected with power wire. Only total accumulated
※ ○ : Applied, - : Not applied electric energy is displayed in standard wired remote controller. In premium wired remote
controller, that are displayed into week / month / year.

152 / 153
INDOOR UNITS _ CEILING CONCEALED DUCT _ KEY FEATURES

O ORT
R O
Using a spiral duct (Embedded or flexible type) and New mid-static ducts provide ideal solution for installation
stream chamber, it is possible to operate cooling / heating in limited space.
for several rooms simultaneously.

270mm

INDOOR
UNITS
380
mm
298
mm

CEILING CONCEALED DUCT


270 270
mm mm

Conventional New Conventional New

T T
The alarm is activated when the filter needs to be The indoor temperature can be checked using the thermistors
cleaned, and the time remaining for cleaning is displayed in the remote controller as well as from the indoor unit.
on the creen. There may be a significant difference between ceiling and
floor air temperature. Two thermistors can optimize indoor air
Remain Time Until Indoor Filter Cleaning + Alarm
temperature for a more comfortable environment.

Indoor Unit Thermistor


Standard Wired
Remote Controller

Remain time until indoor filter cleaning 2,400hr.

Premium Wired
Remote Controller
Remote Controller Thermistor
Remain time until indoor filter cleaning 1,729hr.

I O O
I S D O Indoor unit can be controlled by external devices without
The low static duct allows the air intake at the rear or dry contact, so customer can save cost of installation.
bottom under specific installation conditions.
Connection between an indoor unit and external devices directly
Not Necessary
Air intake at the rear or bottom
Motion Detector
Sensor

Not Necessary
for Dry Contact

Key Tag

※ In case of needing more functions beside on / off control, a dry contact is required
to be installed.

154 / 155
INDOOR UNITS _ CEILING CONCEALED DUCT _ SPECIFICATION

ID ST TI I ST TI
ARNU07GM1A4 / ARNU09GM1A4 ARNU28GM2A4 / ARNU36GM2A4
ARNU12GM1A4 / ARNU15GM1A4 ARNU42GM2A4 / ARNU48GM3A4
ARNU18GM1A4 / ARNU24GM1A4 ARNU54GM3A4

INDOOR
UNITS
U RNU RNU RNU RNU RNU RNU U RNU RNU RNU RNU RNU

CEILING CONCEALED DUCT


kW 2.2 2.8 3.6 4.5 5.6 7.1 kW 8.2 10.6 12.3 14.1 15.8
kW 2.5 3.2 4.0 5.0 6.3 8.0 kW 9.2 11.9 13.8 15.9 18.0
I I
Nominal W 39 / 30 / 25 40 / 32 / 26 46 / 38 / 31 67 / 53 / 46 85 / 63 / 55 91 / 74 / 58 Nominal W 123 / 81 / 57 184 / 123 / 81 231 / 162 / 111 172 / 105 / 65 260 / 215 / 172

D Body mm 900 x 270 x 700 900 x 270 x 700 900 x 270 x 700 900 x 270 x 700 900 x 270 x 700 900 x 270 x 700 D Body mm 1,250 x 270 x 700 1,250 x 270 x 700 1,250 x 270 x 700 1,250 x 360 x 700 1,250 x 360 x 700
D Shipping mm 1,100 x 338 x 773 1,100 x 338 x 773 1,100 x 338 x 773 1,100 x 338 x 773 1,100 x 338 x 773 1,100 x 338 x 773 D Shipping mm 1,450 x 338 x 773 1,450 x 338 x 773 1,450 x 338 x 773 1,450 x 428 x 773 1,450 x 428 x 773
Type Sirocco Fan Sirocco Fan Sirocco Fan Sirocco Fan Sirocco Fan Sirocco Fan Type Sirocco Fan Sirocco Fan Sirocco Fan Sirocco Fan Sirocco Fan
Motor Output x Number W x No. 136 x 1 136 x 1 136 x 1 136 x 1 136 x 1 136 x 1 Motor Output x Number W x No. 350 x 1 350 x 1 350 x 1 350 x 1 350 x 1
Air Flow Rate (H / M / L) m³/min 9.0 / 7.5 / 6.0 9.5 / 7.5 / 6.0 11.0 / 9.0 / 7.0 16.0 / 12.0 / 9.0 17.0 / 14.5 / 12.0 19.0 / 16.0 / 14.0 Air Flow Rate (H / M / L) m³/min 28.0 / 24.0 / 21.0 32.0 / 28.0 / 24.0 38.0 / 33.0 / 28.0 40.0 / 34.0 / 28.0 50.0 / 45.0 / 40.0
External Static Pressure External Static Pressure
mmAq (Pa) 6 (59) 6 (59) 6 (59) 6 (59) 6 (59) 6 (59) mmAq (Pa) 6 (59) 6 (59) 6 (59) 6 (59) 6 (59)
(High Mode) (High Mode)
Air Flow Rate (H / M / L) Air Flow Rate (H / M / L)
m³/min 9.0 / 7.5 / 6.0 9.5 / 7.5 / 6.0 11.0 / 9.0 / 7.0 16.0 / 12.0 / 9.0 17.0 / 14.5 / 12.0 19.0 / 16.0 / 14.0 m³/min 28.0 / 24.0 / 21.0 32.0 / 28.0 / 24.0 38.0 / 33.0 / 28.0 40.0 / 34.0 / 28.0 50.0 / 45.0 / 40.0
(Standard Mode) (Standard Mode)
External Static Pressure External Static Pressure
mmAq (Pa) 2.5 (25) 2.5 (25) 2.5 (25) 2.5 (25) 2.5 (25) 2.5 (25) mmAq (Pa) 5 (49) 5 (49) 5 (49) 5 (49) 5 (49)
(Standard Mode) (Standard Mode)
Motor Type BLDC BLDC BLDC BLDC BLDC BLDC Motor Type BLDC BLDC BLDC BLDC BLDC
Pre Filter Pre Filter Pre Filter Pre Filter Pre Filter Pre Filter Pre Filter Pre Filter Pre Filter Pre Filter Pre Filter
Liquid Side mm (inch) Ø6.35 (1/4) Ø6.35 (1/4) Ø6.35 (1/4) Ø6.35 (1/4) Ø6.35 (1/4) Ø9.52 (3/8) Liquid Side mm (inch) Ø9.52 (3/8) Ø9.52 (3/8) Ø9.52 (3/8) Ø9.52 (3/8) Ø9.52 (3/8)
Gas Side mm (inch) Ø12.7 (1/2) Ø12.7 (1/2) Ø12.7 (1/2) Ø12.7 (1/2) Ø12.7 (1/2) Ø15.88 (5/8) Gas Side mm (inch) Ø15.88 (5/8) Ø15.88 (5/8) Ø15.88 (5/8) Ø15.88 (5/8) Ø19.05 (3/4)
Drain Pipe (Internal Dia.) mm (inch) 25 (1) 25 (1) Ø25 (1) Ø25 (1) Ø25 (1) Ø25 (1) Drain Pipe (Internal Dia.) mm (inch) Ø25 (1) Ø25 (1) Ø25 (1) Ø25 (1) Ø25 (1)
Body kg 25.5 25.5 25.5 25.5 25.5 26.5 Body kg 38.0 38.0 39.5 44.0 44.0
S dB(A) 26 / 24 / 23 27 / 25 / 23 27 / 25 / 23 30 / 27 / 23 31 / 28 / 25 32 / 29 / 26 S dB(A) 36 / 34 / 33 37 / 36 / 34 38 / 37 / 36 39 / 37 / 35 42 / 40 / 39
S dB(A) 55 / 54 / 51 55 / 54 / 52 56 / 54 / 52 59 / 57 / 55 59 / 57 / 55 59 / 58 / 56 S dB(A) 59 / 57 / 55 60 / 59 / 57 62 / 61 / 60 63 / 60 / 59 65 / 64 / 62
S Ø, V, Hz 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 S Ø, V, Hz 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50
mm2 x No. 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C mm2 x No. 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C
Note : 1. Performance tested under EN14511 Note : 1. Performance tested under EN14511
2. Capacities are based on the following conditions. 2. Capacities are based on the following conditions.
- Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero
- Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero
3. Due to our policy of innovation, some specifications may be changed without notification. 3. Due to our policy of innovation, some specifications may be changed without notification.

Accessories Accessories
RNU RNU RNU RNU RNU RNU RNU RNU RNU RNU RNU
D ○ D ○
- -
R D PRLDNVS0 R D PRLDNVS0
PRGK024A0 (~5.6kW) -
I PRIP0 I PRIP0
R - R -
○ ○
I - I -
O S - O S -
- -
IR R PWLRVN000 IR R PWLRVN000
ABZCA ABZCA
PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible), PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible),
D D
PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus) PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus)
I ○ I ○
PWFMDD200 PWFMDD200

※ ○ : Applied, - : Not applied ※ ○ : Applied, - : Not applied


Option : Refer to model name in table Option : Refer to model name in table

156 / 157
INDOOR UNITS _ CEILING CONCEALED DUCT _ SPECIFICATION

I ST TI O ST TI
ARNU76GB8A4 / ARNU96GB8A4 ARNU05GL1G4 / ARNU07GL1G4
ARNU09GL1G4

INDOOR
UNITS
U RNU RNU U RNU RNU RNU

CEILING CONCEALED DUCT


kW 22.4 28.0 kW 1.7 2.2 2.8
kW 25.2 31.5 kW 1.9 2.5 3.2
I I
Nominal W 765 / 500 / 500 800 / 750 / 750 Nominal W 29 / 26 / 24 31 / 28 / 24 39 / 29 / 24

D Body mm 1,562 x 460 x 688 1,562 x 460 x 688 D Body mm 700 x 190 x 700 700 x 190 x 700 700 x 190 x 700
D Shipping mm 1,806 x 537 x 825 1,806 x 537 x 825 D Shipping mm 862 x 255 x 781 862 x 255 x 781 862 x 255 x 781
Type Sirocco Fan Sirocco Fan Type Sirocco Fan Sirocco Fan Sirocco Fan
Motor Output x Number W x No. 375 x 2 375 x 2 Motor Output x Number W x No. 19 x 1 19 x 1 19 x 1
Air Flow Rate (H / M / L) Air Flow Rate (H / M / L)
m³/min 60.0 / 50.0 / 50.0 72.0 / 64.0 / 64.0 m³/min 6.7 / 6.2 / 5.5 7.5 / 6.5 / 5.5 9.0 / 7.0 / 5.5
(High Mode-Factory Set) (High Mode-Factory Set)
External Static Pressure External Static Pressure
mmAq (Pa) 22 (216) 22 (216) mmAq (Pa) 2.54 (25) 2.54 (25) 2.54 (25)
(High Mode) (High Mode)
Air Flow Rate (H / M / L) Air Flow Rate (H / M / L)
m³/min 64.0 / 50.0 / 50.0 76.0 / 64.0 / 64.0 m³/min 6.7 / 6.2 / 5.5 7.5 / 6.5 / 5.5 9.0 / 7.0 / 5.5
(Standard Mode) (Standard Mode)
External Static Pressure External Static Pressure
mmAq (Pa) 15 (147) 15 (147) mmAq (Pa) 0 (0) 0 (0) 0 (0)
(Standard Mode) (Standard Mode)
Motor Type BLDC BLDC Motor Type BLDC BLDC BLDC
Pre Filter Pre Filter Pre Filter Pre Filter Pre Filter
Liquid Side mm (inch) Ø9.52 (3/8) Ø9.52 (3/8) Liquid Side mm (inch) Ø6.35 (1/4) Ø6.35 (1/4) Ø6.35 (1/4)
Gas Side mm (inch) Ø19.05 (3/4) Ø22.2 (7/8) Gas Side mm (inch) Ø12.7 (1/2) Ø12.7 (1/2) Ø12.7 (1/2)
Drain Pipe (Internal Dia.) mm (inch) Ø25 (1) Ø25 (1) Drain Pipe (Internal Dia.) mm (inch) Ø25 (1) Ø25 (1) Ø25 (1)
Body kg 87.0 87.0 Body kg 17.5 17.5 17.5

S dB(A) 45 / 41 / 40 47 / 42 / 41 S dB(A) 25 / 24 / 22 26 / 24 / 22 28 / 25 / 22
S dB(A) 70 / 68 / 68 72 / 69 / 68 S dB(A) 48 / 46 / 45 50 / 47 / 45 53 / 49 / 45
S Ø, V, Hz 1, 220-240, 50 1, 220-240, 50 S Ø, V, Hz 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50
mm2 x No. 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C mm2 x No. 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C

Note : 1. Performance tested under EN14511 Note : 1. Performance tested under EN14511
2. Capacities are based on the following conditions. 2. Capacities are based on the following conditions.
- Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero
- Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero
3. Due to our policy of innovation, some specifications may be changed without notification. 3. Due to our policy of innovation, some specifications may be changed without notification.

Accessories Accessories
RNU RNU RNU RNU RNU
D ○ D ○
- -
R D PRLDNVS0 R D PRLDNVS0
○ PRGK024A0
I PRIP0 I PRIP0
R - R -
○ ○
I - I -
O S - O S -
- -
IR R PWLRVN000 IR R PWLRVN000
ABZCA ABZCA
PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible), PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible),
D D
PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus) PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus)
I ○ I ○
PWFMDD200 PWFMDD200

※ ○ : Applied, - : Not applied ※ ○ : Applied, - : Not applied


Option : Refer to model name in table Option : Refer to model name in table

158 / 159
INDOOR UNITS _ CEILING CONCEALED DUCT _ SPECIFICATION

O ST TI O ST TI
ARNU12GL2G4 / ARNU15GL2G4 ARNU21GL3G4 / ARNU24GL3G4
ARNU18GL2G4

INDOOR
UNITS
U RNU RNU RNU U RNU RNU

CEILING CONCEALED DUCT


kW 3.6 4.5 5.6 kW 6.2 7.1
kW 4.0 5.0 6.3 kW 7.0 8.0
I I
Nominal W 41 / 34 / 29 56 / 41 / 34 71 / 56 / 41 Nominal W 72 / 53 / 48 103 / 63 / 48

D Body mm 900 x 190 x 700 900 x 190 x 700 900 x 190 x 700 D Body mm 1,100 x 190 x 700 1,100 x 190 x 700
D Shipping mm 1,062 x 255 x 781 1,062 x 255 x 781 1,062 x 255 x 781 D Shipping mm 1,262 x 255 x 781 1,262 x 255 x 781
Type Sirocco Fan Sirocco Fan Sirocco Fan Type Sirocco Fan Sirocco Fan
Motor Output x Number W x No. 19 x 1, 5 x 1 19 x 1, 5 x 1 19 x 1, 5 x 1 Motor Output x Number W x No. 19 x 2 19 x 2
Air Flow Rate (H / M / L) Air Flow Rate (H / M / L)
m³/min 10.0 / 8.5 / 7.0 12.5 / 10.0 / 8.5 15.0 / 12.5 / 10.0 m³/min 17.5 / 14.0 / 12.0 20.0 / 16.0 / 12.0
(High Mode-Factory Set) (High Mode-Factory Set)
External Static Pressure External Static Pressure
mmAq (Pa) 2.54 (25) 2.54 (25) 2.54 (25) mmAq (Pa) 2.54 (25) 2.54 (25)
(High Mode) (High Mode)
Air Flow Rate (H / M / L) Air Flow Rate (H / M / L)
m³/min 10.0 / 8.5 / 7.0 12.5 / 10.0 / 8.5 15.0 / 12.5 / 10.0 m³/min 17.5 / 14.0 / 12.0 20.0 / 16.0 / 12.0
(Standard Mode) (Standard Mode)
External Static Pressure External Static Pressure
mmAq (Pa) 0 (0) 0 (0) 0 (0) mmAq (Pa) 0 (0) 0 (0)
(Standard Mode) (Standard Mode)
Motor Type BLDC BLDC BLDC Motor Type BLDC BLDC
Pre Filter Pre Filter Pre Filter Pre Filter Pre Filter
Liquid Side mm (inch) Ø6.35 (1/4) Ø6.35 (1/4) Ø6.35 (1/4) Liquid Side mm (inch) Ø9.52 (3/8) Ø9.52 (3/8)
Gas Side mm (inch) Ø12.7 (1/2) Ø12.7 (1/2) Ø12.7 (1/2) Gas Side mm (inch) Ø15.88 (5/8) Ø15.88 (5/8)
Drain Pipe (Internal Dia.) mm (inch) Ø25 (1) Ø25 (1) Ø25 (1) Drain Pipe (Internal Dia.) mm (inch) Ø25 (1) Ø25 (1)
Body kg 23.0 23.0 23.0 Body kg 27.0 27.0
S dB(A) 30 / 27 / 25 33 / 30 / 28 35 / 32 / 29 S dB(A) 35 / 29 / 28 36 / 33 / 28
S dB(A) 50 / 47 / 46 54 / 51 / 47 56 / 54 / 51 S dB(A) 59 / 55 / 54 63 / 59 / 55
S Ø, V, Hz 1, 220-240, 50 1, 220-240, 50 1, 220-240, 50 S Ø, V, Hz 1, 220-240, 50 1, 220-240, 50
mm2 x No. 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C mm2 x No. 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C

Note : 1. Performance tested under EN14511 Note : 1. Performance tested under EN14511
2. Capacities are based on the following conditions. 2. Capacities are based on the following conditions.
- Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero
- Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero
3. Due to our policy of innovation, some specifications may be changed without notification. 3. Due to our policy of innovation, some specifications may be changed without notification.

Accessories Accessories
RNU RNU RNU RNU RNU
D ○ D ○
- -
R D PRLDNVS0 R D PRLDNVS0
- PRGK024A0
I PRIP0 I PRIP0
R - R -
○ ○
I - I -
O S - O S -
- -
IR R PWLRVN000 IR R PWLRVN000
ABZCA ABZCA
PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible), PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible),
D D
PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus) PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus)
I ○ I ○
PWFMDD200 PWFMDD200
※ ○ : Applied, - : Not applied ※ ○ : Applied, - : Not applied
Option : Refer to model name in table Option : Refer to model name in table

160 / 161
INDOOR UNITS _ FRESH AIR INTAKE INDOOR UNITS _ FRESH AIR INTAKE _ SPECIFICATION

R S IR INT R S IR INT
O S ARNU76GB8Z4 / ARNU96GB8Z4

The LG Fresh Air Intake Unit (FAU) is the alternative solution for ventilation, which supplies the fresh outdoor
air indoors as well as being able to cool and heat air inside simultaneously. It means the indoor space can have
positive air pressure consistently, which can block cold, hot or contaminated air from outside.

INDOOR
UNITS
This allows the indoor space to have consistent positive air pressure blocking cold.

Fresh Air Intake

100%
Outdoor Air Indoor Unit Diffuser Indoor Unit Diffuser Indoor Unit Diffuser U RNU RNU

FRESH AIR INTAKE


kW 22.4 28.0
kW 21.4 26.7
Air Conditioning
I
Air Conditioning + Nominal W 230 / 200 / 200 360 / 230 / 230
Outdoor Air Supply
D Body mm 1,562 x 460 x 688 1,562 x 460 x 688
D Shipping mm 1,806 x 537 x 825 1,806 x 537 x 825
Type Sirocco Fan Sirocco Fan
Motor Output x Number W x No. 375 x 1 375 x 1
MULTI V 5 Outdoor Unit
Air Flow Rate (H / M / L)
m³/min 23.7 / 13.2 / 13.2 35.7 / 23.7 / 23.7
(High Mode-Factory Set)
External Static Pressure mmAq (Pa) 22 (216) 22 (216)
Motor Type BLDC BLDC
O Long Life Filter Long Life Filter
Natural outdoor air is utilized as seasons change for cost efficiency. Liquid Side mm (inch) Ø9.52 (3/8) Ø9.52 (3/8)
Gas Side mm (inch) Ø19.05 (3/4) Ø22.2 (7/8)
S S S Drain Pipe (Internal Dia.) mm (inch) Ø25 (1) Ø25 (1)
Fresh Air Intake Fresh Air Intake Body kg 73.0 73.0
S dB(A) 45 / 43 / 43 47 / 45 / 45
S dB(A) 70 / 67 / 67 72 / 70 / 70
Indoor Unit Diffuser Indoor Unit Diffuser S Ø, V, Hz 1, 220-240, 50 1, 220-240, 50
OFF OFF mm2 x No. 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C
Note : 1. Performance tested under EN14511
Warm Air Cool Air 2. Capacities are based on the following conditions.
+ + - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero
- Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero
Outdoor Air Supply Outdoor Air Supply
3. Due to our policy of innovation, some specifications may be changed without notification.

CAUTION
MULTI V 5 Outdoor Unit MULTI V 5 Outdoor Unit 1. Operation range (Cooling : 5°C ~ 43°C, Heating : -5°C ~ 43°C) 2. Installation of exhaust fan is recommended for a sealed room. 3. Indoor Unit Connection
N
Fresh air intake units only 1) The total capacity of fresh air intake unit should be 50 ~ 100% of outdoor unit.
are connected with outdoor units 2) The max. quantity of fresh air intake is 4 units.

I S Mixture connection with


general indoor unit and fresh intake units
1) The total capacity of indoor units (Standard Indoor Unit + Fresh Air Intake Unit) should be 50 ~ 100% of outdoor unit.
2) The total capacity of fresh air intake unit should be less than 30% of the total capacity of indoor units.

Min. 2m

Accessories
1/30 Slope RNU RNU
Outlet Air D ○
-
R D PRLDNVS0
-
I PRIP0
R -
Exhaust Air

I -
Inlet Hood Intake Air Duct Fresh Air Intake Unit O S -
Exhaust Fan Door -
IR R PWLRVN000
-
PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible),
D
PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus)
I ○
PWFMDD200
※ ○ : Applied, - : Not applied
Option : Refer to model name in table

162 / 163
INDOOR UNITS _ CEILING SUSPENDED INDOOR UNITS _ CEILING SUSPENDED _ KEY FEATURES

S RT O ORT I IN SUS ND D

D D
I IN SUS ND D Access your air conditioner anytime and from anywhere. Modern elegance design with V-shape and
black vane is appropriate for any commercial space.
T
It received iF Design Award.
Search “LG ThinQ” on Google market or Appstore then
LG ThinQ download the app.

INDOOR
UNITS
LG ThinQ
Wi-Fi

CEILING SUSPENDED
Easy Registration and Log-in
Follow the easy set-up steps that will
activate LG ThinQ’s impressive feature. High ceiling mode provides powerful cooling and heating up to
4.2m in height from floor, 15m away from ceiling.

* Wi-Fi modem (Option) is necessary


for this function

O ORT ONSO
O T
Easy in / out filter structure as well as a simplified two-piece
The ceiling and floor models can be installed either on the filter, which slides out for easy cleaning and maintenance.
ceiling or on the floor.

D One Touch Filter

• Modern design with V-shape and black vane • Retail Vertical air flow direction can be adjusted using remote controller,
• Powerful air speed and volume can reach up to 15m • Shop and horizontal Air flow direction can be adjusted manually.
• Restaurant T T
Users can purchase a wired remote controller that includes
a second thermistor, allowing for temperature checks from
Horizontal Vertical
100 °
93 ° multiple locations.
S
Smart Wi-Fi ○ ○ 80 °
Close 63 ° Close
Fast Cooling & Heating Jet Cool ○ ○
Cooling Heating
Sleep mode ○ ○ Two
Thermistors
Timer (On / Off) ○ ○
Remote
Comfort Timer (Weekly) ○ ○ Indoor Unit Controller Thermistor
The filter change alarm informs you when the unit has been
Two thermistor control
Group control




operating for 2,400 hours. 15M
15M
Thermistor

※ ○ : Applied, - : Not applied

One Touch Filter Velocity in Stn Frame


Contour 1
2,000e+001
Filter Change Alarm
ANSYS
R15.0

1,800e+001
1,600e+001
1,400e+001
1,200e+001
1,000e+001
8,000e+000
164 / 165
6,000e+000
4,000e+000
2,000e+000
Velocity in Stn Frame
0,000e+000 ANSYS
Contour 1 [m s^-1] R15. 0
2,000e+00 1
1,800e+00 1
1,600e+00 1
INDOOR UNITS _ CEILING SUSPENDED _ SPECIFICATION

I IN SUS ND D I IN SUS ND D
ARNU18GV1A4 / ARNU24GV1A4 ARNU36GV2A4 / ARNU48GV2A4

INDOOR
UNITS
U RNU RNU U RNU RNU

CEILING SUSPENDED
kW 5.6 7.1 kW 10.6 14.1
kW 6.3 8.0 kW 11.9 15.9
I I
Nominal W 23 / 20 / 17 25 / 21 / 17 Nominal W 84 / 77 / 66 91 / 79 / 66
Morning Fog Morning Fog Morning Fog Morning Fog
R RAL 9001 RAL 9001 R RAL 9001 RAL 9001
D Body mm 1,200 x 235 x 690 1,200 x 235 x 690 D Body mm 1,600 x 235 x 690 1,600 x 235 x 690
D Shipping mm 1,315 x 320 x 772 1,315 x 320 x 772 D Shipping mm 1,715 x 320 x 772 1,715 x 320 x 772
Type Cross Flow Fan Cross Flow Fan Type Cross Flow Fan Cross Flow Fan
Motor Output x Number W x No. 85.9 x 1 85.9 x 1 Motor Output x Number W x No. 125 x 1 125 x 1
Air Flow Rate (H / M / L) m³/min 13.5 / 12.5 / 12.0 14.0 / 13.0 / 12.0 Air Flow Rate (H / M / L) m³/min 27.0 / 24.0 / 20.0 29.0 / 24.0 / 20.0
Motor Type BLDC BLDC Motor Type BLDC BLDC
Pre Filter Pre Filter Pre Filter Pre Filter
Liquid Side mm (inch) Ø6.35 (1/4) Ø9.52 (3/8) Liquid Side mm (inch) Ø9.52 (3/8) Ø9.52 (3/8)
Gas Side mm (inch) Ø12.7 (1/2) Ø15.88 (5/8) Gas Side mm (inch) Ø15.88 (5/8) Ø15.88 (5/8)
Drain Pipe (Internal Dia.) mm (inch) Ø16 (5/8) Ø16 (5/8) Drain Pipe (Internal Dia.) mm (inch) Ø16 (5/8) Ø16 (5/8)
Body kg 29.0 29.0 Body kg 37.0 37.0
S dB(A) 36 / 34 / 33 37 / 35 / 33 S dB(A) 48 / 46 / 44 49 / 47 / 44
S dB(A) 61 / 59 / 56 62 / 59 / 56 S dB(A) 68 / 66 / 64 68 / 67 / 66
S Ø, V, Hz 1, 220-240, 50 1, 220-240, 50 S Ø, V, Hz 1, 220-240, 50 1, 220-240, 50
mm2 x No. 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C mm2 x No. 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C

Note : 1. Performance tested under EN14511 Note : 1. Performance tested under EN14511
2. Capacities are based on the following conditions. 2. Capacities are based on the following conditions.
- Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero
- Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero
3. Due to our policy of innovation, some specifications may be changed without notification. 3. Due to our policy of innovation, some specifications may be changed without notification.

Accessories Accessories
RNU RNU RNU RNU
D - D -
- -
R D PRLDNVS0 R D PRLDNVS0
- -
I PRIP0 I PRIP0
R - R -
○ ○
I - I -
O S - O S -
- -
IR R - IR R -
- -
PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible), PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible),
D D
PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus) PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus)
I ○ I ○
PWFMDD200 PWFMDD200

※ ○ : Applied, - : Not Applied ※ ○ : Applied, - : Not Applied


Option : Refer to model name in table Option : Refer to model name in table

166 / 167
INDOOR UNITS _ CONSOLE INDOOR UNITS _ CONSOLE _ KEY FEATURES

S RT O ORT
D
ONSO Access your air conditioner anytime and from anywhere. The console protects cold draft from windows to provide
comfortable environment.
T
Without Console
Search “LG ThinQ” on Google market or Appstore then
download the app.

INDOOR
LG ThinQ

UNITS
Wi-Fi
LG ThinQ

CONSOLE
Without Console

* Wi-Fi modem (Option) is necessary for this function

O ORT
D
During the cooling operation, the vane adjusts upwards to direct the S
air flow towards the ceiling. When heating, the vane directs the warm There are 5 different stages to control air flow direction.
air downwards to balance the room temperature especially for floor.
Step3 Step4
Step2
Cooling
Step5

Step1

It is possible to install and connect the outdoor unit in


Heating (Normal) 6 different ways. (Right Side, Right Back, Right Floor,
Left Side, Left Back, Left Floor)
• 6 Way flexible piping • Residential building
• Cold draft window protection • Hotel
• Condensation protection • Historical building

Smart Wi-Fi ○
Energy Efficiency Jet Cool -
Health Ionizer ○
Fast Cooling & Heating Jet Cool ○ Heating (Option)
Sleep Mode ○
Timer (On / Off) ○
Comfort Timer (Weekly) ○
Two Thermistor Control ○
Group Control ○
※ ○ : Applied, - : Not applied

168 / 169
INDOOR UNITS _ CONSOLE _ SPECIFICATION

ONSO ONSO
ARNU07GQAA4 / ARNU09GQAA4 ARNU12GQAA4 / ARNU15GQAA4

INDOOR
UNITS
U RNU RNU U RNU RNU

CONSOLE
kW 2.2 2.8 kW 3.6 4.5
kW 2.5 3.2 kW 4.0 5.0
I I
Nominal W 15 / 12 / 10 15 / 12 / 10 Nominal W 18 / 15 / 13 24 / 19 / 17
Morning Fog Morning Fog Morning Fog Morning Fog
R RAL 9001 RAL 9001 R RAL 9001 RAL 9001
D Body mm 700 x 600 x 210 700 x 600 x 210 D Body mm 700 x 600 x 210 700 x 600 x 210
D Shipping mm 775 x 662 x 284 775 x 662 x 284 D Shipping mm 775 x 662 x 284 775 x 662 x 284
Type Turbo fan Turbo fan Type Turbo fan Turbo fan
Motor Output x Number W x No. 48 x 1 48 x 1 Motor Output x Number W x No. 48 x 1 48 x 1
Air Flow Rate (H / M / L) m³/min 6.7 / 5.9 / 4.8 6.7 / 5.9 / 4.8 Air Flow Rate (H / M / L) m³/min 7.5 / 5.9 / 4.8 8.7 / 6.7 / 5.9
Motor Type BLDC BLDC Motor Type BLDC BLDC
Pre Filter Pre Filter Pre Filter Pre Filter
Liquid Side mm (inch) Ø6.35 (1/4) Ø6.35 (1/4) Liquid Side mm (inch) Ø6.35 (1/4) Ø6.35 (1/4)
Gas Side mm (inch) Ø12.7 (1/2) Ø12.7 (1/2) Gas Side mm (inch) Ø12.7 (1/2) Ø12.7 (1/2)
Drain Pipe (Internal Dia.) mm (inch) Ø12 (15/32) Ø12 (15/32) Drain Pipe (Internal Dia.) mm (inch) Ø12 (15/32) Ø12 (15/32)
Body kg 14.0 14.0 Body kg 14.0 14.0
S dB(A) 37 / 34 / 28 37 / 34 / 28 S dB(A) 39 / 34 / 28 42 / 37 / 31
S dB(A) 53 / 50 / 44 53 / 50 / 44 S dB(A) 56 / 50 / 44 58 / 53 / 50
S Ø, V, Hz 1, 220-240, 50 1, 220-240, 50 S Ø, V, Hz 1, 220-240, 50 1, 220-240, 50
mm2 x No. 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C mm2 x No. 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C

Note : 1. Performance tested under EN14511 Note : 1. Performance tested under EN14511
2. Capacities are based on the following conditions. 2. Capacities are based on the following conditions.
- Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Cooling : Indoor temp. 27°C (80.6°F) DB / 19°C (66.2°F) WB, Outdoor temp. 35°C (95°F) DB / 24°C (75.2°F) WB, Interconnecting piping length 7.5m, Level difference of zero
- Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero - Heating : Indoor temp. 20°C (68°F) DB / 15°C (59°F) WB, Outdoor temp. 7°C (44.6°F) DB / 6°C (42.8°F) WB, Interconnecting piping length 7.5m, Level difference of zero
3. Due to our policy of innovation, some specifications may be changed without notification. 3. Due to our policy of innovation, some specifications may be changed without notification.

Accessories Accessories
RNU RNU RNU RNU
D - D -
- -
R D PRLDNVS0 R D PRLDNVS0
PRGK024A0 PRGK024A0
I PRIP0 I PRIP0
R - R -
○ ○
I ○ I ○
O S - O S -
- -
IR R - IR R -
- -
PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible), PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible),
D D
PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus) PDRYCB320 (Universal input), PDRYCB400 (2 points input), PDRYCB500 (Modbus)
I ○ I ○
PWFMDD200 PWFMDD200

※ ○ : Applied, - : Not Applied ※ ○ : Applied, - : Not Applied


Option : Refer to model name in table Option : Refer to model name in table

170 / 171
INDOOR UNITS _ COMPATIBILITY INDOOR UNITS _ FEATURE FUNCTIONS

O TI I IT TUR UN TIONS
S I S S S D R
N R
S III S II S S

Dry Contact for


PREMTA000 Simple Dry 2 points Dry Thermostat

INDOOR
NEW
PQRCH- PDRYCB300 For Modbus

UNITS
PREMTA000A PREMTBB10 PREMTB100 PREMTBB01 PREMTB001 PQRCVCLOQ PQRCVC0QW PQRCHCA0Q PWLSSB21H Contact Contact
CA0QW PDRYCB500
PREMTA000B (H/P) PDRYCB000 PDRYCB400 NEW
PDRYCB320
N

ARNU-A4
ARNU-B4
○ ○ ○ ○ ○ ○ ○ ○ ○ ○ PREMTA000
PREMTB100 PREMTB001 PQRCVCL0Q PQRCHCA0Q NEW
4 Way PREMTA000A PWFMDD200
PREMTBB10 PREMTBB01 PQRCVCL0QW PQRCHCA0QW PWLSSB21H (H/P)
PREMTA000B

COMPATIBILITY / FEATURE FUNCTIONS


Ceiling
ARNU-B4 On / Off ○ ○ ○ ○ ○ ○ ○
Mounted
ARNU-C4
○ ○ ○ ○ ○ ○ ○ ○ ○ ○
Cassette
2 Way / 1 Way Fan Speed Control ○ ○ ○ ○ ○ ○ ○

Temperature Setting ○ ○ ○ ○ ○ ○ ○
ARNU-A4 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
Round CST Mode Change ○ ○ ○ ○ - ○ ○

Auto Swing ○ ○ ○ ○ ○ ○
ARNU-A4 ○ ○ ○ ○ ○ △ ○ ○ ○ ○ Vane Control
○ ○ ○ ○ ○ ○ ○
High Sensible (Louver Angle)

E.S.P
Ceiling ○ ○ ○ ○ ○ - -
(External Static Pressure)
Concealed ARNU-A4 ○ ○ ○ ○ ○ △ ○ ○ ○ ○
Duct Electric Failure
High / Mid Statics ○ ○ ○ ○ ○ - ○
Compensation

Indoor Temperature Display ○ ○ ○ ○ ○ ○


ARNU-G4 ○ ○ ○ ○ ○ △ ○ ○ ○ ○
Low Statics
ALL Button Lock
○ ○ ○ ○ ○ - -
(Child Lock)
FAU
Schedule / Timer Weekly - Yearly Weekly - Yearly Weekly - - Sleep / On / Off Weekly
(Fresh Air ARNU-Z4 ○ ○ ○ ○ ○ △ ○ ○ ○ ○
intake)
Additional Mode Setting 1) ○ ○ ○ - - - -
U TI

Convertible Time Display ○ ○ ○ - - ○ -


& Ceiling ARNU-A4 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
Suspended Humid. Display ○ ○ - - - - -

Advanced Lock
(mode, set point, set point Advanced Lock Advanced Lock - - - - -
Console ARNU-A4 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○ range, on/off Lock)

Filter Sign ○ ○ ○ - - - -
ARNU-A4
Wall Energy Management 2) ○ ○ ○ - - - -
Mounted
ARNU-C4 ○ ○ ○ ○ ○ ○ ○ ○ ○ ○
ARNU-N4
Dual Set Point ○ ○ - - - - -

Human Detection - ○ - - - - -
HYDRO
KIT 1)
ARNH-A4 - - - - - - ○ - ○ -
Temp, Humidity
○ ○ - - - - -
Compensation
Energy
Recovery
Wi-Fi AP mode setting ○ ○ ○ ○ ○ ○ -
Ventilator ○ ○ ○ - - - ○ - - ○
Operation Status LED ○ ○ ○ ○ ○ - -
Ventilation
Energy Recovery Wireless Remote Controller
○3) - ○3) ○3) ○3) - -
Ventilator with Receiver
DX coil
○ ○ ○ - - - ○ - - ○
T Display 5 inch Color 4.3 inch Color 4.3 inch mono 2.6 inch mono 2.6 inch mono 2 inch mono -

Size (W x H x D, mm) 137 x 121 x 16.5 120 x 120 x 16 120 x 120 x 16 64 x 120 x 15 64 x 120 x 15 51 x 153 x 26 -
AHU Communication Kit ○ ○ ○ - - △ - - - -
Black Light Control for
○ ○ - - - - -
Screen Saver

※ ○ : Compatible, △ : Need wired remote controller / IR receiver, - : Not compatible ※ ○ : Applied, - : Not Applied
1) It has a separate remote controller. 1) It might not be indicated or operated at the partial product.
2) Centralized control (PACEZA000 / PACS5A000 / PACP5A000 / PLNWKB000) and PDI (PQNUD1S40 / PPWRDB000) should be installed for this function.
3) For ceiling type duct.
Note
- Indoor unit should have functions requested by the controller.
- If you need more detail, please refer to the manual of product. (http://partner.lge.com: Home> Doc.Library> Manual)

172 / 173
OT T R
SO UTION

SO UTION
OT T R
HYDRO KIT

174 / 175
HOT WATER SOLUTION _ HYDRO KIT HOT WATER SOLUTION _ HYDRO KIT _ KEY FEATURES

DRO IT I I N
S T DRO IT
Equivalent installation cost of traditional boiler with reduced D
• Lower operation cost compared to fossil fuel-based systems such as boilers. • Where Hot Water is needed such as domestic Hot Water, operational costs.
Outdoor Unit High Temperature HYDRO KIT Heating
• More energy saving through MULTI V heat recovery system. In-floor or radiant heat. Where cold water is needed such as U TI DRO IT
Refrigerant - Refrigerant -
by Hot Water
(Air Conditioning + Hot Water Supply + Floor Heating) Refrigerant Water
Fan coil unit and chilled beam. U TI
Air-Refrigerant

(Hot Water Supply + Floor Heating)


U TI O IR
50°C 80°C
(Hot Water Supply + Floor Heating)

- Building Type : Dormitory, Flats


- Cooling / Floor Heating / Sanitary Hot Water for 10 years High Temperature Technology
- Cooling : MULTI V IV Indoor Unit

Pressure
Water
- Floor Heating : Medium Temp. HYDRO KIT (1ea)

SO UTION
OT
- Sanitary Hot Water : High Temp. HYDRO KIT (2ea), Sanitary Hot Water
Tanks R410A
- Electricity Cost : Average Cost in EU
R134A

T R
- Gas Cost : Average Cost in EU Stage 1
Hot Water Heating Cooling - Oil Cost : Average Cost in EU Stage 2
Air
Initial Costs Annual Operating Costs
Enthalpy

HYDRO KIT
25,000 100% 90% 95% 25,000 229%
20,000 20,000
R U 15,000 15,000 171%
100% Applicable to a variety of facilities including hospitals,
Radiator 10,000 10,000

5,000 5,000
residences and resorts that need floor heating and
Gas Boiler Oil Boiler Gas Boiler Oil Boiler domestic hot water supply.
FCU
Floor heating LCC
50,000
Oil boiler
Gas boiler
40,000

30,000

20,000 Dormitory Hotel Office Restaurant

10,000
1 2 3 4 5 6 7 8 9 10 (Year)

Thermal Storage Tank

Hot water+ Radiant heating HR unit (Cooling & Hot water) Thermal Storage System S Fitness Hospital Factory Residential

R
Energy costs can be minimized by reusing the wasted

ON NI N heat from indoor units.


Constant simultaneous
Conventional
Absorbed heat is released to outdoor air. cooling and heating operating
T S S during summer to provide hot
T water by using wasted heat
Total solution provided with heat pump, air conditioning Green energy solution through the reduction of CO2 Heat
Released
(Cooling by refrigerant and cold water / heating by emissions. energy from indoor cooling
pump
refrigerant hot water) and domestic hot water supply. Heat
Absorption
process.
S
CO2 Emissions
Refrigerant piping Water piping Conventional Boiler Domestic
(%) Hot Water Tank
HR Unit Hot Water Supply Cooling
Indoor Unit 120

HYDRO KIT
Domestic
Hot Water Tank 100
100%
Absorbed heat from indoor space is used for making hot water. O
76% Hot water can be supplied
T at all times in the office by
60
DRO IT HR Unit cooling the HR unit to
MULTI V 5 40 30%
On Average
pump Heat
Absorption
warm up the sanitary tank,
High temperature using waste energy.
MULTI V 5 Domestic
20 HYDRO KIT
(Heat Recovery) Hot Water Tank
Oil Gas Hot Water Supply Cooling
Boiler Boiler
MULTI V
Outdoor Unit
(Water Cooled) Middle temperature

176 / 177
HOT WATER SOLUTION _ HYDRO KIT _ SPECIFICATION

DRO IT DRO IT
ARNH04GK2A4 / ARNH10GK2A4 ARNH04GK3A4 / ARNH08GK3A4

U RN RN U RN RN

SO UTION
OT
kW 12.3 28.0 kW 13.8 25.2
kW 13.8 31.5 I Nominal1) W 2,300 5,000
I Nominal1) W 10 10 Morning Gray Morning Gray

T R
Morning Gray Morning Gray R RAL 7030 RAL 7030
R RAL 7030 RAL 7030 D Body mm 520 x 1,080 x 330 520 x 1,080 x 330
D Body mm 520 x 631 x 330 520 x 631 x 330 D Shipping mm 682 x 1,168 x 423 682 x 1,168 x 423
D Shipping mm 677 x 687 x 418 677 x 687 x 418 Liquid Side mm (inch) Ø9.52 (3/8) Ø9.52 (3/8)

HYDRO KIT
Liquid Side mm (inch) Ø9.52 (3/8) Ø9.52 (3/8) Gas Side mm (inch) Ø15.88 (5/8) Ø19.05 (3/4)
Gas Side mm (inch) Ø15.88 (5/8) Ø22.2 (7/8) Drain Pipe (Internal Dia.) A (inch) 25A (Male PT 1) 25A (Male PT 1)
Drain Pipe (Internal Dia.) A (inch) 25A (Male PT 1) 25A (Male PT 1) Inlet A (inch) 25A (Male PT 1) 25A (Male PT 1)
Inlet A (inch) 25A (Male PT 1) 25A (Male PT 1) Outlet A (inch) 25A (Male PT 1) 25A (Male PT 1)
Outlet A (inch) 25A (Male PT 1) 25A (Male PT 1) Body kg 87.0 91.0
Body kg 29.2 33.7 S dB(A) 43 46
S dB(A) 26 26 S Ø, V, Hz 1, 220-240, 50 1, 220-240, 50
S Ø, V, Hz 1, 220-240, 50 1, 220-240, 50 mm2 x No. 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C
mm2 x No. 1.0 ~ 1.5 x 2C 1.0 ~ 1.5 x 2C 1) Nominal : Performance tested under EN14511
Note : 1. Capacities are based on the following conditions :
1) Nominal : Performance tested under EN14511
- Heating : Indoor 20°C (68°F) DB / 15°C (59°F) WB, Outdoor 7°C (44.6°F) DB / 6°C (42.8°F) WB, Water Inlet 55°C (131°F) / Outlet 65°C (149°F)
Note : 1. Capacities are based on the following conditions :
2. Piping Length : Interconnected Pipe Length = 7.5m
- Cooling : Indoor 27°C (80.6°F) DB / 19° C (66.2°F) WB, Outdoor 35°C (95°F) DB / 24°C (75.2°F) WB, Water Inlet 23°C (73.4°F) / Outlet 18°C (64.4°F)
3. Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero.
- Heating : Indoor 20°C (68°F) DB / 15°C (59°F) WB, Outdoor 7°C (44.6°F) DB / 6°C (42.8°F) WB, Water Inlet 30°C (86°F) / Outlet 35°C (95°F)
4. MULTI V S 4HP (ARUN040GSS0, ARUN040LSS0) cannot be connected to HYDRO KIT.
2. Piping Length : Interconnected Pipe Length = 7.5m
5. MULTI V Water S cannot be connected to HYDRO KIT.
3. Difference Limit of Elevation (Outdoor ~ Indoor Unit) is Zero.
4. MULTI V S 4HP (ARUN040GSS0, ARUN040LSS0) cannot be connected to HYDRO KIT.
5. MULTI V Water S cannot be connected to HYDRO KIT.
6. Anti freezing liquid should be added under 10°C (outdoor temp.) during cooling mode.

Accessories Accessories
RN RN RN RN
D - D -
- -
R D PRLDNVS0 R D PRLDNVS0
- -
I ○ I ○
R - R -
- -
I - I -
O S - O S -
- -
IR R - IR R -
- -
PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible) PDRYCB000 (1 point contact), PDRYCB300 (8 points for thermostat compatible)
D D
PDRYCB320 (Universal input) PDRYCB320 (Universal input)
I ○ I ○
PWFMDD200 PWFMDD200

※ ○ : Applied, - : Not applied ※ ○ : Applied, - : Not applied


Option : Refer to model name in table Option : Refer to model name in table

178 / 179
NTI TION
SO UTIONS

SO UTIONS
NTI TION
ERV

180 / 181
VENTILATION SOLUTIONS _ ERV VENTILATION SOLUTIONS _ ERV _ KEY FEATURES

I I I N
O O
N R R O R Efficiency and comfort is ensured through the high-efficiency
energy recovery central core which recovers energy from
LG ERV reduces energy loss with auto fan speed control
following CO2 level

NTI TION R
Fine CO2 level
the indoor air and transfers it to the fresh incoming air High occupancy Low occupancy CO2 level
without mixing the air stream. (high CO2 level) (low CO2 level) Fan speed

- Reduce power consumption


for ventilation
- Reduce cooling, heating
energy loss by ventilation

Air Filter
Low Energy Saving
Exchanger Air (Annually)
Supply Air Extra
high high
Outdoor Air Indoor Air

9 o’clock 10 11 12 13 14 15 16 17
※ This function is operated with ‘Night Time Free Cooling’ on remote controller. (with MULTI V only)
※ Energy saving ratio can be differed by weather condition.
※ Test Condition - Office (49,000ft2) / Occupancy : 30 / Area : London, UK
- ERV (1000 CMH) + MULTI V IV (12HP) Unit Combination
- Other conditions are subject to BREEAM.

SO UTIONS
NTI TION
S S O
The exhausting system using high static and sirocco fan LG ERV senses outdoor temperature and operates
removes contaminants effectively from indoor air. Supply automatically following weather condition.
and exhaust air flows are completely separated in the total High temp. Natural ventilation
Heat recovery LG ERV heat recovery mode
heat exchanger, LG ERV can filter out the impurities before mode LG ERV bypass mode
supplying outdoor air and make indoor air fresh and healthy.

ERV
Proper temp. Energy Saving
Bypass mode (Annually)
Exchanger Air Supply Air
Exchanger Damper
Low temp.
Air Heat recovery
Return
Air mode

Supply Month Jan. Feb. Mar. Apr. May. Jun. Jul. Aug. Sep. Oct. Nov. Dec.
Air
Outdoor Heat recovery mode Bypass mode
Indoor Air Air
Outdoor Air
Indoor Outdoor Indoor Outdoor

Outdoors Indoors Total Heat Exchanger Automatic


Change
Damper Damper
Heat Exchanger Heat Exchanger
※ This function is operated with ‘Auto’ mode by wired remote control.
※ Energy saving ratio can be differed by weather condition.
※ Test Condition: - Office (49,000ft2) / Occupancy : 30 / Area : London, UK
N T - ERV (1,000 CMH) + MULTI V IV (12HP) Unit Combination
- Other conditions are subject to BREEAM.
During summer nights, indoor heat can be discharged

N SSIT O R outdoors and cool outdoor air can be brought indoors for
energy savings.
D O
Afternoon Night Morning When the air conditioner and ERV are switched on simultaneously,
Indoor temp. Outdoor temp.(winter) delay operation can reduce unnecessary heating and cooling
Energy Recovery Ventilation (ERV)
22°C -5°C
energy loss by slowing down automatic ERV operation.
Operation Delay operation
Set Temp. Operation starts Operation air conditioner simultaneously. Operation starts with air conditioner.
C
16 ° ERV makes inside cooler Inside Temp.
with bypass mode like Outside Temp. ON Energy consumption Fine CO2 level
natural ventilation Energy Saving (Annually)
OFF CO2 level
ON
Natural Ventilation

Outdoor temp. Indoor temp. Energy Saving Office time


-5°C Inside is getting starts
-5°C 22°C (Annually)
higher in the night
because of business Operation
machines. time
Indoor temp Outdoor temp
Comfort air + Energy Saving 22°C -5°C ※ This function is operated with ‘Night Time Free Cooling’ on remote controller. (with MULTI V only)
Demand only Demand
Compare to natural ventilation ※ Energy saving ratio can be differed by weather condition.
S ※ This function is operated with ‘Night Time Free Cooling’ on remote controller. (with MULTI V only)
Heat exchanger collects wasted ※ Test Condition ※ Energy saving ratio can be differed by weather condition.
Natural Ventilation loss - Office (49,000ft2) / Occupancy : 30 / Area : London, UK ※ Test Condition - Office (49,000ft2) / Occupancy : 30 / Area : London, UK
energy while ventilating. heat energy. - ERV (1000 CMH) + MULTI V IV (12HP) Unit Combination - ERV (1,000 CMH) + MULTI V IV (12HP) Unit Combination
- Other conditions are subject to BREEAM. - Other conditions are subject to BREEAM.

182 / 183
VENTILATION SOLUTIONS _ ERV _ KEY FEATURES

O ORT R I I IT ON NI N ON NI N
O
CO2 sensor senses CO2 level in the room. Users can monitor Wired remote controller is easy for usage. Fast ventilation mode prevents the spread of contaminants During the summer, ERV DX can transform outdoor
CO2 level on new wired remote controller, and ERV controls under negative indoor pressure and makes indoor air fresh warm air into cool air for indoors and it can prevent cold
the fan speed automatically following the level. and comfortable quickly. drafts during the winter by supplying warm air.
Only Exhausting
CO2 Level Visualization
CO2 sensor senses indoor CO2 level and displays it on new wired remote controller. Convenient
• Flexible display
- Dual display with air conditioner.
- Zoom selected directory to increase legibility.
Exhausting operation causes Cooling
negative indoor air pressure,
and cannot fully ventilate.
Easy
• Navigation buttons, easy to use.
• Easy installation setting

Visible
Main display Further information • Indoor CO2 level Exhausting and Supplying
If the CO2 level is above 900ppm in CO2 level and room condition are • Alarm for filter change / Remained time to change filters Fast Ventilation Mode Simultaneously
the room, the red mark is on. displayed continuously.
Monitoring CO2
O 1,215 ppm
Exhaust

SO UTIONS
comfort level Heating

NTI TION
Fan
※ The remote controller screen image CO2 1 wired remote controller up to 16 ERV (Including air Supply
CO2
may change. 1215 ppm SEVERE Fan
※ Applicable to only Standard III, Premium
conditioner). It is convenient for large common space
remote controller. such as lobby.
Several units combination
O 16 units group control is available with 1 remote controller.
Using CO2 sensor, LG ERV controls exhaust air flow automatically

ERV
to keep indoor air fresh under settled CO2 concentration. Good looking interior S T S
The high static pressure fan can control the air volume LG ERV DX can be used as a Total Air Conditioning Solution.
depending on the length of the duct. It is also easy to It can control condition of incoming air with the DX coil and
CO2 Sensor
RS3 Remote
control the pressure level by using the remote controller humidifier for making comfortable indoor air.
(AHCS 100H0)
(Internal type : Default) Controller for a more flexible duct installation and easier testing. In the summer, LG ERV DX controls the air indoors by cooling
Conventional New and dehumidifying incoming air. In winter, it can provide warm
Air
CO2
(ppm) Controller & installation cost saving Volume air by heating and humidifying the incoming air.
Heat Exchange DX Coil Humidification
Windows Windows Windows Windows
Closed Open Closed Open
2,500

Exhaust Supply
Air Air
1,000

0 ERV with CO2


Concentration Control
Time (min)

I S Outdoor Return
D - LG ERV can be interlocked with air conditioners Air Air

LG ERV durability is increased through bacteria-resistant material and controlled individually. External Static Pressure (mmAq)

of heat exchanger and corrosion protection coating. It prevents - This function can be operated when the system
shortening product life due to corrosion and mold and supplies is connected with 1 remote controller. I U TI
high quality air to inside by minimizing the bacteria. Filter can be conveniently changed and cleaned. LG ERV DX can be interlocked with MULTI V.
Others LG ERV It can be controlled individually by a wired remote
Remote
Inside ERV Inside ERV Controller controller connected to MULTI V indoor units.
Corrosion
occurrence Indoor Units
Corrosion
protection coating MAX. 16
+ Finish insulator
ERV Unit Remove Side Panel

Heat exchanger and filter Heat exchanger

Outdoor unit
ERV DX

Change Filter Remove Heat Exchanger


Breading mold Bacteria-resistant

184 / 185
VENTILATION SOLUTIONS _ ERV _ SPECIFICATION

R R
LZ-H025GBA4 / LZ-H035GBA4 LZ-H080GBA4 / LZ-H100GBA4
LZ-H050GBA4 LZ-H150GBA4 / LZ-H200GBA4

CMH CMH
N 250 (147) 350 (206) 500 (294) N 800 (471) 1,000 (589) 1,500 (883) 2,000 (1,177)
(CFM) (CFM)
S Ø, V, Hz 1, 220-240, 50 / 60 S Ø, V, Hz 1, 220-240, 50 / 60
Step - SUPER-HIGH / HIGH / LOW Step - SUPER-HIGH / HIGH / LOW
Current SH / H / L Amps 0.70 / 0.60 / 0.42 1.10 / 0.95 / 0.60 1.92 / 1.58 / 0.79 Current SH / H / L Amps 2.77 / 2.16 / 1.44 3.41 / 2.90 / 1.76 5.60 / 5.40 / 2.90 6.80 / 5.90 / 3.60
Power Input SH / H / L W 97 / 78 / 52 180 / 163 / 88 240 / 220 / 90 Power Input SH / H / L W 390 / 280 / 187 480 / 385 / 210 780 / 540 / 377 960 / 770 / 420
CMH 250 / 250 / 150 350 / 350 / 210 500 / 500 / 320 CMH 800 / 800 / 660 1,000 / 1,000 / 800 1,500 / 1,500 / 1,200 2,000 / 2,000 / 1,600
Air Flow SH / H / L Air Flow SH / H / L
(CFM) (147 / 147 / 88) (206 / 206 / 123) (294 / 294 / 124) (CFM) (471 / 471 / 388) (589 / 589 / 471) (883 / 883 / 706) (1,177 / 1,177 / 942)

SO UTIONS
Pa 100 / 70 / 50 150 / 130 / 100 150 / 100 / 50 Pa 200 / 110 / 60 160 / 90 / 50 200 / 110 / 60 160 / 90 / 50

NTI TION
External Static Pressure SH / H / L External Static Pressure SH / H / L
R (inWTR) (0.40 / 0.28 / 0.20) (0.60 / 0.52 / 0.40) (0.60 / 0.40 / 0.20) R (inWTR) (0.80 / 0.44 / 0.24) (0.64 / 0.36 / 0.20) (0.80 / 0.44 / 0.24) (0.64 / 0.36 / 0.20)
Temperature Exchange Temperature Exchange
SH / H / L % 80 / 80 / 83 75 / 75 / 77 78 / 78 / 79 SH / H / L % 79 / 79 / 82 77 / 77 / 78 79 / 79 / 82 77 / 77 / 78
Efficiency Efficiency
Enthalpy Exchange Heating (SH / H / L) % 70 / 70 / 72 68 / 68 / 70 73 / 73 / 75 Enthalpy Exchange Heating (SH / H / L) % 72 / 72 / 74 70 / 70 / 72 72 / 72 / 74 70 / 70 / 72
Efficiency Cooling (SH / H / L) % 66 / 66 / 68 63 / 63 / 65 66 / 66 / 69 Efficiency Cooling (SH / H / L) % 63 / 63 / 66 59 / 59 / 63 63 / 63 / 66 59 / 59 / 63
Noise Level Noise Level
SH / H / L dB(A) 29 / 28 / 24 32 / 30 / 27 34 / 32 / 25 SH / H / L dB(A) 40 / 37 / 31 41 / 38 / 32 43 / 40 / 34 44 / 41 / 35
(Sound Level, 1.5m) (Sound Level, 1.5m)

ERV
Step - SUPER-HIGH / HIGH / LOW Step - SUPER-HIGH / HIGH / LOW
Current SH / H / L Amps 0.70 / 0.60 / 0.42 1.10 / 0.95 / 0.60 1.92 / 1.58 / 0.79 Current SH / H / L Amps 2.77 / 2.16 / 1.44 3.41 / 2.90 / 1.76 5.60 / 5.40 / 2.90 6.80 / 5.90 / 3.60
Power Input SH / H / L W 97 / 78 / 52 180 / 163 / 88 240 / 220 / 90 Power Input SH / H / L W 390 / 280 / 187 480 / 385 / 210 780 / 540 / 377 960 / 770 / 420
CMH 250 / 250 / 150 350 / 350 / 210 500 / 500 / 320 CMH 800 / 800 / 660 1,000 / 1,000 / 800 1,500 / 1,500 / 1,200 2,000 / 2,000 / 1,600
Air Flow SH / H / L Air Flow SH / H / L
(CFM) (147 / 147 / 88) (206 / 206 / 123) (294 / 294 / 124) (CFM) (471 / 471 / 388) (589 / 589 / 471) (883 / 883 / 706) (1,177 / 1,177 / 942)
Pa 100 / 70 / 50 150 / 130 / 100 150 / 100 / 50 Pa 200 / 110 / 60 160 / 90 / 50 200 / 110 / 60 160 / 90 / 50
External Static Pressure SH / H / L External Static Pressure SH / H / L
(inWTR) (0.40 / 0.28 / 0.20) (0.60 / 0.52 / 0.40) (0.60 / 0.40 / 0.20) (inWTR) (0.80 / 0.44 / 0.24) (0.64 / 0.36 / 0.20) (0.80 / 0.44 / 0.24) (0.64 / 0.36 / 0.20)
Noise Level Noise Level
SH / H / L dB(A) 29 / 29 / 25 32 / 30 / 27 35 / 33 / 25 SH / H / L dB(A) 41 / 38 / 32 41 / 39 / 33 44 / 41 / 35 44 / 42 / 36
(Sound Level, 1.5m) (Sound Level, 1.5m)
Type - Air to air cross flow heat exchange Type - Air to air cross flow heat exchange
N kg 44 44 44 N kg 62 140
D WxHxD mm 988 x 273 x 1,014 988 x 273 x 1,014 988 x 273 x 1,014 D WxHxD mm 1,062 x 365 x 1,140 1,313 x 738 x 1,140
Qty EA 4 Qty EA 4 4+2
D D
Size (Ø) mm Ø200 Size (Ø) mm Ø250 Ø250 + Ø350
Qty EA 1 Qty EA 1 2
S S
Type - Direct-Drive (Sirocco Fan) Type - Direct-Drive (Sirocco Fan)
Qty EA 1 Qty EA 1 2
Type - Direct-Drive (Sirocco Fan) Type - Direct-Drive (Sirocco Fan)
Qty EA 2 2 Qty EA 2 4
D Type - Cleanable fibrous fleeces D Type - Cleanable fibrous fleeces
Size (W x H x D) mm 855 x 10 x 160 855 x 6 x 230 Size (W x H x D) mm 1,056 x 6 x 212.5
Model - AHFT035H0 AHFT050H0 Model - AHFT100H0
Qty EA 2 2 Qty EA 2 4
O O
Type - F7 F7 Type - F7
Size (W x H x D) mm 423.5 x 132 x 25 425 x 194 x 25 Size (W x H x D) mm 520 x 192 x 25
D PDRYCB000 D PDRYCB000

Note : 1. ERV mode : Total Heat Recovery Ventilation mode Note : 1. ERV mode : Total Heat Recovery Ventilation mode
2. Refer to dimensional drawings. 2. Refer to dimensional drawings.
3. Noise level : 3. Noise level :
- The operating conditions are assumed to be standard. - The operating conditions are assumed to be standard.
- Sound measured at 1.5m below the center the body. - Sound measured at 1.5m below the center the body.
- Sound level will vary depending on a range of factors such as the construction (acoustic absorption coefficient) of particular room in which the equipment is installed. - Sound level will vary depending on a range of factors such as the construction (acoustic absorption coefficient) of particular room in which the equipment is installed.
- The sound level at the air discharge port is about 8 dB(A) higher than the unit's operating sound. - The sound level at the air discharge port is about 8 dB(A) higher than the unit’s operating sound.
4. Temperature and Enthalpy Exchange Efficiency at cooling Indoor Temperature : 26.5°C DB, 64.5% RH, Outdoor Temperature : 34.5°C DB, 75% RH 4. Temperature and Enthalpy Exchange Efficiency at cooling Indoor Temperature : 26.5°C DB, 64.5% RH, Outdoor Temperature : 34.5°C DB, 75% RH
5. Temperature and Enthalpy Exchange Efficiency at heating Indoor Temperature : 20.5°C DB, 59.5% RH, Outdoor Temperature : 5°C DB, 65% RH 5. Temperature and Enthalpy Exchange Efficiency at heating Indoor Temperature : 20.5°C DB, 59.5% RH, Outdoor Temperature : 5°C DB, 65% RH
6. Temperature Exchange efficiency is tested at heating condition. 6. Temperature Exchange efficiency is tested at heating condition.

186 / 187
VENTILATION SOLUTIONS _ ERV _ SPECIFICATION

R IT D OI R IT D OI
LZ-H050GXH4 / LZ-H080GXH4 LZ-H050GXN4 / LZ-H080GXN4
LZ-H100GXH4 LZ-H100GXN4

N N N
Cooling kW 4.93 7.46 9.12 Cooling kW 4.93 7.46 9.12
Heating kW 6.73 9.80 11.72 Heating kW 6.73 9.80 11.72
T T
SH / H / L % 86 / 86 / 87 80 / 80 / 81 76 / 76 / 78 SH / H / L % 86 / 86 / 87 80 / 80 / 81 76 / 76 / 78

Cooling (SH / H / L) % 61 / 61 / 63 50 / 50 / 53 45 / 45 / 50 Cooling (SH / H / L) % 61 / 61 / 63 50 / 50 / 53 45 / 45 / 50


Heating (SH / H / L) % 76 / 76 / 77 67 / 67 / 69 64 / 64 / 66 Heating (SH / H / L) % 76 / 76 / 77 67 / 67 / 69 64 / 64 / 66
O R Outdoor air Temperature °C -15 ~ 45 -15 ~ 45 -15 ~ 45 O R Outdoor air Temperature °C -15 ~ 45 -15 ~ 45 -15 ~ 45
Heat Exchange Mode (SH / H / L) CMH 500 / 500 / 440 800 / 800 / 640 1,000 / 1,000 / 820 Heat Exchange Mode (SH / H / L) CMH 500 / 500 / 440 800 / 800 / 640 1,000 / 1,000 / 820
R R
Bypass Mode (SH / H / L) CMH 500 / 500 / 440 800 / 800 / 640 1,000 / 1,000 / 820 Bypass Mode (SH / H / L) CMH 500 / 500 / 440 800 / 800 / 640 1,000 / 1,000 / 820

SO UTIONS
NTI TION
External Static Pressure (SH / H / L) Pa 160 / 120 / 100 140 / 90 / 70 110 / 70 / 60 External Static Pressure (SH / H / L) Pa 180 / 150 / 110 170 / 120 / 80 150 / 100 / 70
System Natural Evaporating Type System -
Amount kg/h 2.70 4.00 5.40 Amount kg/h -
Pressure Feed Water Mpa 0.02 ~ 0.49 Pressure Feed Water Mpa -
Heat Exchange Mode (SH / H / L) dB(A) 38 / 36 / 33 39 / 37 / 34 40 / 38 / 35 Heat Exchange Mode (SH / H / L) dB(A) 39 / 37 / 35 41 / 38 / 36 41 / 39 / 36
S S
Bypass Mode (SH / H / L) dB(A) 39 / 37 / 34 40 / 38 / 35 40 / 38 / 35 Bypass Mode (SH / H / L) dB(A) 39 / 37 / 35 41 / 38 / 36 41 / 39 / 36
R R410A R R410A
S Ø, V, Hz 1, 220-240, 50 / 60 S Ø, V, Hz 1, 220-240, 50 / 60

ERV
I Heat Exchange Mode (SH / H / L) kW 0.25 / 0.20 / 0.15 0.42 / 0.35 / 0.25 0.48 / 0.42 / 0.27 I Heat Exchange Mode (SH / H / L) kW 0.25 / 0.20 / 0.15 0.42 / 0.35 / 0.25 0.48 / 0.42 / 0.27
N Bypass Mode (SH / H / L) kW 0.25 / 0.20 / 0.15 0.42 / 0.35 / 0.25 0.48 / 0.42 / 0.27 N Bypass Mode (SH / H / L) kW 0.25 / 0.20 / 0.15 0.42 / 0.35 / 0.25 0.48 / 0.42 / 0.27
N R Heat Exchange Mode (SH / H / L) A 1.5 / 1.3 / 1.0 2.5 / 2.0 / 1.5 3.6 / 3.2 / 2.3 N R Heat Exchange Mode (SH / H / L) A 1.5 / 1.3 / 1.0 2.5 / 2.0 / 1.5 3.6 / 3.2 / 2.3
R Bypass Mode (SH / H / L) A 1.5 / 1.3 / 1.0 2.5 / 2.0 / 1.5 3.6 / 3.2 / 2.3 R Bypass Mode (SH / H / L) A 1.5 / 1.3 / 1.0 2.5 / 2.0 / 1.5 3.6 / 3.2 / 2.3
Air to air cross flow total heat (Sensible + Latent heat) exchange Air to air cross flow total heat (Sensible + Latent heat) exchange
Specially processed non-flammable paper Specially processed non-flammable paper
Multidirectional fibrous fleeces Multidirectional fibrous fleeces
D WxHxD mm 1,667 x 365 x 1,140 D WxHxD mm 1,667 x 365 x 1,140
N kg 105 N kg 98
Liquid mm Ø6.35 Liquid mm Ø6.35
Gas mm Ø12.7 Gas mm Ø12.7
Water mm Ø6.35 Water mm -
Drain Pipe (Internal Dia.) mm (inch) Ø25 (1) Drain Pipe (Internal Dia.) mm (inch) Ø25 (1)
D D mm Ø250 D D mm Ø250
Note : 1. Cooling Capacity Test condition - Indoor temperature : 27°C DB, 19°C WB / Outdoor temperature : 35°C DB Note : 1. Cooling Capacity Test condition - Indoor temperature : 27°C DB, 19°C WB / Outdoor temperature : 35°C DB
2. Heating Capacity Test condition - Indoor temperature : 20°C DB / Outdoor temperature : 7°C DB, 6°C WB 2. Heating Capacity Test condition - Indoor temperature : 20°C DB / Outdoor temperature : 7°C DB, 6°C WB
3. Humidifying capacity is based on the following conditions - Indoor temperature : 20°C DB, 15°C WB / Outdoor temperature : 7°C DB, 6°C WB 3. Humidifying capacity is based on the following conditions - Indoor temperature : 20°C DB, 15°C WB / Outdoor temperature : 7°C DB, 6°C WB
4. Cooling and heating capacities are based on the following conditions. : Fan is based on High and Super-high. 4. Cooling and heating capacities are based on the following conditions. : Fan is based on High and Super-high.
5. The operating sound measured at the point 1.5 m below the center of the unit is converted to that measured at an anechoic chamber. 5. The operating sound measured at the point 1.5 m below the center of the unit is converted to that measured at an anechoic chamber.
6. The specifications, designs and information here are subject to change without notice. 6. The specifications, designs and information here are subject to change without notice.

Accessories Accessories
N N N
D - D -
- -
R D PRLDNVS0 R D PRLDNVS0
- -
I - I -
R - R -
- -
I - I -
O S AHCS100H0 O S AHCS100H0
- -
IR R - IR R -
- -
PDRYCB000 (1 point contact) PDRYCB000 (1 point contact)
D D
PDRYCB500 (Modbus) PDRYCB500 (Modbus)
I ○ I ○
- -

※ ○ : Applied, - : Not applied ※ ○ : Applied, - : Not applied


Option : Refer to model name in table Option : Refer to model name in table

188 / 189