FICHTNER JV
Middle Marsyangdi Hydroelectric Project
Project Completion Report - Volume 4C
Nepal Electricity Authority – NEA
Project Commissioning Report
FICHTNER JV
Middle Marsyangdi Hydroelectric Project
TABLE OF CONTENTS
1 INTRODUCTION 1
2 REFERENCE DOCUMENTS 1
3 TESTS DURING ASSEMBLY AND PRE-COMMISSIONING 1
3.1 MAIN INLET VALVES 1
3.1.1 MIV Closing in Dead Water 1
3.2 TURBINES 2
3.2.1 Opening and Closing Time of Wicket Gate in Dry Condition2
3.2.2 Closing Tendency of Wicket Gate 3
3.3 TURBINE GOVERNORS 4
3.3.1 Oil Accumulator Volume Test 4
3.3.2 Governor Dead Band/Sensitivity Test (at Factory) 5
3.3.3 Governor Dead Time Test (at Factory) 6
3.4 GENERATORS 7
3.4.1 Stator Winding HV Testing 7
3.4.2 Stator Winding Insulation Resistance Measurement 7
3.4.3 Stator Winding Ohmic Resistance Measurement 8
3.4.4 Inside Diameter Stator Wound 8
3.4.5 Rotor Winding – Ohmic Resistance Measurement 9
3.4.6 Rotor Winding AC Voltage Test 9
3.4.7 Rotor Winding – Insulation Resistance Measurement 9
3.4.8 Diameter Rotor Complete 9
3.5 EXCITATION SYSTEM 10
3.6 CO2 GENERATOR FIRE EXTINGUISHING SYSTEM 10
3.7 UNIT TRANSFORMERS 10
3.7.1 Insulation Resistance 10
3.7.2 Ratio Test 11
3.7.3 Magnetizing Current Test 11
3.7.4 Short Circuit Test 11
3.7.5 Winding Resistance 12
3.8 110 BATTERIES 13
3.8.1 Power House Discharge Test 10 Hours 110 A 13
3.8.2 Headworks Discharge Test 10 Hours 54.6 A13
3.9 132 & 33 KV TRANSMISSION LINES 14
3.9.1 Measurement Insulation Resistance 132 kV Line 14
3.9.2 Measurement Insulation Resistance 33 kV Line 14
3.9.3 Attenuation Measurement OPGW 132 kV Line 15
3.9.4 Attenuation Measurement ADSS 33 kV Line 16
3.9.5 Contact Resistance Measurement of ACSR Conductor Joint at TW1 of 132 kV
Line 17
4 RUNNING TESTS 18
FICHTNER JV I
Middle Marsyangdi Hydroelectric Project
Project Completion Report - Volume 4C
Nepal Electricity Authority – NEA
Project Commissioning Report
FICHTNER JV II
Middle Marsyangdi Hydroelectric Project
Project Completion Report - Volume 4C
Nepal Electricity Authority – NEA
Project Commissioning Report
6 COMMISSIONING SCHEDULE 46
6.1 Basic Commissioning Schedule Dated 20.11.2009 46
FICHTNER JV III
Middle Marsyangdi Hydroelectric Project
Project Completion Report - Volume 4C
Nepal Electricity Authority – NEA
Project Commissioning Report
1 INTRODUCTION
2 REFERENCE DOCUMENTS
Most of the information included in this document has been extracted from the following Test
Protocols prepared by the Manufacturers. The following listing gives the details:
Alstom O&M Manuals (Lot E):
3.2 TURBINES
3.4 GENERATORS
UNIT 1 UNIT 1
Phase Phase Phas Phase
Phase U Phase V
W U eV W
12.05.20 12.06.20 12.08.2 28.07.2 28.06 28.06.
Date of test
08 08 008 008 .2007 2007
[kVd
Test voltage 0.5 0.5 0.5 0.5 0.5 0.5
c]
Winding temperature 27.5 27.5 27.5 31.5 31.5 32 [°C]
Ambient air temperature 26 28 28 29 29 29 [°C]
Relative humidity 72 71 74 67 67 66 [%]
Insulation after 1 min [MΩ
(R1)
138 172 164 368 375 361
]
Insulation after 10 min [MΩ
(R10)
152 180 167 423 435 419
]
Pol. Index(IP=R 10R1) 1.10 1.05 1.02 1.15 1.16 1.16
Unit 1 Unit 2
31.666
3 phases winding temperature (average temp.) 27.5 [°C] [°C]
7
OHMIC
RESISTANCE UNIT 1 UNIT 2
PHASE U
Test 1 Test 2 Test 3 Average Test 1 Test 2 Test 3 Average
Applied
82.25 82.28 82.28 82.99 83.01 83.01 [mVdc]
voltage
Applied
10.000 10.000 10.000 10.000 10.000 10.000 [Adc]
current
Ohmic
8.225 8.228 8.228 8.227 8.299 8.301 8.301 8.3 [mΩ]
resistance
Ohmic
resistance 7.99 7.99291 7.99291 7.99194 7.94088 7.9428 7.94216 7.94216 [mΩ]
(at 20°C)
OHMIC RESISTANCE Test 1 Test 2 Test 3 Average Test 1 Test 2 Test 3 Average
PHASE V
Applied
2.20 82.21 82.22 83.11 83.1 83.13 [mVdc]
voltage
Applied
10.000 10.000 10.000 10.000 10.000 10.000 [Adc]
current
Ohmic 8.22 8.221 8.222 8.221 8.311 8.31 8.313 8.311 [mΩ]
resistance
Ohmic
resistance 7.98514 7.98611 7.98709 7.98611 7.95236 7.95141 7.95428 7.95268 [mΩ]
(at 20°C)
OHMIC RESISTANCE Test 1 Test 2 Test 3 Average Test 1 Test 2 Test 3 Average
PHASE W
Applied
82.21 82.23 82.28 83.13 83.14 83.15 [mVdc]
voltage
Applied
10.000 10.000 10.000 10.000 10.000 10.000 [Adc]
current
Ohmic
8.221 8.223 8.226 8.223 8.313 8.314 8.315 8.314 [mΩ]
resistance
Ohmic
resistance 7.98611 7.98806 7.99097 7.98838 7.95428 7.95523 7.95619 7.95523 [mΩ]
(at 20°C)
average winding
27.5 [°C] average winding temperature 31.5 [°C]
temperature
ambient temperature [°C] ambient temperature
20 29 [°C]
UNIT 1 UNIT 2
Average Average
Injected current 10.0 10.0 10.0 10.0 10.0 10.0 [Adc]
Voltage 0.5762 0.5763 0.57627 0.5866 0.5869 0.58677 [Vdc]
Ohmic resistance 0.05762 0.05763 0.06763 0.05866 0.05869 0.05868 [Ω]
Ohmic resistance (at 0.05599 0.056 0.066 0.05654 0.05657 0.05655 [Ω]
20°C)
UNIT 1 UNIT 2
Rotor winding temp. 27.4 29.6 [°C] (average all RTDs)
Ambient temp. 28 28 [°C}
GENERATOR 1 GENERATOR 2
Date Measured 12.08.2008 14.11.2008 28.07.2008 18.11.2008
Test Voltage (kVdc) 0.5 0.5 0.5 0.5
Winding Temperature (°C) 27.4 31.5 29.6 31
Ambient Temperature (°C) 26 29 29 31
Relative Humidity (%) 27 39 66 38
Insulation Resistance after 1 min. (R1) MΩ 1.9 3000 43.6 2500
Insulation resistance after 10 min. (R10) MΩ 2.4 4000 51.9 3500
Pol. Index (IP=R10/R1) 1.26 1.33 1.19 1.4
UNIT 1
Deviation to
Position NDT DE AVERAGE
3610,00mm
Pole 1-10 3610.98 3609.90 3610.44 +0.44
Pole 2-11 3611.03 3609.93 3610.48 +0.48
Pole 3-12 3610.73 3610.02 3610.38 +0.38
Pole 4-13 3610.78 3609.98 3610.38 +0.38
Pole 5-14 3610.80 3610.00 3610.40 +0.40
Pole 6-15 3610.75 3609.88 3610.32 +0.32
Pole 7-16 3610.78 3609.98 3610.38 +0.38
Pole 8-17 3611.00 3609.90 3610.45 +0.45
Pole 9-18 3610.95 3609.92 3610.44 +0.44
Total Average 3610.41 +0.41
Average Air Gap: 19.98 mm (19.80 - 20.70) 8 measurements
UNIT 2
Deviation to
Position NDT DE AVERAGE
3610,00mm
Pole 1-10 3609.37 3,608.85 3609.11 -0.89
Pole 2-11 3609.15 3609.14 3609.15 -0.85
Pole 3-12 3609.23 3608.60 3608.92 -1.08
Pole 4-13 3609.43 3608.80 3609.12 -0.88
Pole 5-14 3609.35 3608.80 3609.08 -0.92
Main IR Value
Transf. SI. No Temperature
winding 15 sec 60 Sec 600 sec PI
HV/E 8.27 27.9 117 4.19 32°C
B-29814 unit 1 HV/LV 7.92 20.8 164 7.89 32°C
LV/E 7.44 50.3 69.9 1.38 32°C
HV/E 9.34 36.6 77.4 2.11 32°C
B-29816 unit 1 HV/LV 5.21 37.9 119 3.13 32°C
LV/E 5.42 25.8 66.6 2.58 32°C
HV/E 5.31 13.4 42.4 3.16 32°C
B-29820 unit 1 HV/LV 4.89 19.7 72.7 3.69 32°C
LV/E 5.08 14.4 40.9 2.84 32°C
HV/E 17.3 64.4 128 1.98 32°C
B-29815 unit 2 HV/LV 10.6 48.9 185 3.78 32°C
LV/E 6.84 51.3 115 2.24 32°C
HV/E 8.15 24.1 67.8 2.81 32°C
B-29818 unit 2 HV/LV 9.91 48.1 128 2.66 32°C
LV/E 6.77 28.9 76.5 2.64 32°C
HV/E 6.01 19.6 56.8 2.89 32°C
B-29817 unit 2 HV/LV 5.66 36.7 104 2.83 32°C
LV/E 5.83 22.8 50.7 2.22 32°C
HV/E 9.21 14.72 37.8 2.56 32°C
B-29819 Spare HV/LV 7.02 13.9 49.0 3.52 32°C
LV/E 4.65 10.5 27.6 2.62 32°C
Transformer SI.
Tap No. HV Side in ohms LV Side in milli ohms
No
1 0.86
2 0.83
B-29814 unit 1 3 0.81 11.52
4 0.78
5 0.76
1 0.86
2 0.83
B-29816 unit 1 3 0.81 11.53
4 0.78
5 0.76
1 0.87
2 0.84
B-29820 unit 1 3 0.81 11.59
4 0.79
5 0.77
1 0.86
2 0.83
B-29815 unit 2 3 0.81 11.46
4 0.78
5 0.76
1 0.86
2 0.84
B-29818 unit 2 3 0.81 11.58
4 0.79
5 0.77
1 0.86
2 0.84
B-29817 unit 2 3 0.81 11.63
4 0.79
5 0.76
1 0.86
2 0.84
B-29819 Spare 3 0.81 11.65
4 0.79
5 0.77
3.9.5 Contact Resistance Measurement of ACSR Conductor Joint at TW1 of 132 kV Line
4 RUNNING TESTS
4.1 MAIN INLET VALVE
Tests before increasing the size Tests after increasing the size of
of counterweights counterweights
MIV 1 At: 10, 20, 30 and 41.5 MW At: 10 MW
MIV 2 At: 10, 20 and 30 MW At: 10, 20, 30 and 40 MW
4.2 TURBINE
Unit 1 Unit 2
Overspeed Devices Test Operated Max. Final Test Operated Max. Final
setting at (%) speed setting setting at (%) speed setting
(%) rise (%) (%) (%) rise (%) (%)
Mech. (hydraulic) 165 167 171.4 165
Electrical No.1 105 105 - 167
(digital governor)
Electrical No.2 115 114 -- 165
(speed relay )
4.2.4 Heat Run at Generator Nominal Load – Bearing and Cooling water Temperatures
4.2.5 Heat Run at Generator Nominal Load – Bearing Temperatures and Levels
4.4 GENERATOR
4.4.1 Balancing
BALANCING OF GENERATOR
UNIT 1 UNIT 2
Measurements
speed Vn Vn Vn Vn Vn [min-1]
active power -- 30 -- 4 25 [MW]
reactive power -- 0.8 -- 4.8 1.8 [Mvar]
stator voltage Un 10.8 Un 10.8 10.8 [kV]
stator current -- 1.65 -- 0.34 1.3 [kA]
field current 730 939 732 818 874 [A]
NDE Side voltage to earth 0 0 0 0 0 [Vdc]
10.9 11.3 10 10 11.7 [Vac rms]
34 31.6 30 30 34.5 [Vac pp]
main frequency 150 150 149 149 150 [Hz]
PF 0.9
stator S 38.90 37.43 38.42 42.37 [MVA]
P 35.46 33.80 34.66 38.50 [MW]
Q 15.94 16.07 16.57 17.65 [Mvar]
PF 0.91 0.90 0.90 0.90
U 11.45 11.46 11.02 11.02 [kV]
I 1959 1887 2013 2210 [A]
Hz 49.92 49.00 49.90 49.65 [Hz]
Uf 95.10 95.90 88.90 105.00 [V]
rotor
1328.0 1318.0 1318.0 1386.0
If [A]
0 0 0 0
PF 1.0
stator S 9.98 19.83 29.42 40.99 42.25 43.01 3.95 9.94 10.00 19.94 35.27 [MVA]
P 9.84 19.54 29.37 40.78 40.8 42.85 3.93 9.86 9.98 19.91 35.14 [MW]
Q -0.9 -1.8 7.85 4.1 11 6.5 0.42 -1.27 -0.62 -1.02 3.03 [Mvar]
PF 0.99 0.99 1.00 1.00 1.00
U 10.78 10.75 11.20 10.55 10.67 10.65 10.67 10.85 10.75 [kV]
I 2199 2326 0.21 0.54 0.54 1.06 1.89 [kA]
Hz 49.70 49.80 49.60 49.77 50.30 [Hz]
Uf 45 49 81.7 72.3 99.3 54.4 .. .. .. .. 67.9 [V]
rotor
If 657.4 732 840 1100 1285 1094 688 683 786.8 952 [A]
UNIT 1 UNIT 2
Generator short-
TEST n0:1 n0 1 n0 1
circuited
At rated load
n0:2 n02 n02
0 0 0
n 3: Generator overload n3 n3
date 20.01. 03.02.09 05.12.08 14.01.09 14.02.09
duration 3 5 2 4 4 [h]
ELECTRICAL
stator S 0 38.5 0 35 42.2 [MVA]
DATA
P 0 35 0 35 38.8 [MW]
Q 0 16 0 3 16.8 [Mvar]
cosΦ 0 0.9 NA 0.99 0.92
U 0 11.4 0 10.8 11.1 [kv]
I 2.05 1.95 2.05 1.86 2.2 [kA]
rotor Uf 43.6 96 46.3 70 105 [V]
if 666 1309 732 1000 1364 [A]
stator
TEMPERATURE average 53 70.5 53.1 62 82.3 [°C]
winding
max. 55 74 54 64 84 [°C]
stator core average 33 55 33 47.3 60.5 [°C]
max. 33 55 33 47.3 61 [°C]
rotor winding 36.4 74 27 50 84.9 [°C]
cooling air air inlet average 17 22.5 18 18.8 25.5 [°C]
max. 17 23 19 20.3 26 [°C]
air
average 31.2 45 30 37.2 49 [°C]
outlet
max. 32.2 45 30 37.3 49 [°C]
cooling water inlet 12 14 12.4 10.8 12 [°C]
cooling water outlet 15 21 16.5 17.1 22 [°C]
NDE bearing guide segment 40.4 41.2 52.4 44.6 44.8 [°C]
thrust segment 61.4 65.6 66 65 65.8 [°C]
oil 35.9 37 42 36.4 37 [°C]
guide bearing oil 36.4 38 42 36.6 38 [°C]
oil inlet 30 31 35 32.1 33 [°C]
oil outlet 36 38 43 37.8 39 [°C]
cooling water outlet 16 21 16.5 17.1 [°C]
DE bearing guide segment 46.7 45.8 53 51.9 50.4 [°C]
oil 37.9 39 41 43.4 44 [°C]
guide bearing oil 38.1 39 41 43.5 44 [°C]
oil inlet
35 36 37 37.3 38 [°C]
oil outlet 40 41 43 45.2 46 [°C]
cooling water outlet 16 21 16.5 17.1 [°C]
TEMPERATURE stator winding max.
38 48 35 45.2 58.5 [K]
RISE
stator core max.
(above cold air) 16 32.5 14 28.5 36.5 [K]
rotor winding
19.4 51.6 11 31.2 59.4 [K]
cooling air
15.2 22.5 11 18.5 23.5 [K]
air cooler cooling water 12 14 [K]
4.5 EXCITATION
4.5.1 Automatic Voltage Build-up Curve with the Automatic Channel (unit 1)
4.5.2 De-excitation Curve with the Automatic Channel by Field Breaker Opening (unit 1)
4.5.3 De-excitation Curve by Protection Trip with the Automatic Channel (unit 1)
4.5.4 +10% Stator Voltage Step with the Automatic Channel in Operation (unit 1)
4.5.5 Power System Stabilizer Tuning at rated Active Power without/with PSS (unit 2)
LOAD % 100 75 50
GENERATOR
DATA
APPARENT POWER MVA 39.00 29.25 19.50
ACTIVE POWER MW 35.10 26.33 17.55
REACTIVE
MVAr 17.00 12.74 8.50
POWER
POWER FACTOR
0.90 0.90 0.90
(overexcited)
ARMATURE VOLTAGE kV 11.00 11.00 11.00
ARMATURE CURRENT A 2046.97 1535.23 1023.48
ROTOR
V 88.62 76.45 65.65
VOLTAGE
ROTOR
A 1296.00 1118 960
CURRENT
MEASURED LOSSES
WINDAGE LOSSES P (windage)* kW 92.45 92.45 92.45
LOWER GUIDE BEARING LOSSES kW 10.31 10.31 10.31
COMBINED THRUST - GUIDE BEARING
kW 54.40 54.40 54.40
LOSSES
TOTAL MECHANICAL BRUSH LOSSES PB mech kW 1.30 1.30 1.30
TOTAL ELECTRICAL BRUSH LOSSES PB EL kW 5.18 4.47 3.84
ARMATURE COPPER LOSSES PCU 75* kW 121.48 68.34 30.37
ARMATURE STRAY LOSSES PSL* kW 62.71 35.27 15.68
CORE LOSSES PFE* kW 119.58 119.58 119.58
ROTOR LOSSES Pt75* kW 114.86 85.47 63.02
EXCITATION LOSSES PEX (Excit. Transformer and
kW 10.00 8.00 6.00
converters)
TOTAL MEASURED
kW 592.27 479.60 396.95
LOSSES
TEST DATA
GENERATOR ACTIVE kW 35100.00 26325.00 17550.00
POWER
GENERATOR ACTIVE INPUT POWER kW 35692.27 26804.60 17946.95
MEASURED EFFICIENCY % 98.34 98.21 97.79
GUARANTEED VALUES
GUARANTEED EFFICIENCY
% 98.420 98.320 97.950
(CONTRACT)
TOTAL GUARANTEED LOSSES kW 563.483 449.817 367.305
TOTAL GUARANTEED LOSSES (Maximum)* kW 619.831 494.799 404.035
DIFFERENCE TOTAL GUARANTEED kW 27.56 15.20 7.080
LOSSES - TOTAL MEASURED
LOSSES
* Max. Losses with the tolerance of - 10% x (1-η) according IEC 60034-1 Sect. 11 Standard
6 COMMISSIONING SCHEDULE
6.1 BASIC COMMISSIONING SCHEDULE DATED 20.11.2009
The wet commissioning of MMHEP was carried out based on the below schedule