1 Characteristics... .. .. .. ....... .. .. ... .. .. .. .. ... .. .. .. .. ... .. .. .. .. ... .. .. .. .. . 1


2 Stipulation.. .... .. .. .. .
.. .... .. .. ... .. .. .. .. .
.. .. .. .. .. .
.. .. .. .. .. .
.. .. .. .. 1
3 Technical Data.. .. .. .. ........ .. .. ... .. .. .. .. ... .. .. .. .. ... .. .. .. .. ... .. ... 2
4 Structure and installation.. ...... .. .. ... .. .. .. .. ... .. .. .. .. ... .. .. .. .. ... ... 3
4.1 outside drawing.. .. .. ...... .. .. ... .. .. .. .. ... .. .. .. .. ... .. .. .. .. ... .. .. .. .. 3
4.2 inside construction drawing.. .. .. ... .. .. .. .. ... .. .. .. .. ... .. .. .. .. ... .. .. .. .. 4
4.3 installation dimension drawing.. .. .... .. .. .. .. ... .. .. .. .. ... .. .. .. .. ... .. .. .. ... 6
4.4 external wiring requirement.. .. .. .. ... .. .. .. .. ... .. .. .. .. ... .. .. .. .. ... .. .. .. .. 6
4.5 external terminal layout drawing. .. .. .. .. .. .. ... .. .. .. .. ... .. .. .. .. ... .. .. .. .. 6
5 From installation to operation. .... .. .. ... .. .. .. .. ... .. .. .. .. ... .. .. .. .. ... .. .. .. .. 7
6 Basic functions... .. .. ... ...... .. .. ... .. .. .. ... .. .. .. .. ... .. .. .. .. ... .. .. ... 7
6.1 start up.. .. .... .. .. ....... .. .. ... .. .. .. .. ... .. .. .. .. ... .. .. .. .. ... .. .. ... 7
6.2 register external device. ...... .. .. ... .. .. .. ... .. .. .. .. ... .. .. .. .. ... .. .. .. .. .. 7
6.3 fire alarm.. .. .. .. .. ....... .. .. ... .. .. .. .. ... .. .. .. .. ... .. .. .. .. ... .. .. .. 8
6.4 monitoring information.. .... .. .. ... .. .. .. .. ... .. .. .. .. ... .. .. .. .. ... .. .. .. .. 9
6.5 associate operation information... .. .. .. .. .. ... .. .. .. .. ... .. .. .. .. ..... .... .. ... 9
6.6 fault alarm..... .... ....... ..... .. .. .. .. .. .
.. .. .. .. .. .
.. .. .. .. .. .
.. .. 9
6.6.1 main power supply fault. .... .. .. .. .. .. ... .. .. .. .. ... .. .. .. .. ... .. .. .. .. .. 9
6.6.2 back-up power supply fault. ... .. .. .. .. ... .. .. .. .. ... .. .. .. .. ... .. .. .. .. ... 9
7 Menu operation function.. ...... .... ... .. .. .. .. ... .. .. .. .. ... .. .. .. .. ... .. .. .. .. 9
7.1 device information.. ...... ...... ... .. .. .. .. ... .. .. .. .. ... .. .. .. .. ... .. .. .. .. 10
7.2 register information... ...... .... ... .. .. .. .. ... .. .. .. .. ... .. .. .. .. ... .. .. .. ... 11
7.3 event record.. .. .... ...... ...... . .. .. .. .. ... .. .. .. .. ... .. .. .. .. ...... 12
7.4 adjust time.. .... .... ...... ..... .. .. .. .. .. ... .. .. .. .. ... .. .. .. .. ... .. 12
7.5 associated setup..... ... .. .. .. ..... .. .. .. ..... .. .. .. ..... .. .. .. .. 12
7.5.1“or”1 logic setup. .. .. .. .. ..... .. .. .. ..... .. .. .. ..... .. .. .. ..... 13
7.5.2“or”2 logic setup. .. .. .. .. ..... .. .. .. ..... .. .. .. ..... .. .. .. ..... 13
7.5.3“and” logic setup.. .. .. .. .
.. .. .. .. .. .
.. .. .. .. .. .
.. .. .. .. .. .
.. .. ... 13
7.5.4 pulse mode module . .. .. .. .... .. .. .. ..... .. .. .. ..... .. .. .. ..... .. ....... 14
7.6 system setup.. ...... ... .. .. .. ..... .. .. .. ..... .. .. .. ..... .. .. .. ..... ... 14
7.7 exit.... ..... ......... .. .. .. .. ..... .. .. .. ..... .. .. .. ..... .. .. .. ..... .. ..... 14
8 System self-check. ........ .. .. .. .. .
.. .. .. .. .. .
.. .. .. .. .. .
.. .. .. .. .. .
.. .. ... 15
9 Lock key/Unlock.. ........ .. .. .. .. ..... .. .. .. ..... .. .. .. ..... .. .. .. ..... .. 15
10 Automatic/Manual switch.. .. .. .. .. ..... .. .. .. ..... .. .. .. ..... .. .. .. ..... .. ....... 15
11 Associated control. ........ .. .. .. .. ..... .. .. .. ..... .. .. .. ..... .. .. .. ..... .. 16
12 Repair and Maintenance. .... .. .. .. ... .... .. .. ... .... .. .. ... .... .. .. ... ... 16
13 Notice. .. ... .......... ... .. .. .. ..... .. .. .. ..... .. .. .. ..... .. .. .. ... 17
14 Our service. ... ........ ... .. .. .. ..... .. .. .. ..... .. .. .. ..... .. .. .. ..... 17
JB-QB-5Si fire alarm control panel (associate operation type) operation manual

Hello!
Welcome to Brightsky World!Connecting newest technology 5iserise fire alarm system that will
Exceed your imagination:directly and plenty figure interface you will be the first time to feel our
products’ reliability,The speed of fire alarm system is quicker than before, Brightsky Electronic
Co., Ltd quests system reliability and accurately that will be embodied completely.

This customer manual will let you know the super function of this kind of machine step by step.

Characteristics
— Graphic menu operation, new design
— Black box record function
— Detector condition display
— 250 intelligent bus device points capacity
— Alarm address information second-conversion accurate locating fire address(can input in the
form of pre-programming at desk computer or laptop)
— All fire protection linkage operation relationship on-site programming
— Standard 485 interface, LAN network and remote communication function

Our Stipulations
In below descriptions:

— all display letter or icon is button,For example: this is Down button , 复位 this

is Reset button.
— Bus equipments which are including heat detectors, smoke detectors, manual call points,
signal input module etc fire alarm touching equipments and Long-range control module etc
Linkage control equipments.
— According to habit or description’s requirements,It will be possible to use“Detector”letter
can take place smoke detector, heat detector, manual call point, signal input module etc fire
alarm touching equipments。
— In the system, from No.001 to No.250, it is standard device address (detector, remote control
module, etc), from No.251 to No.256, it is six multi-line control modules.

Wuxi Brightsky Electronic Co., Ltd


1
JB-QB-5Si fire alarm control panel (associate operation type) operation manual

Technical Data


Main Power: AC 220V (+10%~-15%) ,50HZ
Back-up power supply: DC 24V,2.3AH(built in)
Work consumption: Monitor state:≤2.4W;Alarm state:≤10W
Basic monitoring capacity: 5i series addressable device 250 pieces
Direct external control contact: 6 pairs
Polling cycle: ≤10 second(when Condition abnormity, single point
continues to poll)
Signal transportation distance: ≤1500 meters.
Wiring method: 1、 5i series detectors——2-wire bus, non-polarity;
2、 5i series modules——2-wire bus, polarity(T+——anode,
T-——cathode);
Wire application: RVS-2×1.5mm2 two color plastic soft wire.
Outside control touch points: KA1,KA2 first time alarm, then closed immediately.
YA1,YA2 first time alarm under nobody controlled machine
delay 2 minutes closed.
Outside control touch points capacity: DC 30V,2A.
Operation Environment Temperature: 0℃~55℃
Relatively humidity: ≤95%
External dimension: 440×340×82(H×W×T)mm3
Installation form: Wall mounted type
Weight: About12Kg
Black box record data: Be able to save 500 records(including open, close, alarm, fault
and linkage information)
Linkage programming amount: 150 items(or one, or two, with logic 50 items)
Room number conversion capacity: 250 pieces
Room number conversion 30 pieces English characters
maximum allowable characters
numbers:

2 无锡蓝天电子有限公司
JB-QB-5Si fire alarm control panel (associate operation type) operation manual

Wuxi Brightsky Electronic Co., Ltd


5
JB-QB-5Si fire alarm control panel (associate operation type) operation manual

Fire alarm controller should be installed in a room or place where can be controlled by man,at the
same time please install fire alarm controller on the wall. Normally fire alarm controller’s bottom
is far away from the ground 1.5 meters,It will leave more than 0.5 meter distance in two sides. So
that it will be easy operate and maintenance.

This is installation dimension drawing:

6 无锡蓝天电子有限公司
JB-QB-5Si fire alarm control panel (associate operation type) operation manual
Meanwhile,According to position array figures, in order to check whether wiring
is right or not,Each of hardware whether is solid or not.
4、 Start up.
5、 According to fire code and project linkage operation relationship requirement,
edit linkage operation relationship list based on “linkage operation
programming”section.
6、 Re open the panel, according to “register external device” section, register
external devices.

Basic functions
Start
First time start please press control panel 复位 button,Meanwhile please press main/ reserved
power switch,After controller initialized, indicator and sounder check itself,Then all devices of
bus are loading(at the moment let loose 复位 ),It takes about 2 minutes. Then system comes to
normally monitor and control state,Power of indicate in controller flashes. Attention:Each time
restart system linkage is manually state,at the moment automatic/manually indicator
always flashes.。

类型设定
Fire Alarm Panel
设备号: 010号至011号
2004/10/23 10:28
类 型: 称重模块

Register outside devices


Register outside devices include to register detectors, modules etc connect with bus devices in the
return circuit. Register operating, after start the controller,Press controller power switch,when
controller panel indicator flashes. Press 复位 register,after finish to register, then indicate to have
registered bus devices number and address code. Press or You can check the details’
listing,Press 复位 return to monitor and control state.

参数测试 004号
register :device…
参考值 026
当前值008: 026
类 型: 烟感

Fire alarm
Under normally monitor and control state, the controller patrols registered each
of detectors,monitor each of detectors current smoke consistency or temperature
value,then using the data to calculate and recognize by formula. Using the data
according to formula calculate and recognize. If it is be fit for fire alarm
condition,it can be put into fire alarm state. At the moment,the controller sounds

8 无锡蓝天电子有限公司
JB-QB-5Si fire alarm control panel (associate operation type) operation manual

the alarm,the controller panel’s fire alarm indicator flashes,the displayer


indicates alarm address, number etc information,printer(when you install this
printer)can print alarm address, alarm time,Meanwhile the outside controller
position KA1、KA2 closed,YA1,YA2 begin to delay,If nobody controls controller
(reduce sounder or reduce)this position closed. If linkage position is in the
automatic state,the controller is according to be the first time addressable linkage
logic relation which can set out command in order to start corresponding long-range
control module,so that start or close outside devices.(For example fire pump)。
System uses different pages approach among fire alarm, linkage and default
information ,If there are two or many kinds of alarm information exist at the same
time , Please press or switch to another fire alarm type page,
Press or you can check the up or down information.。
Therein:
fire alarm page displays fire detector, manual call point, etc alarm information
monitoring page displays feedback signal from signal input module and remote control
module.
Linkage operation page displays activation signal of remote control module.
All fault information is displayed in fault page besides power supply and back-up
power supply fault information.

Fire:03 Associate:01
参数测试
Fault:01 Monitor:02 004号
* * * * * *
Fire 参考值
01/03 002 : 026
smoke detector
当前值: 026
2004/10/23 10:26
类 型: 烟感
Memo:room1

In above figure:
“Fire:03”express there are three fire alarm signals for the time being.
“Fault:01”express there is one fault signal for the time being.
“Associate:01”express there is one linkage operation for the time being.
“Monitor:02”express there are two monitoring feedback for the time being.
“Fire 01/03 002”shows that it is first page of fire alarm page. Alarm number is
No.002 device.
“smoke detector”express No.002 is one smoke detector
“2004/10/23 10:26”express it is the alarm time.
“memo:room1”express this detector is installed in “room1”.
Fire alarm display will not disappear by itself. We should use manually reset to
disarm detector alarm condition, then the page will come back to front page.

Monitoring information
All information from signal input module alarm information and remote control
module’s feedback information will be displayed in this page. This page displayed
information format is almost same as in “fire alarm”section. So it is not shown

Wuxi Brightsky Electronic Co., Ltd


9
JB-QB-5Si fire alarm control panel (associate operation type) operation manual
once again here. After the monitoring signal disappears, the relevant display will
also disappear, which is one important different point from fire alarm display.

Associate operation information


Remote control module activated information is shown here. This page displayed
information format is almost same as the one in “fire alarm” section. So we do
not repeat it here. After the module is closed, the display will disappear.

Fault Alarm
In order to ensure fire alarm control system can be longer normally running,The
controller must monitor circuit, detector, long-range control module etc bus
equipment and power, accumulator etc devices,that means there are alarm and default
function. When there has default and alarm,It will set out default alarm sound,
the indicator will flash in the controller ,the monitor displays default type。
If detectors or long-range control module default,The printer(when you set up this
printer)print default address, alarm time,the monitor will display alarm address,
number etc information. At the moment,the operator should obviate the default,
After obviated default ,the controller can reduce automatically,change to normally
Alarm state. This page displayed information format is almost same s the one in “fire
alarm” section. So we do not repeat it here.

Main power fault


Main Power fault is AC 220V Power voltage is not lower than 187V(Including no
electric),the controller indicates main power abort,Main power abort indicator
flashes. At the moment,the controller must have reserved power,otherwise, the
controller is due to no electric so that the controller stops working.

Back-up power supply fault


Reserved power abort tat means reserved power in the controller is lower than
19.2V,reserved power opened wire, reserved power is no charge,the controller
indicates reserved power abort,reserved power abort indicator flashes.

Menu operation function


Under monitor state,according to menu button display input password:

Menu password
进入菜单操作:

10 无锡蓝天电子有限公司
JB-QB-5Si fire alarm control panel (associate operation type) operation manual

After inputted password is correct, enter main menu, otherwise, be back to monitor
state.
There are seven menu options in main menu,these include “Device information”、
“Register information” 、“Event record” 、
“Adjust time” 、“Associated setup”、 “System
setup”、“Exit”。

Main
功能菜单 Menu

参数测试
Device information

According to or press to your need information,According to enter


function listing.

Device information
“Device information” function is look at each device’s detailed information,
which include registered analogue value, current analogue value (smoke value and
temperature value), device type, status (whether isolated or not) and remark
information.

Device No. : 001


参数测试
Base Value : 028 004号
Current Value: 028/003
参考值
Type: smoke : 026
detector
Status: normal
当前值: 026
Memo: room1
类 型: 烟感

“Device No. :001”express current querying No.001 device;


“Base Value: 028”express this device registered value is 028;
“Current Value: 028/003”express this device current smoke value 028,heat value
is 003;
“Type: smoke detector”express this device type is smoke detector;
“Status: normal”express this device currently works normally. If in “isolated”,it
expresses this device has been isolated and it cannot alarm。
“Memo:room1” express this device’s annotation, that is to say, this device’s installation
location is in “room1”。
Push down or plus one or minus one to change current device number;
Push down or plus ten or minus ten to change current device number;
Push down 自检 (self-test) to change device condition;
Push down 消音 (silence) to return;
Push down menu key (middle key in below small box) and one sub-menu will appear.
This sub-menu has three items:“edit memo”、 “copy memo”、“return” 。

Wuxi Brightsky Electronic Co., Ltd


11
JB-QB-5Si fire alarm control panel (associate operation type) operation manual

参数测试
1:edit memo
004号
2:copy memo
参考值: 026
0:return
当前值: 026
类 型: 烟感

push down corresponding digital key to enter relevant function。

“Edit Memo”is one text edition interface. It’s function mainly is input device
installation location, that is remark, in order to show its accurate alarm lication.

Memo edit 联动控制 No.001


Hello world
模块号:000
ABC 001 012
按消音打开,自检关闭

push down 自检 (self-test) switch input method;


push down 消音 (silence) delete current cursor location character;
push down menu key( middle key in below small box) to store modification and return。

“Copy Memo” is copy current device remark to other device。

Copy No.001 to
或1逻辑控制 00条

控制源: 001号至020号
From: 002 to 006

控制对象: 120号至123号

push down 自检 (self-test)to start copy;


push down 消音 (silence) to return。

Register information
“Register information” function is check registered external device numbers。

Device Total:120
登录查阅 总数:100
001 002 003 004 005
006
001 007
002 008
003 009
004 010
005
011 012 013 014 015
006
016
007
017
008
018
009
019
010
020
011
021 012
022 013
023 014
024 015
025

Press or check details’ listing,Press 复位 return main menu。

Event Record

12 无锡蓝天电子有限公司
JB-QB-5Si fire alarm control panel (associate operation type) operation manual

“Event Record” is query historic alarm records, which include: Fire、Fault、


Monitor、Associate、Power-On、Power-Off、Reset、AC Fault、DC Fault、 Manual Status、
Auto Status, etc.

Event Record Total:500 406


001
001 故障 017号
manual status
2002/02/24 10:32:20
Time:2004/10/23 10:28
002 开机
002 fire 005
Type:smoke detector
2002/02/24
Time:2004/10/22 10:20:10
10:28

The latest record will be first shown.


Push down or to query above or next record. Push down 消音 (silence) to
return main menu.
Push down 1 to print(when ancillary device is installed) events record.

Adjust Time
“Adjust Time” is set up date and time in the system。

时间设置Time
Adjust

2002/04/22 10:53:21
2004/10/22

Push down or to move cursor;


Push down digital key to change time value;
Push down 自检 (self-test) to store date and time modification and start to use new
date and time.
Push down 消音 (silence) to give up modification and directly return main menu.

Associated Setup
“Associated Setup” is automatic associated/linkage operation after the fire alarm
happens. The control panel will make a judge from alarm information and start or
close relevant devices based on linkage operation programmed logic relationship ( in
manual operation condition, all linkage operation dependency relationship is not
valid). It has five menu items, which include :“OR1 Logic Setup”、“OR2 Logic Setup” 、
“AND Logic Setup”、“Pulse Mode Setup”and “Exit”

Associated operation
1:OR1 Logic setup
2:OR2 Logic setup
3:AND Logic setup
4:pluse mode setup
0:exit

Push down corresponding digital key to enter relevant function.

OR1 Logic Setup


Wuxi Brightsky Electronic Co., Ltd
13
JB-QB-5Si fire alarm control panel (associate operation type) operation manual
“OR1 Logic Setup”: if any one detector in one detectors group alarms, it will
initiate or close corresponding device.

OR1 logic setup 000


或1逻辑控制 00条
Activate source:
控制源:From: 001号至020号
001 to 003
Activate object:
控制对象:
From: 120号至123号
011 to 012

now we use above chart example to explain all data meaning in “OR1 Logic Setup”
programming. That is: set up any one detector (from No.001 to No.003) to alarm within
“Activate source”range,it will activate remote control modules(from No.011 to
No.012) within “Activate object”date range. Top right corner “000”express current
one is No.00 item (one item per page).
Push down digital key to edit various data items. Push down or to move
cursor,push down or to edit or query above or next item(page) data. After
the setup is completed, input end item, that is, set up this page’s first data
item as “ 0 ”。 Push down 消音 (silence) to return associated/linkage operation
programming menu.

OR2 Logic Setup


“OR2 Logic Setup”: if any two detectors alarm in one detectors group, it will start
or close relevant devices.
Chart example and setup method is referred to “OR1 Logic Setup”

AND Logic Setup


“AND Logic Setup”: if any one detector in one group and any one detector in another
group alarm simultaneously, it will start or close relevant devices.

AND logic setup 000


或1逻辑控制
Activate source: 00条
From: 001 to 003
控制源:From: 001号至020号
006 to 009
Activate object:
控制对象: From: 120号至123号
015 to 015

Now we use above chart example to explain various data meaning in AND logic
programming, that is: any one detector (from No.001 to No.003) set up within
“Activate source1”data item range and any one detector (from No.006 to No.009)
set up within “Activate source2” data item range alarm simultaneously, it will
activate the remote control module(from No.015 to No.016) set up in “Activate
object” data item range. Top right corner “000” express current item is No.00
item(each item per page).
This page’s other operation is referred to “OR1 Logic Setup” section.

Pulse Mode Module

14 无锡蓝天电子有限公司
JB-QB-5Si fire alarm control panel (associate operation type) operation manual

“Pulse Mode module” expresses remote control module activation is point activated
method, that is, after the module is closed and two seconds delay, it will be broken
up once again.

pluse mode module 000


或1逻辑控制 00条

控制源: 001号至020号
From: 021 to 023

控制对象: 120号至123号

For example, in above figure, the control modules from No.021 to No.023 has been
set up into point activation mode.
This page’s other operation is referred to “OR1 Logic Setup” section.

System Setup
In this sub-menu, you can set up and decide whether the printer need to print the
information on real-time base and the control panel need to monitor main power supply
and back-up power supply, etc.

System setup
系统管理
real time print > yes
AC monitor : yes
1 打印机
DC monitor :禁止
: yes
real time polling : no
2 主电监视
address code :允许
: 000
capacity : 000
3 备电监视
fire repeater :允许
: 000

Push down or to move cursor to next or above item.


Push down 自检 (self-check) to change item status.
Push down digital key to edit item content.
Push down 消音 (silence) to store setup and return main menu.
If we set up the printer into non-workable status, the printer will not print out
real-time information when there is fire alarm, fault, associated operation and
monitoring signal input. But this setup will not influent printing operation in
“Event Record”.

Exit
It expresses to return monitoring condition. In any interface in main menu, you can
directly push down 0 to return monitoring condition.

System self-check
System self-check: check system’s display LCD, condition indication LEDs and alarm
sounders. In polling condition, push down 自检 (self-check) to enter this function。
Wuxi Brightsky Electronic Co., Ltd
15
JB-QB-5Si fire alarm control panel (associate operation type) operation manual

Test Sound
测试音响

during self-check process, all status LEDs in the front face of the panel will flash,
the sounder will send out ambulance car sounder, printer ( if the ancillary device
has been installed) will print out “Fire Alarm Panel”。After self-check is completed,
it will return to monitoring condition.

Lock key/Unlock
To avoid non-operator’s non-proper operation, this control panel has lock key
function. In monitoring condition, push down lock key( fourth key start from left
to right in small box in the panel)button to enter this function.

输入上锁密码:
Keyboard lock

Input lock password. If it is correct, lock key LED will flash. If the key is locked,
it cannot do other operation besides silence and unlock operation. If you want to
unlock the key, please push down lock key button, it will show “Keyboard Unlock”
in the LCD display interface.

Automatic/Manual switch
If the system is not monitored by the operator, we can set up the fire alarm control
panel into automatic status, that is: when there is fire alarm, the control panel
can open or close relevant external devices based on pre-set associated operation
logic relationship and it does not need manual interference. When we open the fire
alarm control panel, it is in manual condition. In this condition, all associated
logic relationships are not valid. That is, associated device cannot be
automatically closed based on fire alarm. In monitoring condition, push down
“manual/automatic” switch button (the fourth key from left to right in the small
box of the panel) to enter this function.

手动自动切换:
Switch to auto status

16 无锡蓝天电子有限公司
JB-QB-5Si fire alarm control panel (associate operation type) operation manual

The same as lock key operation procedure, input switch password. If it is correct,
the system will be switched from automatic condition to manual condition. Or vice
versa, corresponding “manual/automatic” LED in the panel will be illuminated in
manual condition.

Associated control
Except that we can use associated logic relationship to active the devices in
automatic condition, we also can use system provided “ Associate Operate” function
to open or close the devices. For example, for some kind of requirement, you want
to some one ventilation fan in third floor, and the remote control module number
is No.008 which controls this ventilation fan, you can do following operation:
In polling condition, push down 1 key to enter associated function;
Push down digital key to input remote control module number 008;
Other push-key operation will have indication in the LCD.

Associate operate
联动控制
module No : 008
模块号:000
Key’silence’ open
Key’selfcheck’ close
按消音打开,自检关闭
Key’reset’ return

Repair and Maintenance


— Open the machine and it does not implement self-check function, the panel does
not have any response:
please check main power supply and back-up power supply to see whether they are
in normal condition. After check and repair, please open the machine once again.
— After the machine is open, LCD display mixed codes(cannot be read):
character library piece or program slice is broken or it is not plugged tightly.
Please change or plug the microprocessor once again and the issue will be solved.
— After the machine is open, control panel LEDs and sounder self-check are normal,
but the LCD does not have back light and display:
The reason is that LCD contrast degree is too small. Therefore, we cannot see
any display content. Please adjust main board’s contrast degree potentiometer
and the issue will be solved.
— After the machine is open, LCD always displays “system initialization, please wait”:
This expresses that the serial EEPROM microprocessor is broken, the control
panel always fetch the data. Please change the microprocessor and the issue will
be solved.
— The devices cannot be registered:
Possible reason is that we set up non-proper “device type” in the system
Wuxi Brightsky Electronic Co., Ltd
17
JB-QB-5Si fire alarm control panel (associate operation type) operation manual
management. 5i series bus device should be set up into “intelligent”
condition.
— Device registration is not complete
Possible reason is that device address exceeds the system capacity. For example,
if the system capacity is 32 points, then the device address which exceeds 32
points cannot be registered.

Notice
— Fire alarm control panel should have good ground connecting protection. In the
control panel, there should be have earth-connecting sign. The earth connection
requirement should follow the stipulation in GBJ116-88 “automatic fire alarm
th
system design code” 4 section.
— Fire alarm control panel is specific fire protection device. The system owner
need to appoint one full-time person to manage and maintain and check its
function on regular time and make written record. If the system is in fault
condition, please ask professional person or contact original manufacturer to
repair it.
— When the main power source is cut off and the system uses back-up battery power
source, if the control panel sends out back-up battery power fault alarm signal,
it expresses the back-up battery voltage is too low. In this time, we need to
take other offset measures to avoid battery damage caused by back-up battery
unrestrained discharge.

Our Service
The control panel operator must be trained by our company. For some basic
maintenance work, the persons who have been trained can deal with. But during the
operation, if you meet some abnormal situation which you are not familiar with,
please call us and our technical engineers will make relevant answers for you. Or,
we can dispatch our persons to your site system to make service(based on China
market).
Also you can visit our company website (www.bsky.cn) to understand our company
development and read any document you are interested in.

Special notes
Wuxi Brightsky Electronic Co., Ltd follows continuous development strategy. So we
keep the rights to modify our current product ranges and technical specification
which does not need to inform our customers in advance.

18 无锡蓝天电子有限公司
JB-QB-5Si fire alarm control panel (associate operation type) operation manual

This operation manual copy right belongs to Wuxi Brightsky Electronic Co., Ltd

Wuxi Brightsky Electronic Co., Ltd