Professional Documents
Culture Documents
Note 1 Note 4
Note 1 Note 4
Note 1 Note 4
2 2
This guide shall only be used in conjunction with performing the necessary calculations in a flash hazard analysis to determine the proper cal/cm . If the results of the calculations exceed the cal/cm that correspond to the HRC
found on this guide, you must use clothing that complies with the calculation.
Panelboards or Other Equipment Rated 240V and Below 600V Class Switchgear (with power circuit breakers or fused
NEMA E2 (fused contactor) Motor Starters, 2.3kV thru 7.2kV - CONTINUED
- Note 1 switches) - Note 4
Task (equipment is energized & work is done V-Rated V-Rated Task (equipment is energized & work is done V-Rated V-Rated Task (equipment is energized & work is done V-Rated V-Rated
within the flash protection boundary) Gloves Tools HRC within the flash protection boundary) Gloves Tools HRC within the flash protection boundary) Gloves Tools HRC
Perform infrared thermography and other non-
contact inspection outside the restricted approach 0 CB or fused switch or starter operation with 0 Insertion or removal (racking) of CBs from cubicles, 4
boundary enclosure doors closed doors open or closed
Circuit Breaker (CB) or fused switch operation with 0 Reading a panel meter while operating a meter 0 Removal of bolted cover (to expose bare, energized 4
covers on switch electrical-cal conductors and circuit parts)
Open hinged covers (to exposed bare, energized 0 CB or fused switch operation with enclosure doors 1 Task (equipment is energized & work is done V-Rated V-Rated
electrical conductors and circuit parts) open within the flash protection boundary) Gloves Tools HRC
Perform infrared thermography and other non-
Work on energized electrical conductors and circuit Y Y 1 contact inspection outside the restricted approach 2 Reading a panel meter while operating a meter 0
parts, including voltage testing boundary switch
Task (equipment is energized & work is done V-Rated V-Rated Insertion or removal (racking) of CBs from cubicles, 4 Removal of bolted cover (to expose bare, en- 4
within the flash protection boundary) Gloves Tools HRC doors open or closed energized electrical conductors and circuit parts)
Circuit Breaker (CB) or fused switch operation with 0 Removal of bolted covers (to exposed bare, 4 Work on energized electrical conductors and circuit Y Y 4
covers on energized electrical conductors and circuit parts) parts, including voltage testing
Perform infrared thermography and other non-
Other 600V Class (277v thru 600v, nominal equipment)
contact inspection outside the restricted approach 1 - Note 2 (except as indicated)
Work on control circuits with energized electrical Y Y 4
boundary conductor and circuit parts >120 V, exposed
CB or fused switch operation with Y 1 Task (equipment is energized & work is done V-Rated V-Rated Insertion or removal (racking) of CBs from cubicles, 4
covers off within the flash protection boundary) Gloves Tools HRC doors open or closed
CB or fused switch or starter operation with 0 Application of safety grounds, after voltage test - Y 2* Task (equipment is energized & work is done V-Rated V-Rated
enclosure doors closed Lighting or small power transformer (600v max) within the flash protection boundary) Gloves Tools HRC
Reading a panel meter while operating a meter 0 Revenue meters (kW-hour, at primary voltage and Y 2* Insertion or removal (racking) of ground and test 0
switch current) Insertion or removal device with doors closed
Work on control circuits with energized electrical Removal of bolted cover (to expose bare, energized
conductors and circuit parts 120 V or below, Y Y 0 electrical conductors and circuit parts) - Lighting or 2* Insertion or removal (racking) voltage trans-former 0
exposed small power transformer (600v max) on or off the bus door closed
Perform infrared thermography and other non-
contact inspection outside the 1 Work on energized electrical conductors and circuit Y Y 2* 0
restricted approach boundary parts, including voltage testing CB operation with enclosure doors closed
CB or fused switch or starter operation with 1 Y 2* Insertion or removal (racking) of CBs from cubicles, 0
enclosure doors open Application of safety grounds, after voltage test doors closed
Work on control circuits with energized electrical
Open hinged covers (to exposed bare, energized 1 Insertion or removal of plug-in devices into or from Y 2* conductors and circuit parts 120 V or below, Y Y 2
electrical conductors and circuit parts)--Note 3 busways exposed
Work on energized electrical conductors and circuit Y Y 2* NEMA E2 (fused contactor) Motor Starters, 2.3kV thru 7.2kV Insertion or removal of CBs from cubicles, doors 4
parts, including voltage testing open
2* Y 2
Contactor operation with enclosure doors open Insulated cable examination, in open area
Definitions: Y = Yes (Required) Opening hinged covers (to expose bare, energized 3 Opening hinged covers (to expose bare, energized 3
electrical-cal conductors and circuit parts) electrical conductors and circuit parts)
V-Rated Gloves: Rubber Insulating Gloves rated and tested for the maximum
line-to-line voltage upon which work will be done. Leather protectors must be Perform infrared thermography and other non-
worn externally if rubber insulating gloves could be damaged. contact inspection outside the restricted approach 3 Outdoor disconnect switch operation (hookstick Y Y 3
boundary operated)
V-Rated Tools: Insulated and Insulating Hand Tools rated and tested for the
maximum line-to-line voltage upon which work will be done
Work on control circuits with energized electrical Y Y 3 Work on energized electrical conductors and circuit Y Y 4
conductor - and circuit parts >120 V, exposed parts, including voltage testing
Work on energized electrical conductors and circuit Y Y 4 Insulated cable examination, in manhole or other Y 4
parts, including voltage testing confined space
Minimum Hard Hat, Safety Glasses or Goggles, Hearing Protection, Leather Work
HRC Protective Clothing cal/cm2 Shoes and Leather Gloves Apply to All
Arc rated flash suit over FR coveralls Arc rated switching hood,
*Working on circuits over 40 cal/cm2 should be avoided
4 or FR long-sleeve shirt & pants 40 Rubber insulating gloves (AN) because of blast hazard.
Restricted Approach
Limited Approach Boundary Boundary Includes Arc Flash Protection Boundary
Nominal System Voltage Exposed Movable Exposed Fixed Circuit Inadvertent Movement Prohibited Approach (Panelboards Only)
2 3
Range, Phase to Phase Conductor Part Adder Boundary
Less than Not specified Not specified Not specified Not specified Not specified
50
1
50 to 300 10 ft. 0 in. 3 ft. 6 in. Avoid contact Avoid contact 4 ft. 0 in.
1
301 to 750 10 ft. 0 in. 3 ft. 6 in. 1 ft. 0 in. 0 ft. 1 in. 4 ft. 0 in.
2 4
751 to 15 kV 10 ft. 0 in. 5 ft. 0 in. 2 ft. 2 in. 0 ft. 7 in. 40 ft. 0 in.
2 4
15.1 kV to 36 kV 10 ft. 0 in. 6 ft. 0 in. 2 ft. 7 in. 0 ft. 10 in. 40 ft. 0 in.
1
In the absence of a engineering calculation, use 4 feet (for panelboards only) when the product of clearing time of 2
cycles (.033 sec) and the available bolted fault current of 50 ka or any combination not exceeding 100 ka cycles.
When the product of clearing times and bolted fault current exceeds 100 ka cycles, then do the calculation. This 4 feet rule
applies only to panelboards, not MCC’s and switchgear. An arc flash protection boundary calculation should be done for
MCC’s and switchgear operations.
2
For single-phase systems, select the range that is equal to the system’s maximum phase-to-ground voltage multiplied by 1.732.
3
A condition in which the distance between the conductor and a person is not under the control of the person. The term
is normally applied to overhead line conductors supported by poles.
4
In the absence of arc flash boundary calculations on equipment labeling, default to 40 feet.
APPOROACH BOUNDARIES
Limited Approach Boundary: An electrical shock boundary whereby only qualified people can enter because they have the skills and
knowledge to recognize and avoid electrical hazards. Unqualified people must stay outside the Limited Approach Boundary so they
cannot contact energized parts.
Restricted Approach Boundary: The distance from exposed energized parts where there is an increased risk of electrical shock due to
electric arc over combined with inadvertent movement. A qualified person must wear PPE for protection (typically rubber insulating
gloves and use insulated tools) from the electrical shock hazard when working within the Restricted Approach Boundary.
Prohibited Approach Boundary: The distance from an exposed energized electrical conductor or circuit part within which work is
considered the same as making contact with the electrical conductor or circuit part. A qualified person must avoid performing work
with the Prohibited Approach Boundary.
Arc Flash Protection Boundary: The distance from an arc source at which a person could receive a second-degree burn if an
electrical arc flash would occur. All people must wear appropriate PPE while working/standing within this approach boundary.
Develop a plan for keeping unqualified people and qualified people not wearing PPE, outside the approach boundary. For large
electrical rooms, cordon off the work area with barricades and signs. Small electrical rooms can be controlled by keeping everyone
outside the electrical room with a closed door and a spotter.
When working in a panel in a hallway of an occupied building, set up a barricade system to keep unqualified people out.
Justification for Work (130.1): Staff Electric’s company policy is – NO HOT WORK!
Our policy is to de-energize by placing the energized electrical conductors and circuit parts into an electrically safe work condition to
protect exposed employees working within the Limited Approach Boundary. Staff Electric follows the requirements of NFPA 70E and
OSHA for justifying hot work.
NFPA 70E 130.1(A) Energized electrical conductors and circuit parts to which an employee might be exposed shall be put into
an electrically safe work condition before an employee works within the Limited Approach Boundary of those conductors or
parts.
• Interruption of life support equipment • Performing diagnostics and testing (e.g. start up and
• Deactivation of emergency alarm systems trouble shooting circuits that are part of a continuous
• Shutdown of hazardous location ventilation process that would otherwise need to be completely
equipment shutdown in order to permit work on 1 circuit or
• Removal of illumination from an area piece of equipment.)