ANSI/ASHRAE Standard 154-2003

Ventilation for
Commercial
Cooking
Operations
Approved by the ASHRAE Standards Committee on June
28, 2003; by the ASHRAE Board of Directors on July 3,
2003; and by the American National Standards Institute
on September 25, 2003.

ASHRAE Standards are updated on a five-year cycle; the


date following the standard number is the year of ASHRAE
Board of Directors approval. The latest copies may be
purchased from ASHRAE Customer Service, 1791 Tullie
Circle, NE, Atlanta, GA 30329-2305. E-mail:
orders@ashrae.org. Fax: 404-321-5478. Telephone: 404-
636-8400 (worldwide) or toll free 1-800-527-4723 (for or-
ders in U.S. and Canada).

©Copyright 2003 American Society of Heating,


Refrigerating and Air-Conditioning Engineers, Inc.
ISSN 1041-2336

When addenda or interpretations to this standard have


been approved, they can be downloaded free of charge
from the ASHRAE web site at http://xp20.ashrae.org/stan-
dards/addenda.htm or http://xp20.ashrae.org/standards/
intpstd.htm.
ASHRAE Standard Project Committee 154
Cognizant TC: TC 5.10, Kitchen Ventilation
SPLS Liaison: Waller S. Clements

Chris P. Rousseau, Chair* Edward D. Fitts* Daniel P. Restelli*


David C. Bixby Eliott B. Gordon
William C. Sharp*
Stephen L. Brown* John L. Harrod*
Chris B. Check Richard D. Hermans* Richard T. Swierczyna*
Charles N. Claar* Ronald R. Huffman Louis W. Vogel*
Vikram P. Doshi Richard M. Kelso
Frank H. Watier*
Gary M. Elovitz* Joseph N. Knapp
Donald R. Fisher* Phil O. Morton* Bruce Zimmerman
*Denotes members of voting status when the document was approved for publication

ASHRAE STANDARDS COMMITTEE 2002-2003


Thomas E. Watson, Chair David E. Knebel
Van D. Baxter, Vice-Chair Frederick H. Kohloss
Charles G. Arnold William J. Landman
Dean S. Borges Merle F. McBride
Paul W. Cabot Ross D. Montgomery
Charles W. Coward, Jr. Cyrus H. Nasseri
Brian P. Dougherty Davor Novosel
Hakim Elmahdy Dennis A. Stanke
Arthur D. Hallstrom Michael H. Tavares
Matt R. Hargan Steven T. Taylor
Richard D. Hermans David R. Tree
Stephen D. Kennedy Terry E. Townsend, CO
Maureen Grasso, ExO

Claire B. Ramspeck, Manager of Standards

SPECIAL NOTE
This American National Standard (ANS) is a national voluntary consensus standard developed under the auspices of the American
Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE). Consensus is defined by the American National Standards
Institute (ANSI), of which ASHRAE is a member and which has approved this standard as an ANS, as ìsubstantial agreement reached
by directly and materially affected interest categories. This signifies the concurrence of more than a simple majority, but not necessarily
unanimity. Consensus requires that all views and objections be considered, and that an effort be made toward their resolution.î
Compliance with this standard is voluntary until and unless a legal jurisdiction makes compliance mandatory through legislation.
ASHRAE obtains consensus through participation of its national and international members, associated societies, and public
review.
ASHRAE Standards are prepared by a Project Committee appointed specifically for the purpose of writing the Standard. The
Project Committee Chair and Vice-Chair must be members of ASHRAE; while other committee members may or may not be ASHRAE
members, all must be technically qualified in the subject area of the Standard. Every effort is made to balance the concerned interests
on all Project Committees.
The Manager of Standards of ASHRAE should be contacted for:
a. interpretation of the contents of this Standard,
b. participation in the next review of the Standard,
c. offering constructive criticism for improving the Standard,
d. permission to reprint portions of the Standard.

DISCLAIMER
ASHRAE uses its best efforts to promulgate Standards and Guidelines for the benefit of the public in light of available
information and accepted industry practices. However, ASHRAE does not guarantee, certify, or assure the safety or
performance of any products, components, or systems tested, installed, or operated in accordance with ASHRAEís Standards
or Guidelines or that any tests conducted under its Standards or Guidelines will be nonhazardous or free from risk.

ASHRAE INDUSTRIAL ADVERTISING POLICY ON STANDARDS


ASHRAE Standards and Guidelines are established to assist industry and the public by offering a uniform method
of testing for rating purposes, by suggesting safe practices in designing and installing equipment, by providing proper
definitions of this equipment, and by providing other information that may serve to guide the industry. The creation
of ASHRAE Standards and Guidelines is determined by the need for them, and conformance to them is completely
voluntary.
In referring to this Standard or Guideline and in marking of equipment and in advertising, no claim shall be
made, either stated or implied, that the product has been approved by ASHRAE.
CONTENTS

ANSI/ASHRAE Standard 154-2003,


Ventilation for Commercial Cooking Operations
SECTION PAGE
Foreword ................................................................................................................................................................... 2
1 Purpose .......................................................................................................................................................... 2
2 Scope ............................................................................................................................................................. 2
3 Definitions....................................................................................................................................................... 2
4 Exhaust Hoods ............................................................................................................................................... 4
5 Exhaust Systems............................................................................................................................................ 6
6 Replacement Air ............................................................................................................................................. 6
7 References ..................................................................................................................................................... 7
Appendix A: Air Balance Table and Graphic ........................................................................................................ 8

© Copyright 2003 American Society of Heating,


Refrigerating and Air-Conditioning Engineers, Inc.
1791 Tullie Circle NE
Atlanta, GA 30329
www.ashrae.org

All rights reserved.


(This foreword is not part of this standard. It is merely ductless hood: a listed packaged system incorporating a hood,
informative and does not contain requirements necessary a fan, and air treatment devices designed to remove substan-
for conformance to the standard. It has not been pro- tially all grease and particulate matter from the airstream
cessed according to the ANSI requirements for a stan- before reintroducing the treated air into the occupied space.
dard and may contain material that has not been subject
to public review or a consensus process.) equipment, light-duty: equipment with a light duty rating,
including
FOREWORD • Gas and electric ovens (including standard, bake, roast-
The model codes, and the many local amendments to ing, revolving, retherm, convection, combination con-
them, are not uniform in dealing with the complicated subject vection/steamer, conveyor, deck or deck-style pizza, and
of ventilation for commercial cooking operations. The intent pastry ovens)
of this standard is to address this problem by bringing cohe- • Electric and gas steam-jacketed kettles
sion and consistency to the issues that arise in providing venti- • Electric and gas compartment steamers (both pressure
lation for commercial cooking. While it is not comprehensive, and atmospheric types)
this standard does address most of the key concerns surround- • Electric and gas cheesemelters
ing the subject of ventilation for commercial cooking. • Electric and gas rethermalizers
Special thanks are due to Don Fisher, Joe Knapp, and
Dick Kelso. Without their vision and dedication, this standard equipment, medium-duty: equipment with a medium duty
would not have been written. rating, including
• Electric discrete element ranges (with or without oven)
1. PURPOSE • Electric and gas hot-top ranges
• Electric and gas griddles
The purpose of this standard is to provide design criteria
• Electric and gas double-sided griddles
for the performance of commercial cooking ventilation
• Electric and gas fryers (including open deep-fat fryers,
systems.
donut fryers, kettle fryers, and pressure fryers)
• Electric and gas pasta cookers
2. SCOPE
• Electric and gas conveyor (pizza) ovens
2.1 This standard covers the determination of the following: • Electric and gas tilting skillets/braising pans
(a) Airflow rates for exhaust hoods • Electric and gas rotisseries
(b) Replacement air configurations
equipment, heavy-duty: equipment with a heavy duty rating,
(c) Hood types including
(d) Fan systems • Electric and gas underfired broilers
• Electric and gas chain (conveyor) broilers
2.2 This standard does not address the life safety and health
• Gas open-burner ranges (with or without oven)
aspects of ventilating commercial cooking operations.
• Electric and gas wok ranges
• Electric and gas overfired (upright) broilers
3. DEFINITIONS
• Salamanders
approved: acceptable to the authority having jurisdiction.
equipment, extra heavy-duty: equipment with an extra heavy
centrifugal fan (also referred to as a “utility set”): typically a duty rating, including
single-inlet fan with scroll housing and a backward-inclined • Appliances utilizing solid fuel such as wood, charcoal,
or an airfoil centrifugal impeller. It can provide a higher static briquettes, and mesquite to provide all or part of the heat
efficiency capability than a typical power roof ventilator. Air source for cooking.
enters the impeller axially and leaves it in a substantially radial
direction. The fan must include provisions for handling grease exfiltration: uncontrolled outward leakage of indoor air
and for cleaning access. It may be listed under Underwriters through openings in the building or space envelope, including
Laboratories (UL) Standard 705, Standard for Power Ventila- both intentional and unintentional openings. The driving force
tors, in accordance with UL Subject 762, “Outline of Investi- for exfiltration is a pressure difference between indoor and
gation for Power Roof Ventilators for Restaurant Exhaust outdoor air.
Applications.”
grease ducts: a containment system for the transportation of
compensating hood: an exhaust hood with integral provision air and grease vapor. The system is designed and installed to
to deliver makeup air. The makeup air delivery may be config- reduce the possibility of the accumulation of combustible
ured for front face discharge, down discharge, internal condensation, thus reducing the possibility of damage if a fire
discharge, or any combination thereof. occurs within the ventilation system.

cooking effluent: matter rising from cooking equipment grease (laden) exhaust: effluent from a cooking process that
during equipment operation, such as moisture, vapor, prod- contains grease particles or grease vapor. This type of exhaust
ucts of combustion, smoke, and particulate matter. requires a Type I hood.

2 ANSI/ASHRAE STANDARD 154-2003


grease removal device: a listed device designed and installed hood exhaust fire (actuated) damper: a damper arranged to
to remove grease vapor and/or particles from the airstream, seal off airflow automatically to restrict the passage of fire and
such as, but not limited to, baffle filters, removable extractors, excessive heat.
and stationary extractors.
hood type: see Type I hood and Type II hood.
greasetight: constructed and performing in such a manner as
to prevent the passage of grease under normal operating infiltration: see replacement air.
conditions.
internal discharge makeup air: see makeup air, internal
hood: a device designed to capture cooking and/or warewash- discharge.
ing effluent. The following types of hoods are available:
1. Wall-mounted canopy hood—A wall canopy exhaust hood labeled: equipment or materials to which has been attached a
is mounted against a wall above a single appliance or a line label, symbol, or other identifying mark of an organization
of appliances, or it may be free-standing with a back panel acceptable to the authority having jurisdiction. This organiza-
from the rear of the appliance(s) to the hood. It overhangs tion is concerned with product evaluation and maintains peri-
the front and sides of the appliance(s) on all open sides. The odic inspection of the production of labeled equipment or
wall acts as a back panel, forcing replacement air to be materials. By labeling the equipment or materials, the manu-
drawn across the front of the cooking equipment, thus facturer indicates compliance with appropriate standards or
increasing the effectiveness of the hood to capture and performance in a specified manner.
contain effluent generated by the cooking operations.
liquid-tight: constructed and performing in such a manner as
2. Single-island canopy hood—A single-island canopy hood
is placed over a single appliance or appliance line. It is open not to permit the passage of any liquid at any temperature.
on all sides and overhangs the front, rear, and sides of the
listed: equipment or materials included in a list published by
appliance(s). A single-island canopy is more susceptible to
an organization acceptable to the authority having jurisdic-
cross-drafts and requires a greater exhaust airflow than an
equivalent-sized wall-mounted canopy to capture and tion. This organization is concerned with product evaluation
contain effluent generated by the cooking operations. and performs periodic inspections of production of listed
equipment or materials. The list states either that the equip-
3. Double-island canopy hood—A double-island canopy ment or material meets appropriate standards or that it has
hood is placed over back-to-back appliances or appliance been tested and found suitable for use in a specified manner.
lines. It is open on all sides and overhangs both front and the
sides of the appliance(s). It may have a wall panel between makeup air: see replacement air.
the backs of the appliances. The fact that exhaust air is
drawn from both sides of the double canopy to meet in the makeup air, face discharge: makeup air delivered directly to
center causes each side of this hood to emulate a wall an interior plenum of the exhaust hood such that it is intro-
canopy hood, and thus it functions much the same with or duced into the space through the front face of the hood.
without an actual wall panel between the backs of the appli-
ances. makeup air, down discharge: makeup air delivered directly to
4. Backshelf or proximity hood—A backshelf hood is also the interior plenum of an exhaust hood such that it is intro-
referred to as a low-proximity hood or as a sidewall hood duced vertically downward, typically from the front edge of
when wall mounted. Its front lower lip is low over the appli- the hood. Sometimes this kind of makeup air is referred to as
ance(s) and typically is set back from the front of the appli- an “air curtain.”
ance(s). It is always closed to the rear of the appliances by
a panel when free-standing or by a panel or wall when wall makeup air, internal discharge: makeup air delivered directly
mounted, and its height above the cooking surface varies. to the interior of an exhaust hood such that it is exhausted
This style of hood can be constructed with partial end without entering the occupied space. Sometimes this kind of
panels to increase its effectiveness in capturing the effluent makeup air is called “short-circuit makeup air.”
generated by the cooking operations.
manifold hood exhaust system: see multiple hood exhaust
5. Eyebrow hood— An eyebrow hood is mounted directly to
system.
the face or top of an appliance above the opening(s) or
door(s) from which effluent is emitted, overhanging the multiple hood exhaust system: a system in which more than
front of the opening(s) to capture the effluent.
a single hood is connected to a common exhaust duct and fan.
6. Pass-over hood—A pass-over hood is a backshelf hood
constructed low enough to allow food to be passed over the net exhaust flow rate: the exhaust flow rate for a hood, minus
top. any internal discharge makeup air.

hood category, Type I: Type I hoods fall into two categories. outdoor air: air outside a building or taken from outdoors and
One is the conventional (non-listed) category, which meets the not previously circulated through an HVAC system.
design, construction, and performance criteria of the applica-
ble national and local codes. The second is a listed category in packaged: provided by a manufacturer or vendor in a substan-
accordance with UL Standard 710.1 tially complete and operable condition.

ANSI/ASHRAE STANDARD 154-2003 3


power roof ventilator (also referred to as an “up-blast fan”): a or at the duct outlet. The fan must include provisions for
fan designed for curb mounting on a roof or, within size and handling grease and cleaning access. It may be listed under
design constraints, for wall mounting. Air enters the fan in a UL Standard 705, Standard for Power Ventilators,2 in accor-
typical axial arrangement but discharges radially from the dance with UL Subject 762, “Outline of Investigation for
centrifugal impeller and turns 90 degrees to exit through the Power Roof Ventilators for Restaurant Exhaust Applica-
top of fan. It may be listed under UL Standard 705, Standard tions.”3 Code may require additional external protection for
for Power Ventilators,2 in accordance with UL Subject 762, grease collection in the event of grease leakage.
“Outline of Investigation for Power Roof Ventilators for
Restaurant Exhaust Applications.”3 Type I hood: a hood designed to capture smoke and/or grease-
laden vapor produced by a cooking process, incorporating
recirculating system: see ductless hood. listed grease-removal devices and fire-suppression equip-
ment.
replacement air: outdoor air that is used to replace air
removed from a building through an exhaust system. Replace- Type II hood: a hood designed to capture heat, odors, products
ment air may be derived from one or more of the following: of combustion, and/or moisture where smoke or grease-laden
makeup air, supply air, transfer air, and infiltration. However, vapor is not present. A Type II hood may or may not have
the ultimate source of all replacement air is outdoor air. When filters or baffles and does not have a fire-suppression system.
replacement air exceeds exhaust, the result is exfiltration.
• makeup air (dedicated replacement air): outdoor air 4. EXHAUST HOODS
deliberately brought into the building from the outside
and supplied to the vicinity of an exhaust hood to 4.1 Where Required
replace air, vapor, and contaminants being exhausted. 4.1.1 A Type I hood shall be provided when a cooking
Makeup air is generally filtered and fan-forced, and it operation within a commercial or institutional food service
may be heated or cooled depending on the requirements facility produces smoke or grease-laden vapors.
of the application. Makeup air may be delivered through
Exceptions:
outlets integral to the exhaust hood or through outlets in
the same room. 1. Cooking equipment not used for commercial purposes and
• supply air: air entering a space from an air-condition- installed within dwelling units.
ing, heating, or ventilating apparatus for the purpose of 2. Equipment such as microwave ovens, toasters, steam
comfort conditioning. Supply air is generally filtered, tables, popcorn poppers, hot dog cookers, coffee makers,
fan-forced, and either heated or cooled as necessary to rice cookers, egg cookers, and holding/warming ovens.
maintain specified temperature conditions. Only the
4.1.2 A Type II hood may be used whenever a Type I hood
quantity of outdoor air within the supply airflow may be
is not required.
used as replacement air.
• transfer air: air transferred from one room to another 4.2 Hood Sizing
through openings in the room envelope, whether it is 4.2.1 Hood overhangs shall comply with Table 1.
transferred intentionally or not. The driving force for
4.2.2 The overhang or setback shall be measured from the
transfer air is generally a small pressure differential
edge of the cooking surface as the appliance will be installed
between the rooms, although one or more fans may be
to the inside edge of the hood. Space between sides of appli-
used.
ances, backs of appliances, and between appliances and walls
• infiltration: uncontrolled inward leakage or flow of out-
or end panels shall be included in overall hood dimensions. In
door air into the building or space through openings in
the case of island hoods, appliance flues shall be included in
the building or space envelope, whether intentional or
the cooking surface dimensions.
unintentional. The driving force for infiltration is a pres-
sure difference across the building envelope. 4.2.3 Hoods shall be mounted above the cooking surface
as follows:
short-circuit makeup air: see makeup air, internal discharge. 4.2.3.1 Canopy Type Hood. The vertical distance
between the front lower edge of the hood and the cooking sur-
solid-fuel cooking equipment: cooking processes where solid face shall not exceed 48 inches (1219 mm). The front inside
fuel such as wood, charcoal, or coal provide all or part of the edge thereof shall be a minimum of 78 inches (1981 mm)
heat source for cooking. above the finished floor. The inside hood height shall be a
minimum of 24 inches (610 mm).
transfer air: see replacement air.
4.2.3.2 Eyebrow Type Hood. The front inside edge of
tubular centrifugal fan (also referred to as an “in-line fan”): the hood shall be a minimum of 78 inches (1981 mm) above
a centrifugal impeller located within a cylindrical or rectan- the finished floor.
gular housing, discharging in an axial direction. Its perfor- 4.2.3.3 Backshelf/Pass-over Type Hood. The vertical
mance is similar to that of a centrifugal blower except its distance between the front lower edge of the hood and the
capacity and pressure are lower due to the less efficient fan cooking surface shall be a maximum of 24 inches (610 mm)
arrangement. It is mounted in line in an exhaust duct system above the cooking surface.

4 ANSI/ASHRAE STANDARD 154-2003


TABLE 1
Minimum Overhang Requirements

End Front Rear


Type of Hood Overhang Overhang Overhang
Wall-mounted canopy 6 in. (154 mm) 6 in. (154 mm) N/A
Single-island canopy 6 in. (154 mm) 6 in. (154 mm) 6 in. (154 mm)
Double-island canopy 6 in. (154 mm) 6 in. (154 mm) N/A
Eyebrow N/A 6 in. (154 mm) N/A
Backshelf/Pass-over 6 in. (154 mm) 10 in. (254 mm) (setback) N/A
N/A = not applicable

TABLE 2a

Minimum Net Exhaust Flow Rate,


CFM per Linear Foot of Hood Length

Light Medium Heavy Extra Heavy


Duty Duty Duty Duty
Type of Hood Equipment Equipment Equipment Equipment
Wall-mounted 200 300 400 550
canopy
Single island 400 500 600 700
Double island 250 300 400 550
(per side)
Eyebrow 250 250 Not allowed Not allowed
Backshelf/ 300 300 400 Not allowed
Pass-over

TABLE 2b

Minimum Net Exhaust Flow Rate,


L/s per Linear Meter of Hood Length

Light Medium Heavy Extra Heavy


Duty Duty Duty Duty
Type of Hood Equipment Equipment Equipment Equipment
Wall-mounted 310 464 619 852
Canopy
Single island 619 774 929 1,084
Double island 387 464 619 852
(per side)
Eyebrow 387 387 Not allowed Not allowed
Backshelf/ 464 464 619 Not allowed
Pass-over

Exceptions: 4.3 Type I Hood Airflow Rates


4.3.1 The net exhaust flow rate for Type I kitchen hoods
1. Side Panels. Overhang is not required where full side panels shall comply with Table 2a or Table 2b.
or partial side panels (panels angled from the front lip of the
4.3.2 The net exhaust flow rate is the total exhaust airflow
hood to the rear of the hood at cooking-surface height) are
rate of a hood minus the makeup airflow rate delivered
provided to reduce the open area between the appliances
directly to the interior of the hood cavity (i.e., the internal
and the hood.
makeup hood).
2. Listed hoods are to be installed in accordance with the 4.3.3 If a single hood is installed over more than one
terms of their listing organization and their manufacturer's appliance and the appliances have different duty ratings, the
installation instructions. exhaust hood shall meet the requirements of the appliance that

ANSI/ASHRAE STANDARD 154-2003 5


has the highest minimum net exhaust flow rate according to around buildings. Minimum horizontal distance between dis-
Table 2a or 2b, unless the hood is designed to accommodate charge and intake shall be 10 ft (3 m) unless otherwise speci-
different flow rates over the length of the hood. fied by the applicable code. Exhaust discharge shall not
impinge on obstacles such as overhangs, parapets, other
Exception: Exhaust flow rates for listed and labeled fac-
equipment, and higher parts of buildings.
tory-built exhaust hoods tested in accordance with
5.3.2 Exhaust airstreams for Type I hoods shall be
UL 7101 shall be permitted in accordance with the
directed away from roof and building surfaces.
listing.
6. REPLACEMENT AIR
5. EXHAUST SYSTEMS
5.1 Airflow Performance 6.1 Room Definition
A room is a space formed by an envelope of defined
5.1.1 Minimum velocity for hood exhaust ductwork is 500
boundaries (i.e., sides, top, and bottom). The boundaries are
fpm (2.54 m/s).
not necessarily solid, but may be imaginary. For the purposes
5.1.2 Maximum velocities are not limited by this stan- of this section, a room may be defined as an entire free-stand-
dard. ing structure or as a portion of a structure. Room definition
5.2 Fans must be applied consistently within each system.
5.2.1 Fans shall be of sufficient capacity to provide the 6.2 Air Balance
required airflow against the system’s resistance. Expected air
6.2.1 Design plans for a facility with a commercial
temperatures, altitude, windage, and system effects shall be kitchen ventilation system shall include a table or diagram
taken into account when determining fan capacity. Fan air
indicating the design outdoor air balance (see example in
performance shall be tested and certified according to AMCA Appendix A). The design outdoor air balance shall indicate all
Standard 210.4 Belt drive fans shall be considered to allow for
exhaust and replacement air for the facility, plus net exfiltra-
speed adjustment for final system balancing. tion if applicable. Total replacement air airflow rate shall
5.2.2 Exhaust fans (power roof ventilators, centrifugal or equal total exhaust airflow rate plus the net exfiltration.
tubular centrifugal fans) serving Type I hoods shall be capable Note: Although individual replacement air sources need
of handling hot, grease-laden air and flare-up conditions. The not be 100% outdoor air, sufficient outdoor air must be intro-
fan shall be designed to contain and properly drain grease duced into the system to compensate for each exhaust and
removed from the airstream. The fan housing or scroll that exfiltration component. For example, for 100 cfm (47 L/s)
contains the grease shall be fully welded so that it is liquid transfer air from room A to room B to qualify as replacement
tight. The fan impeller shall be a self-cleaning design. air, at least 100 cfm (47 L/s) outdoor air must be provided to
Exception: Fans listed under UL Standard 705, Standard room A (e.g., as outdoor air to an environmental air system
serving room A, infiltration to room A, or transfer air from
for Power Ventilators,2 in accordance with UL Sub-
another room).
ject 762, “Outline of Investigation for Power Roof
Ventilators for Restaurant Exhaust Applications.”3 6.2.2 Operation of systems where airflows can vary
(including, but not limited to, HVAC systems incorporating
5.2.3 Power roof ventilators shall be hinged with tip-over variable air volume, systems with outdoor air economizer
restraints. control, or exhaust systems with variable airflow) shall be
5.2.4 Provisions shall be made to drain grease from any controlled to comply with the requirements of this standard
part of the fan that may collect grease. Access shall be pro- over the full range of anticipated airflows. Additional air bal-
vided for cleaning the fan wheel. Fan drive assemblies shall ance diagrams or tables shall be provided as necessary to indi-
be separated from the airstream. Covers shall be provided for cate compliance over the full range of anticipated airflow.
motor weather protection for outdoor installation and as belt
6.2.3 Where the design air balance relies upon transfer air
guards for indoor applications.
from a source beyond the facility’s control (e.g., air drawn
5.2.5 Makeup systems shall be interlocked to operate into an individual tenant’s facility from the common areas of
only when the exhaust fan is operating. The makeup air sys- a shopping mall), this source shall be identified.
tem must shut down when the fire-suppression system is acti-
vated. The makeup air intake shall be located to prevent 6.3 Pressure Differentials
recirculation of exhaust air. Air filters shall be used to limit the 6.3.1 The commercial kitchen ventilation system shall be
entrance of dust, dirt, insects, and other unwanted matter. designed to establish pressure differentials to control odor
migration and to control dust, dirt, and insects in accordance
5.3 Exhaust Discharge
with the following criteria:
5.3.1 Kitchen ventilation exhaust systems shall be
designed to prevent re-entrainment into building intakes. Pre- 1. The kitchen of a food-service facility shall be maintained
vailing winds and velocities shall be considered when locat- under a negative pressure with respect to dining areas and
ing intakes and exhausts, and intakes should be located adjacent non-food areas.
upwind from exhausts. Refer to the 2001 ASHRAE Hand- 2. A freestanding food-service facility (i.e., a food-service
book—Fundamentals,5 Chapter 16, for airflow patterns facility that entirely occupies a single building) shall be

6 ANSI/ASHRAE STANDARD 154-2003


maintained under a positive pressure with respect to 6.4.2 The minimum required net exhaust shall be deter-
outdoors. mined in accordance with Section 4.3 of this standard.
Exception: where migration of food odors to adjacent
6.5 Draft Control
interior rooms within the same tenancy would not
be objectionable. Display cooking under a hood 6.5.1 Air delivery shall be arranged to avoid cross-drafts,
located in the dining area is not considered a which may impair hood performance.
kitchen.
3. Where a food-service facility shares a party wall with an 6.5.2 Where openings are provided for non-fan-forced
adjacent non-food-service facility, such as a retail center or transfer air and/or infiltration, such openings shall be sized for
a shopping mall, the food-service facility shall be main- air velocities not to exceed 500 fpm (2.54 m/s) based on the
tained under a negative pressure with respect to outdoors free area of the opening. Such openings shall be arranged to
and the adjacent spaces. avoid creating drafts on personnel. Openings provided for
transfer air must remain open during system operation. Con-
Exception: where the separation between the food ser- sideration shall be given to minimizing air velocity when
vice facility and the adjacent interior room is sealed openings are used as pass-through openings for prepared
substantially airtight to prevent odor migration. food.
4. In shopping malls and other occupancies where a food-
service facility is open to another tenancy or to the mall
common area, the food-service facility may be under a 7. REFERENCES
negative pressure with respect to the non-food-service 1UL
occupancy. 710, Exhaust Hoods for Commercial Cooking Equip-
ment, Underwriters Laboratory, 333 Pfingsten Road,
6.3.2 The pressure in any room in which a draft-hood
Northbrook, IL, 60062, 1995.
vented appliance, such as a gas water heater, is located shall
2UL 705, Power Ventilators, Underwriters Laboratory, 333
be maintained no lower than 0.02 inches of water column (5.0
Pa) below outdoor ambient pressure. Pfingsten Road, Northbrook, IL, 60062, 1994.
3UL 762, Outline of Investigation for Power Roof Ventilators
6.4 Internal Discharge Makeup Air
6.4.1 Where a hood has internal discharge makeup air, the for Restaurant Exhaust Applications, Underwriters Lab-
exhaust airflow required to meet this standard shall be the net oratory, 333 Pfingsten Road, Northbrook, IL, 60062,
exhaust from the hood, calculated as follows: 1999.
4
(ENET = EHOOD – MAID) AMCA 210, Laboratory Methods of Testing Fans for Rat-
ings, Air Movement and Control Association, 30 West
where University Drive, Arlington Heights, IL 60004, 1999.
ENET = net hood exhaust, 5
2001 ASHRAE Handbook—Fundamentals, American Soci-
EHOOD = total hood exhaust, ety of Heating, Refrigerating and Air-Conditioning
MAID = makeup air, internal discharge. Engineers, Inc., Atlanta, GA 30339.

ANSI/ASHRAE STANDARD 154-2003 7


(This appendix is not part of this standard. It is merely informative and does not contain requirements necessary for
conformance to the standard. It has not been processed according to the ANSI requirements for a standard and may
contain material that has not been subject to public review or a consensus process.)

APPENDIX A
This appendix provides an example of the type of design outdoor air balance referred to in Section 6.2.1.

TABLE A-1
Air Balance Table

Kitchen Systems Airflow In Airflow Out


• kitchen exhaust (KX) 4000
• makeup air (MUA) to hood 1500
• makeup air (MUA) to kitchen 1000
• HVAC supply (SUP) 800
TOTAL 3300 4000
Net = 4000 – 3300 = 700 transfer air (TA) from dining room
Dining Room Systems Airflow In Airflow Out
• outside air (OSA) 1900
• transfer air (TRA) to water closet (WC) 200
• supply air to kitchen (SUP) 800
• transfer air to kitchen (TRA) 700
TOTAL 1900 1700
Net = 1900 – 1700 = 200 exfiltration
Note: Units of either cfm or L/s can be assigned to the values in this example air balance as long as the same units are used throughout.

Figure A-1 Diagram for air balance example.

8 ANSI/ASHRAE STANDARD 154-2003


POLICY STATEMENT DEFINING ASHRAEíS CONCERN
FOR THE ENVIRONMENTAL IMPACT OF ITS ACTIVITIES

ASHRAE is concerned with the impact of its membersí activities on both the indoor and outdoor environment. ASHRAEís
members will strive to minimize any possible deleterious effect on the indoor and outdoor environment of the systems and
components in their responsibility while maximizing the beneficial effects these systems provide, consistent with accepted
standards and the practical state of the art.
ASHRAEís short-range goal is to ensure that the systems and components within its scope do not impact the indoor and
outdoor environment to a greater extent than specified by the standards and guidelines as established by itself and other
responsible bodies.
As an ongoing goal, ASHRAE will, through its Standards Committee and extensive technical committee structure,
continue to generate up-to-date standards and guidelines where appropriate and adopt, recommend, and promote those new
and revised standards developed by other responsible organizations.
Through its Handbook, appropriate chapters will contain up-to-date standards and design considerations as the material is
systematically revised.
ASHRAE will take the lead with respect to dissemination of environmental information of its primary interest and will seek
out and disseminate information from other responsible organizations that is pertinent, as guides to updating standards and
guidelines.
The effects of the design and selection of equipment and systems will be considered within the scope of the systemís
intended use and expected misuse. The disposal of hazardous materials, if any, will also be considered.
ASHRAEís primary concern for environmental impact will be at the site where equipment within ASHRAEís scope
operates. However, energy source selection and the possible environmental impact due to the energy source and energy
transportation will be considered where possible. Recommendations concerning energy source selection should be made by
its members.